Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards
by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
POLSKI
VENTILATOR
Original instruction
[Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared
Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands
LIMBA ROMÂNĂ
www.lg.com
P/NO : MFL67855541 Copyright © 2018 LG Electronics Inc. All Rights Reserved.
Table of contents
TABLE OF CONTENTS
3 SAFETY PRECAUTIONS
7 Preparing for operation
7 Service
7 Standards for Model
8 INTRODUCTION
8 Symbols used in this manual
8 Feature dimension diagram
12 INSTALLATION
12 Installation map
14 Installation of main body
14 Connection of duct
16 Method to connect power cord
17 How to connect remote controller(accessory)
18 Group control
19 Installer setting -How to enter installer setting mode
20 Available accessories
22 TEST RUNNING
22 Method to operate and select air volume – Interlinked operation with ventilation.
23 Method to operate and select air volume – Ventilation single operation
24 In case of finding a problem at a test running
24 Airborne noise emission
24 Available accessories
2 Ventilator
Safety precautions
Safety precautions
ENGLISH
To prevent injury to the user or other people and property damage, the following instructions
must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
WARNING
Installation
Do not use a defective For electrical work, Always ground the
or underrated circuit contact the dealer, product.
breaker. Use this appli- seller, a qualified elec-
ance on a dedicated trician, or an author-
circuit. ized service center.
• There is risk of fire or • Do not disassemble or • There is risk of fire or
electric shock. repair the product. There is electric shock.
risk of fire or electric shock.
Install the panel and Always install a dedi- Use the correctly rated
the cover of control cated circuit and breaker or fuse.
box securely. breaker.
• There is risk of fire or • Improper wiring or instal- • There is risk of fire or
electric shock. lation may cause fire or electric shock.
electric shock
Installation manual 3
Safety precautions
Do not let the product For re-installation of Do not open the main-
run for a long time when the installed product, tenance cover of the
the humidity is very always contact the main body during
high and a door or a dealer or an author- operation.
window is left open. ized service center.
• Moisture may condense • There is risk of fire, elec- • Otherwise, it may cause
and wet or damage furni- tric shock, explosion or electrical shock.
ture. injury.
Use the outdoor air Install the air intake Do not install this product
suction hole with the where polluted air can in a refrigerated ware-
net installed to ensure not be directly sucked house, heated swimming
that birds could not in. pool or other location
come in. where the temperature
and humidity are signifi-
cantly different.
• Remove estrange things • It may cause various • There is risk of electrical
like the bird’s nest. accidents, including suffo- shock, malfunctioning.
Otherwise, it may cause cation, due to the suction
scarcity of indoor oxygen. of harmful gasses(CO,
etc.)
4 Ventilator
Safety precautions
ENGLISH
wooden buildings clad with metal incorporated in the fixed wiring in
laths, wire laths or metal, these accordance with the wiring rules.
ducts must be installed in such a
way that they will not make electri-
cal contact with the metal laths, wire
laths or metal sheets. (Power leak-
age can cause ignition)
Operation
When the product is Don't touch a dedicat- When the product is
soaked (flooded or ed circuit or breaker not be used for a long
submerged), contact with wet hands. time, disconnect the
an authorized service power supply plug or
center. turn off the breaker.
• There is risk of fire or • There is risk of electric • There is risk of product
eletric shock. shock. damage or failure, or
unintended operation.
When flammable gas Be cautious that water Turn the breaker off
leaks, turn off the gas could not enter the when cleaning or
and open a window for product. maintaining the prod-
ventilation before turn uct.
the product on.
• Do not use the telephone • There is risk of fire, elec- • There is risk of electric
or turn switches on or off. tric shock, or product shock.
There is risk of explosion damage.
or fire.
The outside ducts must be tilted at a Glove should be worn when doing
gradient (1/30 or more) down toward the installation work. (There is risk
the outdoor area from the ventilator of injury.)
unit, and properly insulated. (The
entry of rain water may cause power
leaks, fire or damage to household
property.)
Installation manual 5
Safety precautions
CAUTION
Installation
Don't connect the Do not install the prod- Install the product in
ground wire to the uct at a smoky and an insulated space
window frame or water oily place like kitchen from outdoor air.
cock. or factory.
• There is risk of electric • Otherwise. oil may • In case of installing the
shock. adhere to the filter or product outside of the
heating exchanger and insulated layer, dewing
cause trouble. occurs inside of the main
body in winter.And it caus-
es electrical shock or
falling of condensed water.
Keep level even when Use two or more peo- Do not install the prod-
installing the product. ple to lift and transport uct where it will be
the product. exposed to sea wind
(salt spray) directly.
• To avoid vibration or • Avoid personal injury. • It may cause corrosion on
water leakage. the product. Corrosion,
particularly on the con-
denser and evaporator
fins, could cause product
malfunction or inefficient
operation.
Operation
Use a soft cloth to Clean the filter and the Do not use the product
clean. Do not use heat exchanger regu- for special purposes,
harsh detergents, wax larly and use the such as preserving
or thinner, etc. gloves for cleaning. foods, works of art, etc.
