File - 158 - Ds - HRMW - 700 - t6 (FICHA 700 KVA)
File - 158 - Ds - HRMW - 700 - t6 (FICHA 700 KVA)
File - 158 - Ds - HRMW - 700 - t6 (FICHA 700 KVA)
Prime Standby
Voltage VAC Phase PF
kVA kW kVA kW
120/240 1 1.0 N.A. N.A. N.A. N.A.
120/208 3 0.8 693 554 762 610
120/240 Delta 3 0.8 N.A. N.A. N.A. N.A.
277/480 3 0.8 693 554 762 610
347/600 * 3 0.8 693 554 762 610
Rating Definitions: (N.A. = Not available for model designated)
Prime - All Rental Sets are Prime Rated - Prime rating is applicable for supplying
power to a varying load in lieu of utility for an unlimited amount of running of
amount of running time. (Max. load factor = 80%) A 10% overload capacity is
available for 1 out of every 12 hours.
Standby - Applicable for a varying emergency load for the duration of a utility
power outage with no overload capability.
Photo depicts a typical model but may not include options such as trailer. *600V - 347/600 volt connection option does not include voltage change-over.
HIPOWER® Systems Inc ▪ 16002 W. 110th Street ▪ Lenexa ▪ KS 66219 ▪ Ph 913.495.5557 ▪ Fax 913.495.5575 www.hipowersystems.com
HIPOWER Sound Attenuated Enclosure: Model - J10R
Noise level at 23 feet (7 meters) 75 dBA
Dimensions - inches 197.0 L X 83.0 W X 105.0 H
Dry weight – lbs. 19,500 lbs.
Fuel System:
Grade #2 Diesel - ULSD
Tank capacity – US gallons (liters) 634 US gallons (2,400 liters)
Approximate run time at 100% load 17.8 hours
Prime Rating Fuel consumption:
100% load – US gallons/hour (liters/hour) 36.61 (138.57)
75% load - US gallons/hour (liters/hour) 27.73 (105.00)
50% load - US gallons/hour (liters/hour) 19.70 (74.58)
25% load - US gallons/hour (liters/hour) 10.93 (41.38)
Alternator Specification:
Manufacturer Stamford
Model HCI 544 F Winding 311 - HCI 544 E (Winding 17 - 600V)
Voltages 277/480V - 120/208V - 347/600V (Special Wdg 17)
Alternator Type 4-pole, rotating field
Excitation System Brushless with AVR model DER-1
Power factor 0.8
Number of leads 12 - re-connectable
Stator Pitch 2/3
Insulation Class H
Windings – Temperature Rise 125° C
Enclosure (IEC-34-S) IP 23
Bearing Single, sealed
Coupling Flexible disc
Amortisseur windings Full
Voltage regulation – no load to full load plus or minus 1%
TIF < 50
Line harmonics 5% maximum
Standard Accessories: (see back-page for control panel details)
● Radiator with pusher fan ● Standard and secondary water separator with visible level on fuel filters
● Heavy duty single-stage air filter with service indicator ● All rotating components (i.e. fan) protected with metal guards
● Heavy-duty engine start batteries in rack with cables ● All hot components (i.e. exhaust) protected with metal guards
● Battery disconnect switch ● Ground connection prepared for ground spike (not supplied)
● External emergency stop switch ● Main line ABB UL listed circuit breaker for overload protection
● Distribution power panel
Covered panel NEMA 3R/IP67rated weather proof assembly – Individual Square-D QOU branch breakers - 2 x 20A 125V NEMA 5-20 GFCI duplex
receptacles with metal flap cover - 3 x 50A 125/250V CS6369 Twist -lock receptacles - 50A California Style twist lock - 6 sets Camlock devices
rated 400A - Color coded Camlock devices 3Ф - 5W black, red, blue, white & green - Pad lockable swing door access - Auxiliary bus bars with
mechanical lugs - 2 x Quad Barrel Lug per phase - Mechanical lugs up to 600MCM cable *See image RH back-page
● Control panel DSE 8610 AUTO START LOAD SHARING MODULE “incorporates a generator to generator paralleling control system”
Optional Accessories:
□ Fuel tank leak detection sensor with alarm □ Interior lights
□ Alternator anti-condensation heaters □ Shore power receptacle
□ Winterization kit for low ambient temperature □ Engine Block heater
□ Electric actuator and louvers for air intake and exhaust □ Control panel heater
□ Snow hoods for air intake and exhaust □ Three-way ‘Quick’ connect fuel valve to external fuel supply
□ Three- wheel DOT certified towing trailer □ Automatic fuel transfer pump
HIPOWER® Systems Inc ▪ 16002 W. 110th Street ▪ Lenexa ▪ KS 66219 ▪ Ph 913.495.5557 ▪ Fax 913.495.5575 www.hipowersystems.com
Generator Digital Control Panel - for manual, automatic and remote control Model DSE 8610
The DSE model 8610 digital control panel: Is back-lit with four line LCD text display, and fully configurable.
It works with the engine electronic governor and alternator AVR, with PLC functionality, protected front panel
programming.
Control panel includes: Manual and automatic start, multiple display languages, PC configurable eleven inputs
and eight outputs, multi event exerciser timer, with audible alarm, engine protection, fault condition notification to
a designated PC, event log (250), kW overload alarms, RS232 and RS 485 remote communications (usable at the
same time), Modbus RTU, SMS alert messaging, DESNet connection for system expansion, auto voltage sensing,
data logging and trending, engine preheat, and Ethernet monitoring.
Paralleling ability included: The DSE 8610 provides the ability for parallel operation and load sharing between
two or more generator sets.
Engine alarms included: High coolant temperature, low oil pressure, low coolant level, unexpected shutdown,
low fuel level, stop failure, low battery voltage, battery charging alternator failure, over-speed,
1200 AMP DISTRIBUTION PANEL
under-speed, start failure and emergency stop.
Alternator alarms included: Overload, unbalanced voltage, over voltage, under voltage, over
frequency, under frequency, short circuit, reverse power, and incorrect phase sequence.
Instrumentation and gauges included: 3 ammeters, frequency meter, voltmeter plus selector,
hour meter, fuel gauge, battery charger gauge, oil pressure gauge, water temperature gauge,
siren and emergency stop button.
Panel Front Panel Front - Door Open
Pictures of Control Panel (Top photo) and Distribution Panel may include optional equipment and/or accessories
W L
Fuel Tank Data Generator Data *
Run Time Hours Capacity (Gals) L = Length W = Width H = Height Weight lbs dBA
17.8 634 197.0” 83” 105” 19,500 75
* All measurements are approximate and for estimation purposes only. Weights are with dry fuel tank. Sound level measured at 23ft (7m) and does not account for ambient site conditions.
NFPA 99 BS5514
NFPA 110 SAE J1349
ISO 8528-5 DIN6271
ISO 1708A.5 IEE C62.41 TESTING
ISO 3046 NEMA ICS 1
your partner for power ™
© 2012 HIPOWER® Systems Inc. All rights reserved.
HIPOWER® is a registered trademarks of Himoinsa Power Systems, Inc.. HIMOINSA® is a registered trademark of
Himoinsa SL. Other company, product, or services names may be trademarks or service mark of others. Specifications
your partner for power
are subject to change without notice. Ref# 555-10095-April 2012
HIPOWER® Systems Inc ▪ 16002 W. 110th Street ▪ Lenexa ▪ KS 66219 ▪ Ph 913.495.5557 ▪ Fax 913.495.5575 www.hipowersystems.com