Ips 1
Ips 1
Ips 1
Project Engineer
JAUNPUR NAGAR PALIKA PARISHAD AREA INTERCEPTION/DIVERSION OF DRAINS AND
SEWAGE TREATMENT SCHEME, DISTRICT – JAUNPUR
ESTIMATE FOR EXPENDITURE ON OPERATION AND MAINTENANCE OF PUMPING PLANTS AND SUB STATION FOR A
PERIOD OF 12 MONTHS
Sl.
No. Description Qty. Unit Months Rate Amount
1 2 3 4 5 6 7
1 EXPENDITURE ON STAFF FOR O&M OF PUMPING
PLANTS
a) Operators 4 Nos. 12 18000.00 864000.00
b) Mechanic 1 Nos. 12 20000.00 240000.00
c) Supervisor 1 Nos. 12 20000.00 240000.00
d) Electrician 1 Nos. 12 20000.00 240000.00
e) Helper 4 Nos. 12 18000.00 864000.00
TOTAL - A 2448000.00
A Fixed Charges
Project Engineer
JAUNPUR NAGAR PALIKA PARISHAD AREA INTERCEPTION/DIVERSION OF DRAINS AND SEWAGE
TREATMENT SCHEME, DISTRICT – JAUNPUR
ESTIMATE FOR SUB-STATION
PROJECT ENGINEER
JAUNPUR NAGAR PALIKA PARISHAD AREA INTERCEPTION/DIVERSION OF DRAINS AND
SEWAGE TREATMENT SCHEME, DISTRICT – JAUNPUR
ESTIMATE OF POWER CONNECTION
Project Engineer
JAUNPUR NAGAR PALIKA PARISHAD AREA INTERCEPTION/DIVERSION OF DRAINS
AND SEWAGE TREATMENT SCHEME, DISTRICT – JAUNPUR
Project Engineer
Design Calculation
SPS-1
Three (2W+2S) numbers pumping plants each of P/2 capacity will be provided
Transformer
Alternative - 1
Total Load for 2 nos peak flow pump motor set = 59.68 KW
Misc Load = 10 KW
Total Load = 69.68 KW
Hence Transformer KVA required at 0.8 power factor &
20% margin
= 104.52 KVA
Next commercial rating = 125 KVA
Operating Voltage = 11/0.415 KV
file:///conversion/tmp/scratch/513700323.xlsx
JAUNPUR NAGAR PALIKA PARISHAD AREA INTERCEPTION/DIVERSION OF DRAINS AND SEWAGE
TREATMENT SCHEME, DISTRICT – JAUNPUR
16 Installation, commissioing & testing for one IPS 1 Job 20000 20000
17 Trial run for 3 month period for one IPS 1 Job 15000 15000
TOTAL 3670000
Say Rs. In Lacs 36.70
Project Engineer
Annexure-1
S. No. Particulars Qty. Rate Amount
Project Engineer
Annexure-2
S. No. Particulars Qty. Rate Amount
Project Engineer
JAUNPUR NAGAR PALIKA PARISHAD AREA INTERCEPTION/DIVERSION OF DRAINS AND
SEWAGE TREATMENT SCHEME, DISTRICT – JAUNPUR
ESTIMATE FOR SUPPLY AND INSTALLATION OF PUMPING PLANTS ALONG WITH OTHER
ACCESSORIES
Casing- 2% Nici
Impeller - CF8M
Shaft - AISI410
Capacity – 3900 LPM
Total Head – 15 Mtr.
HP of Motor – 20 (4W + 2 SB) 6 Set 12.50 75.00
1.2 Accessories of each submersible pumping Plant
(a) Pedestal with autocoupling – 1 No.
(b) SS guide pipe – approx. 9 M
(c) SS chain with shackles – approx. 9 M
(d) CIDF Bend 200mm dia x 90º - 1 No. 6 Sets 2.25 13.50
2 Auto transformer starter of 25 H.P. with oil suitable for above pumping 6 Nos. 1.22 7.32
plant.
