Inverter / Charger With Solar Charge Controller: Steca Solarix PLI
Inverter / Charger With Solar Charge Controller: Steca Solarix PLI
Inverter / Charger With Solar Charge Controller: Steca Solarix PLI
Purpose ...................................................................................................................................................... 1
Scope ......................................................................................................................................................... 1
Keywords and symbols............................................................................................................................... 1
Introduction........................................................................................................................................... 3
Features ..................................................................................................................................................... 3
Basic System Architecture .......................................................................................................................... 3
Product Overview ....................................................................................................................................... 4
Installation ............................................................................................................................................. 5
Operation ............................................................................................................................................ 13
Specifications....................................................................................................................................... 33
Troubleshooting................................................................................................................................... 36
Contact ................................................................................................................................................ 38
Scope
This manual provides safety and installation guidelines as well as information on wiring and operation.
Keyword Description
DANGER Immediate danger of death or serious bodily injury
WARNING Possible danger of death or serious bodily injury
CAUTION Possible danger of light or medium bodily injury or damage to equipment
This symbol indicates a warning or danger, pay particular attention to these sections.
WARNING: This chapter contains important safety and operating instructions. Read
and keep this manual for future reference.
2. CAUTION Only qualified service professionals may perform the installation work described in this
manual.
3. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and
all appropriate sections of this manual.
4. CAUTION To reduce risk of injury, charge only rechargeable deep-cycle lead-acid batteries with
liquid electrolyte, AGM or gel. Other types of batteries may burst, causing personal injury and
damage, if they are not approved by Steca Elektronik. Use only batteries with 48 Vdc nominal
voltage.
5. Do not disassemble the unit, doing so may cause damage to the unit, personal injury and leads to a
total loss of warranty. Contact your dealer when service or repair is required. Incorrect re-assembly
may result in a risk of electric shock or fire.
6. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or
cleaning. Turning off the unit will not reduce this risk.
8. CAUTION For optimum operation of this unit, please follow the required specification to select
appropriate cable sizes. Failure to do so may cause damage.
9. Be very cautious when working with metal tools on or around batteries. A potential risk exists in
short-circuiting batteries or other electrical parts, potentially causing an explosion or fire. Use only
insulated tools.
Steca Solarix PLI 5000-48 Instructions, Page 1
10. Please strictly follow installation procedure when connecting or disconnecting AC or DC terminals.
Please refer to the ”Installation” section of this manual for the details.
11. WARNING Ensure that all cables, particularly the AC input, AC output, photovoltaic (PV) and
battery cables are seated properly in their contacts and tightened correctly. No cable insulation may
protrude into the corresponding cable terminals. Any materials other than the cable / cable lug /
ring terminal inserted into the terminals could cause excessive heating, damage and / or fire.
12. Make sure to use a battery fuse as close as possible to the battery terminal with a rating of 250 to
300 A DC as over-current protection for the battery and battery cables. The fuse must be able to
reliably protect the battery cables from short-circuit or overload.
13. WARNING This inverter is required to be connected to a permanent grounded wiring system via the
appropriate terminals. Failure to do so may cause serious personal injury. Be sure to comply with
local requirements and regulations when installing this inverter.
14. Never allow the AC output and DC input to be short-circuited. Do NOT connect to the AC mains
when the DC input short circuits.
15. If one of the following components is damaged immediately take the device out of operation and
disconnect it from the AC mains, battery and PV modules: the device itself (not functioning, visible
damage, smoke, penetration of liquid etc.), connected cables or solar modules.
Do not switch the system on again before the device has been repaired by a dealer or the
manufacturer, damaged cables or solar modules have been repaired by a technical specialist.
16. Any use of this product aside from its intended purpose as described in this manual could lead to
damage and/or serious personal injury. Opening any part of the device apart from the bottom cover
as described in this manual will void the warranty and can lead to damage and/or serious personal
injury.
