EMC Design Guideline For Configuring A System With FA Products
EMC Design Guideline For Configuring A System With FA Products
EMC Design Guideline For Configuring A System With FA Products
BQN-P0E100083.E
1 / 24
Contents
2. Introduction
7. Countermeasure Member
9. Recommended Configurations
BQN-P0E100083.E
2 / 24
1. Warnings and Precautions Regarding Safety
Warnings and precautions regarding the products are listed in their instruction manuals and attached documents. Do not attempt
to design, install, operate, maintain, or inspect the equipment until you have read through all the documents carefully. Only
professional engineers (who have taken proper training or who have licensed to work on electrical equipment) must design,
install, operate, maintain, or inspect the equipment. This guideline provides general information about EMC countermeasures. If
compliance to standards such as safety standards is required, such standard must precede this guideline.
2. Introduction
This guideline shows recommended methods for designing a control cabinet, laying out of FA products, wiring, and inserting
places of countermeasure members to prevent malfunction due to noise superimposed among the products when multiple FA
products are placed in a control cabinet. Noise problems may not be solved depending on the products, system scale, grounding
environment, and so on even if the countermeasures in this guideline are taken. Use this guideline as reference for
countermeasures and designing. Mitsubishi Electric Corporation does not guarantee that all the noise problems are solved by
this guideline.
Mitsubishi Electric’s FA products alone comply with the EMC standards in each country. Refer to manuals of each product for
the complied standards. Be sure to take countermeasures against noise required by each product when configuring a system,
and then refer to this guideline. A manufacturer who sells equipment which the FA products are installed in to an end-user must
be liable for compliance with the EMC standards. Make sure that the final product complies with the standards.
EMC stands for Electromagnetic Compatibility and indicates ability of devices and systems to operate in their electromagnetic
environment. EMC includes two elements: emissions/EMI (Electromagnetic Interference) referring to capacity to suppress noise
generated from the product, and immunity/EMS (Electromagnetic Susceptibility) referring to ability to tolerate noise from besides
the product. Requirements of the EMI must meet the regulation values of the radiated interference, conducted interference, and
power supply harmonic currents. Requirements of EMS must meet the immunity standards of the static electricity, radiated noise,
conducted noise, electrical fast transient/burst, lightning surge, power supply frequency magnetic field, instantaneous power
failure, and voltage dip. EMC is regulated each country and region. The final products which the end-user use must satisfy the
Mitsubishi Electric's FA products alone comply with the standards required by each product. Refer to instruction manuals and
technical documents of each product for information of compliance with the standards in each country and measures to comply
Conducted
Conducted noise
interference Static
electricity
AC line Electrical fast
transient/burst Device
AC line
Power supply harmonic current Device Instantaneous power failure/voltage dip
BQN-P0E100083.E
3 / 24
4. Types of Noise and Transmission
Basically, there are two types of noise: "normal mode noise" and "common mode noise". Figure 2 shows the difference between
the normal mode noise and the common mode noise by giving an example of signal line.
"Normal mode noise" is a noise that occurs between signal lines or power lines. The noise current flows in the same path as the
signal. "Common mode noise" is a noise that occurs between the ground and signal line or power line. The noise current flows in
a different path from the signal and goes back to the noise source through the ground. The common mode noise is generated by
induction or unbalanced impedance. Generally, devices are affected more by the common mode noise than by the normal mode
noise, and thus it is important to have countermeasures against the common mode noise.
Load
Signal source
Load
Signal source
Noise source
Noise source
1) Conducted noise: electromagnetic noise propagated along a power, signal, or ground line. The noise is transferred through
2) Induction noise: crosstalk noise induced and superimposed on a cable which is laid along a cable with a noise current. When
a power input/output line of especially a drive device is laid along with a control signal cable, noise may be superimposed.
There are two types of induction noise: "electrostatic induction noise" generated by capacitive coupling and "electromagnetic
3) Radiated noise: release of noise from a cable through devices in a form of electromagnetic wave. The noise is radiated and
received by the cables and the patterns on circuit boards which work as an antenna.
