Connection Solutions: AI 301 / Issue V - 03/16
Connection Solutions: AI 301 / Issue V - 03/16
Connection Solutions: AI 301 / Issue V - 03/16
5
Reversible Armour Clamping Ring (RAC)
General identification ring orientation for:
6
Braid 'X',
SWA Flat Steel Wire 'Y',
Position Steel Tape 'Z'
Ring Position
1. Backnut
2. Middle Nut
3. Reversible Armour Clamping Ring (RAC)
4. Armour Spigot
5. Rubber Pot
6. Entry (with captive deluge seal)
IMPORTANT: The arrowhead indicating the
correct armour thickness or type should point
towards the equipment
Note: Armour cable acceptance sizes are marked on
Cable Preparation Gland Preparation the clamping ring.
II
6
5
Armour / braid
4
I I
4
3
3 3
Note:
Tape armour must be 2
re-trimmed at 90° to the
2 vertical axis of the cable 2
after it has been spread,
to ensure that the full 1
face is correctly
1 presented. 1
Shroud option
A B C
Strip Cable to suit equipment as shown above and Push the cable through the armour spigot . Spread Remove the rubber pot from the entry . Place
expose the armour/braid 'I' removing all cable fillers. armour/braid over the armour spigot until the end the entry over the armour spigot . Move the
'I' = 20mm for cable gland sizes Os to A of the armour/braid is up against the shoulder of the sub-assembly and up to meet the entry .
'I' = 25mm for cable gland sizes B to C2 armour cone. Position the armour clamping ring .
'I' = 32mm for cable gland sizes D to F
'II' to suit equipment.
If required, fit shroud.
See Notes re. Drain Wires.
2 2
2
D E F
Hold the entry in position with a spanner/wrench Unscrew the middle nut and visually inspect that Remove the entry , spread the cable cores out for
to prevent rotation. Hand tighten the middle nut the armour/braid has been successfully clamped the compound packing. Pack the compound between
onto the entry and turn a further half to three between the armour spigot and the armour the cores shown. See notes below and Fig. 7 for
quarters of a turn with a spanner/wrench. clamping ring . If armour/braid not clamped repeat compound preparation.
assembly.
The mixing and installation of the compound at an ambient temperature below 4°C is not recommended due to extended curing periods.
The storage of the compound shall be at temperatures between 5°C and 30°C.
Tape
6
5 Remove surplus 6
compound
Compound
35mm
5
2
4
Remove surplus 1
compound
G H I
With all gaps and voids filled, bring the conductors Replace the entry over the rubber pot ensuring Locate and hand tighten the sub-assembly and
back together and pack more compound around the that compound does not cover the end of . to the entry .
outside of the conductors. Tape the conductors
together to prevent disturbance of the compound IMPORTANT: The conductors must not be
seal. Pass the rubber pot over the armour spigot moved for a minimum of four hours.
and remove any surplus compound. from the top of
rubber pot and the joint face as indicated.
5
6
2
1
1
J K
Allow the compound to cure. (See Fig. 7 for Curing Times). Untighten Re-assemble the rubber pot and the entry . Tighten the
the sub-assembly and from the entry to enable inspection. sub-assembly and to the entry until resistance is felt and
The rubber pot may be removed for inspection to ensure that the add half to three quarters of a turn to with a spanner / wrench.
packing is satisfactory. Tighten the backnut to form a seal around the cable, then
tighten a further full turn using a wrench / spanner. Ensure that
Add further compound if necessary the middle nut does not rotate when tightening the backnut.
Ensure that the deluge seal is pulled down into position. Locate
the shroud over the cable gland, if applicable.
The following instructions are the various BASEEFA approved methods of passing drain wires etc. through the compound barrier
and should be followed if permitted by cable installation specifications.
DRAIN WIRE PREPARATION
1.0 INSULATING DRAIN WIRES WITH HEAT SHRINK OR COLD SHRINK TUBING
1.1 Fold back the armour / braid and bend it to right angles from the inner sheath.
1.2 Remove foils and tape level with the outer sheath, exposing the drain wires and insulated conductors. Cut back a further 10mm of inner sheath.
