Turbine Overspeed Trip Protection PDF
Turbine Overspeed Trip Protection PDF
Turbine Overspeed Trip Protection PDF
by
Charles R. Rutan
Senior Engineering Advisor
Lyondell/Equistar Chemicals, LP
Alvin, Texas
ELECTRONIC TRIP SYSTEM Since the speed sensors are critical to the operation of the
turbine, at least one spare speed sensor is normally installed. If an
API recommends two speed sensors where:
electronic fault tolerant governor is used, then three additional
• “A” or “B” trip signal is seen, then the turbine trips. speed sensors and one spare are installed. A separate speed sensor
• “A” or “B” loss of signal or power, an alarm is given but the is installed for the vibration monitoring system. All the speed
sensors are reading one multitooth “speed pickup wheel” that is
turbine remains running.
being held in position by a nonferrous mounting bracket (Figures
• “A” and “B” loss of signal or power, the turbine trips. 3 and 4). In addition to the speed sensors, two radial vibration
Figure 1 is the simplest system that can be used for a “special probes, two thrust (axial position probes), thrust bearing tempera-
purpose steam turbine.” This system is adequate if the loss of the ture indicators, and radial bearing temperature indicators are
turbine and the equipment driven by the turbine does not result in normally installed. As is readily apparent to the most casual
a significant upset and/or pose a safety hazard and/or damage the observer, the thrust end of the turbine is now taking on the appear-
environment. If a turbine is determined to be in a critical service, a ance of the Starship Enterprise.
fault tolerant overspeed trip system should be utilized. In this case
a minimum of three speed sensors is required where:
• Any combination of two trip signals will result in a turbine trip,
i.e., “A” and “B,” “B” and “C,” or “A” and “C.”
• The loss of power signal or power of any one of the speed
sensors will result in an alarm.
• The loss of power or signal of any two of the speed sensors will
result in a turbine trip.
(Note: This is for a de-energized to trip configuration as preferred
by API.)
the centrifugal force increases from the speed, rpm, the plunger
Figure 5. Mechanical Overspeed Trip Mechanism (Side View). overcomes the spring force causing the plunger to protrude
outward.
A stationary lever, set with a relatively tight clearance, is posi-
tioned such that when the plunger moves out, the lever is struck.
The lever is integral with the emergency mechanical trip device.
When the mechanical trip is actuated, the hydraulic oil is dumped
to the drain, which results in the immediate closing of the valve
rack and trip valve.
The overspeed trip device is critical to the safety of the turbine.
Without the overspeed protection, the turbine would run to destruc-
tion when the load (compressor, pump, or generator) was lost.
How fast the turbine accelerates determines how fast the
overspeed trip system must respond (refer to Figure 10). If the
turbine valves change their position instantaneously, this measure-
ment of time is now as the time constant, TC. The speed is a first
order function of torque, and then the mathematical equation is:
n = − ε − t / TC (1)
Figure 6. Mechanical Overspeed Mechanism Installed in Turbine
Rotor. where:
n = Per unit change, speed
ε = 2.71828
t = Time, seconds
TC = Time constant, seconds
From Equation (1), when t = TC, then n = 1 2 1/ε or n = 0.63.
Figure 8. Mechanical Overspeed Mechanism Disassembled. Figure 10. Overspeed Trip System.
112 PROCEEDINGS OF THE THIRTY-SECOND TURBOMACHINERY SYMPOSIUM • 2003
Then, the rotor time constant gives the length of time that it The speed of the steam inlet valve(s), trip valve(s), solenoid
takes the rotor to reach 63 percent of its total speed change due to valve(s), electronic and/or hydraulic controls or relays, and the rate
an instantaneous change in the turbine valve position. of change of the load are measured relative to the rotor response
The rate of change at the instant the inlet valve’s position time. The understanding of the total system response is critical.
changes are found by differentiating Equation (1) and setting the Any change that requires more than 1/10 of the rotor response time
time to zero. The result is: constant should be considered too slow. It is apparent that the
slower the rotor response time and the load change coupled with a
fast steam control(s) system is very desirable.
dn (2)
LOSS OF LOAD
dt = TC
From Equation (2), dn = 1.0 when dt = TC, which leads to a Loss of the load, prior to this, has been considered instanta-
second definition of the rotor time constant. The rotor time neous. This means that the loss of the load took zero time. The
constant gives the length of time it would take the rotor to reach maximum speed change of the turbine rotor is the result of an
100 percent of its total speed change due to an instantaneous instantaneous loss of load. Thus, what is the difference between the
change in turbine valve position if it continued to change speed at turbine rotor speed response to an instantaneous loss of load as
its initial rate. opposed to a sudden loss of load?