BQN-P0E100083.E
4 / 24
[ Inside control cabinet ]
Noise source
Power supply Conducted
noise
Electrostatic
induction
noise Electromagnetic
induction noise
Control Control
device device
The drive devices generate a large amount of noise because a high voltage and large currents are being switched by switching
elements such as IGBT. For reference, noise transmission paths in the inverter system are shown in Figure 4.
Noise flows into the ground through a capacitance between motor windings or through a stray capacitance between the casing
and the ground in a drive system having an inverter circuit, creating large loops which generate a large common mode noise.
Noise source
BQN-P0E100083.E
5 / 24
4.3. Basics of the EMC countermeasures
1) Separating from a noise source and transmission path by laying out of devices and cables
3) Securing a noise return path by grounding or stabilizing ground by lowering impedance of the common ground
4) Shielding the noise transmission path by using an EMC noise filter or insulation transformer
Table 1 shows the section No. of typical countermeasures, and Table 2 shows the section No. of countermeasure members.
FA products affects EMC. To secure the EMC performance effectively, it is important to consider the EMC countermeasures
when designing a control cabinet. Earthing (grounding) must conform to the requirements of national and local safety regulations
Before designing the control cabinet, it is necessary to clarify the usage environment of the cabinet. The principle and criteria of
designing the cabinet against EMC must be established based on the information.
1) Customer requirements and restrictions: When taking countermeasures against EMC, whether the countermeasure member
is available or shielding ground is possible affects the design of the control cabinet. Cabinet dimensions and
BQN-P0E100083.E
6 / 24
2) Information on usage environment: The peripheral noise environment and noise tolerance standard can be determined by the
usage environment of the control cabinet. Sufficient grounding may not be available depending on the environment, but
earthing (grounding) must conform to the requirements of national and local safety regulations and electrical code. When the
equipment is used in a situation related to safety or in a highly public facility, higher EMC (Electromagnetic Compatibility) will
be required.
3) Information on devices to be used: After selecting devices that satisfy necessary specification for designing the electrical
circuit, the electromagnetic compatibility of each device must be clarified. Necessity of additional countermeasures against
noise is determined depending on the electromagnetic compatibility of each device. In addition, obtaining information about
recommended measures is also important when the additional countermeasures are needed.
1) Customer requirements
and restrictions
2) Information on
usage environment EMC
specifications
of cabinet are
determined.
3) Information on devices
to be used
Internal dimensions of Affects the device size and selection of the countermeasure
Size of control cabinet control cabinet members.
Cost of control cabinet and Affects the countermeasure plan such as cost for the
Cost devices countermeasure members.
Water-proof, Affects the material of the control cabinet, process of openings,
Specifications heat resistance, etc. etc.
2) Information on usage environment
Machine tools/plant Affects the noise control method because grounding and
Equipment/facility facilities/ships/railways/ special requirements (emergency radio band regulation) must
construction machineries be fulfilled.
Safety related equipment Affects the noise control method because such equipment and
Safety consideration
and highly public facilities facilities require high EMC requirement level.
Electromagnetic
EMC standard, etc. Confirm the actual electromagnetic compatibility.
compatibility
Countermeasures
Recommended
recommended by a Obtain recommended methods against noise when necessary.
countermeasures
manufacturer
BQN-P0E100083.E
7 / 24
5.2. Flow of designing control cabinet
After the necessary information is obtained, design the control cabinet by following the flow in Figure 6.
• Grasp the electromagnetic compatibility such as if the device is generating noise, if the noise tolerance is high,
etc.
5.3 Electro- • Investigate if countermeasure members are necessary (based on the electromagnetic compatibility of the
magnetic device and environment).
compatibility
• Categolize the wiring for the devices, and create wiring diagrams for each.
6.1 Creating • Wiring diagrams for power lines, signal lines, ground lines, etc.
wiring
diagrams
• Design the control cabinet. (Selection of metal casing, process of openings, shielding, and plating of the
mounting panels.)
6.3 • Isolate the devices which generate noise and which are susceptible to noise.