1.3 Pass 100mm length of heat shrink or cold shrink tubing over the drain wire until it comes into contact with the foils, then shrink the tubing evenly down onto the drain wire
so that no air pockets occur.
1.4 To insulate the joint between the foils and the tubing a suitable piece of 10mm long shrink tubing or neoprene stretch tubing or a 10mm wide lap of PVC tape may be used.
1.5 After completing 1.1 to 1.4 on each drain wire, lay the armour / braid parallel to the cable, if applicable, then carry out instruction B.
2.0 INSULATING DRAIN WIRES / SCREENS WITH SEPARATE INSULATED CRIMPED CONDUCTORS OR SOLDERED CONNECTION
2.1 Fold back the armour / braid and bend to right angles from the inner sheath.
2.2 Remove a further 15mm of inner sheath (See Fig. 1).
2.3 Unravel one or two groups of wires from the screen wires, then remove the remainder of the screen wires (See Fig. 2).
2.4 Twist the group of screen wires into a pigtail and cut to 15mm long.
2.5 Crimp an insulated conductor to the pigtail wih a suitable insulated butt ferrule (or soldered connection), leaving enough length of the insulated conductor to enable the
remote end to be connected to the earth terminal in the equipment. (See Fig. 3). Note: There shall be a minimum of 10mm of compound on both ends of the crimped
/soldered joint.
2.6 To insulate the joint between the screen wires and the insulated conductor, place one lap of PVC insulating tape over the exposed metallic joint.
2.7 After completing 2.1 to 2.6 on each drain wire, lay the armour / braid parallel to the cable. Then carry out instruction B.
Foils
Outer Sheath
90
The compound may be adversely affected by some
80
Shore Hardness
solvent vapours. If such vapours are likely to be
70 present in the vicinity of the cable gland in service,
suitable precautions may be necessary.
60
(Contact Hawke's Technical Dept).
50
40 The compound cures at a Shore D hardness of 85,
40 ºC
30 when it can be handled. The compound when fully
25 ºC cured is suitable for use at a temperature range of
20 -60°C to +80°C.
4 ºC
10
0
4 8 12 16
Time (Hours) Fig. 7
Compressed
Outer Steel Wire Armour/
Maximum
Size Inner Sheath/Cores Dimensions
Length
Length
Size Sheath Tape/Braid
Ref Max. Max. ATEX
Orientation Orientation Across Across
Metric NPT Over Inner Max. No. Min. Max.
Cores Sheath of Cores
1 2 Flats Corners
Os M20 ½" 8.9 10.0 12 5.5 12.0 0.8/1.25 0/0.8 67.0 83.0 24.0 26.5
O M20 ½" 8.9 10.0 12 9.5 16.0 0.8/1.25 0/0.8 67.0 83.0 24.0 26.5
A M20 ½" - ¾" 11.0 12.5 15 12.5 20.5 0.8/1.25 0/0.8 67.0 84.0 30.0 32.5
B M25 ¾" - 1" 16.2 18.4 30 16.9 26.0 1.25/1.6 0/0.7 73.6 91.0 36.0 39.5
C M32 1" - 1¼" 21.9 24.7 42 22.0 33.0 1.6/2.0 0/0.7 78.0 98.0 46.0 50.5
C2 M40 1¼" - 1½" 26.3 29.7 60 28.0 41.0 1.6/2.0 0/0.7 82.4 100.0 55.0 60.6
D M50 1½" - 2" 37.1 41.7 80 36.0 52.6 1.8/2.5 0/1.0 88.7 116.0 65.0 70.8
E M63 2" - 2½" 47.8 53.5 100 46.0 65.3 1.8/2.5 0/1.0 92.7 124.0 80.0 88.0
F M75 2½" - 3" 59.0 66.2/65.3 120 57.0 78.0 1.8/2.5 0/1.0 99.4 122.0 95.0 104.0