Manual DMC 50720P
Manual DMC 50720P
Manual DMC 50720P
INMOTION TECHNOLOGIES AB
Solkraftsvägen 13
SE-135 70 Stockholm
SWEDEN
Telephone: +46 (0)8 682 64 00
Telefax: +46 (0)8 682 65 80
Info@inmotech.com
http://www.inmotech.com
DMC2
Digital Motion Control Sysytem
APPLICATIONS CENTERS
Part A
GREAT BRITAIN SWEDEN
Inmotion Technologies Inmotion Technologies AB
/Danaher Motion Solkraftsvägen 13
Bridge Mills
Holmfirth
SE-135 70 Stockholm
Telephone: +46 (0)8 682 64 00
User's Manual 5.1
Huddersfield Telefax: +46 (0)8 682 65 80
HD9 3TW
Telephone: +44 (0)1484 68 83 25 Inmotion Technologies AB
Telefax: +44 (0)1484 68 83 26 Box 195
SE-234 23 Lomma
GERMANY Telephone: +46 (0)40 41 48 50
ACC Motion GmbH Telefax: +46 (0)40 41 48 55
Zähringerstrasse 23
DE-77654 Offenburg SWITZERLAND
Telephone: +49 (0)781 919 08-0 ACC Motion SA
Telefax: +49 (0)781 919 08-29 Wehntalerstrasse 6
CH-8154 Oberglatt
Telephone: +41 (0)1 851 5010
ITALY Telefax: +41 (0)1 851 5020
Danaher Motion Srl
Via Brughetti Z.I.
ACC Motion SA
IT-20030 Bovisio Masciago (MI)
La Pierreire
Telephone: +39 0362 594 260
CH-1029 Villars-Ste-Croix
Telefax: +39 0362 594 263
Telephone: +41 (0)21 863 6464
Telefax: +41 (0)21 863 6479
Art.No. 9032 0027 01 (A)
U.S.A.
Inmotion Technologies
211 Overlock Drive
Sewickley, PA 15143-2305
Telephone: +1 (412) 749 0710
12.07.2001
Telefax: +1 (412) 749 0705
Inmotion Technologies AB
Stockholm, Sweden
Table of Contents...............................................................................3
Introduction ........................................................................................7
About DMC2 Documentation ................................................................................. 7
Copyright Notice ................................................................................................ 7
Scope of DMC2 User’s Manual .......................................................................... 7
Related Documentation ..................................................................................... 7
Warning, Caution and Information Notices ........................................................ 7
About the DMC2 Products ..................................................................................... 8
Personal Safety.................................................................................................. 8
Intended Use of the DMC2 ................................................................................. 8
OEM’S Responsibility ........................................................................................ 8
Product Identification ............................................................................................. 9
Trademark Acknowledgements .......................................................................10
Proprietary Statement ......................................................................................10
Warranty Statement .........................................................................................10
Regulations and Directives.................................................................................. 11
Certification ......................................................................................................11
Electrical Regulations ......................................................................................11
Mechanical Regulations...................................................................................11
EMC .................................................................................................................11
European Directives.........................................................................................12
DMC2 Maintenance Notice .................................................................................. 12
Overview of Power Drive System.....................................................13
General ................................................................................................................ 13
System Definitions based on IEC Standards ...................................................... 13
Power Drive System ........................................................................................13
Complete Drive Module ...................................................................................14
Basic Drive Module ..........................................................................................14
Feeding Section and Auxiliaries ......................................................................14
Motor and Sensors...........................................................................................15
System Controller ................................................................................................ 15
Internal Interfaces of the PDS..........................................................................15
Configuring Power Drive Systems ...................................................17
Introduction.......................................................................................................... 17
Power Drive System with the DMC2 .................................................................... 17
DMC2 unit ............................................................................................................ 21
Control Section ................................................................................................21
Control Unit ...................................................................................................21
Resolver Measuring ......................................................................................21
Inputs and Outputs........................................................................................21
Enable Input..................................................................................................22
Ready Relay .................................................................................................22
Position and Speed Regulator ......................................................................23
Positioning Unit (Controller)..........................................................................23
Communication Unit......................................................................................23
Program Memory ..........................................................................................23
Motor Temp Input..........................................................................................23
Brake Relay ..................................................................................................23
Converter Faults ...........................................................................................23
Commutating logic ........................................................................................23
COPYRIGHT NOTICE
This manual is copyrighted 2001 by Inmotion Technologies AB. All rights reserved.
This manual may not be copied in whole or in part, nor transferred to any other
media or language, without the express written permission of Inmotion
Technologies AB.
RELATED DOCUMENTATION
For comprehensive information on details on the DMC2 programming language and
programming tools and controller firmware refer to the User’s Manual 5.x Part B.
WARNING
♦ A Warning informs the user of a hazard or potential hazard
that could result in serious of fatal injury if the precautions or
instructions given in the warning notice are not observed.
CAUTION
♦ A Caution informs the user of a hazard or potential hazard
that could result in injury or damage to the equipment if the
precautions or instructions given in the caution notice are not
observed.