Making the instantaneous valve opening correspond to the full In 0.05 seconds or less, a couple of cycles, a turbine driving an
load change can make the above definition clearer. Thus, the defi- electrical generator can lose full load. This is the type of situation
nition is changed to: the rotor time constant gives the length of where the loss of load must be considered instantaneous. The pro-
time it would take the rotor to reach twice the speed due to a 100 tection system(s) should then be designed accordingly. One
percent instantaneous drop in turbine load, provided the rotor advantage to this situation is that the loss of load can occur without
continued to change speed at its initial rate. the failure of the coupling(s) between the turbine and the generator
This definition is used to generally determine what would and, in some installations, the gearbox. In this situation the time
happen in a very short period of time between the loss of the load constant would include the turbine rotor and the generator rotor,
and the activation of the emergency trip device. It is assumed that WR2. The increase in the overall system rotor time constant will
the steam flow has not been changed and that all relationships are reduce the probability of an overspeed.
linear. Then for an instantaneous change in load and for very small Mechanical drive steam turbines, turbines that drive compres-
values of time: sor(s), pumps, fans, blowers, etc., are entirely different. There are
four ways a sudden loss of load can occur.
• A throttling of the suction, but in this case there would only be
∆ n = L( t TC )
or (3) a partial load reduction. Surging a compressor or breaking suction
of a pump may still require as much as 30 percent of the full load.
The time required to throttle the inlet would require a minimum of
t = ( ∆ n L)TC
where: one second to two seconds. This would only be a problem with
t = Time, seconds very slow 10 second turbines.
• A coupling failure, which is rare in this day and age. There are no
n = Speed change in time “t,” percent
TC = Rotor time constant, seconds
L = Instantaneous load change, percent data on the time; however, in analysis of a few coupling failures, the
complete failure would take one second to two seconds.
• A loss of load due to a process upset takes seconds to be accom-
From Equation (3) it is seen that the rotor TC/10 seconds to
change speed 10 percent if there is an instantaneous 100 percent
change in the load. This is a significant speed change in a short plished. In most cases of a process upset, the loss of load is only
period of time. Thus, extremely fast speed controls and emergency partial. This again gives the system time to respond.
overspeed tripping systems are required to limit the speed rise to a • A catastrophic failure of the discharge piping in close proximity
reasonable value when an instantaneous loss of load occurs. of the driven equipment.
ROTOR TIME CONSTANTS It is apparent, from the discussion above, that a required re-
sponse time of the overspeed trip protection system of one second
The fundamental measure of rotor response is the rotor time is sufficient as a result of a 100 percent sudden loss of load. Again,
constant. From the equation for horsepower, the rotor time constant the response time constant must include the WR2 for all the rotors
can be calculated by substituting the speed and time for accelera- of that drive train.
tion. The rotor time constant is:
TIME LAG AND STORED ENERGY
2
(WR ) (4) During an overspeed situation, there are two reasons the speed
of the rotor will increase above the 110 percent of maximum con-
2
TC = (N ) HP
tinuous speed or high-speed stop. The first is the time lag in the
where: mechanism that closes the steam inlet valves and/or the stop valve.
TC = Rotor time constant, seconds And the second is the steam energy stored in the turbine, nozzle
N = Rated speed, rpm box, valve chest, and piping located between the stop valve and the
WR2 = Rotor inertia, lbs-ft2 steam chest of the turbine.
HP = Rated horsepower By equating the stored energy of the steam to the change in the
The only factor in Equation (4) that depends on the rotor design kinetic energy of the turbine rotor, the change in the rotor speed
of the turbine is the rotor inertia. It, the rotor inertia, cannot be cal- can be determined mathematically. Equation (5) shows the
culated until the design of the turbine is complete. For mechanical maximum speed the turbine rotor can reach above the trip speed
drive turbines the rotor inertia varies considerably, but typically due to the stored energy. Equation (5) is based on the assumption
has an inverse relationship with the speed. The turbine rotor time that the turbine has an efficiency of 60 percent at the design rated
constant, TC, normally lies within a range of two seconds to eight load and steam conditions as the stored energy is used.
