INSTALLATION MANUAL

FRANÇAIS
AIR
CONDITIONER

DEUTSCH
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards
by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
POLSKI

VENTILATOR
Original instruction
[Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared
Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands
LIMBA ROMÂNĂ

[Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-


gu, Changwon-si, Gyeongsangnam-do, KOREA

www.lg.com
P/NO : MFL67855541 Copyright © 2018 LG Electronics Inc. All Rights Reserved.
Table of contents

TABLE OF CONTENTS
3 SAFETY PRECAUTIONS
7 Preparing for operation
7 Service
7 Standards for Model

8 INTRODUCTION
8 Symbols used in this manual
8 Feature dimension diagram

12 INSTALLATION
12 Installation map
14 Installation of main body
14 Connection of duct
16 Method to connect power cord
17 How to connect remote controller(accessory)
18 Group control
19 Installer setting -How to enter installer setting mode
20 Available accessories

22 TEST RUNNING
22 Method to operate and select air volume – Interlinked operation with ventilation.
23 Method to operate and select air volume – Ventilation single operation
24 In case of finding a problem at a test running
24 Airborne noise emission
24 Available accessories

2 Ventilator
Safety precautions

Safety precautions

ENGLISH
To prevent injury to the user or other people and property damage, the following instructions
must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.

WARNING This symbol indicates the possibility of death or serious injury.

CAUTION This symbol indicates the possibility of injury or damage.

Meanings of symbols used in this manual are as shown below.

Be sure not to do.

Be sure to follow the instruction.

WARNING
Installation
Do not use a defective For electrical work, Always ground the
or underrated circuit contact the dealer, product.
breaker. Use this appli- seller, a qualified elec-
ance on a dedicated trician, or an author-
circuit. ized service center.
• There is risk of fire or • Do not disassemble or • There is risk of fire or
electric shock. repair the product. There is electric shock.
risk of fire or electric shock.

Install the panel and Always install a dedi- Use the correctly rated
the cover of control cated circuit and breaker or fuse.
box securely. breaker.
• There is risk of fire or • Improper wiring or instal- • There is risk of fire or
electric shock. lation may cause fire or electric shock.
electric shock

Do not modify or Do not install, remove, Be cautious when


extend the power or re-install the unit by unpacking and
cable. yourself (customer). installing the product.
• There is risk of fire or • There is risk of fire, electric • Sharp edges could cause
electric shock. shock, explosion, or injury. injury.

Installation manual 3
Safety precautions

The fan is to be For installation, Do not install the prod-


installed so that the always contact the uct on a defective
blades are more than dealer or an author- installation stand.
2.3 m above the floor. ized service center.
• There is risk of fire, elec- • It may cause injury, acci-
tric shock, explosion, or dent, or damage to the
injury. product.

Do not let the product For re-installation of Do not open the main-
run for a long time when the installed product, tenance cover of the
the humidity is very always contact the main body during
high and a door or a dealer or an author- operation.
window is left open. ized service center.
• Moisture may condense • There is risk of fire, elec- • Otherwise, it may cause
and wet or damage furni- tric shock, explosion or electrical shock.
ture. injury.

Use the outdoor air Install the air intake Do not install this product
suction hole with the where polluted air can in a refrigerated ware-
net installed to ensure not be directly sucked house, heated swimming
that birds could not in. pool or other location
come in. where the temperature
and humidity are signifi-
cantly different.
• Remove estrange things • It may cause various • There is risk of electrical
like the bird’s nest. accidents, including suffo- shock, malfunctioning.
Otherwise, it may cause cation, due to the suction
scarcity of indoor oxygen. of harmful gasses(CO,
etc.)

Install this product in Install this product in Use the designated


an environment where and environments electrical wires for the
the temperature ranges where the outside air terminal board con-
from –10°C to +45°C intake meets the fol- nections, and connect
and the relative humidi- lowing conditions: the wires securely so
ty is less than 80%. It temperature range is that they will not
condensation is between –15°C and become disconnected.
expected to form, heat +40°C and the relative (Failure to ensure
up the fresh outside air humidity is 80% or proper connections
using a duct heater etc. less. may cause fire.)