OEM’S RESPONSIBILITY
OEM's are responsible for ensuring that DMC2 are used for their intended purpose
only, safe function of the system and for compliance with all applicable regulations.
Responsibility for the safe functioning of the system reverts to the owner or user in
all cases in which a non-professional has done installation, service or repair and
when the system is used for other than its intended purpose.
PRODUCT IDENTIFICATION
A label (see Figure 1 for location) and Figure 2 for containing pertinent product
identification information is affixed to the DMC2 unit. The product label fields
relevant to product identification are described below Table 1.
Field Description
Part No Unique part number assigned to DMC2 with a specific
Supply Voltage.
Edition Indicates the revision level of the article.
2
Cat. No. DMC model 5 0 4 1 2 P CAN
Bus voltage Cont. current Power supply Options
(pk) P = Integral CAN = Extended CAN
5 = 570 VDC 04 = 4 A Omit = No integral
Max. current power supply
A137
12 = 12 A
TRADEMARK ACKNOWLEDGEMENTS
IBM, IBM PC, AT and PC/XT are registered trademarks of International Business
Machines Corporation.
Intel is a registered trademark of Intel Corporation, registered in the United States
Patent and Trademark Office.
Microsoft, MS-DOS, Excel and Windows are registered trademarks of Microsoft
Corporation, registered in the United States and Trademark Office.
Novell and NetWare are registered trademarks of Novell Inc., registered in the
United States Patent and Trademark Office.
PROPRIETARY STATEMENT
The digitally encoded software included in the DMC2 is copyrighted 2001 by
Inmotion Technologies AB. All rights reserved. This software may not be
reproduced, modified, displayed, transferred or copied in any form or in any media,
in whole or in part, without the express written from us.
WARRANTY STATEMENT
We make no warranty of any kind including, but not limited to, any implied
warranties of merchantability and fitness for a particular purpose with regard to this
manual. We assumes no responsibility or liability for errors contained in this
manual or for incidental, special or consequential damages arising out of the
furnishing of this manual, or the use of this manual in operating the equipment, or
in connection with the performance of the equipment when operated.
ELECTRICAL REGULATIONS
• The system is driven by high voltage level of 3-phase 400 VAC. Make sure that
the system is not connected to mains when installation, service or repair is
done.
• The system must be turned off before changing cables or accessories.
• Non-Compliance with the installation instructions in this manual can either
damage the system or cause an electrical shock.
• The system can start automatically when mains are turned on depending on
how the hardware and software configuration is defined.
• When a computer is connected to the DMC2 unit, make sure that both the
DMC2 and the computer are connected to earth ground, for avoidance of
unpredictable voltage swing.
MECHANICAL REGULATIONS
• The servo motor connected to the DMC2 unit consists of moving parts and can
perform high torque's and/or speed in short time (within a few ms).
• Some parts of the DMC2 unit can be very warm, up to 90°C.
• The system shall be installed in a cabinet that gives Pollution Degree 2
EMC
• The DMC2 unit is designed to fulfill European EMC directive 89/336/EEC
referring to EN50081-2 Generic emission standard, Part 2, Industrial
environment and EN50082-2 Generic immunity standard, Part 2, Industrial
environment.
• The DMC2 unit is designed to fulfill FCC (Federal Communications
Commission) rules referring to Part 15.
• Proper installation and use according to this manual must be performed if the
EMC requirements are to be fulfilled.
• The DMC2 unit complies with the limits for a Class A digital device,
pursuant to CISPR11 (International special committee on radio interference)
This equipment generates, uses and radiate radio frequency energy and if not
installed and used in accordance with this manual, may cause harmful
interference to radio communications. Operation of the equipment in a
residential area is likely to cause harmful interference in which case the user
will be required to correct the interference using own expertise. A shielded
cable is required to comply with the limits for a Class A digital device, pursuant
to CISPR11.
EUROPEAN DIRECTIVES
The DMC2 unit fulfills the EC requirements and carries the European CE sign.
However, they will be declared as components for building-up machines. They will
therefore not be powered as long as the machine itself does not comply with the
European Directives.
Machine or Process
Complete Drive
module Motor
Basic drive and
Module Sensors
Feeding
Section
A001_E
1 2 3 4
A003
SYSTEM CONTROLLER
The System Controller includes all the accessories needed for the PDS to perform
its required functions. The system controller could include devices such as a:
• Man machine interface.
• Single or multi axis motion controller.
• PC.
• PLC.
• Terminal.
• Motion control unit.
• Multiaxis controller.
This function may be located external to the remainder of the PDS.
10 14
11 12
13
6
5 9
7 4
15
DMC 2
S2 Product name
S1
POWER ON
CPU OK
1
2
3
4
5
6
7
8
1
LAN2
3
16 NEXT HOST
2
A196_p
10 14
11 12
13
6
5 9
4 7 17
15
DMC 2 DMC 2
Product name
S2
S1
S2
S1 18
POWER ON POWER ON
CPU OK CPU OK
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
LAN2 LAN2
3
16 HOST
NEXT HOST NEXT HOST
2
1
A197_p
Figure 7. Example of PDS with an AC supplied DMC2 unit and a DC supplied unit.
