440 - Example OHL Setting - 1-33
440 - Example OHL Setting - 1-33
440 - Example OHL Setting - 1-33
380 kV OHL
Fault
line i
Figure 20: Impedance distribution for Ph-Ph-E fault with fault resistance
The influence of load (remote infeed and load angle) can increase or
decrease the rotation of the measured fault resistances. The leading phase to
earth loop will however always tend to produce an overreach. For this reason
the default setting of block leading ph-E loop will be used in this example.
If the application is on a double circuit line where simultaneous earth faults on
both lines can occur, the setting only phase-earth loops or all loops should be
used to avoid blocking of the internal fault loop by this setting. Of course
additional grading margin must be applied for Zone 1 in this case to avoid an
overreach during an external 2ph-E fault.