18. CAUTION Heavy device. Take care when lifting the device to avoid injury.
Features
Pure sine wave inverter
Built-in MPPT solar charge controller
Configurable AC input voltage range limit for home appliances or personal computers
Configurable battery charging current based on applications via LCD setting
Configurable AC / solar charger priority via LCD / button setting
Compatible with AC voltage from the grid or generator power
Uninterruptible power supply in case of grid black-out
Bipolar disconnection from the AC input in inverter mode, grid injection is not technically possible
Overload, over-temperature and short-circuit protection
Smart multi-stage battery charger with optional equalisation for optimised battery performance
Cold start function (starting with only battery power and no AC source or PV modules attached)
Consult with your system integrator for other possible system architectures depending on your
requirements.
1. LCD display
2. Status indicator for line / inverter mode
3. Charging indicator
4. Fault indicator
5. Function buttons (ESC, UP, DOWN, ENTER)
6. Circuit breaker
7. AC input
8. AC output
9. RS-232 communication port
10. USB communication port
11. Signal contact
12. PV input
13. Battery connection (positive)
14. Battery connection (negative)
15. Power on/off switch
Preparation
Before connecting all wirings, please take off bottom cover by removing the two screws shown in Fig. 3.
Fix the unit to the wall by using three M5 screws (not included) in the screw holes pictured below in Figure
5. Be sure to take precautions such as wall plugs, ensuring that the inverter’s weight can be safely held by
the wall and screws.
Battery Connection
WARNING: All wiring must be performed by qualified personnel according to local
regulations.
It is very important for system safety and efficient operation to use appropriate cable
cross-sections for the battery connection. The recommended cross-section for the
battery connection is 50 mm² (at 3 metres cable length). Keep the cables between the
inverter and battery as short as possible, preferably ≤ 3 metres. Failure to tighten
connections adequately could lead to overheating or fire.
1. Ensure the ON/OFF power button is set to OFF (see chapter “Power ON/OFF”).
2. Open the circuit breaker or remove the fuse near the battery terminal.
3. Remove 10 mm of insulation on the inverter side of the battery cable from both the positive and
negative lines.
4. Assemble the included battery ring terminal by crimping it to the battery cables on the inverter side,
make sure that none if the insulation interferes with the ring terminal!
5. Connect all battery cells or packs as required to reach 48 Vdc nominal voltage. It is highly
recommended to use at least a 200 Ah capacity battery.
6. Connect the battery-side of the cable to the battery appropriately, ensuring a tight and reliable fit.
7. Remove the M6 nut on the positive and negative battery terminals of the inverter.
8. Insert the ring terminal of the battery cable flatly into the battery connector screws of the inverter,
then tighten the M6 nuts with a torque of 2 - 3 Nm (see Figure 6). Make sure the polarity at both
the battery and the inverter is correct and the ring terminals are tightly screwed to the battery
terminals, ensuring a good electrical connection.
9. Do not insert the battery fuse or turn on the battery circuit breaker yet!
Battery –
Battery +
WARNING: Shock Hazard. Installation must be performed with care due to high
battery voltage in series.
CAUTION: Before connecting to the AC input power source, install a separate AC breaker
between the inverter and AC input power source and turn it off. This will ensure the inverter
can be securely disconnected during maintenance and is protected from over-current from
the AC input. The recommended AC breaker rating is 40 A, follow your local regulations.
There are two terminal blocks, one marked “AC INPUT” and the other “AC OUTPUT”. Do NOT
mix the input and output connectors!
Connect a single inverter to only one phase (L and N).
Follow the steps below to connect the AC input (optional) and AC output to the inverter:
1. Before making AC input/output connection, ensure the battery DC circuit breaker is open and/or
the battery fuse is removed, thus disconnecting the battery.
3. Remove 10 mm of insulation on the inverter side of the PE (protective earth) conductors for both
AC input and AC output. Remove 7 mm of insulation on the inverter side of the L (phase) and N
(neutral) conductors for both AC input and AC output.
4. Connect the PE ( - protective earth) cable of the AC input (Figure 7) to the corresponding
terminal on the inverter and connect the PE ( - protective earth) conductor of the AC output
(Figure 8) to the corresponding terminal on the inverter. Tighten the terminal clamps with a torque
of 1.4 - 1.6 Nm.