It is a consumer venti-
lator, not a precision
refrigeration system.
• Otherwise, color or sur- • Adhering to a mass of • There is risk of damage
face of the oroduct mav dust may cause the dete- or loss of property.
deteriorate. rioration of air volume.
Do not block the inlet or outlet of air Do not step on or put anyting on the
flow. product.
• It may cause product failure. • There is risk of personal injury and fail-
ure of product.
6 Ventilator
Safety precautions
ENGLISH
Preparing for operation
1. Contact an installation specialist for installation.
2. Plug in the power plug properly.
3. Use a dedicated circuit.
4. Do not use an extension cord.
5. Do not start/stop operation by plugging/unplugging the power cord.
6. If the supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
Service
1. For repair and maintenance, contact your authorized service dealer.
2. The appliance shall be disconnected from its power source during service and when re-
placing parts
L Z - H 0 5 0 G B A 5
Development Sequence
Function
A: Basic
Model Type
B: Ceiling Concealed Type
Electrical Standard (Volts, Freq., Phase)
220-240 V, 50 Hz, 1 ph / 220 V, 60 Hz, 1 ph
Capacity
Ex) 080 ơ 800 CMH 100 ơ 1,000 CMH
Heat Exchange Type
H: Total Heat Recovery
Installation manual 7
Introduction
Introduction
Symbols used in this manual
This symbol alerts you to hazards that could cause harm to the
product.
EA RA
(Exhaust Air) (Return Air)
OA SA
(Outdoor Air) (Supply Air )
Blower for supplying air F
Air filter
Unit : mm
Figure Pitch of suspension fixture Nominal Duct connection flange Duct pitch Weight
Model
diameter
A B C D E F G H J K L kg
LZ-H025GBA4 1 014 988 273 939 1 025 135 200 194 252 96 590 198 44
h It necessary to secure sufficient space for maintenance more than the dimensions described in the
product service.
8 Ventilator
Introduction
ENGLISH
Blower for exhausting air Suspension fixture
EA RA
(Exhaust Air) (Return Air)
OA SA
(Outdoor Air) (Supply Air )
Blower for supplying air F
Air filter
Unit : mm
Figure Pitch of suspension fixture Nominal Duct connection flange Duct pitch Weight
Model
diameter
A B C D E F G H J K L kg
LZ-H035GBA5
1 014 988 273 939 1 025 135 200 194 252 96 590 198 44
LZ-H050GBA5
h It necessary to secure sufficient space for maintenance more than the dimensions described in the
product service.
Installation manual 9
Introduction
RA
(Return Air)
EA
(Exhaust Air)
SA
(Supply Air)
Blower for
OA supplying air
(Outdoor Air)
F
Control box
Maintenance cover
Total heat exchanger
Air filter
Unit : mm
Figure Pitch of suspension fixture Nominal Duct connection flange Duct pitch Weight
Model
diameter
A B C D E F G H J K L kg
LZ-H080GBA5
1 101 1 230 405 1 026 1 263 269 250 242 253 98 567 519 62.8
LZ-H100GBA5
h It necessary to secure sufficient space for maintenance more than the dimensions described in the
product service.
10 Ventilator
Introduction
ENGLISH
D
RA
EA
E
SA
OA
M A J
F
G
H
C
K
L
Unit : mm
Pitch of suspension
Figure Duct connection flange Weight
Model fixture
A B C D E F G H J K L M Kg
LZ-H150GBA5
1 352 1 230 818 1 026 1 263 361 242 253 98 340 350 130 130
LZ-H200GBA5
h It necessary to secure sufficient space for maintenance more than the dimensions described in the
product service.
Installation manual 11
Introduction
Installation
Installation map (LZ-H025GBA4 / LZ-H035GBA5 / LZ-H050GBA5 / LZ-H080GBA5 / LZ-H100GBA5)
Plane figure
RA grille
EA
Ventilator
SA grille
OA
Maintenance space
Inspection hatch
Front view
Duct slope: More than 1/30(wall side)
obtaining of right distance
(Preventing penetration of rain water) Duct Ceiling fixing bolt(Supplied by installer)
Ventilator
EA
OA 1m or more 1m or more
SA RA
Inspection hatch
SA grille RA grille
Maintenance cover
Control box
SA grille
EA
Ventilator
main body
OA
More than 600
Maintenance space
600x600
Inspection hatch
12 Ventilator
Installation
ENGLISH
Plane figure
RA grille
EA
Ventilator
OA
Maintenance
space SA grille
Inspection
hatch
Front view
Duct slope: More than 1/30(wall side)
obtaining of right distance
(Preventing penetration of rain water) Ceiling fixing bolt(Supplied by installer)
Inspection SA grille
hatch RA RA SA SA
1m or more 1m or more
RA grille
Maintenance cover
Control box
SA grille
EA
Ventilator
main body
OA
More than 600
Maintenance space
600x600
Inspection hatch
Installation manual 13
Installation
Connection of duct
After securely connect the duct with the duct connection flange, wrap it with a commercial aluminium
tape so that air cannot be leaked.