4 Ventilator
Safety precautions

When passing metal ducts through Means for disconnection must be

ENGLISH
wooden buildings clad with metal incorporated in the fixed wiring in
laths, wire laths or metal, these accordance with the wiring rules.
ducts must be installed in such a
way that they will not make electri-
cal contact with the metal laths, wire
laths or metal sheets. (Power leak-
age can cause ignition)

Operation
When the product is Don't touch a dedicat- When the product is
soaked (flooded or ed circuit or breaker not be used for a long
submerged), contact with wet hands. time, disconnect the
an authorized service power supply plug or
center. turn off the breaker.
• There is risk of fire or • There is risk of electric • There is risk of product
eletric shock. shock. damage or failure, or
unintended operation.
When flammable gas Be cautious that water Turn the breaker off
leaks, turn off the gas could not enter the when cleaning or
and open a window for product. maintaining the prod-
ventilation before turn uct.
the product on.
• Do not use the telephone • There is risk of fire, elec- • There is risk of electric
or turn switches on or off. tric shock, or product shock.
There is risk of explosion damage.
or fire.

The outside ducts must be tilted at a Glove should be worn when doing
gradient (1/30 or more) down toward the installation work. (There is risk
the outdoor area from the ventilator of injury.)
unit, and properly insulated. (The
entry of rain water may cause power
leaks, fire or damage to household
property.)

Installation manual 5
Safety precautions

CAUTION
Installation
Don't connect the Do not install the prod- Install the product in
ground wire to the uct at a smoky and an insulated space
window frame or water oily place like kitchen from outdoor air.
cock. or factory.
• There is risk of electric • Otherwise. oil may • In case of installing the
shock. adhere to the filter or product outside of the
heating exchanger and insulated layer, dewing
cause trouble. occurs inside of the main
body in winter.And it caus-
es electrical shock or
falling of condensed water.
Keep level even when Use two or more peo- Do not install the prod-
installing the product. ple to lift and transport uct where it will be
the product. exposed to sea wind
(salt spray) directly.
• To avoid vibration or • Avoid personal injury. • It may cause corrosion on
water leakage. the product. Corrosion,
particularly on the con-
denser and evaporator
fins, could cause product
malfunction or inefficient
operation.
Operation
Use a soft cloth to Clean the filter and the Do not use the product
clean. Do not use heat exchanger regu- for special purposes,
harsh detergents, wax larly and use the such as preserving
or thinner, etc. gloves for cleaning. foods, works of art, etc.
It is a consumer venti-
lator, not a precision
refrigeration system.
• Otherwise, color or sur- • Adhering to a mass of • There is risk of damage
face of the oroduct mav dust may cause the dete- or loss of property.
deteriorate. rioration of air volume.
Do not block the inlet or outlet of air Do not step on or put anyting on the
flow. product.
• It may cause product failure. • There is risk of personal injury and fail-
ure of product.

6 Ventilator
Safety precautions

ENGLISH
Preparing for operation
1. Contact an installation specialist for installation.
2. Plug in the power plug properly.
3. Use a dedicated circuit.
4. Do not use an extension cord.
5. Do not start/stop operation by plugging/unplugging the power cord.
6. If the supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.

Service
1. For repair and maintenance, contact your authorized service dealer.
2. The appliance shall be disconnected from its power source during service and when re-
placing parts

Standards for Model

L Z - H 0 5 0 G B A 5

Development Sequence
Function
A: Basic
Model Type
B: Ceiling Concealed Type
Electrical Standard (Volts, Freq., Phase)
220-240 V, 50 Hz, 1 ph / 220 V, 60 Hz, 1 ph

Capacity
Ex) 080 ơ 800 CMH 100 ơ 1,000 CMH
Heat Exchange Type
H: Total Heat Recovery

Indicates that this is LG's VENTILATION system

Installation manual 7
Introduction

Introduction
Symbols used in this manual

This symbol alerts you to the risk of electric shock.

