Cable Type and Bushing Type Current Transformers
Cable Type and Bushing Type Current Transformers
BUSHING TYPE
CURRENT TRANSFORMERS
CT_IT_2020_R01
CABLE TYPE
CURRENT TRANSFORMERS
01
INDEX
APPLICATIONS 04
KAT-60/80 05
KATK-60/80 06
KAT-60/130/180 07
KAT-85/98 08
KATK-85/98 09
SAA-120 11
HKA-100 12
HKA-120 13
HKA-120/150/180/200/270 14
02
GENERAL INFORMATION
Instrument Transformers: An instrument transformer is a piece of electrical equipment which converts primary
electrical values current or voltage-into comparable secondary values which are suitable for the devices to which it is
connected. They are defned in two kinds;
Current transformers convert primary rated current to a proper current level (1A…5A) which can be used by meter-
ing or protection devices. They can have several secondary windings with magnetically separated cores of the same
or different characteristics.
It is the value that Current Transformer can withstand at defned current value while remaining in the limits of
current error. As described in IEC 61869-2, Standard values of rated primary current 120%, 150% and 200% of primary
current.
Limits of current error and phase displacement for measuring current transformers
As described IEC 61869-2;
For classes 0.1 – 0.2 – 0.5 and 1, the current error and phase displacement at rated frequency shall not exceed the
values given in table when the secondary burden is any value from 25 % to 100 % of the rated burden.
For classes 0,2 S and 0,5 S the current error and phase displacement at the rated frequency shall not exceed the
values given in table when the secondary burden is any value from 25 % and 100 % of the rated burden.
Secondary terminals
One of the secondary terminals should be earthed for safety.
Secondary winding of a current transformer must not be operated with an open circuit. It should be connected
measuring devices before application of primary connection as seen in FIGURE-1.
The secondary winding of current transformer which will not be used must always be short-circuited and earthed
as seen in FIGURE-2.
For the transformer with reconnectable and/or tapped secondaries, unused terminals must be left open as seen
in FIGURE-3.
If cable type current transformers will be assembled on to isolated HV cable, shielded cable should be earthed as
seen on FIGURE-4 to be able to prevent effects caused by the possible leakage current flow on measuring systems.