seconds. There are rotors with a rotor response as quick as 0.5
seconds and some as long as 10 seconds. (5)
2
(N f Nt ) = +( ( BTU )) WR 2 ( N
t ) 2
TURBINE OVERSPEED TRIP PROTECTION 113
where:
Nf = Maximum speed
Nt = Trip speed, rpm
BTU = Total stored energy
WR2 = Rotor inertia, lbs-ft
The amount of stored energy in the steam chest, nozzle box, and
the turbine case downstream of the nozzle box is extremely
difficult to quantify. In an effort to make things a bit easier,
Equation (5) can be reduced to address the stored energy in the
piping between the trip throttle valve and the steam chest. Thus,
the feet of inlet piping (P) between the trip throttle valve and steam
chest required to reach an overspeed can be calculated.
P= TCV (6)
where:
P = Length of inlet piping between trip throttle valve and turbine
steam chest, feet
TC = Turbine rotor time constant, seconds
V = Steam velocity in inlet piping, ft/sec
With a steam inlet velocity of 150 ft/sec and a 1/2 second time
constant, the length of pipe required to overspeed the turbine from
a trip speed of 110 percent of the rated speed to a maximum speed
of 115 percent of the rated speed would be 7.125 feet of equivalent
pipe. Figure 12. Dual Electronic System.
If the actual overspeed trip of the rotor exceeds the API margin
of error, then action should be taken to address the time lag and/or TESTING
the stored energy. The time lag due to slow response of the system A steam turbine solo is the testing of the turbine with the turbine
can be remedied by the replacement of slow valves with faster uncoupled from the machine train. The soloing of the turbine is
valves and/or increasing the hydraulic pressure in the control oil required to:
• Determine the actual critical speed
system. True stored energy can be addressed by lowering the trip
speed set point of the overspeed protection mechanical or electri-
cal. This, however, can present a problem. If the true trip speed is • Define minimum governor set point (low speed stop)
• Determine maximum governor set point (high speed stop)
above the desired trip speed due to very rapid acceleration of the
turbine rotor but the actual trip speed is within the design parame-
ters at a slow acceleration from the governor high speed stop, then • Test the emergency trip systems
early trips may be experienced. Although the machine is ade- Included in the testing of the emergency test systems is the
quately protected, the early trip may become a problem to the testing of the overspeed trip set point(s). As long as the governor
reliability of the process. This situation can be seen if the WR2 of functions properly, the operation of running up to the overspeed
the equipment train is very low. An example of this would be set point(s) is a conscious decision of the individuals involved in
where a turbine is driving a single compressor, the turbine has 15 the testing. The highest exposure to a potentially dangerous
percent excess power, and the molecular weight of the gas being situation for the individuals and equipment involved is at this
compressed is low. A simple electronic system is shown in Figure point in time.
11, and a dual electronic system is shown in Figure 12. Every company that the author has been associated with,
directly or as a nonpaid consultant, has had a written overspeed trip
test procedure for turbines. In most cases, the procedure is
followed to the letter when testing the large and/or critical turbines.
Typically these procedures define responsibilities, frequency,
exceptions, maintenance activities, safety requirements, and proce-
dures. In the past few years, in addition to the written procedure, a
graphical outline of the procedure for each individual steam
turbine was developed and provided to all the individuals involved
in the overspeed trip testing (Figure 13). This has minimized any
confusion or misunderstanding.
During the research for this paper, it was found that the run to an
overspeed failure of a large/critical steam turbine was rare. It is
believed that this is a result of the amount of attention to the
detailed procedures is at its highest. These situations are typically
on new installations or after an overhaul where sensitivity is at its
highest. With the use of electronic overspeed trip protection and
the upfront testing of the emergency trip system, the overspeed
testing as it relates to speed should be a nonevent. Problems with
high vibration due to rotor bows and rubs, unbalance, damaged
bearings, and improperly installed bearings, etc., are outside the
scope of this paper.
The preliminary steps to validate the safety protection systems
Figure 11. Simple Electronic System. function prior to the physical testing of the turbine overspeed are:
114 PROCEEDINGS OF THE THIRTY-SECOND TURBOMACHINERY SYMPOSIUM • 2003
Incident 2
An incident showing a turbine driving a generator with an
instantaneous loss of load is shown in Figures 17, 18, 19, and 20.
governor oil pump shaft failure. The overspeed trip valve closed,
but not fast enough to prevent a very severe overspeed. No one was
injured during this event.