This symbol alerts you to hazards that could cause harm to the
product.

NOTICE This symbol indicates special notes.

Feature dimension diagram


Model : LZ-H025GBA4

Blower for exhausting air Suspension fixture

EA RA
(Exhaust Air) (Return Air)

OA SA
(Outdoor Air) (Supply Air )
Blower for supplying air F

Maintenance cover Control box

Total heat exchanger

Air filter
Unit : mm

Figure Pitch of suspension fixture Nominal Duct connection flange Duct pitch Weight
Model
diameter
A B C D E F G H J K L kg

LZ-H025GBA4 1 014 988 273 939 1 025 135 200 194 252 96 590 198 44

h It necessary to secure sufficient space for maintenance more than the dimensions described in the
product service.

8 Ventilator
Introduction

Model : LZ-H035GBA5 / LZ-H050GBA5

ENGLISH
Blower for exhausting air Suspension fixture

EA RA
(Exhaust Air) (Return Air)

OA SA
(Outdoor Air) (Supply Air )
Blower for supplying air F

Maintenance cover Control box

Total heat exchanger

Air filter

Unit : mm

Figure Pitch of suspension fixture Nominal Duct connection flange Duct pitch Weight
Model
diameter
A B C D E F G H J K L kg

LZ-H035GBA5
1 014 988 273 939 1 025 135 200 194 252 96 590 198 44
LZ-H050GBA5

h It necessary to secure sufficient space for maintenance more than the dimensions described in the
product service.

Installation manual 9
Introduction

Model : LZ-H080GBA5 / LZ-H100GBA5

Blower for exhausting air Suspension fixture

RA
(Return Air)

EA
(Exhaust Air)
SA
(Supply Air)
Blower for
OA supplying air

(Outdoor Air)

F
Control box
Maintenance cover
Total heat exchanger

Air filter

Unit : mm

Figure Pitch of suspension fixture Nominal Duct connection flange Duct pitch Weight
Model
diameter
A B C D E F G H J K L kg

LZ-H080GBA5
1 101 1 230 405 1 026 1 263 269 250 242 253 98 567 519 62.8
LZ-H100GBA5

h It necessary to secure sufficient space for maintenance more than the dimensions described in the
product service.

10 Ventilator
Introduction

Model : LZ-H150GBA5 / LZ-H200GBA5

ENGLISH
D

RA

EA

E
SA

OA

Maintenance cover Control box

M A J

F
G
H
C

K
L

Air filter Total heat exchanger

Unit : mm

Pitch of suspension
Figure Duct connection flange Weight
Model fixture
A B C D E F G H J K L M Kg

LZ-H150GBA5
1 352 1 230 818 1 026 1 263 361 242 253 98 340 350 130 130
LZ-H200GBA5

h It necessary to secure sufficient space for maintenance more than the dimensions described in the
product service.

Installation manual 11
Introduction

Installation
Installation map (LZ-H025GBA4 / LZ-H035GBA5 / LZ-H050GBA5 / LZ-H080GBA5 / LZ-H100GBA5)
Plane figure
RA grille

EA
Ventilator
SA grille
OA

Maintenance space

Inspection hatch
Front view
Duct slope: More than 1/30(wall side)
obtaining of right distance
(Preventing penetration of rain water) Duct Ceiling fixing bolt(Supplied by installer)

New type hood


(Preventing penetration of rain water)

Ventilator

EA
OA 1m or more 1m or more
SA RA
Inspection hatch
SA grille RA grille

Three dimension view

Maintenance cover
Control box

SA grille

Installation of maintenance cover

EA
Ventilator
main body
OA
More than 600

Maintenance space
600x600
Inspection hatch

12 Ventilator
Installation

Installation map (LZ-H150GBA5 / LZ-H200GBA5)

