Air Diffuser
Air Diffuser
Al Ghadeer STP
United Arab Emirates
EDI Project # 19343
Prepared For: Prepared By:
Debashis Bhattacharya Tom Mallory
Eagle Electrical Mechanical Company LLC Environmental Dynamics International
PO Box 19973 5601 Paris Road
Dubai, Columbia, MO 65202
+1-573-474-9456
011-9714-267-2269
dbhattacharya@alhijazgroup.net
Local Representative:
Dilip Tanpure
Waterbird WTC
OFF 4TH INTERCHANGE SHAIKH ZAYED ROAD
UMM SUQQUEM ROAD
NEAR MARINA INTERIORS
AL BARSHA, DUBAI
011-971-4-3405961
To limit potential for "galling", EDI recommends that a commercial grade lubricant be used on all
stainless steel threaded connections.
The drop pipe is to be supported by the contractor such that no downward force is transmitted to the
aeration piping system. The stainless steel drop pipe from the air header piping to be supplied by others.
EDI's scope of supply begins at the stainless steel coupling clamp at 1.0 meters above the basin floor.
Reference EDI Drawing(s) #104222, sheets 1-3.
Table of Contents
Warranty Statement - Project 19343.......................................................... 1
Storage Instructions................................................................................... 12
Receiving Inspection.......................................................................................... 12
Installation Instructions.............................................................................. 16
Air Piping Installation.......................................................................................... 16
Installation Instructions for FlexAirP®P SDM Diffuser Units with locking rib on wedge..23
Start-Up Instructions................................................................................... 28
General Aeration/Mixing Systems Start-Up Instructions.................................... 28
Directions for fixing these items can be found in the •Corrective MaintenanceŽ Troubleshooti.
28
Blower Components........................................................................................... 29
Operation Instructions................................................................................ 34
Description of the Aeration-Mixing System........................................................ 34
Shutdown Conditions......................................................................................... 35
Preventive Maintenance............................................................................. 38
Maintenance Schedule....................................................................................... 38
Diffuser Protection.............................................................................................. 38
Maintenance Schedule....................................................................................... 38
Membrane Protection......................................................................................... 39
Corrective Maintenance.............................................................................. 40
Troubleshooting................................................................................................. 40
Diffuser Express.......................................................................................... 42
The warranty provided by Environmental Dynamics International Inc., (EDI) is limited to the terms set
forth in this Warranty Statement. All other warranties, expressed or implied are excluded and
disclaimed in their entirety. EDI gives no other warranty of any kind, nature or description, expressed or
implied, other than the limited warranties set forth herein, and this warranty exclusion includes but is not
limited to warranties of merchantability and warranties of fitness for a particular purpose, both of which
are excluded and disclaimed in their entirety.
Equipment manufactured by EDI is warranted to be free from defects in materials and workmanship for
twenty four (24) months from start up of the equipment or thirty (30) months from shipment, whichever
occurs first.
Defective part(s) shall be remedied by repair or replacement of the defective part(s) only shipped freight
included, FOB original shipping point1. Costs incurred by EDI (on or off site) 2 shall be reimbursed by
the Purchaser / Owner 3 should EDI find a deficiency to not be due to equipment covered by this
warranty.
The following are excluded from this warranty, but shall not be considered to be limiting to other
exclusions: cleaning and de-watering, labor4, equipment manufactured by others5, process and performance
related to system design or biological process performance, decomposition, abnormal wear and/or
damage caused by site conditions; chemical action, chemical precipitate, physical abrasion points or
abrasive materials, water velocities greater than 2 ft/sec or as approved by EDI, blunt trauma forces,
faulty or substandard structural components, faulty or inadequate maintenance/operation6, equipment
and services provided under a contract which is in a current state of default due to non-payment. 7 EDI
exclusively assumes no responsibility of expense or liability for (a) equipment repairs made or contracted
by Purchaser or Owner without EDI’s written consent; (b) modifications to any of EDI's equipment made
by others which are not approved in advance and in writing by EDI; (c) failure of the Owner to
promptly notify EDI of observed defects and or deficiencies which occur during the warranty period (d)
work by others8, (e) field modifications to allow for removal or replacement of EDI components
1
FOB original shipping point; indicates the point of which risk of loss passes
2
Cost incurred include shall not be limited to; travel, housing, labor and materials; that have been expended to research and
repair such deficiency.
3
Responsible party for the equipment at the time of the warranty claim; generally dictated by project status, pre (Purchaser) or
post (Owner) project hand over.
4
Accessing/uninstalling/replacing/reinstalling any parts.
5
EDI does not warranty equipment manufactured by others. “By others” includes but is not limited to: blowers, DO probes,
electrical panels, engines, motors, any electrical apparatus, etc. Such equipment bears warranties of the respective
manufacturers. Labor costs associated with warranty repairs of equipment manufactured by others shall be borne by others.
6
Please refer to your EDI IO&M manual for maintenance and operation instructions.
7
Default due to non-payment shall not include EDI approved holdbacks.
8
Work by Others shall include but not be limited to; materials furnished or labor provided by any contractor, subcontractor or
material supplier not working directly for or directly under EDI.
Page1 www.wastewater.com
Environmental Dynamics International aeration for life™
2 7
3
5
Page2 www.wastewater.com
Environmental Dynamics International aeration for life™
Page3 www.wastewater.com
Environmental Dynamics International aeration for life™
NOTES:
All calculations included in these tables are estimates and should only be used as a guideline for design of the system. Specific operating
conditions such as initial start-up, aging of membranes, standby blowers started for emergency situations, etc., are not accounted for in these
calculations. Provisions and/or safety factors to account for these conditions must be considered and added when designing the overall system.