Designing of
control • Install the countermeasure members where necessary.
cabinet • Take countermeasures by isolating the wires by types and using shielded cables.
The electromagnetic compatibility of the devices to be used in the control cabinet depends on the types of the devices. Generally,
power devices and drive devices generate a large noise (noise generating devices), and control devices and sensors are
susceptible to noise. To understand the electromagnetic compatibility, refer to the compatible EMC class in each manual.
The manuals also list countermeasure members necessary for compliance with the EMC standard. Refer to the manuals when
selecting devices. (Even if costs of the devices with high electromagnetic compatibility are high, when the cost of the noise
The control cabinets for the drive devices generating noise and the control devices susceptible to noise should be isolated.
Drive devices
Control devices
BQN-P0E100083.E
8 / 24
6. Designing Control Cabinet
Cables used in the control cabinet will be noise transmission paths. Effective methods for suppressing noise transmitted on the
・ Band by wiring systems (power input/output system, or signal/control system) and keep the wiring as short as possible.
(Do not fold the cable.)
・ Extra length of the cable can be a path for the noise and transmits the noise to other cables and devices. Adjust the cable as
short as necessary.
Good Bad
Device B Device B
Device Device
A A
BQN-P0E100083.E
9 / 24
・ The power input/output system cables for the drive devices generate a large amount of noise. Keep them away from the
power input cables, control lines, and signal lines of the control devices, and do not lay those cables along each other. The
noise will cut in from the power input/output cables of the drive devices due to capacitive coupling and magnetic coupling. If
unavoidable, isolate the cables of the different systems by using a duct, and cross the cables perpendicularly to limit the
・ Use shielded wires for the control and signal lines when the wires are laid outside the control cabinet.
・ Refer to section 6.2.2 for the shield termination of the control and signal lines.
Communication cable
Control cable Power input cable Signal cable
Isolated
Provide ducts
for the power Power Avoid passing the
cables and that cables and power cables and
for the control/ Less affected by noise control/
communication
signal cables when the cables are signal cables
are in the cables together
separately. isolated by ducts, and
Drive Drive same duct. through the same
moreover a metal hole. Otherwise,
device device
separator (requires the cables will be
Isolated
Control cable grounding) is inserted affected by noise.
Communication cable between the ducts.
Power Power Communication cable
Control cable
input cable input cable
Motor Motor
Motor output cable Motor output cable
It is recommended that you keep a distance of 300 mm or longer between the power cables and the communication/signal/control
cables. For some reason, if the cables are laid along close to each other, isolate the ducts and insert a metal separator to suppress
the noise influence. Be sure to ground the separator to the cabinet.
300 mm or longer
Communication/signal/control cables
Wiring duct Wiring duct
Install the control devices and the drive devices in isolated control cabinets. The most effective method of noise control is to
When space is limited and it is unavoidable to install the control devices and the drive devices together in the same control
cabinet, be sure to ground referring to section 6.2.1 2) to suppress the mutual interference noise.
Grounding is the most important countermeasure against noise. Be sure to ground as recommended as possible.
BQN-P0E100083.E
10 / 24
6.2.1. Grounding of devices
1) Between cabinets
・ Prepare isolated control cabinets for the control devices and for the drive devices, and each cabinet must have a dedicated
grounding. If it is difficult to have a dedicated grounding, have a shared grounding.
Do not use a common grounding because the devices affect each other by the common impedance. For example, if an
inverter and a PLC have a common grounding, the noise current flows from the inverter to the common impedance, and the
Ground
potential Ground potential
2) Grounding inside the control cabinet when the control devices and the drive devices are in the same cabinet
・ The noise of the drive devices cut in the control devices, and therefore, install countermeasure member such as an EMC
noise filter on the power supply side of the drive devices. Installing the EMC noise filter suppresses the noise from cutting in
・ Ground the drive devices and the control devices to each dedicated grounding bar in a way that the grounding bar is shared
by the same system devices. Ground the grounding bars by sharing the grounding terminal of the control cabinet.