FIGURE-4
04
CABLE TYPE CURRENT TRANSFORMERS
KAT-60/80
TYPE ØD L
KAT-60/195-60 60 60
KAT-60/195-100 60 100
KAT-80/195-60 80 60
KAT-80/195-100 80 100
KAT-80/195-120 80 120
KAT-80/195-150 80 150
TECHNICAL DATA
Rated primary current lpr A 40.......8000A
Rated secondary current Is A 1A, 5A
Rated frequency Hz 50Hz, 60Hz
Class rated burden VA Acc. to customer requirement
Accuracy class Acc. to customer requirement
Insulation level 0,72 / 3 / - kV
Rated short time thermal current lth min. 100*lpr
Insulation class E
Standart IEC, VDE, ANSI, AS, CAN, GOST, etc. 05
CABLE TYPE CURRENT TRANSFORMERS
KATK-60/80
TECHNICAL DATA
Rated primary current lpr A 40-8000A
Rated secondary current Is A 1A, 5A
Rated frequency Hz 50Hz, 60Hz
Class rated burden VA Acc. to customer requirement
Accuracy class Acc. to customer requirement
Insulation level 0,72 / 3 / - kV
Rated short time thermal current lth min. 100*lpr
Insulation class E
06 Standart IEC, VDE, ANSI, AS, CAN, GOST, etc.
KAT-60/130 / 180
TYPE ØD L
KAT-60/250-120 60 120
KAT-130/250-60 130 60
KAT-130/250-120 130 120
KAT-180/250-60 180 60
KAT-180/250-120 180 120
TECHNICAL DATA
Rated primary current lpr A 40.......8000A
Rated secondary current Is A 1A, 5A
Rated frequency Hz 50Hz, 60Hz
Class rated burden VA Acc. to customer requirement
Accuracy class Acc. to customer requirement
Insulation level 0,72 / 3 / - kV
Rated short time thermal current lth min. 100*lpr
Insulation class E
Standart IEC, VDE, ANSI, AS, CAN, GOST, etc. 07
CABLE TYPE CURRENT TRANSFORMERS
KAT-85/98
TYPE ØD L A B
KAT-85/190-95 85 95 95 50
KAT-85/190-150 85 150 150 75
KAT-85/190-205 85 205 205 130
KAT-98/190-95 98 95 95 50
KAT-98/190-150 98 150 150 75
KAT-98/190-205 98 205 205 130
TECHNICAL DATA
Rated primary current lpr A 40.......8000A
Rated secondary current Is A 1A, 5A
Rated frequency Hz 50Hz, 60Hz
Class rated burden VA Acc. to customer requirement
Accuracy class Acc. to customer requirement
Insulation level 0,72 / 3 / - kV
Rated short time thermal current lth min. 100*lpr
Insulation class E
08 Standart IEC, VDE, ANSI, AS, CAN, GOST, etc.
KATK-85/98
1A 5A
1 Primary and 2x2,5 mm² 2x4 mm²
1 Secondary S1-Black, S2-Brown S1-Black, S2-Brown
2 Primary and 3x2,5 mm² 2x4 mm²
1 Secondary S1-Black, S2-Brown, S3-Grey S1-Black, S2-Brown, S3-Grey
TYPE ØD L A B
1 Primary and 2x(2x2,5 mm)² 2x(2x4 mm)²
2 Secondary 1S1-Black, 1S2-Brown 1S1-Black, 1S2-Brown KATK-85/190-95 85 95 95 50
2S1-Black, 2S2-Brown 2S1-Black, 2S2-Brown
2x(3x2,5 mm)² 2x(3x4 mm)² KATK-85/190-150 85 150 150 75
2 Primary and 1S1-Black, 1S2-Brown, 1S3-Grey 1S1-Black, 1S2-Brown, 1S3-Grey
2 Secondary KATK-85/190-205 85 205 205 130
2S1-Black, 2S2-Brown,2S3-Grey 2S1-Black, 2S2-Brown,2S3-Grey
3x(3x2,5 mm)² 3x(3x4 mm)² KATK-98/190-95 98 95 95 50
2 Primary and 1S1-Black, 1S2-Brown, 1S3-Grey 1S1-Black, 1S2-Brown, 1S3-Grey KATK-98/190-150 98 150 150 75
3 Secondary 2S1-Black, 2S2-Brown,2S3-Grey 2S1-Black, 2S2-Brown,2S3-Grey
3S1-Black, 3S2-Brown,3S3-Grey 3S1-Black, 3S2-Brown,3S3-Grey KATK-98/190-205 98 205 205 130
TECHNICAL DATA
Rated primary current lpr A 40.......8000A
Rated secondary current Is A 1A, 5A
Rated frequency Hz 50Hz, 60Hz
Class rated burden VA Acc. to customer requirement
Accuracy class Acc. to customer requirement
Insulation level 0,72 / 3 / - kV
Rated short time thermal current lth min. 100*lpr
Insulation class E
Standart IEC, VDE, ANSI, AS, CAN, GOST, etc. 09
TECHNICAL INFORMATION FOR
SAA SPLIT CORE CURRENT TRANSFORMERS
ASSEMBLY
Split Core Current Transformers have a magnetic circuit which is splitted two parts and its max. operating votage
is 0.72 kV with non-insulated busbars. However they can be used with fully insulated cables on all voltage level. These
transformers can be assembled to the system without any power interruption and without the need of demounting
any conductor.
These transformers are used for measuring and protection.
Moreover; they are used for special applications such as measurement of leakage current with precision cores
which have high magnetic permeability.
In case of an earth leakage the balance of the current in cable is distrupted and the resultant earth leakage current
excites the transformer. Depending on the measurement procedure of the earth fault currents, either a secondary
current or a voltage transformer simply actuates earth fault detectors and/or relays.