5. Connect the L (phase) and N (neutral) conductors to the respective AC input (Figure 7) and AC
output (Figure 8) terminals. Tighten the terminal clamps with a torque of 1.4 - 1.6 Nm.
6. Make sure all connections are secure and tightened correctly, ensuring a good electrical
connection.
CAUTION: Some appliances such as air conditioners require at least 2 - 3 minutes to restart
after a loss of power to have enough time for the refrigerant gas to settle. If a power
shortage occurs and power is re-supplied in a short time, this may cause damage to such
appliances. To prevent this kind of damage, please check the appliance manufacturer
guidelines, the appliance may be equipped with a time-delay function during installation. If
this is disregarded, this inverter may trigger an overload fault and cut off output to protect
your appliances, potentially nonetheless causing internal damage to the appliance.
PV Connection
WARNING: All wiring must be performed by qualified personnel according to local
regulations.
It is very important for system safety and efficient operation to use appropriate cable
cross-sections for the PV connection. The minimum recommended cross-section for
the PV connection is 12 mm². Failure to tighten connections adequately could lead to
overheating or fire.
PV Module Selection
When selecting proper PV modules, please be sure to consider the following parameters:
1. The open-circuit voltage (Voc) of the PV array at the lowest temperatures present throughout the
year in the installation location does not exceed the maximum PV open-circuit voltage of the PV
input of the inverter.
2. The MPP voltage (Vmpp) of the PV array must be higher than the minimum PV MPP voltage of the
PV input of the inverter.
3. The total power in watt-peak (Wp) of the PV array should not exceed 1.2x the nominal charge
power of the inverter.
Follow the steps below to connect the PV input (optional) to the inverter:
1. Ensure the circuit breaker between the PV modules and the inverter side of the PV cables is open so
that there is no voltage on the PV cables before the connection.
2. Remove 10 mm of insulation on the inverter side of the battery cable from both the positive and
negative PV cables.
3. Check the correct polarity of the connection cable from the PV modules and PV input connectors
on the inverter.
4. Connect the positive and negative cables from the PV array to the respective PV terminals on the
inverter (Figure 9). Tighten the terminal clamps with a torque of 1.4 - 1.6 Nm
5. Make sure the connections are secure and tightened correctly, ensuring a good electrical
connection.
PV +
Final Assembly
After connecting all wirings, please slide the bottom cover back onto the bottom of the inverter and fasten
the two screws as shown below (Figure 10).
Now the fuse/circuit breaker of the battery can be inserted/closed to electrically connect the inverter to the
battery. Next the AC input circuit breaker can be closed, then the AC output breaker and finally the
fuse/circuit breaker of the PV connection.
1. When program 38 is set to “disable” (see chapter “Configuration”), it can be used to deliver a
signal to an external device (such as an AC generator) when battery voltage reaches its warning
level.
2. When program 38 is set as “enable” and the unit is working in battery / inverter mode, it can be
used to trigger an external grounding box (not included). This grounding box can then connect
neutral (N) and protective earth (PE) grounding of the AC output together.
Function 2 is useful for grid-tied installations where the AC input has a TN-C-S or TN-S grounding scheme,
so where PE and N are separate and typically a residual current device (RCD) is used for safety from electric
shock. In order for an RCD on the AC output to function, there must be a bridge between N and PE before it.
This is the case in a TN-C-S or TN-S grounding scheme. However, when the inverter is working in off-grid /
inverter mode, so when both the AC input N and L are disconnected by the internal by-pass / transfer relay,
the bridge between N and PE is no longer active. With program 38 enabled an external grounding box
controlled by the dry contact can bridge N and PE only in off-grid / inverter mode and release the bridge in
line / grid mode.
Grounding is safety-relevant and should only be done by qualified personnel. Make sure local regulations
are adhered to.