・ When it is difficult to install dedicated grounding bars, separate the installation areas for the drive devices and the control
devices on the installation panel, and connect the grounding lines of the devices to the installation panel with the shortest
possible cables. The installation area for the drive devices must be close to the grounding terminal of the control cabinet.
Control cabinet Control cabinet Control cabinet
[Control device area] [Control device area] [Control device area]
Grounding Separate the grounding for the drive Grounding Shortest grounding to the Do not have a common
devices and the control devices by Grounding
on cabinet on cabinet mounting panel (inner panel) on cabinet grounding through
using grounding bars and have a grounding bars.
common grounding.
Fig. 11. Example of installing drive devices and control devices in the same control cabinet
BQN-P0E100083.E
11 / 24
3) Grounding lines
・ Thick wiring lowers impedance and drops the noise easily to the cabinet.
・ Short wiring suppresses unnecessary radiation from the grounding lines themselves and crosstalk from other cables. Refer
to manuals of each product for selecting thickness and length of the grounding lines.
Shielded cables are effective for suppressing the radiated noise. The common mode current inside the shield flows in the
opposite direction from the common mode current flows in the core, and the common mode currents will be canceled. Thus, the
However, using the shielded cables increases the stray capacitance and may increase the conduction noise. Set a filter on the
power supply side of the drive devices to return the conduction noise back to the drive device side.
・ Use a P-clip, U-clip, or clamp fitting to make a contact with a wide surface when grounding the shielded cable.
The clamp fitting which can be grounded with a wide surface is effective for high frequency noise because this type of noise
・ The high frequency noise does not flow easily with pigtail grounding because the pigtail has a smaller surface than the clip
and clamp fitting. If pigtail is used to connect to the terminal, it is recommended that a clamp fitting also be used.
Shield
Example of
cable grounding U-clip
A fitting that attaches
the shield of the Shield
cable effectively to
the cabinet surface P-clip
Cable
External conductor
Clamp part drawing
・ Refer to manuals of each product for connecting the signal, control, I/O, and communication cables to the connectors and
terminal blocks.
BQN-P0E100083.E
12 / 24
・ When connecting the cables between the cabinets, be sure to use shielded cables and ground at the end of both cabinets
for the control devices and the drive devices. If a potential difference is generated between the cabinets because of the
difference in grounding resistance, ground the cable shields with the clamp fittings close to the control devices only in the
cabinet for the control devices to prevent the noise current from cutting in the control signal and communication lines due to
・ When grounding the shielded cable in the same control cabinet, ground the both ends of the cables with the clips or clamp
fittings close to the control device and the drive device. When it is difficult to ground the both ends, ground only on the
control device side. If grounding is executed on the drive device side only, the effect of grounding the shielded cable cannot
be expected, and the noise from the drive device may cut in the control device.
・ Do not ground the shielded cables of the control lines connected to the common terminals (SD, SE, and 5) of the inverter
with clamp fittings.
Ground both ends of the
connection between the
cabinets with clamps. When Cabinet for control devices
Cabinet for drive devices
there is a potential difference
and noise affect the devices,
ground only the control device
cabinet side with a clamp.
Power input cable HUB
Communication cable
Control When there is a
device communication cable in
the same cabinet, ground Communication
Do not ground the shielded Communication cable both ends of the cable or cable
ground of the inverter only the control device
side with a clamp.
control lines on the device
side. Signal, control, Control device
and I/O cables
Ground both ends of the
shielded ground of the
Inverter Servo servo control lines. Control device
Connect the shielded ground of the amplifier When noise affect the
inverter control lines to the common devices, ground only the
terminals (SD, SE, and 5). Do not control device side.
connect it on the device side. Power input cable
Motor
Fig. 13 Grounding of signal, control, and I/O shielded cables and communication cables
・ Generation and transmission of the common mode noise due to the potential difference in grounding between the control
devices and drive devices
It is recommended that the signal, control, and I/O shielded cables be grounded on the control device side.
As illustrated in Figure 14, when there are grounding points for both the drive devices and the control devices, the common
mode noise is being transmitted to the grounding points of the drive devices, and therefore the potential will be high against
If the signal, control, I/O, and communication shielded cables are grounded on the drive device side, the grounding potential
will be high. The potential difference from the control device side causes the noise to transmit to the control device side.
