Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Novus XT Series: Outdoor UPS System

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Novus XT Series

Outdoor UPS System

> Telcordia, Seismic Zone-4 approved NEMA 3R outdoor


weather-resistant enclosure
> Complete conditioning & reliable backup power for critical
revenue-generating equipment
> Simple, flexible installation options for pole, wall and pedestal configurations
> Maintenance bypass feature allows easy and efficient battery and
UPS replacement
> Wide temperature range -40–+50˚C with full solar load
> Over one million Alpha power installations worldwide

Alpha’s Novus XT Series power systems provide critical power protection to outside plant communication
applications. Both four and eight battery systems are available, as well as generator options for extended runtime
applications. The Novus XT Series also works to protect equipment from the surges and spikes present in normal
utility power. Temperature-compensated charging maximizes battery life in the harsh, outside plant environment.
Flexible power, runtime and voltage configurations make the Novus XT Series the best choice for outdoor
powering applications around the world. Intelligent buck and boost operation provides stable output during high
and low voltage conditions.
Novus XT System

Standard Features Power Modules


Input / Output Surge Protection Novus power modules are available in three power ratings: 1250, 2000
and 2200VA. Power module selection should be based on needed output
Intelligent buck/boost operation for greater protection
power rating and backup time
Hot swappable UPS and batteries
Noise suppression, FCC Class B 1250VA Power Module 50Hz 60Hz
Multiple mounting configurations Input / Output Voltage nominal: 230VAC 120VAC
Rugged, outdoor weather resistant construction Input / Output Frequency nominal: 50Hz 60Hz
Lockable enclosure Input Current: 10A 20A
NRTL / CSA / CE approved Input Voltage Variation: 177 – 258VAC 92 – 135VAC
Output Power: 1250VA 1250VA
8 Battery System also includes: Active Output Power: 875W 875W
Telcordia Zone 4 approved with Battery Retention Bar Typical Efficiency: >95% >95%
Telcordia salt fog tested, 14 day operational Max Charge Current: 6A 6A
Telcordia approved Door Restraint Battery Backup Time*: 2 – 8Hrs 2 – 8Hrs

2000VA / 2200VA Power Modules 50Hz 60Hz


General Specifications
Input / Output Voltage nominal: 230VAC 208/240VAC
Output
Input / Output Frequency nominal: 50Hz 60Hz
Output Voltage Regulation: 5% Input Current: 15A 15A
Waveform: Pure sine wave Input Voltage Variation: 195 – 265VAC 176 – 276VAC
Typical Efficiency: >95%
Output Power
Typical Output Voltage THD: <5%
2000VA: 2000VA 2000VA
Typical Transfer Time: 2ms typical
2200VA: 2200VA 2200VA
Audible Noise at 1m: <55dbA
Active Output Power
Environment 2000VA: 2000W 2000W
2200VA: 2200W 2200W
Operating Temperature: -35 – +50˚C
Typical Efficiency: >95% >95%
Max Charge Current: 10A 10A
Agency Compliance
Battery Backup Time*: 2 – 16Hrs 2 – 16Hrs
Lightning/Surge Protection: Passes ANSI/IEEE
C.62.41/C.62.45 Cat A&B
Communication & Alarms
NEMA 3R DB-9 compatible connector / RS-232 interface capable of monitoring,
controlling, and calibrating the UPS, using ASCII commands with terminal
emulation software. External Alarm Signal with relay contacts for a) line
Enclosure Specifications fail, b) low battery warning, c) UPS needs service.

Dimensions 4-Battery 8-Battery


Highline / Brownout Protection
Width (in/mm): 24/610 31/788 Buck and Boost mode increases / decreases voltage by 12% of nominal
Height (in/mm): 36/914 37/956 line voltage if input voltage falls above or below 12% of nominal.
Depth (in/mm): 14/56 16/407
Weight (lb/kg)**: 350/158 812/368
Finish: Powder coat white over aluminum

* Backup time depends on load, battery, and operating temperature.


Optional DC Generator provides up to 100Hrs backup.
** Weight dependent upon internal battery choice.

4-Battery

049-084-14-004 (5/05)
: