Series F61
Liquid Flow Switches
Product Bulletin
Note: These controls are designed for use only as T-body types
operating controls. Where an operating control These types are mounted in the liquid line with the
failure would result in personal injury or loss of housing at the top. An angle of 120° is allowed
property, it is the responsibility of the installer to (as indicated in Figure 1).
add devices or systems that protect against, or
warn of, control failure. The arrow on the body and cover must point in the flow
direction. To avoid turbulences it is advised to mount the
Caution controller at a distance of minimal 10xD (on each side)
away from elbows, valves and other appendages.
Do not use with hazardous fluids or in The T-body types cannot be mounted in a vertical pipe.
hazardous atmosphere.
Wiring
Installation A special vapour proof PG-16 nipple for cable inlet is
delivered by the IP67 type controls. This nipple has to be
Pipe-insert types used to keep the control vapour tight.
To allow the switch to detect changes in the liquid flow,
the paddle must not touch the pipe or any other obstacle Contact Function
in the pipe. The Pipe-insert types are mounted on top of
the liquid line.
An angle of 120° is allowed (as indicated in Figure 1).
2 3
To keep the flow switch close to the pipe and to provide
an adequate paddle length in the flow stream the use of a
reducing tee for larger pipe sizes is advised.
The arrow on the cover must point in the flow direction. >
To avoid turbulence it is advised to mount the controller
at a distance of minimal 10xD (on each side) away from
elbows, valves and other appendages.
1
The Pipe-insert types can be mounted in a vertical pipe
as long as the flow is up-stream. This mounting position
affects the adjustment of the controller. Figure 2: 1-3 closes on flow increase
2
PB_F61_07 2018
18 124.1
Up 16 110.3
Down 14 96.5
10 69.0
8 55.2
6 41.4
4 27.6
Flow
2 13.8
2
2 0 0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Flow Rate (GPM)
3
3 16
1" pipe
15
14
1
1
3 x M4 x 6 13
COM
COM
12
wire 0.5 to 4 mm2
(20-12 AWG) 11
[kPa]
10
9
Pressure drop
8
Figure 3: Adjustment
7
4
11 /4 " pipe
(using paddle for 1" pipe)
3
2" pipe
2
21 /2 " pipe
3" pipe
1
0
0 1 2 3 4 5 6 7
[dm3/s]
Flow rate
3
PB_F61_07 2018
Notes:
1 dm3/s = 3.6 m3/h = 15.6 U.S. gal./min. = 13 U.K. gal./min.
* Flow rates for these sizes are calculated.
** For 4" and 5" line pipe the 6" paddle is trimmed
4
PB_F61_07 2018
Pipe-insert
Range Paddles Paddles
dm3/sec Connection IP class st. st AISI 301 st. st AISI 316L Application
Water / Ethylene glycol /
F61SB-9100 0.15/46 (ISO 7-R1) IP43 1", 2", 3", 6" ---
Sea water
Water / Ethylene glycol /
F61TB-9100 0.15/46 (ISO 7-R1) IP67 1", 2", 3", 6" ---
Sea water
Water / Ethylene glycol /
F61TB-9104 0.15/46 (ISO 7-R1) IP67 1", 2", 3", 6" --- Sea water
Gold flashcontacts
Water / Chlorinated water /
F61TB-9200 0.15/46 (ISO 7-R1) IP67 --- 1", 2", 3"
Ethylene glycol
T-Body
Range
dm3/sec Connection IP class Application
F61SD-9150 0.04/0.07 1/2-14 NPTF IP43 Water/Ethylene glycol
F61SD-9175 0.04/0.07 3/4-14 NPTF IP43 Water/Ethylene glycol
F61TD-9150 0.04/0.07 1/2-14 NPTF IP67 Water/Ethylene glycol
Note:
Paddles not mounted, packed with the control
17
121
39.5
61
59 38 mm Hex
C
A. Cable inlet hole Ø 22.7 mm; Dust cap installed on IP43 types.
B. Vapour proof PG-16 nipple installed on IP67 types
C. Drain hole plug
F61SD/TD Dimensions
5
PB_F61_07 2018
100 60
A B
17
45
115
30 C 28
55
25
E
7 29
37
43
1” 54
67
1¼”
1½” 83
2” 107
1”
2½” 134
162
3”
4”
5”
6”
A. Cable inlet hole Ø 22.7 mm; Dust cup is installed on IP43 types.
B. Vapour proof PG-nipple installed on IP67 types.
C. 33 mm Hex. F61SB/TB
45 mm F61TB-9200
D. 1” paddle D = 25.4 mm
2”, 3”, 6” paddle D = 28.45 mm
E. Drain hole plug
F61SB/TB
6
PB_F61_07 2018
7
PB_F61_07 2018
Technical Specifications
Pipe Insert Types T-body Types
Type Number F61SB-9100 F61TB-91xx F61TB-9200 F61SD-91xx F61TD-9150
Max Liquid Pressure 20 bar 20 bar 10 bar 20 bar 20 bar
Max. Liquid Temp.* 120°C 120°C 100°C 100°C 100°C
Min. Liquid Temp.** 0°C -30°C -30°C 0°C -30°C
Max. Ambient Temp.* +55°C +55°C +55°C +55°C +55°C
Min. Ambient Temp. ** -40°C -40°C -40°C -40°C -40°C
Ambient Humidity 10-95% 10-95% 10-95% 10-95% 10-95%
Contact Type SPDT snap-acting switch
Electrical Rating 15(8) A 230 Vac (except F61TB-9104; max 400 mA / 15 Vdc)
Wiring Connections Screw terminals 1 up to 2.5 mm2
IP43 IP67 IP67 IP43 IP67
Enclosure
(IP23 w/o plug) Vapour proof Vapour proof (IP23 w/o plug) Vapour proof
Materials cover / case Polycarbonate
Materials in contact
See "F61 Wetted Materials" Table
with liquid
Notes:
* The max. liquid temperature of 100°C is at 20°C ambient. At higher ambient temperatures the max. allowed ambient becomes lower.
Models F61SB-9100 are tested at 21°C ambient. The max. liquid temp. is 110°C at an ambient temp. of 21°C for ambielt temp. <20°C the max.
liquid temp. is 120°C. The temperature of the electrical switch inside should not exceed 70°C.
** The low liquid temperature combined with a low ambient temp.should not lead to freezing of the liquid inside the body / diaphragm / bellows.
Please observe the liquid freezing point.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these
specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages resulting
from misapplication or misuse of its products.
Building Efficiency
Headquarters: Milwaukee, Wisconsin, USA
Branch Officies: Principal Cities World-wide
Johnson Controls® is registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners.
© Copyright 2018 Johnson Controls. All rights reserved. Any unauthorized use or copying is strictly prohibited.
www.johnsoncontrols.com