BQN-P0E100083.E
13 / 24
Shielded cable for signal, control, and I/O
IC V
Ground connection
Control system grounding (Low potential)
V:potential difference
GND IC:common mode noise
Fig. 14 Noise transmission mechanism of grounding lines of shielded cable
・ Use a shielded cable, shielding cover, or metal pipe (conduit pipe) for the motor output cable.
・ Connect the shield of the shielded cable to the ground on both ends (drive unit side: control cabinet, and motor side: motor
terminal box or grounding terminal).
・ If the shield is connected by pigtail (shield wires are tied up and extended), it is less effective than the grounding by the clips
or clamp fittings.
・ Use a shielded cable with four cores for the motor output, and connect one to the ground terminal on the motor side and to
the ground terminal on the drive unit.
・ Be sure to ground the motor side because it is effective to suppress the noise.
・ Note that the grounding method of the encoder cable connecting the drive unit and the motor varies for vector inverters and
servos.
・ For the vector inverter, ground one side on the drive unit side to the control cabinet with a crimp fitting.
・ For servo, ground both drive unit side and motor side with crimp fittings.
・ Use a metal control cabinet. The radiated noise will be suppressed and the grounding will be stabilized.
・ Weld or screw the cabinet's top plate and side plate without any space on the joining sections. Keep the intervals between
the welding or screws to 100 mm or less. (To have 20 dB or higher shielding effect, keep the opening length to 1/20 or less
of the wave length of the shielding frequency. Refer to Figure 15. When the opening length L is 100 mm (0.1 m), the
・ The installation panels (inner panels) of the cabinet must be plated to have sufficient grounding for the devices, and be sure
to connect the installation panel to the grounding terminal of the cabinet.
・ Open holes for leading cables from the control cabinet. Separate holes must be provided for the cables of each system and
have enough distance from each other.
・ There are general and EMC-dedicated control cabinets. The EMC-dedicated control cabinet has following features. It is
effective to use the EMC-dedicated control cabinet especially when enhancing the noise control. (Refer to Figure 16.)
1) Shield characteristics of casing: It has a sealing structure by being welded without any space. A rectangular wire for
grounding and shielding gaskets are provided.
2) Process of opening: The opening is shielded with a punched metal to prevent leakage of noise.
3) The inside the cabinet is plated so that the noise from the devices can be released easily.
BQN-P0E100083.E
14 / 24
Calculation of shielding frequency f [MHz] and
opening length L [m] with shielding effect of 20 [dB].
・ Opening length L [m]
150
L=
10 ∗ f
Bad Good
・ Shielding frequency [MHz]
150
f=
10 ∗ L
When the long side (indicated by ↔) of the opening is welded or screwed with an interval of 100 mm or shorter, noise of
Paint mask
シールドガスケット
Shielding gasket
Control
cabinet
Metal cabinet
Door
Packing
Plated inside cabinet
BQN-P0E100083.E
15 / 24
6.3.2. Layout of devices in the control cabinet
Please note the following when laying out the devices in the control cabinet.
・ Consider the electromagnetic compatibility of the devices and the wiring route.
・ Lay out the devices to make the wiring as short as possible and not to connect different types of cables.
・ Secure the positions for the EMC noise filter, clips, clamp fittings, ferrite cores, and amorphous cores.
・ Install the EMC filter on a bare metal or a plated metal to release the noise from the filter. (Refer to Figure 17.)
・ Isolate the control devices and the drive devices with a metal shielding plate, etc.
・ Ground the control cabinet with a thick short cable (4.2 mm2 or thicker is recommended).
BQN-P0E100083.E
16 / 24
7. Countermeasure Member
Methods of using the general noise countermeasure members are listed. (not in recommended order)
・ When the ferrite core or amorphous core is attached, its magnetic loss effect converts the noise to heat or the inductance
component increases the impedance to lower the noise.