ENGLISH
Plane figure
RA grille

EA
Ventilator
OA
Maintenance
space SA grille
Inspection
hatch

Front view
Duct slope: More than 1/30(wall side)
obtaining of right distance
(Preventing penetration of rain water) Ceiling fixing bolt(Supplied by installer)

New type hood


(Preventing penetration
of rain water)
EA
OA

Inspection SA grille
hatch RA RA SA SA
1m or more 1m or more
RA grille

Three dimension view

Maintenance cover
Control box

SA grille

Installation of maintenance cover

EA
Ventilator
main body
OA
More than 600

Maintenance space
600x600
Inspection hatch

Installation manual 13
Installation

Installation of main body


Assembly of washer, nut
Ceiling fixing bolt
Tighten the common washer and nut (more than 21mm (M10)
for the outside diameter of M10, to the commercial ceil- Nut
ing fixing bolt (M10) as shown in the right figure.
Spring washer
• For the ceiling fixing bolt, perform work less than
50mm under the ceiling fixing bracket. Washer
Nut

Connection of duct
After securely connect the duct with the duct connection flange, wrap it with a commercial aluminium
tape so that air cannot be leaked.
Adjust the duct from the ceiling so that no force is applied to the main body of the ventilation system.
Always use two ducts at the outdoor with the heat insulating material for prevention of dewing.

Duct

Taping

14 Ventilator
Installation

ENGLISH
Heat insulating material
CAUTION:
Aluminium
• Check that there are no foreign materi-
als (paper, vinyl, etc) or cutoff powders
in the duct before connecting the duct.
• Take care so that shock may not be Main body
applied to the damper plate within the
main body when performing the duct Duct to OA
connection work.
Duct connection flange
• It is recommended to perform adiabat-
ic treatment even to the duct pipe at
the indoor side where ambient temper-
ature is expected higher than room
temperature when the main body of
the ventilation system for cooling in
summer. Rapid bending Excessive bending

• Take care so that work may not be per-


formed as in the left figure. Otherwise,
it may cause reduction of air volume
or abnormal noise.
Too close bending Rapid reduction of
to outlet duct diameter

CAUTION:
• In -10℃ below ambient temperature, when ventilation is installed the equivalent space in
the outdoor and outdoor, It may cause condensation, you must install drainage facili-
ties(drain pan) and MD(Motorized Damper) at SA/RA duct.

Installation manual 15
Installation

Method to connect power cord


Release two screws and then open the Cover of control box
cover of the control box. Screw
• With reference to the below wiring diagram, accu-
rately connect the main power cords into the termi-
nal block.

After inserting the power cord into the bushing, fully insert it into the termi-
nal block for connection.
• Fix the power cords with the clamp.
• Make sure that the power cords may not be removed by pulling them.

LZ-H025GBA4 / LZ-H035GBA5 / LZ-H050GBA5 LZ-H150GBA5 / LZ-H200GBA5


LZ-H080GBA5 / LZ-H100GBA5
GND Power M.D. Power M.D. GND

M.D. M.D.
GND
1(L) 2(N) 3(L) 4(N) 1(L) 2(N) 3(L) 4(N) GND
Cord clamp
Not Not
available available
GN/YL BR BL BR BL GN/YL

CAUTION
The power cord connected to the unit should be selected according to the following specifications .

WARNING
Indoor unit ground wires are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).

Wiring specifications

Wiring specifications Sheathed wire (should be complied with 60245 IEC 53 standard)
Size 0.75 - 1.25 mm2
Length MAX. 100 m
External contact specifications Normally closed contact (Current tolerance 10 mA - 0.5 A)

Precautions when laying power wiring Power wire


Round pressure terminal
Use round pressure terminals for connections to the
power terminal block.

16 Ventilator
Installation

How to connect remote controller(accessory)

ENGLISH
Please connect indoor unit and remote controller using connection cable.

Please check if connector is normally connected.

Indoor
Unit side
Connecting cable

Please use extension cable if the distance between wired remote controller and
indoor unit is more than 10m.