Incident 5
On 01/01/98, a condensing steam turbine driving a water pump
Figure 17. Turbine Rotor (Incident 2). in the United Kingdom failed during an overspeed trip test. The
turbine was rated for 600 hp at 4643 rpm, with a steam inlet
Incident 3 pressure of 40 psig. Two reed tachometers were used to measure
the turbine speed, and the first trip test was successfully completed
On 02/24/01, a condensing steam turbine driving a blower in a at 5400 rpm. On the second test, the operator reported the reed
steel plant went past the overspeed set point. One individual was tachometer reading was 4900 rpm and heard the trip mechanism
killed and another individual was injured. The turbine developed start to “clatter” as the turbine disintegrated. The operator at the
about 8500 hp and was designed to run at 4100 rpm with the trip throttle valve died on the way to the hospital from the injuries
overspeed trip set at 4500 rpm. The first overspeed trip test was suc- sustained; two other employees received severe injuries requiring
cessful. On the retest, the highest logged speed was 4988 rpm, but multiple surgeries. Debris from the turbine was scattered over a
eyewitness accounts say the reed tachometer showed 5300 rpm. wide radius, and adjacent equipment was damaged. Calculations
show that the blades should not have been overstressed and thrown
Incident 4
below 8000 rpm. The incident investigation concluded that there
A catastrophic failure of a 300 hp, 3600 rpm, boiler feed water may have been a misinterpretation of the turbine speed on the reed
pump drive turbine occurred on 05/30/00. The turbine disin- tachometer, the overspeed trip mechanism malfunctioned, and
tegrated due to overspeed following a coupling failure and a excessive steam flow was available for the test.
116 PROCEEDINGS OF THE THIRTY-SECOND TURBOMACHINERY SYMPOSIUM • 2003
Incident 6
An operator, about 15 years ago, was putting a steam turbine
driven refrigeration compressor online, and he was reading the
speed with a reed tachometer setting on the auxiliary oil pump
turbine, which was normally off. The lube oil pump was running
because the shaft driven governor oil pump had failed. The lube oil
turbine ran at 3600 rpm and the main turbine was designed to run
at 3800 rpm. The operator kept giving the main turbine more steam
because he believed the turbine would not speed up past 3600 rpm.
Calculations showed that the compressor impellers actually flew
apart at 5400 rpm. Pieces of the compressor were thrown through-
out the building barely missing the operator. The overspeed trip
valve should have prevented the turbine from overspeeding, but
the valve was stuck open from steam deposits.
INSURANCE DATABASE
A commercial insurance company (Clark, 2002) has been main-
taining a database concerning overspeed failures. The database
captures, when possible, the:
• Year of the incident
• Size of the turbine
• Driven object
• Why the governor failed to control the speed
• Why the overspeed trip failed
• Other factors/information
This is an excellent database; however, it is not totally accurate.
The database input information is based on information supplied
by companies that are insured by this company and individual
input. If the overspeed incident does not result in major damage
and/or personnel injuries, the incident may not be reported. (Refer
to APPENDIX A for a sample incident table.)
CONCLUSION
A safe, reliable, fast-acting overspeed trip protection system is
required. The system will be tested initially while the turbine is
down and then again, at speed, with the turbine uncoupled from its
load. When the solo testing is performed, the level of risk to the
personnel and equipment is at its greatest. The designer must take
into consideration the instantaneous loss of load while the turbine
is in operation. However, the entire protection system—electrical,
mechanical, and hydraulic components—must perform flawlessly.
Human errors can and must be minimized through training and
practice, but they can never be eliminated. Every turbine must be
treated as the most critical and dangerous piece of equipment in the
plant.
TURBINE OVERSPEED TRIP PROTECTION 117
APPENDIX A
Table A-1. Steam Turbine Overspeed Incidents—Contributing Factors (05/02/97)—#1 through #20.
INCIDENT YEAR SIZE DRIVEN WHY GOVERNOR FAILED TO WHY OVERSPEED TRIP OTHER FACTORS / INFORMATION
NUMBER OBJECT CONTROL SPEED FAILED
1 >5000 hp T/T Valve Stuck Occurred during normal operation; exact
details not known.
2 <5000 hp T/T Valve Stuck Occurred during normal operation; exact
details not known.
3 <5000 hp T/T Valve Not Operational Occurred during uncoupled overspeed trip
test. One fatality. Turbine destroyed.