・ The impedance is proportional to the square of windings on the ferrite core or the amorphous core. Pass through multiple
times (three or four passes) if possible. However, note that winding too much lowers the high frequency impedance of the
ferrite core or amorphous core because of the stray capacitance between the cables, and cancels the effect.
Current Current
7.1.1. Cautions when attaching the ferrite core and amorphous core
The attachment method of the ferrite core and amorphous core varies depending on the noise types (common mode noise or
The common mode noise is the dominant source. Therefore, attaching the ferrite core or amorphous core on L and N together
(three phases together for 3-phase power supply) is effective for suppressing the noise.
For the normal mode noise, attach the ferrite cores or amorphous cores on each L and N wire separately. When the core is
attached on each wire, the currents may generate magnetic saturation, causing lower impedance, heat generation, or noise due
to magnetostriction. When the magnetic saturation occurs, reduce the number of passes, replace with a larger ferrite core, or
replace with an amorphous core in which the magnetic saturation hardly occurs.
Common mode noise
コモンモードノイズ
L
N
機器
Device
ノーマルモードノイズ
Normal mode noise
L
N
機器
Device
BQN-P0E100083.E
17 / 24
7.1.2. Attachment position of ferrite core or amorphous core
1) Power input cables of the control devices: Lowers the noise flows on the cable
Lowering the noise from the motor output cable with the ferrite core or amorphous core lowers the noise induced to the other
It is recommended that the cores be attached on the both sides of the cables. If only one side is available, attach the core as
close to the control device as possible. Note that attachment of the ferrite core or amorphous core may deteriorate the signals,
depending on the cable type and length. In addition, for the communication cables, preventing the communication speed to
Control cabinet
Control device
Attach a core to the control line
between the cabinets.
Control device Communication cable
Attach cores to the Core (ferrite/amorphous)
power input/output
cables. Clamp
Signal, control,
and I/O cables
Attach ferrite cores to the control
lines connecting the control device
and the drive device directly.
Drive When attaching the core on one
device side, attach it on the control
device side. (Countermeasure for
the radiated noise in the cabinet)
Mitsubishi Electric has optional ferrite cores available as line noise filters. Please use these filters effective for the noise by
A shielded cable is an electrical cable enclosed by a metal shield. The shield is composed of braided strands of metal or a layer
of metal foil, and is useful for shielding the radiated noise and for returning the common mode currents.
Termination process is important for the shielded cable. Refer to section 6.2.2 for the termination.
BQN-P0E100083.E
18 / 24
7.3. EMC noise filter
・ This filter is often used for the power input lines, and is composed of a capacitor, common mode choke coils, and resistors.
・ Effect of EMC noise filter: Generally, this filter is effective in a band width of 0.1 MHz to ten-odd MHz. It is especially
recommended that the EMC noise filter be installed in the input side of the control devices. In this way, the filter lowers the
noise of the drive devices and decreases the noise transmission to the control devices.
・ Selecting EMC noise filter: When installing the EMC noise filter on the power input lines of the control cabinet at one place,
consider the total power supply capacity of the whole control cabinet, and select the EMC noise filter with a margin. If the
power supply capacity of the EMC noise filter is small, the core built in the filter generates magnetic saturation, eliminating
・ Mitsubishi Electric has capacitor-type optional filters available as radio noise filters FR-BIF. Please use these filters effective
for the radio band width (medium-wave broadcasting band) by connecting to the power supply lines.
・ The effects of the EMC noise filter vary by wiring and grounding methods. Connect the filter as follows:
When the EMC noise filter is installed, leakage current becomes larger. Refer to manuals of each product.
Isolate the input and output of the EMC noise filter. When they are banded together, even if the noise is
attenuated by the filter, the noise of the input side will be conducted to the output side.
Good Bad
入力
Input
フィルタ
Filter フィルタ
Filter
出力
Output
Input and output are isolated Noise will be conducted to the output side from the input side
because the input and output are close to each other.
Ground the EMC noise filter with low impedance. The ground
line will be inductance in the high frequency band. When the
cable is long, the impedance will be large, lowering the noise
attenuation effect of the EMC noise filter.
The filter is more effective when it is grounded by surface.