3 Main Pipes, valves and Specials
(i) CIDF Reflex valve conforming to IS: 5312 suitable for sewage
applicable 200mm dia size.
6 Nos. 0.48 2.88
(ii) CIDF Reflex valve conforming to IS: 5312 suitable for sewage
applicable 350mm dia size.
1 Nos. 0.65 0.65
(iii) Main piping & specials, pipes to conect the pump deliveries and
making out common delivery.
1 Set 6.75 6.75
4 Sluice gate shall confirm to IS 13349 or IS 3042. Door gate, frame, wall,
thimble & stop bar shall be CI per IS 210 Gr FG200.
6 Set 4.25 25.50
5 LT Control Panel for Pumping Plant for SPS-1
LT Control Panel having 3 Nos. incoming of 200 amp MCCB and 10 Nos.
outgoing panels suitable to operated on 380±10% volt, 3 Phase, 50 Hz, AC
supply as per details given below:
1 Set 8.50 8.50
Sl. Particulars Qty. Rate Amount
No. (in Lacs) (in Lacs)
1 2 3 4 5
(a) 3 Nos. Incoming Panels each consisting of following items:
(i) MCCB of 100 Amp -3 Nos. with indicating lamps and mechanical
on/off indication
(ii) CTs of suitable ratio – 1 No.
(iii) Ammeter with selector switch – 1 No.
(iv) Voltmeter with selector switch – 1 No.
(v) Power factor meter (0.5 Lag & 0.5 Lead) – 1 No.
(vi) Frequency meter – 1 No.
(vii) KWH meter – 1 No.
(viii) 2 Pole over current relay and one pole earth fault relay – 1 No.
(b) Bus bar chamber having 3 Nos. bus bars for phase and 1 No. bus bar
for neutral suitable size – 1 No.
(vii) Automatic start / stop device according to level in the sump – 1 No.
PROJECT ENGINEER
JAUNPUR NAGAR PALIKA PARISHAD AREA INTERCEPTION/DIVERSION OF DRAINS AND
SEWAGE TREATMENT SCHEME, DISTRICT – JAUNPUR
Techincal Statement of Lift Pumping Station atTail end of Quila Mohalla drain
= 0.0127 m³/s
Q = π/4 d² V
Qx 4
V = d²
πx
0.0127 x 4
d = π x 2.75
0.05
= 0.077
8.64
d = 0.077 m
d = 77 mm
Say = 80 mm
4 Design of common header
Capacity of one pump = 760 LPM
Total discharge of pump when 4 pump are running = 4 x 760
= 3040 LPM
3040
In m³/s. =
1000 x 60
= 0.05 m³/s
Q = π/4 d² V
Qx 4
V = d²
πx
0.05 x 4
d = π x 2.5
0.203
= 0.1606779691
7.850
d = 0.161 m
d = 161 mm
Say = 150 mm
5 Capacity of Breakers
Capacity of T.F = 63 KVA
No. of T.F = (1W + 1S)
6 Size of Cable
ii HT Cable Size
Rating of Transformer = 200 KVA
Full Load Current ( Ifl ) = 200
1.7321 x 11
= 10.50 Amp
Derating Factor = 0.87
Current Capacity Cable considering derating = 10.50/0.87
= 12.07 Amp
ii LT Cable Size
Rating of Transformer = 200 KVA
Full Load Current ( Ifl ) = 200
1.7321 x 0.4
= 288.67 Amp
Derating Factor = 0.87
Current Capacity Cable considering derating = 288.67/0.87
= 331.8 Amp
Project Engineer
JAUNPUR NAGAR PALIKA PARISHAD AREA INTERCEPTION/DIVERSION OF DRAINS AND
SEWAGE TREATMENT SCHEME, DISTRICT – JAUNPUR