CAUTION
When installing the wired remote controller, do not bury it in the wall.
(It can cause damage in the temperature sensor.)
Do not install the cable to be 50m or above.
(It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote controller
side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.

Installation manual 17
Installation

Group control
When installing more than 2
units of air conditioner to one
wired remote controller, please
connect as the right figure. GND
Signal wire
• If it is not event communication 12V
indoor unit, set the unit as slave.
• Check for event communication
GND Signal wire
through the product manual.
When controlling multiple indoor units with event communication function with one remote con-
troller, you must change the master/slave setting from the indoor unit.
- Indoor units, the master/slave configuration of the product after completion of indoor unit power
‘Off’ and then ‘On’ the power after 1 minutes elapsed sign up.
- For ceiling type cassette and duct product group, change the switch setting of the indoor PCB.

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

#1 switch Off: Master #1 switch On: Slave


(Factory default setting)

- For wall-mount type and stand type product, change the master/slave setting with the wireless
remote controller. (Refer to wireless remote controller manual for detail)
h When installing 2 remote controllers to one indoor unit with event communication function, set
the master/slave of the remote controller. (Refer to remote controller master/slave selection)
When controlling the group, some functions excluding basic operation setting, fan level
min/mid/max, remote controller lock setting and time setting may be limited.

When installing more than 2 wired remote


controllers to one air conditioner, please
connect as the right picture.
GND
Signal wire GND
• When installing more than 2 units of wired Signal wire
12V
remote controller to one air conditioner, set 12V
B Y R B Y R
one wired remote controller as master and
the others all as slaves, as shown in the
right picture.
• You cannot control the group as shown in
Master Slave
the right for some products.
• Refer to the product manual for more detail. <When simultaneously connecting
2 sets of wired remote controller>

• When controlling in groups, set the master/slaver of the remote controller. Refer to
Installer setting section on how to set master/slave for more detail.

18 Ventilator
Installation

Installer setting -How to enter installer setting mode

ENGLISH
CAUTION
Installer setting mode is to set the detail function of the remote controller.
If the installer setting mode is not set correctly, it can cause problems to the product, user injury or
property damage. This must be set by an certificated installer, and any installation or change that is
carried out by a non-certificated person should be responsible for the results. In this case, free service
cannot be provided.

1 Ifit enters
pressing button long for 3 seconds,
into remote controller setter
setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.

2 When you enter the setting mode


initially, Function code is displayed on
the bottom of the LCD screen.

Function code Value

• Some categories of the menu may not be displayed according to the function of the prod-
uct, or the menu name may be different.

Installation manual 19
Installation

Accessory Model: PREMTB100


• In the menu screen, press [<,>(left/right)] button to select the setting category, and press
[∧(up)] button for 3 seconds to enter the password input screen for the installer setting.
• Input the password and press [OK] button to move to the installer setting list.

OK OK

h Installer setting password


Main screen → menu → setting → service → RMC version information → SW Version
Example) SW version : 1.00.1 a
In the above case, the password is 1001.

• Some categories of the menu may not be displayed according to the function of the prod-
uct, or the menu name may be different.
• For more details, refer to the remote controller manual.

Available accessories
Remote controller (PQRCVSL0/PQRCVSL0QW/ PREMTB100)
F7 filter(AHFT035H0/050H0/100H0/100H1)

20 Ventilator
Installation

<Installer setting code table>

ENGLISH
General ventilation product

No. Function Code Value

1 Test run 01 01 : Test run setup

2 Address setting 02 00~FF : Address of central control


<ESP level> <ESP value> <Example>
3 SA(Supply Air) ESP 03
01 : Low 0~255
EA(Exhaust Air) ESP 02 : High
4 04 Function Code ESP step ESP value
03 : Super high
01 : Normal
5 Product direction 05
02 : Opposite
01 : Supply air first
6 Quick refresh priority 06
02 : Exhaust air first
00 : Slave
7 Master setting 07
01 : Master
00 : Auto-off
8 Dry contact 09
01 : Auto-on
9 Release of 3 minute delay 10 01 : Set
01 : Variable
10 Zone state test run 11
02 : Fixed

h Some contents may not be displayed depending on the product function

Installation manual 21
Test running

Test running
Method to operate and select air volume – Interlinked operation with ventilation.
It is used when air conditioner is interlinked with ventilation product.
It is a function that cools and refreshes indoor air using the ventilation product at the same time oper-
ating the air conditioning function.

