Wind Ananlysis Calculation For MR Pankaj Pachlore: 8.5 + 3 11.5 Between 1.5 & 10 M

This document provides the wind analysis calculation for a structure design for Mr. Pankaj Pachlore. It includes calculations of basic wind speed, design wind pressure, internal and external pressure coefficients, uplift forces on purlins and rafters, and wind forces on columns. It also includes the selection and design checks of U-channel purlins and welds.

Uploaded by

hitesh gandhi
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
140 views

Wind Ananlysis Calculation For MR Pankaj Pachlore: 8.5 + 3 11.5 Between 1.5 & 10 M

This document provides the wind analysis calculation for a structure design for Mr. Pankaj Pachlore. It includes calculations of basic wind speed, design wind pressure, internal and external pressure coefficients, uplift forces on purlins and rafters, and wind forces on columns. It also includes the selection and design checks of U-channel purlins and welds.

Uploaded by

hitesh gandhi
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 9

Wind Ananlysis Calculation for Mr Pankaj Pachlore

1) Rise of structure = FGL + Ht of Structure


= 8.5 + 3
= 11.5

2) Average Height of = between 1.5 & 10 m


Surrounding
Obstructions

3) Maximum Dimesions = 4.716 m


of Structure

4) Local Topography = Flat area (< 3 degree)

5) Air Permeability in = > 20 %


building

6) Basic Wind Speed (Vb) = 39 m/s


(As per IS 875 III)

7) Angle of Structures = 10 degrees

8) K1 = 0.92 ( ref table -1)


K2 = 1.01 ( ref table -2)
K3 = 1 (clause 5.3.3)

9) Design Wind Pressure = 0.6 Vz^2


(Pz)

Design Wind Speed (Vz) = Vb x K1 K2 x K3


= 39x0.92x1.01x1
= 36.24 m/s

Design Wind Pressure (Vz) = 0.6 x 36.24x36.24


= 788 N/sqm
= 0.788 KN/Sqm

10) Co-efficient of Internal pressure (Cpi)


(ref. IS875III. Pg 41, figure 2)
Length of structure (b) = 4.68 m
width of structure (d) = 3.514 m
b/d = 1.33
Therefore , for Value of b/d>1
Maximum internal presure = 0.8

11) Co-efficient of External pressure (Cpe)


(ref. IS875III. Pg 47, table 8)
For Ø = 0
Cpe = -0.9
Now
Cpi - Cpe = 1.7

12) Hence,
Maximum Wind Pressure = 0.788x1.7
acting on roof = 1.34 KN/Sqm

13) Uplift acting on Purlin

Vertical component = cos Ø x 1.34


= 1.32 KN/Sqm
Module Size
Length = 1.96 m
Breadth = 0.99 m

Module Weight = 0.125 KN/sqm

Now, Uplift Member load on = 1.32X1.96/2,


purlin = 1.29 Kn/m

Downward Module = 0.125 KN/m


Weight on purlin =

Hence, Net Uplift Acting on Purlin = uplift force - downward weight


= 1.165 KN/m

Length fo Purlin = 2.01 m


Point Load acting on Rafter = 1.165 X 2.01/2
= 1.17 KN
Point Load on Rafter with 2
modules on purlin = 1.17x 2
= 2.34 KN

For Staad
Net Uplift UDLon Purlin = 1.165 KN/m
Net Uplift Point load on Rafter = 1.17 KN
Net Uplift Point load on Rafter = 2.34 KN
with 2 modules at a point

Force on Columns
c/c distance of columns in Z = 3.706 m
direction

c/c distance of columns in x = 1.724 m


direction

Wind Force acting on columns = maximum wind pressure x half of


in Z direction distance between 2 columns
2.48 KN/m
Wind Force acting on columns = 1.16 KN/m
in X direction
Design Note for Mr Pankaj Pachlore

Wind Ananlysis Calculation

1) Rise of structure = FGL + Ht of Structure


= 8.5 + 3
= 11.5

2) Average Height of = between 1.5 & 10 m


Surrounding
Obstructions

3) Maximum Dimesions = 4.716 m


of Structure

4) Local Topography = Flat area (< 3 degree)