10
14
11 20 12
6 7
13
5 17
4 9
19
15
DM C 2 DM C 2 DM C 2
S2
S1
S2
S1 S1
S2
Atlas PS
P OWE R ON
CP U O K
1
2
P OWE R ON
CP U O K
1
2
P OWE R ON
CP U O K
1
2
Power Supply
PS Unit 18
3 3 3
4 4 4
5 5 5
6 6 6
7 7 7
8 8 8
PS580160
3
LAN2 LAN2
LAN2
8
2
A198_P
16 1 21
DMC2 UNIT
The DMC2 is the Basic Drive Module in a Power Drive System illustrated in Figure
9. It consists of a control section, converter section and, for AC-supplied models,
part of the feeding section.
DMC2
Control section
Brake
Power supply
section Converter
section Motor
Temperature
sensor
A007_I
Resolver
CONTROL SECTION
Figure 10. presents a block diagram of the Control Section of a DMC2. Functions
assigned to the blocks are described below
CONTROL UNIT
The control unit handles the firmware flow for each servo cycle, administrates the
serial communication and executes the application code. The control unit
apportions CPU time among the firmware, communications and the application.
RESOLVER MEASURING
Handles excitation and feedback signals from the resolver for control of rotor
position, and axis speed and position. This function also supports a second
resolver for master/slave tracking applications.
ENABLE INPUT
Hardware input that must be high before the firmware can enable the power output
stage of the Converter. When this input is low, the power output stage is disabled.
CPU OK
X4 Communication
X5 unit
Control unit Temp.
HSI
X7a Resolver X6
I/O Input Position unit measuring
Output Resolver
X7b input
X4, +5 V
Positioning and Phase
X5 speed regulator
X4, X5, -15 split
X7b V DC/DC
X4, X5, +15 V
X7b Commutating
Current
+24 V regulator logic
X7b
Figure 10. Control Section Block diagram. (Shaded blocks handled by software).
READY RELAY
A relay contact set that closes when no converter faults are indicated and the
DMC2 is ready for use. The ready relay will be open after power up until a reset
pulse has been sent to the power stage in the converter section.
If one of these faults is indicated, the ready relay contact will open:
• Short circuit protection active in converter section.
• Over voltage level in converter section.
• Too low logic voltage level in converter section.
• Too low logic voltage level in control section
• OUT.Fault have been set from the software.
Any software fault can be programmed to set OUT.Fault and open the read relay
contact.
COMMUNICATION UNIT
Contains serial communication interface for RS-232, RS-422, Daisy chain, Sync
signal (and CAN bus connection).
PROGRAM MEMORY
Contains memory for Firmware and application program and a non-volatile
EEProm memory for parameter storage.
BRAKE RELAY
Software controlled relay that could be used for control of a brake in the motor.
CONVERTER FAULTS
Disables the power output stage and de-energizes the Ready relay upon
recognition of a fault signal from the Converter section.
COMMUTATING LOGIC
Turns on and off the switches (IGBT’s) in the output power stage depending on
motor angle and magnitude of torque (current) command.
LED UNIT
A group of ten fronts panel LEDs. (Power On, CPU OK and LED 1 thru LED 8) and
associated drive electronics.
LEDs controlled by hardware.
Power On Green, lit when +5 V are available in controller section.
CPU OK Green, lit when CPU has started up and runs.
LEDs controlled by software.
LD 1 Green, Software defined.
LD 2 Yellow, Software defined.
LD 3 Yellow, Software defined.
LD 4 Yellow, Software defined.
LD 5 Red, Software defined.
LD 6 Red, Software defined.
DC/DC (CONVERTER)
Reduces the +24VDC to +15VDC, -15VDC and +5VDC supply voltage for the logic
in the controller section.
4
+ +
1 2 3 5
+ 8
X1 _ X10 /
6 X20
_ _
X34
A009_p
9
7
X31
5
5
3 6
X31 +
1 1 2
+ 6
2 _ 4 X32 or
X33
3 _
4 X34
7
A010_p
Figure 12. Block diagram of power supply section of stand-alone power supply.
RECTIFIER
Six-pulse rectification of the three-phase input power.
STORAGE CAPACITOR
Storages energy and filters the six pulse rectified voltage on the DC bus.
CONVERTER SECTION
Enable
Control Control power Current Converter
unit +24 V Converter faults unit stage regulator faults
X10
or X20 + +
Output
power
stage Short
Dynamic Step IGBT Current
DC Bus Over circuit X11 or
brake down measuring protection
voltage X21 to
control DC/DC
Motor
converter
_ _
X13
or X22
A011_G
Dynam.
brake control
CURRENT MEASURING
The current measurements are done in two motor phases with isolated current
sensors able to measure AC, DC and impulse currents.
CABLING
POWER CABLE
Power cables shall be chosen so that national electrical regulations are fulfilled in
the country where the system is to be used. We recommend that the power cable
be sized for 2 times the fused current or at least 1.5 mm2.