Inverter
Condition Dry contact port:
unit status
NC & C NO & C
Power Off Unit is off and no output is powered. Closed Open
Output is powered from AC input. Closed Open
Output is Program Battery voltage < Low DC
Open Closed
powered 01 set to warning voltage
from “Utility” Battery voltage > value set in
Battery or Program 13 or battery charging Closed Open
Power On Solar. reaches floating stage
Program Battery voltage < value set in
Open Closed
01 is set Program 12
to “SBU” Battery voltage > value set in
or “Solar Program 13 or battery charging Closed Open
first” reaches floating stage
Inverter
Condition Dry contact port:
unit status
NC & C NO & C
Power Off Unit is off and no output is powered. Closed Open
Unit is in stand-by mode, line mode or fault mode Closed Open
Power On
Unit is in battery mode or power-saving mode Open Closed
Operation
Power ON/OFF
Once the unit has been correctly installed and the batteries are well connected, simply press the ON/OFF
switch in Figure 11 to the ON position (located on the button of the case) to turn on the inverter.
LC-display
LED indicators
Function buttons
Function Buttons
Button Description
ESC Exit setting mode
UP Go to previous selection
DOWN Go to next selection
ENTER Confirm the selection in setting mode or enter setting mode
LC-Display Icons
Indicate output voltage, output frequency, load percent, load in VA, load in
Watt and discharging current.
Battery Information
> 1.983
> 2.033
Mute Operation
Configuration
After pressing and holding the “ENTER” button for 3 seconds, the unit will enter its configuration / setting
mode. Press the “UP” or “DOWN” button to select different setting programs. Then press the “ENTER”
button to confirm the selection or “ESC” to exit.
30 A 40 A
Maximum charging
50 A 60 A
current: configure the total
charging current for solar
and AC chargers
70 A 80 A (default)
02 combined.
110 A 120 A
130 A 140 A
50 Hz (default) 60 Hz
09 AC Output frequency
Available options:
2A 10 A
20 A 30 A (default)
Maximum AC input
11
charging current
40 A 50 A
60 A
46 V (default) 47 V
48 V 49 V
50 V 51 V
Battery voltage below
which the inverter switches
the power source to AC in /
12
utility when selecting “SBU
52 V 53 V
priority” or “Solar first” in
program 01.
54 V 55 V
56 V 57 V
49 V 50 V
51 V 52 V
53 V 54 V (default)
59 V 60 V
61 V 62 V
63 V 64 V
Float voltage
27
(see Figure 12)
If “User-Defined” is selected in program 05, this program
can be configured. The range of settings is from 48.0 V to
64.0 V in 0.1 V increments for each click.
Default setting: 42.0 V
Input frequency = 50 Hz
AC Input frequency
PV voltage = 60 V
PV voltage
PV charging current = 50 A
Charging current
Output frequency
Load in VA
When the load power ≥ 1 kVA, it is shown as kVA:
Load in Watt
When the load power ≥ 1 kW, it is shown as kW:
Note:
Stand-by mode: The Charging by AC input.
inverter is not powered
on yet but at this time,
the inverter can charge No AC output is supplied
the battery without AC by the unit but it can
output. charge batteries. Charging by PV energy.
Power saving mode: If
enabled, the AC output of
the inverter will be turned
off when the connected
load is below ~ 50 W and No charging.
turn back on when the
load is above ~ 100 W.
Note:
Errors are caused by
PV energy can charge
internal circuit errors or
batteries.
external causes such as No charging.
over-temperature, a
short-circuited output
etc.
Charging by PV energy.
The unit will provide
power from the AC input
directly to the AC output.
The inverter unit is
galvanically isolated from
Line mode
both the grid neutral and Charging from AC input.
phase wires by integrated
switching relays. It can
also charge the battery in
line mode.
02 Over temperature
51 Over-current or surge
56 Battery disconnected
Battery Equalisation
The charge controller is equipped with an equalisation function. It reverses the buildup of negative
chemical effects like stratification, a condition where acid concentration is greater at the bottom of the
battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the
plates. If left unchecked, this condition, called sulfation, will gradually reduce the overall capacity of the
battery. Therefore, it is recommended to equalise battery periodically if it is a flooded / liquid-electrolyte
type lead-acid battery. Refer to your battery manual or manufacturer for compatibility.
1. “Equalisation voltage” in program 34, chapter “Configuration”. This defines the desired battery
voltage during the equalisation phase.