5) Air Permeability in = > 20 %


building

6) Basic Wind Speed (Vb) = 39 m/s


(As per IS 875 III)

7) Angle of Structures = 10 degrees

8) K1 = 0.92 ( ref table -1)


K2 = 1.01 ( ref table -2)
K3 = 1 (clause 5.3.3)

9) Design Wind Pressure = 0.6 Vz^2


(Pz)

Design Wind Speed (Vz) = Vb x K1 K2 x K3


= 39x0.92x1.01x1
= 36.24 m/s

Design Wind Pressure (Vz) = 0.6 x 36.24x36.24


= 788 N/sqm
= 0.788 KN/Sqm

10) Co-efficient of Internal pressure (Cpi)


(ref. IS875III. Pg 41, figure 2)
Length of structure (b) = 4.68 m
width of structure (d) = 3.514 m
b/d = 1.33
Therefore , for Value of b/d>1
Maximum internal presure = 0.8

11) Co-efficient of External pressure (Cpe)


(ref. IS875III. Pg 47, table 8)
For Ø = 0
Cpe = -0.9

Now
Cpi - Cpe = 1.7

12) Hence,
Maximum Wind Pressure = 0.788x1.7
acting on roof = 1.34 KN/Sqm

13) Uplift acting on Purlin

Vertical component = cos Ø x 1.34


= 1.32 KN/Sqm
Module Size
Length = 1.96 m
Breadth = 0.99 m

Module Weight = 0.125 KN/sqm

Now, Uplift Member load on = 1.32X1.96/2,


purlin = 1.29 Kn/m

Downward Module = 0.125 KN/m


Weight on purlin =

Hence, Net Uplift Acting on Purlin = uplift force - downward weight


= 1.165 KN/m

Length fo Purlin = 2.01 m


Point Load acting on Rafter = 1.165 X 2.01/2
= 1.17 KN
Point Load on Rafter with 2
modules on purlin = 1.17x 2
= 2.34 KN

For Staad
Net Uplift UDLon Purlin = 1.165 KN/m
Net Uplift Point load on Rafter = 1.17 KN
Net Uplift Point load on Rafter = 2.34 KN
with 2 modules at a point

Force on Columns
c/c distance of columns in Z = 3.706 m
direction

c/c distance of columns in x = 1.724 m


direction

Wind Force acting on columns = maximum wind pressure x half of


in Z direction distance between 2 columns
2.48 KN/m

Wind Force acting on columns = 1.16 KN/m


in X direction
Design of Purlin

Section Selected For Purlin = U Channel Cold Formed GI


Yeild Strength = 210 N/Sqmm
Ultimate Tensile Strenth = 310 N/Sqmm
E= 200000 N/Sqmm

Properties of U channel (IS 811)

weight = 2.08 kg/m


Area 2.66 cm^2
Ixx = 6.63 cm^4
Iyy = 5.73 cm^4
Zxx = 3.32 cm^3
Zyy = 2.74 cm^3
Permissible Strength = 250 N/sqmm

Factored UDL on Purlin = 1.5 x1.165


= 1.7475 KN/m
Length of Purlin = 2.01 m

Moment on Purlin = W x L / 10
= 0.35 KNm

Now
Zyy = Moment / 165
= 2121.212 mm^3
= 2.12 cm^3
Hence
Provided Zyy > Required Zyy

Deflection in Purlin = 5 x WxL^3 / 384 Eiyy


= 0.010749 mm

Allowable Defletion = L/180


= 11.17 mm

Hence deflection check is ok

Provided U Purlin 41x41x15x2 is OK

Design of Weld

Weld Size = 4 mm
Throat Thickness = 2.8 mm
Maximum Force = 9.4 KN (from staad)
Permissible Shear Stress in = 100 N/sqmm
weld(Ʈs)

Length of Weld Required = Load / Ʈs x Throat Thickness


= 33.57 mm

Length of Weld Available around SHS 72x72x3.2 and 60x602.6 is


more than required. Hence 4 mm weld size is OK
Design Note for Mr Pankaj Pachlore