MOTOR CABLE
Motor cables shall be chosen so that national electrical and EMC regulations are
fulfilled in the country where the system is to be used. We recommend that the
motor cable be sized for 2 times the continuos motor current or at least 1mm2.
Table 7. and Table 8. lists some motor cables available from us. A complete motor
cable installation requires a threaded strain relief to be mounted on the motor
junction box.
Table 9. lists strain relief’s for the motor cable types listed in Table 7. and Table 8.
RESOLVER CABLE
Resolver cables shall be chosen so that national electrical and EMC regulations
are fulfilled in the country where the system is to be used. We recommend resolver
cables with shielded pair twisted conductors with an external common shield and
an area of at least 0.25 mm2.
If cables recommended by us are used, electrical and EMC regulations within EC
and USA are fulfilled. We supplies completed resolver cable assemblies in various
lengths as well as un-terminated cable, which may be ordered in custom lengths.
Table 10.- Table 13. lists available resolver cable selections. Table 14. and Table
20. lists available resolver cable accessories.
COMMUNICATION CABLE
Cable assemblies for DMC2 to PC and DMC2 to DMC2 interconnection are listed in
Table 15. and Table 16. The DMC2 to PC cables use a F 9 pin DSUB and 9 pol
metal housing on the PC end. Cable assemblies for DMC2 to Terminal PC are
listed in Table 17.
FUSES
REQUIREMENTS
Fuses shall be chosen so that national electrical regulations are fulfilled in the
country where the system is to be used. We recommend time delay fuse with a
delayed opening of approximately 1 min total delay for 1.5 to 2 times rated current.
Table 2 below lists the fuse ratings for the various DMC2 models.
If a circuit breaker is used, it must have a current interrupting capacity 6000 A and
a delayed opening of approximately 1 min total delay for 1.5 to 2 times rated
current of the DMC2. If a circuit breaker is used, it should be used in conjunction
with 100 amp fuses.
EMC FILTERS
REQUIREMENTS
EMC filters shall be chosen so that national electrical regulations are fulfilled in the
country where the system is to be used. The filters used shall be tested to comply
with the EMC regulations. We recommend the filters listed in Table 21. which have
been tested together with the DMC2 unit. For filter dimensions, see part C.
CONTACTORS
One or two different types of contactors may be required depending on the system
configuration:
• All system configurations use a main contactor. Paragraph “Main contactor
selection” provides guidelines for main contactor selection. Table 22.
• Systems utilizing a stand-alone power supply require an additional contactor,
which inserts inrush current limiting resistance into the in feed circuit for the
first 50 ms. after power-up. Paragraph “Inrush current contactor selection”
provides guidelines for inrush current contactor selection. Table 23.
• For Inrush Resistor, See Table 24.
• The make current shall be lower than the contactor’s rated make current
capacity.
• Operating rated voltage (50 or 60 Hz) shall be not less than the line-to-line
voltage of the AC input voltage.
Peak power for 1 second in Watt is the same as pulse energy in Joule,
i J = W/s
TRANSFORMER SELECTION
In some application it is a need for transformer to convert the input voltage or for
safety reasons.
Requirements on the transformer for a typical servo application with acceleration
and deceleration peak torque of 2-3 times the continues torque:
• The output voltage should be 400 V AC.
• The transformers that have a continuous power rating equal our higher than
the total continuous output power needed for the application.
• The transformer shall have a maximum of 5 % voltage drop at two times the
continuous output power needed for the application.
0121 28 50412P
3x400 3 3 12 1.9 90 7 18.7 10 40 76 3.8
0121 42 50412P-CAN
0121 30 50720P
3x400 5 5 20 3.4 90 7 18.7 10 40 76 3.8
0121 44 50720P-CAN
0121 32 51540P
3x400 11 11 40 7.4 155 14 18.7 20 80 160 6.8
0121 46 51540P-CAN
1)
Not including dynamic breaking power loss
2)
Including internal current to output power
Power
1)
20D604B GMSTB 2.5/4-ST-7.62 X1 1 1
20D504R PC4 HV/4-ST-7.62 X1 1 1 1 1
Motor
Temp. switch
20D502A MSTBA 2.5/2-ST-5.08 X35 1
+24Volt Extenal DC
Connector Kit No 9032 0119 70 9032 0104 94 9032 0103 53 9032 0104 95 9032 0103 52 9032 0104 96 9032 0108 51
1)
20D604B This connector is only for DMC delivered before Feb 2001.
27M015A RC-LY12Y11Y-0.25 Shielded with three twisted and shielded pairs 0.25 By the meter -40 to +70 7.5x∅ 10
SYNC CABLE
Table 18
Order No Name Length No of leads Cable area Shield
m mm²
DMC2 SYNCBOX
Table 19
Order No Name No of connectors
CONNECTOR.
