A 1 2 B A-A 3: Rev - Sheet Doc. Sign. Date Originated by Checked by L. Weight Scale

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

RKS.КТК3.

000
- Crossbonding link box KTK-3.
A-A - Single core bonding cable mandatory parameters:
A 3 - copper stranded conductor with the cross-section from
2 B 789
95 to 400 mm²;
- insulation withstand voltage of 10 kV DC;
1
- BIL in accordance with IEC 60840 and IEC 62067.

299
299

- Cable lugs (hexagonal compressing) for copper


conductors from 95 to 400 mm² are in scope of supply.

35,5
164
164

128
- Conductor cross-section of bonding cable and earthing
cables and the outer diameter must be specified in

max
100 100
7 6 5 4 6 7 purchase order.
- Protection class: IP68.
A 0
- Ambient temperature during operation from -60 C to
First use

499,5
B (1 : 1) C (1 : 1) 0
+50 C.
56 points 4 points

R9
Directory №

23
rubber seal

7 18
701

Ref.
Grounding
Sign. and date

Name Description Quantity


Electrical diagram №
1 Housing Stainless steel 1
2 Cover Stainless steel 1
7 3 Busbar Tinned copper 3
Copy inv. №

4 Busbar Tinned copper 3


5 SVL Uc=6 kV * 3
6 Insulator Ur=10 kV 6
Repl. inv. №

C 7 Cable lugs Tinned copper 7

320 *other on request


RKS.КТК3.000
Sign. and date

L. Weight Scale
Rev. Sheet Doc. №
Originated by Danilov
Sign. Date
Crossbonding link box 60,0 1:5
Checked by Burushin КТК-3
Sheet Sheets 1
Orig. inv. №

Examined by LLC "RKS-Plast"


Approved by Grigoriev
Copy by Size A2