Adjust the duct from the ceiling so that no force is applied to the main body of the ventilation system.
Always use two ducts at the outdoor with the heat insulating material for prevention of dewing.
Duct
Taping
14 Ventilator
Installation
ENGLISH
Heat insulating material
CAUTION:
Aluminium
• Check that there are no foreign materi-
als (paper, vinyl, etc) or cutoff powders
in the duct before connecting the duct.
• Take care so that shock may not be Main body
applied to the damper plate within the
main body when performing the duct Duct to OA
connection work.
Duct connection flange
• It is recommended to perform adiabat-
ic treatment even to the duct pipe at
the indoor side where ambient temper-
ature is expected higher than room
temperature when the main body of
the ventilation system for cooling in
summer. Rapid bending Excessive bending
CAUTION:
• In -10℃ below ambient temperature, when ventilation is installed the equivalent space in
the outdoor and outdoor, It may cause condensation, you must install drainage facili-
ties(drain pan) and MD(Motorized Damper) at SA/RA duct.
Installation manual 15
Installation
After inserting the power cord into the bushing, fully insert it into the termi-
nal block for connection.
• Fix the power cords with the clamp.
• Make sure that the power cords may not be removed by pulling them.
M.D. M.D.
GND
1(L) 2(N) 3(L) 4(N) 1(L) 2(N) 3(L) 4(N) GND
Cord clamp
Not Not
available available
GN/YL BR BL BR BL GN/YL
CAUTION
The power cord connected to the unit should be selected according to the following specifications .
WARNING
Indoor unit ground wires are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
Wiring specifications
Wiring specifications Sheathed wire (should be complied with 60245 IEC 53 standard)
Size 0.75 - 1.25 mm2
Length MAX. 100 m
External contact specifications Normally closed contact (Current tolerance 10 mA - 0.5 A)
16 Ventilator
Installation
ENGLISH
Please connect indoor unit and remote controller using connection cable.
Indoor
Unit side
Connecting cable
Please use extension cable if the distance between wired remote controller and
indoor unit is more than 10m.
CAUTION
When installing the wired remote controller, do not bury it in the wall.
(It can cause damage in the temperature sensor.)
Do not install the cable to be 50m or above.
(It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote controller
side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
Installation manual 17
Installation
Group control
When installing more than 2
units of air conditioner to one
wired remote controller, please
connect as the right figure. GND
Signal wire
• If it is not event communication 12V
indoor unit, set the unit as slave.
• Check for event communication
GND Signal wire
through the product manual.
When controlling multiple indoor units with event communication function with one remote con-
troller, you must change the master/slave setting from the indoor unit.
- Indoor units, the master/slave configuration of the product after completion of indoor unit power
‘Off’ and then ‘On’ the power after 1 minutes elapsed sign up.
- For ceiling type cassette and duct product group, change the switch setting of the indoor PCB.
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
- For wall-mount type and stand type product, change the master/slave setting with the wireless
remote controller. (Refer to wireless remote controller manual for detail)
h When installing 2 remote controllers to one indoor unit with event communication function, set
the master/slave of the remote controller. (Refer to remote controller master/slave selection)
When controlling the group, some functions excluding basic operation setting, fan level
min/mid/max, remote controller lock setting and time setting may be limited.
• When controlling in groups, set the master/slaver of the remote controller. Refer to
Installer setting section on how to set master/slave for more detail.
18 Ventilator
Installation
ENGLISH
CAUTION
Installer setting mode is to set the detail function of the remote controller.
If the installer setting mode is not set correctly, it can cause problems to the product, user injury or
property damage. This must be set by an certificated installer, and any installation or change that is
carried out by a non-certificated person should be responsible for the results. In this case, free service
cannot be provided.
1 Ifit enters
pressing button long for 3 seconds,
into remote controller setter
setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
• Some categories of the menu may not be displayed according to the function of the prod-
uct, or the menu name may be different.
Installation manual 19
Installation
OK OK
• Some categories of the menu may not be displayed according to the function of the prod-
uct, or the menu name may be different.
• For more details, refer to the remote controller manual.
Available accessories
Remote controller (PQRCVSL0/PQRCVSL0QW/ PREMTB100)
F7 filter(AHFT035H0/050H0/100H0/100H1)
20 Ventilator
Installation
ENGLISH
General ventilation product
Installation manual 21
Test running
Test running
Method to operate and select air volume – Interlinked operation with ventilation.
It is used when air conditioner is interlinked with ventilation product.
It is a function that cools and refreshes indoor air using the ventilation product at the same time oper-
ating the air conditioning function.
22 Ventilator
Test running
ENGLISH
Method to operate and select air volume – Ventilation single operation
It is a function to cool and refresh the indoor air using general ventilation product..
1 Press
controller.
button on the remote
Installation manual 23
Test running
Are the PCB and remote con- Connect rightly PCB and remote
troller rightly connected? controller.
Available accessories
Remote controller (PQRCVSL0/PQRCVSL0QW)
F7 filter (AHFT035H0/AHFT050H0/AHFT100H0)
PI485 gateway
24 Ventilator