2. “Equalisation duration” in program 35, chapter “Configuration”. This defines the duration of the
equalisation program in minutes.
3. “Equalisation timeout” in program 36, chapter “Configuration”. This defines the maximum
duration of the equalisation program in minutes. The duration may be prolonged due do voltage
fluctuations at the battery or insufficient power from the charger. This timeout ensures that the
equalisation process is stopped, at the latest after the timeout has elapsed.
However, during the equalisation phase, once the equalisation duration has elapsed and if the battery
voltage has not reached the equalisation voltage, the charge controller will extend the battery equalisation
phase time until the battery voltage reaches the equalisation voltage. If battery voltage is still lower than
the equalisation voltage once the equalisation timeout has elapsed, the charge controller will exit the
equalisation phase and return to float phase (see Figure 13).
Specifications
Line Mode Specifications
Inverter model: Solarix PLI 5000-48
* As soon as a valid voltage and frequency is detected at the AC input, the inverter will synchronise its AC
output to the input in battery mode. This is to avoid frequency or voltage mismatch between the AC input
and AC output and to enable the fast switching times typical of uninterruptible power supplies (UPS).
Cold Start Voltage 46.0 Vdc (minimum battery voltage for power up for inverter)
Low Battery Warning Voltage
@ load < 20% 44.0 Vdc
@ 20% ≤ load < 50% 42.8 Vdc
@ load ≥ 50% 40.4 Vdc
Low Bat. Warning Return Voltage
@ load < 20% 46.0 Vdc
@ 20% ≤ load < 50% 44.8 Vdc
@ load ≥ 50% 42.4 Vdc
Low Battery Cut-off Voltage Only valid for “AGM / Gel” or “Flooded” battery types in Program 05
@ load < 20% 42.0 Vdc
@ 20% ≤ load < 50% 40.8 Vdc
@ load ≥ 50% 38.4 Vdc
High Battery Cut-off Voltage 66 Vdc
Charging Curve:
T1 = 10 x T0
10 minutes ≤ T1 ≤ 8 hours
Troubleshooting
Problem LCD / LED / Buzzer Explanation / Possible cause What to do
Unit shuts down LCD/LEDs and buzzer
automatically will be active for 3 The battery voltage is too low 1. Re-charge battery.
during start-up seconds and then (< 1.91 V / Cell) 2. Replace battery.
process. complete shut-off.
1. Check if batteries and the
1. The battery voltage is far too wiring are correctly
No response after
No indication. low. (< 1.4 V / Cell) connected.
power on.
2. Battery polarity reversed. 2. Re-charge battery.
3. Replace battery.
Input voltage is
Check if AC breaker is
displayed as 0 on the
Input protector is tripped. tripped and AC wiring is
LCD and green LED is
correctly connected.
flashing.
AC input is active 1. Check if AC wires are too
but the unit only thin and/or too long.
works in battery Green LED is Insufficient quality of AC power 2. Check whether generator
mode. flashing. (mains power or generator). (if applied) is working well or
if input voltage range setting
is correct. (UPSAppliances)
Green LED is “Solar First” is set as the priority Change the output source
flashing. of the output source. priority to “Utility first”.
When the unit is
turned on, the
LCD display and LEDs Check if battery fuse & wires
internal relay is Battery is disconnected.
are flashing. are correctly connected.
switched on and
off repeatedly.
Exclusion of Liability
The manufacturer can neither monitor the compliance with this manual nor the conditions and methods
during the installation, operation, usage and maintenance of the controller. Improper installation of the
system may result in damage to property and, as a result, to bodily injury.
Therefore, the manufacturer assumes no responsibility and liability for loss, damage or costs which result
from or are in any way related to incorrect installation, improper operation, incorrect execution of
installation work and incorrect usage and maintenance.
Similarly, we assume no responsibility for patent right or other right infringements of third parties caused
by usage of this controller. The manufacturer reserves the right to make changes to the product, technical
data or installation and operating instructions without prior notice.
Contact
In the case of complaints or faults, please contact the local dealer from whom you purchased the product.
They will help you with any issues you may have.
E-mail service@stecasolar.com
Internet www.steca.com