Also account for differences between positive displacement blowers and centrifugal blowers during design. Contact EDI for design assistance.
The piping segments analyzed had the path of highest resistance to airflow. "Equivalent Length" refers to the pipe segment length plus the
equivalent length of pipe due to fittings/valves (based on Crane Company data).
A diffuser "unit" is defined as a single membrane or component; not a full diffuser assembly.
The airflow capacity of each diffuser unit in this application is 40 (Nm3/h)
Operating the diffuser at the high end of the range will result in reduced performance and increased operating pressure. Use the maximum airflow
range for short term operations such as peak loads or system maintenance.
Uniformity: At the Design airflow, this system will provide 97% of the initial airflow to the last diffuser.
Therefore, uniformity among diffusers on a common unvalved section is ± 1.7% .
Page4 www.wastewater.com
Environmental Dynamics International aeration for life™
NOTES:
All calculations included in these tables are estimates and should only be used as a guideline for design of the system. Specific operating
conditions such as initial start-up, aging of membranes, standby blowers started for emergency situations, etc., are not accounted for in these
calculations. Provisions and/or safety factors to account for these conditions must be considered and added when designing the overall system.
Also account for differences between positive displacement blowers and centrifugal blowers during design. Contact EDI for design assistance.
The piping segments analyzed had the path of highest resistance to airflow. "Equivalent Length" refers to the pipe segment length plus the
equivalent length of pipe due to fittings/valves (based on Crane Company data).
A diffuser "unit" is defined as a single membrane or component; not a full diffuser assembly.
The airflow capacity of each diffuser unit in this application is 79 (Nm3/h)
Operating the diffuser at the high end of the range will result in reduced performance and increased operating pressure. Use the maximum airflow
range for short term operations such as peak loads or system maintenance.
Uniformity: At the Design airflow, this system will provide 94% of the initial airflow to the last diffuser.
Therefore, uniformity among diffusers on a common unvalved section is ± 3.2% .
Page5 www.wastewater.com
Environmental Dynamics International aeration for life™
NOTES:
All calculations included in these tables are estimates and should only be used as a guideline for design of the system. Specific operating
conditions such as initial start-up, aging of membranes, standby blowers started for emergency situations, etc., are not accounted for in these
calculations. Provisions and/or safety factors to account for these conditions must be considered and added when designing the overall system.
Also account for differences between positive displacement blowers and centrifugal blowers during design. Contact EDI for design assistance.
The piping segments analyzed had the path of highest resistance to airflow. "Equivalent Length" refers to the pipe segment length plus the
equivalent length of pipe due to fittings/valves (based on Crane Company data).
A diffuser "unit" is defined as a single membrane or component; not a full diffuser assembly.
The airflow capacity of each diffuser unit in this application is 79 (Nm3/h)
Operating the diffuser at the high end of the range will result in reduced performance and increased operating pressure. Use the maximum airflow
range for short term operations such as peak loads or system maintenance.
Uniformity: At the Design airflow, this system will provide 94% of the initial airflow to the last diffuser.
Therefore, uniformity among diffusers on a common unvalved section is ± 3.2% .
Page6 www.wastewater.com
Environmental Dynamics International aeration for life™
Customer:
Eagle Electrical
Attn: Mr. Teddy Joseph
Page 1 v.20111006
Page7 www.wastewater.com
Environmental Dynamics International aeration for life™
DB - 4228
2
(19) Active surface area per diffuser tube 380 in 2452 cm2
(20) Air release depth of diffusers 14.27 ft 4.35 m
2
(21) Tank floor surface area 3147 ft 292 m2
(22) % Oxygen transfer, SOTE 25.2 % 25.2 %
(23) lb oxygen per h per tube, SOTR 1.51 lb O2/h/unit 0.69 kg O2/h/unit
(24) Winter surface saturation, Csmt 8.42 mg/L 8.42 mg/L
Summer surface saturation, Csmt 6.84 mg/L 6.84 mg/L
(25) Effective depth correction factor 0.40 0.40
(26) Standard condition aerated O2 saturation in the tank, 10.62 mg/L 10.62 mg/L
C*20=9.09*(29.92+0.8828*Item20*Item 25)/29.92
(27) Theta value= 1.024 1.024
(28) AOR/SOR=ALPHA[BETA(C*20)(Csmt/9.09)(Psite/Psc)-
(Item 9)](THETA)^(Item 10-20)/(C*20)
Winter AOR/SOR 0.453 0.453
Summer AOR/SOR 0.458 0.458
(29) Number of EDI FlexAir™ tube membranes required for oxygen
demand (Item 17) / [(Item 23) x (Item 28)] 88 units 88 units
(30) Air requirements for oxygenation (Item 18) x (Item 29) 504 scfm 799 m3N/h
857 m3S/h
2
(31) Assumed Mixing Design Criteria (air requirements) 0.12 scfm/ft 2.05
(32) Air requirements for mixing (Item 31) x (Item 21) 378 scfm 598 m3N/h
642 m3S/h
(33) Number of tube membranes for mixing and/or proper distribution 88 units 88 units
3
(34) Airflow per tube (mixing only) 4.29 scfm per unit 6.80 m N/h per unit
7.29 m3S/h per unit
(35) Design diffuser air fluxrate based on oxygenation or
mixing requirements, use the larger. 2.17 scfm per ft2 37.0 m3N/h/m2
39.7 m3S/h/m2
(36) Diffuser Density: (Area of Tank/Area of Diffusers) ratio
[floor area/(# diffusers x active diffuser area)] 13.55 13.55
(37) Estimated system operating pressure:
(a) Static liquid head 14.27 ft 4.35 m
(b) Pressure loss at blower building and header (estimated) 1.50 ft 0.46 m