Table 20
Order No Name Remark No of pin Connector
9032 0103 17 Connector, female D-SUB incl. hood 9 For external rotary
9032 0103 18 Connector, male D-SUB incl. hood 9 For external rotary
9032 0103 14 CAN termination FBU and CAN communication X4/X5
9032 0103 15 CAN termination With external connection FBU and CAN communication X4/X5
19N117K Connector, male D-SUB incl. hood 15 For resolver cable at DMC X6A
19N117R Connector, Burndy 8 For resolver cable at EP motor
19N410A Connector, AMP Contact 20B231A (8pcs) 8 For resolver cable at SEM motor
19N117A Connector kit 4-10A incl. D-subs 9 pcs.
19N117B Connector kit 15-20A incl. D-subs 9 pcs.
WARNING
♦ Failure in properly ground this equipment could result is
serious or fatal injury to personnel who come into contact
with the equipment. All earth grounds must be installed per
the instructions in this chapter, and the equipment must be
securely connected to a quality earth ground before power is
applied for the first time. In addition, the panel or enclosure
housing the equipment must be securely earth grounded.
♦ Local regulations may require additional grounding measures
beyond those shown in this chapter.
♦ Failure to properly ground the equipment may result in
damage to the equipment or damage to other devices
connected to the equipment.
WARNING
♦ This equipment uses high voltages, which can cause serious
or fatal electrical shock.
♦ Can cause serious or fatal injury.
♦ Only qualified personnel should perform installation and
wiring.
X CONNECTOR’S
Connector Function Interface page
X1 Input power 51
X2 + 24 V External DC 52
X4 Host RS 232, RS 422, LAN 1, X5 52
X5 Next RS 232, RS 422, LAN 1, X4 53
X6A Resolver Feedback 54
X6B Optional Position 56
Available only for DMC2 CAN
Sensor
X7A I/O 57
X7B I/O 57
X8A Measure connection Available only for DMC2 CAN 61
2
X9 LAN 2 Available only for DMC CAN 62
X10 DC Bus X10P, X32, X33 62
X11 Motor 62
X13 Dynamic brake X34 63
X14 Thermistor/brake X35 63
X20 DC Bus X20P, X32, X33 64
X21 Motor 64
X22 Dynamic brake X34 65
X23 Thermistor/brake X35 65
X31 Input power 66
X32 DC Bus X10, X20 66
X33 DC Bus X10, X20 66
X34 Dynamic brake X13, X22 67
X35 Thermistor/brake X14, X23 67
Temperature switch
DSUB CONNECTOR’S
Connector D-Sub miniature in Metal housing Pin Male Female
X4 and X5 High Density, VGA 15 X
X6A Standard 15 X
X6B Standard 25 X
X8A Standard 9 X
X9 Standard 9 X
DMC2 FRONT
Figure 17. I/O Connections for all DMC2 units, bottom view.
Figure 18. DMC2 unit connectors on the topside, Motor, Power, Thermistor, DC
Bus for 50412/P and 50720/P.
Figure 19. DMC2 unit connectors on the topside, Motor, Power, Thermistor, DC
Bus for 51540/P and 53080.
Figure 20. PS 580160 unit connectors on top side, Power, Dynamic brake and
Thermistor.
X1
DMC2 P 50412 50720 51540
2
DMC 50412 50720 51540 53080
Connector See page
Input power is connected to X1 Figure 18 or Figure 19 on top of the DMC2 unit as
shown in Figure 29 for a Single and Figure 30 for a Master/Follower application.
Connect DMC25xxxxP models to 400 VAC mains.
DMC2 X1 Function
1 PE
2 Phase L1
3 Phase L2
4 Phase L3
X2
DMC2 P 50412 50720 51540
DMC2 50412 50720 51540 53080
Connector See page 35
Connections for 24V-logic external supply voltage. When connected, it supplies
the internal control circuit, feedback sensors, communication and I/O ports.
The 24V logic supply shall always be connected before the main supply voltage is
connected to the input power port. External fuse shall be used rated max 1.5A T
(slow).
DMC2 X2 Function Remark
1 0 V Supply Internal connected to X7A,pin 5
2 + 24 V Supply, Internal connected to X7B, pin
+20%: -20%, maximum supply 25
current 0.7A (not including load on
digital outputs)
X4 (HOST)
DMC2 P 50412 50720 51540
2
DMC 50412 50720 51540 53080
Connector See page 46
X4 is used for connections between external PC and other DMC2 units.
X5 (NEXT)
DMC2 P 50412 50720 51540
DMC2 50412 50720 51540 53080
Connector See page 46
X5 is used for communication between two or more DMC2 and for LAN1
communication.
X4 AND X5 CONNECTION
RS 232 INTERFACE
The RS-232 interface is used when connecting a PC to the DMC2. Connect the
serial communication cable from the computer to X4 (Figure 16.).
DMC2 X4 Function PC 9 Pin PC 25 Pin
1 Shield
2 RX 3 2
3 TX 2 3
7 GND 5 7
LAN 1 COMMUNICATION
Connect the Daisy Chain cable from X5 on the first DMC2 unit to X4 on the second
DMC2 unit (Figure 16.). Use the CAN termination 9032 0103 14 at the first DMC2 in
the application and a CAN termination with possibility to measure data 9032 0103
15 at the last DMC2 in the application.