Ventilation interlinked operation

1 Press button on the remote


controller control panel.
- It is only used when air conditioner
and general ventilation is
interlinked.(‘Interlinked operation’ displayed
on the remote controller display)

2 Pressing 'Start/Stop' button at ventilation


mode will start ventilation.

3 Pressing button will change the


ventilation operation mode.
Pressing operation selection button
will change the mode in the order of
'heat exchange → normal → automatic'
❈ It only displays on the remote controller
display when it is in ventilation mode, and it
displays the desired temperature when it
returns to air condition mode.

4 Pressing button in general


ventilation mode will change airflow
speed.
Pressing airflow speed button will
change the mode in the order of 'weak → strong
→ very strong'.
If CO2 sensor is installed, it can select from 'weak
→ strong → very strong → automatic'.

5 Changing back to air conditioner mode


1)Automatic conversion : when no button is
pressed for 15 seconds or longer, it
automatically converts back to air
conditioner mode.
2) Manual conversion : pressing button in
ventilation mode will manually convert.

22 Ventilator
Test running

ENGLISH
Method to operate and select air volume – Ventilation single operation
It is a function to cool and refresh the indoor air using general ventilation product..

Ventilation single operation

1 Press
controller.
button on the remote

2 Pressing button will change


the ventilation mode.

Ventilation Remote controller Contents


mode display
Heat
exchange Circulate indoor air without loss of heat

Normal Directly circulate indoor air without going


through heat exchanger
Circulate indoor air with automatically
Automatic comparing indoor and outdoor air
In the case of heat exchange mode, the display is
shown as below.
→ → → → → → →

3 Pressing button will change


the strength of the wind
- Pressing the button can select
from 'weak → strong → very
strong'.
- If CO2 sensor is installed, it can select from
'weak → strong → very strong → automatic'.

Installation manual 23
Test running

In case of finding a problem at a test running

Symptom Check item Counter-measure


The product doesn't work Is power not supplied? Supply power
Is the indoor temperature less
It's standby mode for protecting
than 15 ℃ (59 ℉) or more than
total heat exchanger.
40 ℃ (104 ℉)?
The product doesn't work through
Is air filtecr, total heat exchanger Follow cleaning and changing
you press the 'On' switch
clogged severely? method.

Are the PCB and remote con- Connect rightly PCB and remote
troller rightly connected? controller.

Switch on Option No. 5.


"Is the outdoor temperature the
Repower the product and check
limit temperature?
The fan doesn't run whether it works or not.
(Less than -10°C (14°F), more
Switch off Option No. 5. and
than 45°C (113°F))"
repower the product once again.

Even though you push the but-


Is the icon " " displaying on It's child lock mode.
ton of remote controller, any
remote controller? Refer to remote controller.
function doesn't work.

Airborne noise emission


The A-weighted sound pressure emitted by this product is below 70 dB.
** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels. Whilst there is a
correlation between the emission and exposure levels, this cannot be used reliably to determine
whether or not further precautions are required. Factor that influence the actual level of exposure of
the workforce include the characteristics of the work room and the other sources of noise, i.e. the
number of equipment and other adjacent processes and the length of time for which an operator
exposed to the noise. Also, the permissible exposure level can vary from country to country. This
information, however, will enable the user of the equipment to make a better evaluation of the hazard
and risk.

Available accessories
Remote controller (PQRCVSL0/PQRCVSL0QW)
F7 filter (AHFT035H0/AHFT050H0/AHFT100H0)
PI485 gateway

24 Ventilator