(c) Pressure loss lateral piping (estimated) 0.50 ft 0.15 m
(d) Pressure loss though FlexAir™ tube (estimated) 1.50 ft 0.46 m
(f) Normal compressor operating pressure (a+b+c+d) 17.77 ft 5.42 m
(38) Normal operating pressure (estimated) 7.70 psig 531.38 millibar
(39) Design over-pressure APPROXIMATE 0.50 psig 34.48 millibar
(40) Recommended blower design pressure 8.20 psig 565.86 millibar
Notes:
Page 2 v.20111006
Page8 www.wastewater.com
Environmental Dynamics International aeration for life™
Consulting Engineer:
Digester Tanks
(6) ALPHA = Ratio of oxygen transfer in waste 0.40 Alpha 0.40 Alpha
to transfer in tap water
BETA = Ratio of solubility of oxygen in 0.95 Beta 0.95 Beta
wastewater to solubility in tap water
(7) Site Elevation 164.04 Feet 50.00 meters
(8) Operating ambient pressure, winter 14.62 psia 1007.60 millibar
Operating ambient pressure, summer 14.62 psia 1007.84 millibar
(9) Dissolved O2 level in the aeration basin 2.00 mg/l 2.00 mg/l
(10) Temperature of waste in aeration basin:
Winter Temperature 75.20 ºF 24.00 ºC
Summer Temperature 96.80 ºF 36.00 ºC
(14) Carbonaceous oxygen requirements for aeration 0.00 lb O2/day 0.00 kg O2/day
at field conditions (Item 11)x(Item 12)x(Item 13)
(15) Ammonia to aeration basin a) concentration 0.00 mg/l 0.00 mg/l
b) weight/day 0.00 lb/day 0.00 kg/day
Page9 www.wastewater.com
Environmental Dynamics International aeration for life™
DB - 4229
3
(18) Air supply for each EDI MaxAir™ diffuser unit 13.50 scfm 21.384 m N/h
2 2
(19) Active surface area per diffuser unit 0 in 0 cm
3 3
(21) Effective Tank Volume 8674.694733 ft 246 meters
(22) Volumetric Aeration Energy (Scfm/tank volume) 41.21 scfm 2305.27 m3N/h
3
1000 ft 1000 m3
(23) % Oxygen transfer, SOTE 13.0 % 13.0 %
(24) Lbs oxygen per hour per unit, SOR 1.832 lb O2/hr/unit 0.831 kg O2/hr/unit
(27) Standard condition aerated O2 saturation in the tank, 9.83 mg/l 9.83 mg/l
C*20=9.09*(29.92+0.8828*Item20*Item 26)/29.92
(29) AOR/SOR=ALPHA[BETA(C*20)(Csmt/9.09)(Psite/Psc)-
(Item 9)](THETA)^(Item 10-20)/(C*20)
Winter AOR/SOR 0.2954 0.2954
Summer AOR/SOR 0.2966 0.2966
3
(31) Air requirements for oxygenation (Item 18)x(Item 30) 357.49 scfm 566.266 m N/h
(32) Number of tubes for mixing and/or proper distribution 28 units 28 units
3
(33) Airflow per unit (mixing only) 5.30 scfm 8.395 m N/h
3
(34) Air requirements for mixing (Item 32) x (Item 33) 148.40 scfm 235.066 m N/h
NOTES:
Page 2
Page10 www.wastewater.com
Environmental Dynamics International aeration for life™
Storage Instructions
Receiving Inspection debris, etc.) into the pipe. Any foreign
r.2011-10-12 materials that are allowed to contaminate
the pipe will need to be removed from the
(FOB EDI only) Shipments shall be
system prior to installation and start-up.
inspected for damage upon receipt. The
recipient/receiver is responsible for all Piping shall be stored on a flat surface to
damages. EDI offers to act on behalf of avoid damaging the pipe sections.
the recipient / receiver in filing a claim If the pipe components are to be stored for
for damage incurred during shipment. more than 6 months, pipe sections are to be
To file a claim against the freight shaded from sunlight.
company, a damage report must be Accessories such as pipe supports,
submitted to EDI within 24 hours of fasteners, etc., packaged in original boxes
delivery. are to be protected from excessive moisture
(FOB Jobsite only) Shipments shall be and rain. Outdoor storage is acceptable
inspected for damage upon receipt. Any provided the ambient air temperature is
damages observed upon receipt must below 140°F (60°C).
be reported to EDI within 24 hours of Small items should be stored in a secure
delivery. EDI will repair or replace location to avoid misplacement and theft.
damaged goods when notified within
this notification period.
(Ex-Works only) Shipments shall be Pre-Installation Storage
inspected for damage upon receipt. The Requirements for a Coarse
recipient/receiver is responsible for all Bubble System
damages. To file a claim against the r.2011-10-12
freight company, file a damage report
Components may be stored outdoors
directly with the shipping company. provided the ambient air temperature is
A full inventory of shipped components below 140ºF (60ºC).
shall be completed within 14 days of the
receipt of shipment. Any deficiencies in
the shipment that are clearly deemed to Post-Installation Storage
be the result of EDI will be reconciled by Requirements for a Coarse
EDI when notified within this time Bubble System
period. r.2011-10-12
When the reactor is drained and the
Pre-Installation Storage aeration system is exposed for a short
Requirements for Plastic Piping period of time (less than 6 months), the
system shall be protected from foreign
r.2011-10-12
objects including but not limited to paint or
PVC, CPVC and ABS piping components weld splatter, falling objects, etc.
may be stored outdoors provided the
• If the ambient air temperature is above
ambient air temperature is below 140°F
140°F (60°C), the system should be
(60°C).
shaded to protect the system from UV
Pipe sections are furnished with end caps to light and excessive heat. A gray fabric
minimize the entry of foreign materials (dirt, tarp is recommended to shade the
Page11 www.wastewater.com
Environmental Dynamics International aeration for life™
Page12 www.wastewater.com
Environmental Dynamics International aeration for life™
When the aeration system is to be idle for When the aeration system is to be idle for
an extended period time (greater than 4 to 6 an extended period time (greater than 4 to 6
weeks), the system should be submerged in weeks) and the units are going to be
approximately 4 feet of clean water provided removed and stored, then the following
the ambient air temperature is greater than storage conditions would apply.