X6A
DMC2 P 50412 50720 51540
2
DMC 50412 50720 51540 53080
Connector See page 46
This connector is used for resolver and external resolver connection. For location
see Figure 17.
EXTERNAL RESOLVER
For input from an external resolver is Rd2 used and is connected to X6A on the
DMC2. See Table 31.
DMC2 X6A Function Rd1 Rd2
1 Shield X
2 Rd1 Sin - X
3 Rd1 Sin + X
4 Rd1 Cos + X
5 Rd1 Cos - X
6 +15 V
7 Ground X X
8 -15 V
9 Excitation X X
10 Rd2 Sin - X
11 Rd2 Sin + X
12 Rd2 Cos + X
13 Rd2 Cos - X
14 PTC Supply
15 PTC Return
SYNCBOX
At applications with more than one resolver is a syncbox necessary to use. Use a
Syncbox cable to connect the DMC2 with the Syncbox at X6A.
X6B
DMC2 P-CAM 50412 50720 51540
DMC2-CAM 50412 50720 51540 53080
Connector See page 46
This connector could be used for the following sensors:
Sensor Description
S1 Multiturn-Resolver with ENDAT serial interface.
S2 SinCos Encoder and Absolute SinCos Encoders with ENDAT serial
interface.
S3 Incremental Encoder with index pulse, TTL interface and 5V supply.
S4 Pulse input, max input frequency 30 kHz.
2
DMC S1 S2 S3 S4 Function Remark
X6B
1 X X Endat Clock+ ENDAT, RS485
2 X X Endat Data+ ENDAT, RS485
3 X X X Endat 0 V 0 V supply; ENDAT or Encoder
4 +12 V (+12 V Supply, 150 mA, not standard opt.).
5 NC
6 X X Enc Cos- ENDAT 1 Vpp or Encoder 5V TTL,120 ohm.
7 X X Enc Sin- ENDAT 1 Vpp or Encoder 5V TTL,120 ohm.
8 X X X Enc Ref- ENDAT 1 Vpp or Encoder 5V TTL,120 ohm.
9 X Rd1 Cos- Internal connected to X6A:5
10 X Rd1 Sin- Internal connected to X6A:2
11 X Excitation Supply Internal connected to X6A:9
12 NC
13 NC
14 X X Endat Clock- ENDAT, RS485
15 X X Endat Data- ENDAT, RS485
16 X X Endat Sence 0 V ENDAT, Voltage drop detection
17 X X Endat Sence 5 V ENDAT, Voltage drop detection
18 X X X Endat 5 V Supply ENDAT, Max 300mA
19 X X Enc Cos+ ENDAT 1 Vpp or Encoder 5V TTL,120 ohm.
20 X X Enc Sin+ ENDAT 1 Vpp or Encoder 5V TTL,120 ohm.
21 X X X Enc Ref+ ENDAT 1 Vpp or Encoder 5V TTL,120 ohm.
22 X Rd1 Cos+ Internal connected to X6A:4
23 X Rd1 Sin+ Internal connected to X6A:3
24 X Excitation Ground Internal connected to X6A:7
25 +24 V (+24 V Supply, 150 mA, not standard opt.).
X7A/B
DMC2 P 50412 50720 51540
DMC2 50412 50720 51540 53080
Connector See page 35
All user connections to the DMC2 I/O are made at X7A and X7B and Figure 17.
illustrates the location.
X7B DMC
26
1 3
2k7 2
X7A
4
5
5
A046_P
PNP TRANSDUCER
Recommended min. conductor area: 0,5 mm2 (AWG20).
X7B DMC
26
1 2
X7A
3
5
4
A047_P
ANALOG OUTPUTS
Recommended min. conductor area: 0,5 mm2 (AWG20).
X8A
DMC2 P-CAN 50412 50720 51540
DMC2-CAN 50412 50720 51540 53080
Connector See page 46
For location, see Figure 17.
DMC2 X8A Function Comment
1 GND
2 NC
3 NC
4 Measure bridge Input + Measure bridge input ±50mV
5 Measure bridge Input - Measure bridge input ±50mV
6 GND
7 -5V Supply Output Supply to measure bridge. Max 10mA.
8 NC
9 +5V Supply Output Supply to measure bridge. Max 10mA.
X9A
DMC2 P 50412 50720 51540
DMC2 50412 50720 51540 53080
Connector See page 46
The CAN Bus is used for an external network. For location, see Figure 17
DMC2 X9A Function Comment
1 NC
2 CiA CAN_L
3 CiA GND
4 NC
5 NC Shield
6 GND Ground
7 CiA CAN_H
8 NC
9 CiA V+ 7-26.5 V Supply
X10
DMC2 P 50412 50720
DMC2 50412 50720
Connector See page 35
Table 36 illustrates the input power connections to a DC supplied unit from an AC
(P version) supplied unit. Connect the DC bus voltage from X10 to X10. Figure 30
shows this application.