Techincal Statement of Lift Pumping Station at Tail end of Jogiyapura Mohalla drain
= 0.0070 m³/s
Q = π/4 d² V
Qx 4
V = d²
πx
0.0070 x 4
d = π x 2.75
0.028
= 0.057
8.64
d = 0.057 m
d = 57 mm
Say = 75 mm
4 Design of common header
Capacity of one pump = 420 LPM
Total discharge of pump when 4 pump are running = 4 x 420
= 1680 LPM
1680
In m³/s. =
1000 x 60
= 0.028 m³/s
Q = π/4 d² V
Qx 4
V = d²
πx
0.028 x 4
d = π x 2.5
0.112
= 0.119
7.850
d = 0.119 m
d = 119 mm
Say = 125 mm
5 Capacity of Breakers
Capacity of T.F = 63 KVA
No. of T.F = (1W + 1S)
6 Size of Cable
ii HT Cable Size
Rating of Transformer = 200 KVA
Full Load Current ( Ifl ) = 200
1.7321 x 11
= 10.50 Amp
Derating Factor = 0.87
Current Capacity Cable considering derating = 10.50/0.87
= 12.07 Amp
ii LT Cable Size
Rating of Transformer = 200 KVA
Full Load Current ( Ifl ) = 200
1.7321 x 0.4
= 288.67 Amp
Derating Factor = 0.87
Current Capacity Cable considering derating = 288.67/0.87
= 331.8 Amp
Project Engineer
JAUNPUR NAGAR PALIKA PARISHAD AREA INTERCEPTION/DIVERSION OF DRAINS AND SEWAGE TREATMENT
SCHEME, DISTRICT – JAUNPUR
Techincal Statement of Lift Pumping Station at Tail end of Achala Ghats drain
= 0.0053 m³/s
Q = π/4 d² V
Qx 4
V = d²
πx
0.0053 x 4
d = π x 2.75
0.021
= 0.049
8.64
d = 0.049 m
d = 49 mm
Say = 50 mm
4 Design of common header
Capacity of one pump = 315 LPM
Total discharge of pump when 4 pump are running = 4 x 315
= 1260 LPM
1260
In m³/s. =
1000 x 60
= 0.021 m³/s
Q = π/4 d² V
Qx 4
V = d²
πx
0.021 x 4
d = π x 2.5
0.084
= 0.103
7.850
d = 0.103 m
d = 103 mm
Say = 100 mm
5 Capacity of Breakers
Capacity of T.F = 63 KVA
No. of T.F = (1W + 1S)
6 Size of Cable
ii HT Cable Size
Rating of Transformer = 200 KVA
Full Load Current ( Ifl ) = 200
1.7321 x 11
= 10.50 Amp
Derating Factor = 0.87
Current Capacity Cable considering derating = 10.50/0.87
= 12.07 Amp
ii LT Cable Size
Rating of Transformer = 200 KVA
Full Load Current ( Ifl ) = 200
1.7321 x 0.4
= 288.67 Amp
Derating Factor = 0.87
Current Capacity Cable considering derating = 288.67/0.87
= 331.8 Amp
Project Engineer
JAUNPUR NAGAR PALIKA PARISHAD AREA INTERCEPTION/DIVERSION OF DRAINS AND
SEWAGE TREATMENT SCHEME, DISTRICT – JAUNPUR
ESTIMATE FOR EXPENDITURE ON OPERATION AND MAINTENANCE OF PUMPING PLANTS AND SUB STATION FOR A
PERIOD OF 12 MONTHS
Sl.
No. Description Qty. Unit Months Rate Amount
1 2 3 4 5 6 7
1 EXPENDITURE ON STAFF FOR O&M OF PUMPING
PLANTS
a) Operators 4 Nos. 12 18000.00 864000.00
b) Mechanic 1 Nos. 12 20000.00 240000.00
c) Supervisor 1 Nos. 12 20000.00 240000.00
d) Electrician 1 Nos. 12 20000.00 240000.00
e) Helper 4 Nos. 12 18000.00 864000.00
TOTAL - A 2448000.00
A Fixed Charges
Project Engineer