32°F (0°C).
• If the ambient air temperature is going to
• If the ambient air temperature is below be less than 100°F (40°C), then a fabric
32°F (0°C), the water level may need to tarp is recommended to cover the
be increased so that the ice layer does equipment.
not contact the aeration system.
• If the ambient air temperature exceeds
• When reactivating a system where ice 100°F (40°C), then the equipment shall
exists, operate the system at a minimum be shaded or stored indoors in which
airflow to avoid movement of ice and the ambient air temperature does not
maintain this airflow condition until the exceed 125°F (52°C).
ice is no longer present.
• The water level should never be lowered
if ice is present. The weight of the ice
may damage the system.
Page13 www.wastewater.com
Environmental Dynamics International aeration for life™
Page14 www.wastewater.com
Environmental Dynamics International aeration for life™
Installation Instructions
Air Piping Installation with a sequence number that indicates that
r.2011-10-13 segment’s position in the lateral run.
Additionally, EDI will provide an arrow on
The Contractor is to confirm that the air the lateral piping. This arrow indicates the
piping is clean during fabrication of laterals direction of airflow in the lateral segment.
and should swab out any debris found in the All arrows should point away from the
pipe before installing the diffuser units. Dirt header toward the lateral end at final
and debris may clog the diffuser unit installation.
requiring an extended start-up procedure
and MAY require the Contractor to remove
and replace diffuser unit at Contractor's Stainless Steel Coupling Clamp
expense. If piping requires further cleaning Installation
before diffuser installation, Contractor may r.2012-11-16
elect to perform water flush or air purge
procedures described at the conclusion of The stainless steel coupling clamp is
this section. NOTE: If this procedure is provided by EDI to make the proper
performed, do so before installing the transition between two sections of pipe.
diffusers. 1) Make sure the pipe is clean. Remove
Transition from the drop pipe to the air any dirt or debris that would interfere
lateral piping is made by a stainless steel with the complete sealing of the gasket
coupling clamp provided by EDI. The around the pipe. Lubricate both the pipe
aeration system typically features a drop and clamp gasket with soapy water. Do
stub designed to be field cut to length and not use oil base pipe lubricant.
solvent welded to the air laterals by 2) Ensure that the pipes are properly
Contractor. The pipes must be aligned aligned prior to installing the clamp or
vertically prior to installing the coupling the clamp may leak. If the clamp is to
clamp or the clamp may leak. The clamp be installed on vertical pipe the pipes
has limited ability to seal misaligned piping. must be aligned vertically before
Also, the gap between the drop pipe and installing the clamp. The clamp has
drop stub shall be less than 0.25”(6.5 mm) limited ability to seal misaligned piping.
to ensure proper sealing of the coupling Also, the gap between the two pipes
clamp. shall be less than 0.25”(6.5 mm) to
Assemble the aeration piping per the EDI ensure proper sealing of the coupling
layout drawing. Start with the drop pipe clamp.
section to ensure proper drop pipe
alignment. Pipe supports should be partially
assembled with the bottom pipe strap, then
placed under the drop pipe section for
support. Pipe support assembly instructions
are in the following section. See the EDI
layout drawing for pipe support locations.
Do not install the anchor bolts until the final
alignment is established for the complete
aeration grid. The remaining air lateral
piping shall be installed using this same
method. All piping segments will be labeled
Page15 www.wastewater.com
Environmental Dynamics International aeration for life™
Page16 www.wastewater.com
Environmental Dynamics International aeration for life™
Page17 www.wastewater.com
Environmental Dynamics International aeration for life™
Installation of the Manual Purge cut the hose to final length at this time.
The discharge hose should be installed
Assembly with minimal bends and turns. Once the
r.2011-10-13
orientation of the discharge hose is
A manual purge assembly has been confirmed, secure the discharge hose
provided to remove accumulated on minimum 3-foot (.9m) centers using
condensation from the EDI aeration system. cable ties provided. If sufficient tie off
locations are not available, additional
1) Connect threaded elbows to the ball
anchorage points may be required and
valve and tighten by hand. Use pipe
are to be supplied by others.
dope on threaded connections.
7) Thread the purge ejector pipe into
2) Using a strap wrench on the valve body
factory installed threaded outlet located
and a closed end wrench on the fitting
on the crown (top) of the pipe section
and noting the proper orientation of the
and tighten by hand. Use pipe dope on
fittings and the valve, further tighten the
threaded connection. Do not use Teflon
fitting an additional one to two threads
tape. Insert the ejector until hand tight.
past hand tightness. Avoid excessive
torque as this may cause thread
damage.
3) Mount valve at the desired location with
PE pipe straps. Anchorage components
are not included and are to be supplied
by others.
Page18 www.wastewater.com
Environmental Dynamics International aeration for life™
excessive torque as this may cause 12) Secure the hose to the drop pipe with
thread damage or damage to the factory cable ties installed 3 ft. (1 m) on center.
installed threaded outlet. If damage to
the ejector pipe or factory installed Installation Instructions for PVC
threaded outlet occurs, contact EDI.