10
SPLIT CORE CABLE TYPE
CURRENT TRANSFORMERS
SAA-120
TECHNICAL DATA
Rated primary current lpr A 50.......2500A
Rated secondary current Is A 1A, 5A
Rated frequency Hz 50Hz, 60Hz
Class rated burden VA Acc. to customer requirement
Accuracy class Acc. to customer requirement
Insulation level 0,72 / 3 / - kV
Rated short time thermal current lth min. 100*lpr
Insulation class E
Standart IEC, VDE, ANSI, AS, CAN, GOST, etc. 11
OUTDOOR CABLE TYPE
CURRENT TRANSFORMERS
HKA-100
TYPE ØX L
HKA-100/235-80 100 80
HKA-100/235-100 100 100
TECHNICAL DATA
Rated primary current lpr A 50.......8000A
Rated secondary current Is A 1A, 5A
Rated frequency Hz 50Hz, 60Hz
Class rated burden VA Acc. to customer requirement
Accuracy class Acc. to customer requirement
Insulation level 0,72 / 3 / - kV
Rated short time thermal current lth min. 100*lpr
Insulation class E
12 Standart IEC, VDE, ANSI, AS, CAN, GOST, etc.
HKA-120
120
• Suitable for outdoor aplication
140 • IP66 protection class with aluminium secondary cover.
120
TYPE ØX L
HKA-120/280-120 120 120
TECHNICAL DATA
Rated primary current lpr A 50.......8000A
Rated secondary current Is A 1A, 5A
Rated frequency Hz 50Hz, 60Hz
Class rated burden VA Acc. to customer requirement
Accuracy class Acc. to customer requirement
Insulation level 0,72 / 3 / - kV
Rated short time thermal current lth min. 100*lpr
Insulation class E
Standart IEC, VDE, ANSI, AS, CAN, GOST, etc. 13
OUTDOOR CABLE TYPE
CURRENT TRANSFORMERS
HKA-120/150/180/200/270
TYPE ØX
HKA-120/350-150 120
HKA-150/350-150 150
HKA-180/350-150 180
HKA-200/350-150 200
HKA-270/350-150 270
TECHNICAL DATA
Rated primary current lpr A 50.......8000A
Rated secondary current Is A 1A, 5A
Rated frequency Hz 50Hz, 60Hz
Class rated burden VA Acc. to customer requirement
Accuracy class Acc. to customer requirement
Insulation level 0,72 / 3 / - kV
Rated short time thermal current lth min. 100*lpr
Insulation class E
14 Standart IEC, VDE, ANSI, AS, CAN, GOST, etc.
BUSHING TYPE
CURRENT TRANSFORMERS
15
SINGLE CORE ASSEMBLED
BUSHING CURRENT TRANSFORMERS
APPLICATIONS
Bushing current transformers are designed and used in oil type power and distribution transformers, high voltage
gas insulated systems, medium voltage air-insulated panels and generators for measuring and protection purposes
between 40A and 30.000A primary currents.
According to the application area, woven polyester and polyester film, or their combination are used for their insu-
lation. Transformers can be produced as a single unit or as a set by bringing together more than one unit. Production
feasibilities based on dimension are as follows;
Each Bushing current transformer is 100% routine tested in accordance to the standard which defined on its label
and are reported to our clients. Transformers can be produced as a single unit or as a set by bringing together more
than one unit.
TECHNICAL DATA
Rated primary current lpr A 40....30.000A
Rated secondary current Is A 1A, 5A
Rated frequency Hz 50Hz, 60Hz
Class rated burden VA Acc. To customer requirement
Accuracy class Acc. To customer requirement
Insulation level 0,72 / 3 / - kV
Rated short time thermal current lth min. 100*lpr
Insulation class E or F
16 Standart IEC, VDE, ANSI, AS, CAN, GOST, etc.
CABLE TYPE AND
BUSHING TYPE
CURRENT TRANSFORMERS
CT_IT_2020_R01