Wind Ananlysis Calculation

1) Rise of structure = FGL + Ht of Structure


= 8.5 + 3
= 11.5

2) Average Height of = between 1.5 & 10 m


Surrounding
Obstructions

3) Maximum Dimesions = 4.716 m


of Structure

4) Local Topography = Flat area (< 3 degree)

5) Air Permeability in = > 20 %


building

6) Basic Wind Speed (Vb) = 39 m/s


(As per IS 875 III)

7) Angle of Structures = 10 degrees

8) K1 = 0.92 ( ref table -1)


K2 = 1.01 ( ref table -2)
K3 = 1 (clause 5.3.3)

9) Design Wind Pressure = 0.6 Vz^2


(Pz)

Design Wind Speed (Vz) = Vb x K1 K2 x K3


= 39x0.92x1.01x1
= 36.24 m/s

Design Wind Pressure (Vz) = 0.6 x 36.24x36.24


= 788 N/sqm
= 0.788 KN/Sqm

10) Co-efficient of Internal pressure (Cpi)


(ref. IS875III. Pg 41, figure 2)
Length of structure (b) = 4.68 m
width of structure (d) = 3.514 m
b/d = 1.33
Therefore , for Value of b/d>1
Maximum internal presure = 0.8

11) Co-efficient of External pressure (Cpe)


(ref. IS875III. Pg 47, table 8)
For Ø = 0
Cpe = -0.9

Now
Cpi - Cpe = 1.7

12) Hence,
Maximum Wind Pressure = 0.788x1.7
acting on roof = 1.34 KN/Sqm

13) Uplift acting on Purlin

Vertical component = cos Ø x 1.34


= 1.32 KN/Sqm
Module Size
Length = 1.96 m
Breadth = 0.99 m

Module Weight = 0.125 KN/sqm

Now, Uplift Member load on = 1.32X1.96/2,


purlin = 1.29 Kn/m

Downward Module = 0.125 KN/m


Weight on purlin =

Hence, Net Uplift Acting on Purlin = uplift force - downward weight


= 1.165 KN/m

Length fo Purlin = 2.01 m


Point Load acting on Rafter = 1.165 X 2.01/2
= 1.17 KN
Point Load on Rafter with 2
modules on purlin = 1.17x 2
= 2.34 KN

For Staad
Net Uplift UDLon Purlin = 1.165 KN/m
Net Uplift Point load on Rafter = 1.17 KN
Net Uplift Point load on Rafter = 2.34 KN
with 2 modules at a point

Force on Columns
c/c distance of columns in Z = 3.706 m
direction

c/c distance of columns in x = 1.724 m


direction

Wind Force acting on columns = maximum wind pressure x half of


in Z direction distance between 2 columns
2.48 KN/m

Wind Force acting on columns = 1.16 KN/m


in X direction
Design of Purlin

Section Selected For Purlin = U Channel Cold Formed GI


Yeild Strength = 210 N/Sqmm
Ultimate Tensile Strenth = 310 N/Sqmm
E= 200000 N/Sqmm

Properties of U channel (IS 811)

weight = 2.08 kg/m


Area 2.66 cm^2
Ixx = 6.63 cm^4
Iyy = 5.73 cm^4
Zxx = 3.32 cm^3
Zyy = 2.74 cm^3
Permissible Strength = 250 N/sqmm

Factored UDL on Purlin = 1.5 x1.165


= 1.7475 KN/m
Length of Purlin = 2.01 m

Moment on Purlin = W x L / 10
= 0.35 KNm

Now
Zyy = Moment / 165
= 2121.2121 mm^3
= 2.12 cm^3
Hence
Provided Zyy > Required Zyy

Deflection in Purlin = 5 x WxL^3 / 384 Eiyy


= 0.010749 mm

Allowable Defletion = L/180


= 11.17 mm

Hence deflection check is ok

Provided U Purlin 41x41x15x2 is OK

Design of Weld

Weld Size = 4 mm
Throat Thickness = 2.8 mm
Maximum Force = 9.4 KN (from staad)
Permissible Shear Stress in = 100 N/sqmm
weld(Ʈs)

Length of Weld Required = Load / Ʈs x Throat Thickness


= 33.57 mm

Length of Weld Available around SHS 72x72x3.2 and 60x602.6 is


more than required. Hence 4 mm weld size is OK