MaxAir Diffuser Units
9) Confirm the required length to secure r.2011-10-13
the purge discharge hose to the ejector
pipe and cut the discharge hose to final To prevent damage during shipment, EDI
length. provides the Spectrum diffuser mount and
10) Insert the purge discharge hose onto the diffuser units for field mounting. The
barbed end of ejector pipe until the hose diffuser unit is factory-mounted to the
contacts the base of the barbed fitting. bottom section of the Spectrum diffuser
The hose end should be square to mount. Other materials/tools required for
ensure full engagement with the fitting. installation include: Spectrum locking
wedge and saddle, O-ring and rubber
mallet.
Prior to installation, ensure that all air piping
is clean and free of debris. When blower
assemblies, header piping, air laterals, and
all units are properly installed, system is
ready for start-up. Refer to "Start-Up
Instructions" for details.
Lateral piping has outlet holes predrilled at
the factory. Pipe surface must be smooth,
clean, and free of all grease and dirt.
Page19 www.wastewater.com
Environmental Dynamics International aeration for life™
Page20 www.wastewater.com
Environmental Dynamics International aeration for life™
Page21 www.wastewater.com
Environmental Dynamics International aeration for life™
Page22 www.wastewater.com
Environmental Dynamics International aeration for life™
Interlocking Ribs
Page23 www.wastewater.com
Environmental Dynamics International aeration for life™
RED
Perforat Ear of “TOP”
Unit Type ion Clamp Sticker
MiniPanel On Top On Top On Top
Page24 www.wastewater.com
Environmental Dynamics International aeration for life™
Page25 www.wastewater.com
Environmental Dynamics International aeration for life™
Page26 www.wastewater.com
Environmental Dynamics International aeration for life™
Start-Up Instructions
General Aeration/Mixing valves to expel water that may be in the
piping. Close the purge valves once all
Systems Start-Up Instructions water has been expelled.
r.2012-07-13
3) Check for minor leaks by completing the
These instructions cover the general start- following steps. Turn the airflow down
up requirements for the aeration system. to very minimal release. If the system
Special start-up requirements outlined in the employs separate drop valves, each grid
Engineer's specifications, contract can be checked separately by throttling
documents, or instructions offered by EDI the valve the valve one at a time.
shall be supplementary to or take Again, take care not to exceed airflow
precedence over these general instructions. capacities in neighboring aeration grids
An overview of start-up procedures is when reducing airflow by this method.
related below: The airflow will not be uniform at this low
1) Confirm that piping and diffusers are level. This is acceptable, as this test is
level by filling the basin with water until only used to check for small leaks that
the diffusers are 1" to 2" under water. are not visible with the design amount of
Diffuser elevation tolerance should be airflow. Check for any observed leaks
within the approved tolerance for the and repair as required.
respective diffusers. Adjust supports or Leaks commonly occur due to:
diffusers as required.
a. missing or misaligned o-ring
a. Fixed Grid Disc System less than
±1/4” b. torn membranes
b. Fixed Grid StreamLine System less c. loose disc retainer ring
than ±1/4”
Directions for fixing these items
c. Fixed Grid Magnum System less can be found in the “Corrective
than ±1/2”
Maintenance” Troubleshooting
d. Fixed Grid MiniPanel System less r.2012-08-02
than ±1/2”
The diffused aeration system supplied
e. Fixed Grid MaxAir System less than requires very little maintenance for long-
±1/2” term operation. Periodic visual inspection of
f. Floating Lateral System less than the system should allow the Operator to
±1/2” determine if the system is performing at
optimum levels. For example, diffuser unit
g. Submerged Lateral System less elevation variations greater than the design
than ±1.0” tolerance, typically ± 1/2" (13mm) will
2) Activate the blower and introduce air to reduce the uniformity of air distribution in
the aeration system. Take note not to the system. In addition, operating airflows
exceed the airflow capacity of the below the design condition will also reduce
system (see headloss calculations the uniformity of air distribution. If operating
provided in the submittals). At 50% conditions warrant airflow rates below the
design air capacity, check piping and design condition, contact EDI for additional
diffusers for obvious leaks, and repair as operational guidelines.
required. Open any manual purge
Page27 www.wastewater.com
Environmental Dynamics International aeration for life™
Below are symptoms and procedures to ends of the membranes at initial start-
follow if inspection of the aeration system up. This is normal and can be expected
reveals abnormal operation: until the membranes are submerged for
a period of time. These small leaks will
Large volume of air in localized area.
stop once the membranes are wetted for
Possible Cause: a period of time, especially for
1) Air leak in aeration piping. polyurethane membranes (up to 2-4
weeks). This is also true for uniformity of
Procedure: ceramic media (if supplied).
1) Access area in question. Inspect joints Reopen the valve as inspection is
for evidence of breakage. completed to each aeration grid, and
Decreased diffuser activity and repeat procedure for the next grid.
increased back pressure noted at 4) Once all deficiencies have been
blower. corrected, maintain air to the system
Possible Cause: and continue filling the basin until the
design depth is reached.
1) Diffusers becoming fouled.
Blower Components
2) Reduced blower discharge air volume.
See the blower installation and start-up
3) Restriction in air header. instructions to assure all blower
Procedure: components are mounted properly and
ready for operation. When EDI provides the
1) Access diffusers and inspect for external blower assemblies, detailed installation and
or internal fouling. start-up instructions are provided in the
2) Confirm blower operating point and rpm blower submittal package.
reading. Blower components should be fully installed
3) Confirm isolation valve position on and fully serviced prior to making final
header and drops. electrical connections and starting up the
aeration system.