FG
Inductance
インダクタンス
Filter Filter
Casing is grounded by surface. Ground line is thick and short. Ground line is thin and long.
BQN-P0E100083.E
19 / 24
7.4. Insulation transformer and NoisecuttransTM (Noisecuttrans is a trademark of Denkenseiki Research Institute Co., Ltd.)
・ Separate the power supplies for the control devices and for the drive devices, and connect an insulation transformer or the
Noisecuttrans.
・ The insulation transformer is effective for suppressing the common mode noise, and the Noisecuttrans is effective for
suppressing both the common mode noise and normal mode noise.
・ Connecting the insulation transformer or the Noisecuttrans to the power supply of the control devices requires a smaller
capacity and therefore cost-effective than connecting to the power supply of the drive devices.
・ However, if the noise from the drive devices is large and has a large influence on the peripheral equipment, shield the noise
from the noise source by connecting the power supply of the drive devices.
Main Junction
power terminal Control system
supply block power supply
PLC
Insulation transformer
GOT
or noisecuttrans
Drive system
power supply
Inverter
・ Connect a lightening surge protector (surge absorber) to the power supply for countermeasures against the lightening
surge.
・ Separate the grounding for the devices and the lightening surge absorber.
・ If not separated, the lightning surge traveling to the ground may flow into the devices.
Device
BQN-P0E100083.E
20 / 24
8. Summary of EMC Countermeasures
EMC countermeasures and effects explained in section 6 and 7 are listed in Table 6.
BQN-P0E100083.E
21 / 24
9. Recommended Configurations
1) A recommended wiring diagram is shown in Figure 25 for when the control cabinets are installed separately for the control
Communication line
Signal, control, and I/O lines
Power input line
Grounding on cabinet
Ground the motor power cable with a shield
Dedicated ground (PE) clamp, etc. within 100 mm from the opening.
Encoder Vector motor
for drive devices
Induction
Ground the motor Clamp the shield ground
motor. to the motor terminal box.
Ground the
motor.
Fig. 25. Recommended wiring diagram inside cabinet (separation by dedicated cabinet)
BQN-P0E100083.E
22 / 24
2) Figure 26 shows a recommended wiring diagram inside cabinet including the layout, wiring, countermeasure member, and
grounding for when there are the control devices and drive devices together in the same cabinet. (having difficulty of
separating cabinets)
Induction
Ground the motor Clamp the shield ground
motor. to the motor terminal box.
Ground the
motor.
Fig. 26. Recommended wiring diagram inside cabinet (control devices and drive devices in one cabinet)
BQN-P0E100083.E
23 / 24
10. Reference (*: Available at Mitsubishi Electric’s Factory Automation Website)
BQN-P0E100083.E
24 / 24
Appendix: List of Countermeasure Members
FR-BIF(-H) Radio noise filter Capacitor type Inverter and servo (-H) is for 400 V AC.
SF series Noise filter Noise filter Inverter and servo Filter for power supply
FR-S5NFSA series Noise filter Noise filter Inverter Filter for 1-phase power supply
A filter pack including a DC
FR-BFP2 Noise filter Filterpack Inverter reactor, zero-phase reactor, and
capacitive filter.
Surge voltage suppression filter
Surge voltage suppression
FR-ASF EMC noise filter Inverter for output side of 400 V class
filter
inverter
Surge voltage suppression filter
Surge voltage suppression
FR-BMF EMC noise filter Inverter for output side of 400 V class
filter
inverter
MT-BSL Sine wave filter EMC noise filter Inverter Connecting the filter on the
output side of the inverter makes
the voltage and current of the
MT-BSC Sine wave filter EMC noise filter Inverter motor almost sine waves.
PLC, GOT, and
AD75CK Cable clamp Clamp fitting For clamping the shielded cable
Motion controller
AERSBAN-DSET Cable clamp Clamp fitting Servo and PLC For clamping the shielded cable
AERSBAN-ESET Cable clamp Clamp fitting Servo and PLC For clamping the shielded cable
BQN-P0E100083.E
App-1 / 1