DMC2 P X10 Function DMC2 X10
1 PE 1
2 + DC bus voltage 570 VDC 2
3 - DC bus voltage 570 VDC 3
X11
DMC2 P 50412 50720
2
DMC 50412 50720
Connector See page 35
Figure 18 shows the connector X11. Table 37. describes the function. The motor
connections are the same for AC and DC supplied DMC2s.
Use the appropriate threaded strain relief with shield connection listed in Table 9 to
secure the motor cable to the junction box at the motor:
The cable shield must make secure metallic contact with the strain relief.
DMC2 X11 Function
1 Shield
2 PE
3 Motor U
4 Motor V
5 Motor W
X13
DMC2 P 50412 50720
2
DMC 50412 50720
Connector See page 35
Make the following dynamic brake circuit connections (Table 38), from X13 Figure
18 on DMC2 unit to X34 on PS unit. Figure 20
DMC2 X13 Function PS unit X34
1. Output dynamic brake regulator, driver. 1
2. Output dynamic brake regulator, -DC. 2
3. NC. 3
X14
DMC2 P 50412 50720
2
DMC 50412 50720
Connector See page 35
Make the following connections (Table 39) at the DMC2,X14, (Figure 18 for
placement) and the terminal block at the motor for thermistor and brake
connections. See motor documentation for correct wiring.
X20
DMC2 P 51540
DMC2 51540 53080
Connector See page 35
Table 40. illustrates the input power connections to a DC supplied unit from an AC
(P version) supplied unit. Connect the DC bus voltage from X20 (P) (Figure 19 for
placement) to X20. Figure 32 show how X20 is connected.
DMC2 P X20 Function DMC2 X20 DMC2 X20
1 PE 1 1
2 PE 2 2
3 + DC bus voltage 570 VDC 3
4 + DC bus voltage 570 VDC 4
5 - DC bus voltage 570 VDC 5
6 - DC bus voltage 570 VDC 6
X21
DMC2 P 51540
DMC2 51540 53080
Connector See page 35
Figure 19. shows the connector X21. Table 41 describes the function The motor
connections are the same for AC and DC supplied DMC2s.
Use the appropriate threaded strain relief with shield connection listed in Table 9 to
secure the motor cable to the motor.
The cable shield must make secure metallic contact with the strain relief.
X22
DMC2 P 51540
2
DMC 51540 53080
Connector See page 35
Make the following dynamic brake circuit connections (Table 42) from X22 Figure
19 on DMC2 unit to X34 on PS unit
DMC2 X22 Function PS unit X34
1 Output dynamic brake regulator, driver 1
2 Output dynamic brake regulator, -DC 2
3 Reserved 3
X23
DMC2 P 51540
2
DMC 51540 53080
Connector See page 35
Make the following connections (Table 43) at the DMC2, (Figure 19 for placement)
X23 and the terminal block at the motor for thermistor and brake connections.
DMC2 X23 Function
1 Motor brake, Contact NO
2 Motor brake, Contact NO
3 NC, used as connection point
4 Thermistor out +15 VDC
5 Thermistor return
X31
PS 580160
Connector See page 35
At the power supply, make the following connections to X31 (see Figure 20 and
Figure 31) Note that the model PS580160 power supply is for 400 VAC, 3 phase
applications. Use a WAGO 284 (10 mm2) Terminal block for interfacing to X31.
PS X31 Function
1 Phase L1, 400 VAC
2 Phase L2, 400 VAC
3 Phase L3, 400 VAC
4 PE
5 Dynamic brake resistor
6 Dynamic brake resistor
Table 45. DC Bus Connection from PS to DMC2 50412 and DMC2 50720.
X34
PS 580160
Connector See page 35
Make the following dynamic brake circuit connections from X34 (Figure 20) on PS
unit to X13 (Figure 18) or X22 (Figure 19) on DMC2 unit.
PS unit X34 Function DMC2 X13 DMC2 X22
1. Output dynamic brake regulator, driver. 1 1
2. Output dynamic brake regulator, -DC. 2 2
3. Reserved. 3 3
X35
PS 580160
Connector See page
Make the following thermistor connections from X35 (Figure 20) on PS unit to X14
(Figure 18) or X23 (Figure 19) on DMC2 unit.
DMC2-P/DMC2 INSTALLATION
INSTALLATION EXAMPLE
16 1 2 3
DMC 2 DMC 2
S2 S2
S1 S1
POWER ON POWER ON
CP U OK CP U OK
1 1
2 2
3 3
4
5
6
7
8
4
5
6
7
8
4
LA N2 LA N2
NE X T HO S T NE X T HO S T
14 15
9
24
VDC
IN OUT
6 7 10
5 8
11
12
A201
3
13
Max
100
200
20
DMC 2 DMC 2
S2 S2
S1 S1
POWER ON POWER ON
CPU OK CPU OK
1 1
2 2
3 3
4 4
5 5
6 6
7 7
150 8
10 8
LAN2 LAN2
100
150
200 2
1
A104
37
B
37 C D
15 15 ∅ 12
40 40
∅ 12
DMC 2 DMC 2
S2 S2
S1 S1
POWER ON POWER ON
CPU OK CPU OK
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
285 285
234 234
LAN2 LAN2
5.5
5.5
7 7
A
A200
Figure 38. DMC2 mounting dimensions (in mm). Depth for all units is 223 mm.