Dissolved oxygen profile not satisfactory
throughout basin. Precautions should be taken throughout
system installation to minimize the
Possible Cause: discharge of airborne particles to the
1) Increased loading to system. aeration system. As a minimum, an air inlet
filter should be installed and operated
2) Reduced blower discharge air volume. during blower servicing procedures. EDI
3) Improper distribution of air in system. recommends a filter efficiency of 93% of 10-
microns. Any solvents used to clean blower
4) Air leak in system. should be bypassed from the aeration
Procedure: piping. The discharge of airborne
particulate matter or solvent into aeration
1) Confirm loading to system. piping may result in damage to diffuser
2) Confirm blower operations. membranes.
3) & 4) See items 1 and 2 above. Upon completion of blower manufacturer's
recommended service, the subsequent
start-up procedures may be followed.
section of this manual.
NOTE: Polyurethane membranes (if
supplied) may exhibit small leaks at the
Page28 www.wastewater.com
Environmental Dynamics International aeration for life™
General Air Piping the cap from the PRV or by opening the
blow-off valve.
Contractor is to confirm the cleanliness of
the air piping. If existing header piping is 2) When the basin has been filled, note the
used, the air purge or water flush cleaning operating pressure at the blowers. The
procedure is recommended prior to pressure relief valve should be adjusted
installation of diffuser units to remove any to free-flow at approximately 1 psig
internal debris that may have accumulated above the normal operating pressure of
in the header piping. Inspect air piping and the system.
diffuser connections for loose fittings or
3) To confirm the PRV operates, partially
damaged pipe. Damaged piping sections
close blower shut-off valve until PRV
and connections should be repaired prior to
releases air. Reopen the shut-off valve
commencing system operations.
to confirm that PRV will reseat. If
Initial System Start-Up required, readjust the PRV to the
recommended setting per instructions in
To start the system, completely open all
the Blower IOM manual.
valves in the air supply system, including
blower shut-off valves, header valves and 4) To properly assess the airflow
lateral isolation/throttling valves. This distribution on the aeration system, the
instruction assumes that uniform water level blower system must be operating at the
is present in all aerated basins served by a design operating point. On dual blower
common blower. If varying water levels are systems, design airflow is typically
present, basins with lower water levels will achieved by operating one blower at
need to have the valve to that basin 100%. On three-blower systems,
throttled back to avoid improper air design airflow is typically based on
distribution. Failure to completely open all operating two blowers at 100%.
valves may result in over-pressuring blower
5) Airflow distribution adjustment between
unit, release of pressure relief valve, motor
laterals should not be conducted until
overload, or poor air distribution in aeration
the full operating depth is obtained and
system with the potential of exceeding
the blower system has been in operation
airflow capacity to diffuser units and
for several days. Small adjustments
damaging the diffuser membranes.
may be made to the isolation/throttling
Once valve positions have been confirmed, valves on the laterals receiving the most
blower unit may be started. EDI does not air. System balancing should be
recommend starting multiple blower units at completed on an incremental basis.
initial system start-up. Subsequent blowers Changes in airflow distribution may
should be brought on-line after the system require 2-8 hours to fully stabilize when
has equalized and uniform diffuser activity is fine-tuning a system. In addition, in
observed throughout the system. situations where multiple basins are
employed and varying water levels exist,
Use blower manufacturer’s recommended
adjustments of lateral valves will be
start-up procedures. EDI recommends that
required to maintain air distribution in
initial pressure surge be reduced through
the tanks.
PRV or blow-off valve.
EDI recommends that the system Operator
Start-up procedures should follow the basic
contact EDI at 573-474-9456 prior to
guidelines as listed below:
making any adjustments to the airflow
1) When starting initial blower, the PRV or distribution.
blow-off valve should be used to reduce
the start-up pressure surge. This is
accomplished by removing weights and
Page29 www.wastewater.com
Environmental Dynamics International aeration for life™
Page30 www.wastewater.com
Environmental Dynamics International aeration for life™
Safety Considerations
Safety Considerations 3) Slippery basin floor.
r.2011-10-13
Precautions:
The diffused aeration system supplied on
this project has no moving parts and poses 1) Avoid access ways without railings.
little to no risk of injury to operations staff. 2) Provide emergency exits/access.
However, routine maintenance may expose
personnel to potential hazards. EDI has 3) Appropriate personal safety equipment.
listed below potential hazards and
recommended precautions when
maintenance procedures are required for Maintenance of Diffuser Units: Tanks
the aeration components. Full
Precautions: Precautions:
2) Use “buddy system” during maintenance 2) Use buddy system and follow standard
activities. safety procedures.
Page31 www.wastewater.com
Environmental Dynamics International aeration for life™
Page32 www.wastewater.com
Environmental Dynamics International aeration for life™
Operation Instructions
Description of the Aeration- determine the aeration system performance.
In regulating the system airflow to control
Mixing System dissolved oxygen levels, the diffuser units
r.2011-10-13 should be operated within their minimum
The aeration-mixing system employs a main and maximum airflow limits.
air header and valved lateral piping system In applications where water level variations
to distribute air throughout the basin. EDI may exist between aeration basins supplied
normally designs the aeration system piping by a single blower, the isolation valves may
to provide uniform air distribution without need to be adjusted to maintain adequate
adjustment to the isolation/throttling valves airflow distribution. This normally requires
on the laterals. However, these valves are valving back the air to the basin with the
typically provided for direct control of airflow reduced water level. NOTE: It is important
distribution on large aeration systems or for to confirm the operating airflow range of the
process control. Airflow distribution will be diffuser units before valving back any
reviewed at the time of start-up by an EDI isolation valve. Damage could result to the
field service representative. If process aeration diffuser if airflow is above the
demands dictate a revised airflow recommendations noted in the Headloss
distribution pattern, contact EDI for Calculations. Please consult EDI
guidance on modification to the system. Engineering Department to confirm
Normal Operation of the Aeration System operating procedure before adjusting any
aeration isolation/throttling valve.