4 1987 >5000 hp Cent. Retrofitted electronic governor T/T Valve assembled improperly Coupling installed incorrectly during
Compressor improperly configured. System in causing it to not close fast enough turnaround. During process upset,
manual; system ignored to prevent overspeed. Valve was coupling spun on shaft which unloaded
overspeed signal. closed after accident; probably turbine. Turbine oversped to complete
closed due to severe vibration destruction; case could not be repaired.
during accident.
5 1995 >5000 hp Cent. T/T Valve stuck; improperly Coupling broke causing turbine to unload.
Compressor adjusted Coupling improperly installed. Rotor
could not be repaired; case was repaired.
6 1987 >5000 hp Generator Probably stuck due to steam Probably stuck due to steam Details not available, but steam quality
deposits. deposits. was a primary factor. Turbine and
generator oversped to complete
destruction.
7 1987 >5000 hp Details not available.
8 1986 >5000 hp Compressor Valve stuck due to boiler Valve stuck due to boiler carryover Extreme boiler carryover.
carryover deposits. deposits.
9 1960s <5000 hp Recip. Cmpr. Direct mechanical type governor; Either stuck open due to steam Gearbox between turbine and compressor
reason governor did not control deposits or failed to close fast failed which unloaded turbine. Turbine
speed not known. enough. Butterfly type valve. centrifugally exploded; totally destroyed
with damage to surrounding building and
objects.
10 1976 <5000 hp Fan Governor was oil pressure to Stuck due to steam deposits. Nipple on gearbox oil drain line broke
close type. Lost oil, so governor due to fatigue. Without oil, gearbox
went wide open. failed which unloaded turbine. Gearbox
oil also supplied governor system.
Turbine centrifugally exploded; large
sections of case thrown some distance.
Total loss.
11 1995 <5000 hp Fan Governor out of service during Probably, trip setpoint set too high. Turbine oversped during uncoupled
uncoupled trip test. overspeed trip test.
12 1988 <5000 hp Fan Probably steam quality and maintenance
related.
13 1970s <5000 hp BFW Pump Pump was in service - may have rotated
or backwards after turbine tripped due to
1980s stuck check valve. Turbine disintegrated.
14 1980s >5000 hp Cent. Unknown Valve stuck, probably steam Oversped during uncoupled trip test.
Compressor deposits. Stopped turbine by manually tripping
governor valve; should have closed
automatically, but did not.
15 1985 <5000 hp Cent. Pump Steam was off to turbine; turbine Steam was off to turbine, turbine Due to pump check valve sticking open,
driven by pump. was driven by pump. turbine oversped in reverse rotation.
Turbine damaged, but all components
stayed in the case.
16 1985 <5000 hp Cent. Pump Steam was off to turbine, driven Steam was off to turbine, turbine Due to check valve sticking open, turbine
by pump. was driven by pump. oversped in reverse rotation. Same
turbine as above. This time, turbine
centrifugally exploded; turbine destroyed.
17 1996 >5000 hp Generator Design of governor system was Trip valve hung open; probably Operator was shutting down turbine
such that governor did not close steam deposits. Prior to the generator. He decreased load on
when overspeed trip signal was accident, the governor valve had generator, then hit emergency trip button
received or when emergency stop been sticking due to steam deposits, which disconnected load. Trip valve did
button was actuated. During and a spare valve was scheduled to not close. Governor valve was wide
incident, governor sensed falling be installed during next outage. open. Turbine oversped. Exciter
speed and opened governor valve centrifugally exploded.
100%
18 >5000 hp Cent. Cmpr. Hydraulic relay in speed sensing /
trip system stuck preventing
closing of trip valve.
19 >5000 hp Cent. Cmpr. Hydraulic relay in speed sensing / Same plant as above accident; stuck relay
trip system stuck preventing was not diagnosed in first incident, so it
closing of trip valve. caused another accident.
20 >5000 hp Insulation sagged enough to interfere with
the movement of the weighted arm on an
extraction line check valve. When turbine
tripped and check valve did not close,
turbine oversped by backflowing
extraction steam.
118 PROCEEDINGS OF THE THIRTY-SECOND TURBOMACHINERY SYMPOSIUM • 2003
Table A-2. Steam Turbine Overspeed Incidents—Contributing Factors (05/02/97)—#21 through #34.