SCREENING
The purpose of screening (shielding) is to prevent unwanted electromagnetic
radiation from entering or escaping the system. This means that screening applies
to cabinets as well as cables. The motor cable, resolver cable and the serial
communication cable must be screened. The screens shall be connected to both
ends of the cable with metallic connector housings (see Figure 39.). The junction
box on the motor (see Figure 41.) must be metallic, not plastic.
STRAIN RELIEF
A complete cable installation, (Motor cable and Resolver cable Figure 41), require
a strain relief to fulfil EMC regulations.
Figure 41. Motor and resolver cable connections at metallic junction box on motor.
The cables shall be mounted along metallic surfaces. If possible, mount the cabinet
and the machine with clean (no paint) surfaces against each other.
(See Figure 42.)
All cables entering the cabinet shall be high frequency earth grounded at the point
where the cable enters the cabinet.
There must be good electrical contact between the DMC2 unit and the shield of the
motor cable. If the motor cable shield is connected to the protective earth rail, the
protective earth rail shall be high frequency grounded to the mounting plate at
several places. (See Figure 34.)
2
5
3
1
4
A035_p
2 2
THERMAL CONSIDERATIONS
When DMC2 units are mounted side by side (see Figure 37.), the cooling effect is
decreased approximately 30 %. Using the cooling effect from the mounting plate
on which the DMC2 units are mounted can compensate this. The necessary area
for compensation is 0,04 m2/DMC2.
At temperatures above 40°C, a fan is recommended because of the decrease of
current rating above this temperature. The use of a fan will also compensate for the
increased ambient temperature and thus avoid the reduced lifetime of the
electronics. The fan can be mounted either on the DMC2 unit or beside it.
I/O
Digital inputs:
Number of inputs 10
Maximum voltage 30 V
Input high > 12.9 V, typical 10 V
Input low <2 V, typical 5 V
Hysteres >3 V, typical 5 V
Input impedance to ground 6.8 kΩ
Filter time 0.7 ms
Digital outputs:
Number of outputs 6
Output high +24 V
Output low < 0.7 V
Max voltage + 30 V DC
Max current 100 mA, short circuits proof.
Max voltage drop 3V
Analog inputs:
Number of inputs 2
Voltage range ±10 V
Common mode voltage ±10 V, Max.
Resolution 14 bit
Linearity 8 bit
Input impedance 40 kΩ
Filter time 0.1 ms
Analog outputs:
Number of outputs 2
Resolution 12 bit
Voltage swing ±10 V
Max current 0.5 mA
Dedicated output for READY signal:
Controlled by Software and hardware
Type Relay, normally open
Max voltage 24V DC
Max current 0.2A
Motor brake relay output:
Rating AC 250 VAC / 2 A
Rating DC 24 VDC / 2A
External freewheeling diode required
MEASURE CONNECTION
Function Specification
Low-level differential analog input for Input ± 50mV
measurement bridge. ± 5 V DC supply available.
LAN2
Function Specification
Second LAN interface in accordance Isolated
with CANopen standard CiA 301. 7-26.5 VDC external supply.
ENVIRONMENTAL DATA
Environment Specification
Pollution degree (IEC 664,A) Degree 2
Altitude 1000 m
Protection class IP 20, Nema 1
EMC, Emission EN 50081-2
EMC, Immunity EN 50082-2
ENVIRONMENTAL TESTS
Operating on average load:
Cold (IEC 68-2-1) ±0ºC, 2 h
Heat (IEC 68-2-2) +40ºC, 2 h
Operating on reduced load:
Cold (IEC 68-2-1) ±0ºC, 2 h
Heat (IEC 68-2-2) +60ºC, 2 h
RESOLVER SPECIFICATION
Winding Configuration 1-phase input / 2 phase output
Primary Rotor
Pole Number 2-pole or more
Operating Frequency 4 kHz
Output Voltage 3 Vrms
Input Voltage 3 - 8 Vrms (depends on Transformation Ratio)
Transformation Ratio 0.4-1.0 at 4kHz
Phase Shift ±45º
Input Current Max 150 mA (preferable max 75 mA) 1)
Electrical Error <25 arc minute
1) 2
DMC resolver output are able to drive 150 mA. If two resolvers are
driven from one DMC2, then each resolvers input current should be max 75 mA.
STARTUP MESSAGE
When power is applied to the DMC2 the following startup message is displayed,
This line is always sent using 9600 baud independent of the settings in the eeprom
related to the COMM group or any programming of the COMM group. The line
gives information about the content of the EEProm used for initialization of the
serial communication (COMM group).
The assignments made to the COMM group by the firmware at startup, are:
If there appears to be a problem communicating with the DMC2, then check the
startup message first to verify that the initial settings are correct.