The following procedures should be
followed on a regular basis to assure Normal Operation of the Blower System
consistent and satisfactory performance of The Aeration-Mixing System normally
the aeration-mixing system. utilizes a centrifugal or positive
The air rate to the system may be adjusted displacement (PD) blower system consisting
to maintain the desired dissolved oxygen of one or more blower units for normal
levels in the basin. When adjusting the operation plus one on-line spare unit. All
airflow rate, the diffusers should be blower units including the spare unit must
operated within the normal operating range be operated on a regular basis to maintain
of the diffuser. Excessive airflow rates will their proper working condition. EDI
result in high pressure drops across the recommends that blower units be operated
diffuser and reduced oxygen transfer sequentially with idle blower units brought
performance. Low airflow rates may result on-line weekly. EDI does not recommend
in incomplete utilization of the diffuser the simultaneous operation of on-line and
membrane and reduced air distribution. spare blowers for an extended period. This
operating condition may deliver airflows
The aeration-mixing system is designed to exceeding the air capacity of the diffuser
provide uniform aeration. Positive dissolved units.
oxygen concentrations should be present
throughout the entire system during normal All blower components should be serviced
operation. A dissolved oxygen profile on a regular basis. For additional
analysis may be used to confirm the information concerning proper blower
performance of the aeration system. operation, service requirements or service
Typically, the dissolved oxygen levels are intervals, reference the Blower Operation
measured at the inlet, the outlet, and the and Maintenance manual.
midpoint locations of each basin to
Page33 www.wastewater.com
Environmental Dynamics International aeration for life™
Page34 www.wastewater.com
Environmental Dynamics International aeration for life™
aeration system. EDI has provided a the valve until only air remains. Close the
manual purge assembly to remove this ball valve once the purging process has
accumulation from the pipe while the been completed.
system is in operation. On a monthly basis,
open the ball valve at the top of the purge
assembly. Allow the water to exit through
Page35 www.wastewater.com
Environmental Dynamics International aeration for life™
Page36 www.wastewater.com
Environmental Dynamics International aeration for life™
Preventive Maintenance
Maintenance Schedule is dependent on the type of surface foulant,
r.2012-08-02 water pressure, distance from unit, etc.
Typically, 5 to 10 seconds are required per
The EDI diffuser unit supplied is a coarse unit.
bubble aeration device that requires minimal
maintenance. With proper operation and Manual Cleaning: Remove any significant
maintenance, this diffuser will provide years accumulation of attached debris. Minor
of long-term performance. surface deposits need not be removed for
operating performance.
EDI recommends that the diffusers be
inspected during normal basin drain-down Diffuser Protection
periods. The aeration system is designed to Good air filtration is recommended for both
allow the diffusers to be accessed by the aeration system and blower system.
dropping the water level in the basin being Typically, roughing filters with a nominal
serviced. The air to the basin being efficiency of 93% removal of 10-micron
serviced should be adjusted to maintain the particles are recommended. Follow blower
recommended minimum airflow rate to the manufacturer’s recommendations regarding
diffusers until the basin is completely care and maintenance of inlet filters.
drained down.
A minor degree of surface deposits or slime
Diffused Aeration System Inspection will build up on the diffuser units over time.
All system components should be inspected This material typically does not impact the
for general wear or damage. This includes operation of the diffuser. In applications
but is not limited to: where a large amount of stringy material
exists, a significant amount of debris may
• Pipe supports including anchor bolts, accumulate on the unit. This material
pipe straps and fasteners. should be removed on a regular basis to
avoid mechanical damage to the diffuser
• Pipe connection including fasteners,
shifts in alignment of pipes and unit.
joints.
• Diffuser assembly including position, Maintenance Schedule
diffuser integrity, etc. r.2011-10-13
• Purge assembly components (if EDI recommends accessing the FlexAir
applicable) including all connections, aeration system on a regular basis
anchor points, and wear at any (annually) to visually inspect the overall
contact points. system and clean the membranes to
remove any accumulated foulants. This
Any worn or damaged components need to activity is beneficial to the Owner, as a
be repaired or replaced. Please contact
reduction in the uniformity of air release or
EDI for assistance in identifying a root an increase in backpressure will impact the
cause and solution.
power use. The FlexAir aeration system is
In Situ Cleaning of Membrane designed to allow the system to be
accessed by dropping the water level in the
If it becomes necessary to remove loose
basin being serviced. Note: to prevent
surface deposits on the diffuser, a low-
solids from entering the system, it is
pressure hosing method is effective. The
important to keep the air flowing through
length of time required to remove deposits
the system until the water level has
Page37 www.wastewater.com
Environmental Dynamics International aeration for life™
dropped below the lateral piping. The air EDI for assistance in identifying a root
to the basin being serviced should be turned cause and solution.
off after the water has dropped below the
In Situ Cleaning of Membrane
lateral piping and diffusers to prevent the
possibility of excessive airflows to the units Typically rubber membrane diffuser units
or damage to the blower unit. The following will require cleaning because of two
items may be helpful in servicing the FlexAir common types of surface build-up:
aeration system during periodic inspections biological and inorganic scaling. The
or maintenance procedures: recommended cleaning procedures for both
types of build-up are detailed below:
• Ladder to access the de-watered
basin Biological build-up is a moss-like growth.