INCIDENT YEAR SIZE DRIVEN WHY GOVERNOR FAILED TO WHY OVERSPEED TRIP OTHER FACTORS / INFORMATION
NUMBER OBJECT CONTROL SPEED FAILED
21 <5000 hp Governor out of service during OEM trip throttle valve linkage Turbine oversped to destruction.
uncoupled trip test. was so "flimsy" it could be
relatively easily distorted enough
that valve would not trip. After
accident, replaced T/T valve on
five machines with similar linkage.
23 1950 to Turbine oversped during uncoupled or
1996 low load test of the overspeed trip system.
All of the following are from Ed Nelson’s
paper.
24 >5000 hp Generator Governor and/or extraction valve Trip valve stem stuck due to poor Also human error. Operator could not
stuck due to poor steam quality. steam quality. During accident decrease generator load below 10% due to
investigation, trip valve stem could sticking governor valve, but he
not be moved with a 25 ton jack disconnected the load anyway. Should
plus oil and sledge hammer. have shutdown machine by closing steam
block valve.
25 >5000 hp Generator Extraction check valve failed to close
because a sprinkler pipe had been
installed that interfered with the check
valve counterweight arm. Unit tripped
during thunderstorm; then oversped with
extraction steam. Generator exploded; oil
fire ensued.
26 >5000 hp Generator Stuck open; reason unknown. Stuck open; reason unknown. Face of coupling flange not machined
true; bending moment caused solid
coupling to break. Turbine oversped.
Because of extreme destruction, cause of
valves sticking open could not be
determined.
27 >5000 hp Cent. Cmpr. Found closed after wreck. Stuck open; probably poor steam Coupling bolts failed sequentially due to
quality. misalignment. Increasing vibration
ignored by operators. Coupling finally
thrown completely. Turbine parts
demolished exhaust casing.
28 >5000 hp Cent. Cmpr. Coupling hub installed with insufficient
shrink fit; also sharp corners on bore.
Fretting/rubbing caused hub to dig into
shaft. Shaft failed by fatigue. Unloaded
turbine oversped.
29 <5000 hp Cent. Pump Direct mechanical type governor After turbine repeatedly tripped on Turbine was tripping on overspeed
failed to respond fast enough overspeed, operators secured because of restricted pump suction.
when trip valve was suddenly overspeed trip in open position When overspeed trip was defeated with
opened. with bailing wire. bailing wire, turbine centrifugally
exploded. Case was destroyed. One
fatality and one serious injury.
30 >5000 hp Generator During startup, first valve in rack Unknown Generator centrifugally exploded during
system "popped" open. Linkage overspeed. Design of control system
system included a spring which required that turbine be started up on
let valve open more than a more governor valve rather than with a block
rigid system would allow. valve. Due to large pressure differential,
Turbine oversped before governor it is common for first rack valve to "pop"
could gain control. open.
31 >5000 hp Cent. Cmpr. Shaft broke causing loss of Shaft broke causing loss of speed When shaft broke, governor sensed low
governor/speed input. indication. speed and went wide open. Turbine
oversped, but components stayed in case.
Speed limited by compressor load.
Design errors included wrong shaft
material and wrong bearing type.
32 >5000 hp Paper mill Valve stuck open; probably due to Trip valve stem was bent. Also, Operators had been able to start turbine
line shaft steam deposits. switch in trip circuit was wired for years in spite of incorrectly wired
"normally open" instead of switch. However, when governor valve
"normally closed" per OEM’s stuck open, turbine oversped when trip
drawing error. valve was reset during startup. Line
shafts tore loose from bearings and
destroyed a large area.
33 >5000 hp Out of service for uncoupled test. Trip inoperative; was being set at Speed was monitored with strobe light.
manufacturer’s test stand. Operator did not notice shaft was
spinning at twice the strobe flashing
speed. One fatality. Turbine destroyed.
34 1997 <5000 hp Cent. Pump Mechanical overspeed trip system Coupling failed which initiated turbine
had been improperly assembled / overspeed. Reason for coupling failure
adjusted during last overhaul. Trip not known.
bolt functioned, but rest of system
not actuated.
TURBINE OVERSPEED TRIP PROTECTION 119
Table A-3. Steam Turbine Overspeed Incidents—Contributing Factors (05/02/97)—#35 through #53.
Table A-4. Steam Turbine Overspeed Incidents—Contributing Factors (05/02/97)—#54 through #57.