The recommended cleaning procedure is to
• Protective gloves and clothing physically dislodge the growth either by
• Crimping or nipper pliers gently brushing the substance off with a soft
plastic bristle brush or by using low-
• Long-handled soft bristle brush for pressure hosing. Care should be taken not
cleaning assembly for observation to abrade the membrane surface during the
• Spare FlexAir membranes and cleaning procedure.
crimping clamps Inorganic scaling is a granular mineral-like
FlexAir Aeration System Inspection precipitate that can form on the membrane
surface. If brushing and hosing the diffuser
All system components should be inspected membrane do not remove the scaling,
for general wear or damage. This includes contact EDI for further instructions.
but is not limited to:
Membrane Protection
• Pipe supports including anchor bolts,
pipe straps and fasteners. The diffuser membranes should be
protected from chemicals that may be
• Pipe connection including fasteners, harmful to the material. If using a cleaning
shifts in alignment of pipes and aid or other substance on or around the
joints. membranes, please contact EDI for
• Diffuser assembly including position, chemical compatibility.
membrane integrity, membrane Good air filtration is required with all FlexAir
clamps, etc. units. The blower system should be
• Purge assembly components equipped with inlet filters having a
including all connections, anchor performance efficiency of 93% removal of
points, and wear at any contact 10-micron particles to prevent clogging of
points. the diffuser membrane. Follow blower
manufacturer’s recommendations regarding
Any worn or damaged components need to care and maintenance of inlet filters.
be repaired or replaced. Please contact
Page38 www.wastewater.com
Environmental Dynamics International aeration for life™
Corrective Maintenance
Troubleshooting 1) Access diffusers and inspect for external
r.2011-10-18 or internal fouling or deformation.
The FlexAir aeration system requires very 2) Confirm blower operating point and rpm
little maintenance for long-term operation. reading.
Periodic visual inspection of the system
should allow the Operator to determine if 3) Confirm isolation valve position on
the system is performing at optimum levels. header and drops.
For example, diffuser unit elevation Dissolved oxygen profile not satisfactory
variations greater than the design tolerance throughout basin.
(refer to Headloss Calculations) will reduce
Possible Cause:
the uniformity of air distribution in the
system. In addition, operating airflows 1) Increased loading to system.
below the design condition will also reduce
2) Reduced blower discharge air volume.
the uniformity of air distribution. If operating
conditions warrant airflow rates below the 3) Improper distribution of air in system.
design condition, contact EDI for additional
4) Air leak in system.
operational guidelines.
5) Excessive foulant accumulated on
Below are symptoms and procedures to diffuser.
follow if inspection of the aeration system
reveals abnormal operating characteristics: Procedure:
Large volume of air in localized area. 1) Confirm loading to system.
Possible Cause: 2) Confirm blower operations.
1) Air leak in aeration piping. 3) & 4) See items 1 and 2 above.
2) Diffuser membrane damaged or 5) Access diffusers and inspect for external
missing. fouling.
Procedure:
1) Access area in question. Inspect joints Replacing FlexAir Diffuser
for evidence of breakage. Membranes
2) Inspect diffuser units for membrane r.2011-10-18
damage. Repair as required. If it becomes necessary to replace rubber
Decreased diffuser activity and membranes, the guidelines below should be
increased back pressure noted at followed:
blower. 1) Remove the stainless steel (S.S.)
Possible Cause: crimping clamps. This is easily
accomplished by bending back the small
1) Diffusers becoming fouled or deformed. tab on the clamp with a crimping tool or
2) Reduced blower discharge air volume. screwdriver. The operator should not
attempt to snip or cut the ear of the
3) Restriction in air header. clamp because S.S. material is very
Procedure: strong and excessive force is required to
shear the material.
Page39 www.wastewater.com
Environmental Dynamics International aeration for life™
2) Gently pull the rubber membrane off the 1) Use a rubber or plastic mallet to remove
support to avoid breaking or damaging sliding wedges from the saddle body.
the support.
2) Remove the saddle body from the
3) Gently install new membrane ensuring lateral piping. Be careful not to damage
the non-perforated area is installed the lateral near the predrilled holes. The
centered over the air discharge holes. Spectrum diffuser mount forms a tight
seal to the lateral with compressed O-
4) S.S. crimping clamps should be fully
rings. Heavy scratches in the lateral
compressed with outside edge of the
near the O-rings could break the
clamp located 1/4" (6mm) from the edge
pressure seal.
of the membrane. For EPDM
membranes, the ear of clamp shall be 3) Re-install the diffuser assembly by
placed on top of unit. For PU following the Installation Instructions.
membranes, the ear of clamp shall be
Questions regarding the aeration-mixing
placed 45-degrees from the top of unit.
system operation, maintenance, etc. should
be forwarded to Environmental Dynamics
Replacing Saddle Mounted International, 5601 Paris Road, Columbia,
Missouri 65202. +1(573)474-9456.
Diffuser Assembly
r.2012-10-17
If it becomes necessary to remove an entire
diffuser assembly, the general procedures
outlined below should be followed:
Page40 www.wastewater.com
Environmental Dynamics International aeration for life™
Page41 www.wastewater.com
Environmental Dynamics International aeration for life™
Page42 www.wastewater.com
Environmental Dynamics International aeration for life™
Page43 www.wastewater.com
Environmental Dynamics International aeration for life™
Page44 www.wastewater.com
Environmental Dynamics International aeration for life™
Page45 www.wastewater.com
Environmental Dynamics International aeration for life™
Page46 www.wastewater.com
Environmental Dynamics International aeration for life™
Page47 www.wastewater.com
Environmental Dynamics International aeration for life™
Page48 www.wastewater.com
Environmental Dynamics International aeration for life™
Page49 www.wastewater.com
Environmental Dynamics International aeration for life™
Page50 www.wastewater.com
Environmental Dynamics International aeration for life™
Page51 www.wastewater.com
Environmental Dynamics International aeration for life™
Page52 www.wastewater.com
Environmental Dynamics International aeration for life™
Page53 www.wastewater.com
Environmental Dynamics International aeration for life™
Page54 www.wastewater.com
Environmental Dynamics International aeration for life™
Page55 www.wastewater.com