1. SCOPE
This SEC Distribution Materials Specification (SDMS) specifies the minimum technical
requirements for design, engineering, manufacture, testing, inspection and performance of all
kind of cable accessories for low and medium voltage, intended to be used in the distribution
system of Saudi Electricity Company (SEC).
1.1. REQUIREMENTS ON THE ACCEPTABILITY OF THE PRODUCTS
The prerequisite for product approval is the positive assessment and approval of the products in
the pre-qualification process by SEC. Compliance with the requirements of this SEC standard is
the basis for the manufacturer and product approval by SEC.
The approval of products or/and manufacturers requires inter alia the carrying out of
investigations as well as the submission of documents, samples and certificates. The documents,
test results, samples and certificates required for the assessment are to be made available to SEC
free of charge.
After specifying the kits, SEC reserves the right to make claims, amendments and additions
exceeding the provisions of this SEC standard. If the kits or any parts thereof are produced by
third parties on behalf of the manufacturer, these must be named with the manufacturer's
specification. SEC reserves the right to carry out audits at the manufacturer's production site at
all times in order to verify compliance with the requirements described in this SEC standard. For
this purpose, it is also possible to take kits out of the running production line. The SEC standard
can be modified or supplemented at any time. The approval of SEC is revocable at any time.
1.2. APPROVED SAMPLE FOR MASS PRODUCTION
At the request of SEC, for example before signing a new contract or in the case of coordinated
product changes, the supplier is obligated to make available one free retained sample, according
to the agreed design.
1.3. REQUIREMENTS FOR PRODUCT CHANGES
After placing the contract, product modifications by the manufacturer are only permitted with the
approval of SEC. Product changes of any kind must be coordinated in advance with SEC
Standardization department. If SEC identifies non-agreed changes, this leads to the blocking of
the manufacturer and the resulting costs are to be assumed by the manufacturer.
If the production location is relocated, or if the company has previously produced at its own
premises, SEC must be informed. Deviations from the SEC standard require the explicit written
approval of SEC. In the case of complaints or product defects, the technical product management
must be informed immediately in writing.
4
12-SDMS-01 REV.04
5
12-SDMS-01 REV.04
Table 2: List of applicable standards for medium voltage
Standard # Title
IEC 60060-1&2 High-voltage test techniques
IEC 60230 Impulse tests on cables and their accessories
Power cables with extruded insulation and their accessories for rated
voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 2:
IEC 60502-2
Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um =
36 kV)
Power cables with extruded insulation and their accessories for rated
voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 4:
IEC 60502-4
Test requirements on accessories for cables with rated voltages from 6
kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)
Test methods for accessories for power cables with rated voltage from 6
IEC 61442
kV (Um = 7.2 kV) up to 30 kV (Um 36 kV)
Compression and mechanical connectors for power cables for rated
IEC 61238-1 voltages up to 30 kV (Um = 36 kV) - Part 1: Test methods and
requirements, (Class A)
Test requirements on accessories for use on power cables of rated voltage
HD 629.1 S2 + A1 from 3,6/6(7,2) kV up to 20,8/36(42) kV - Part 1: Cables with extruded
insulation
Artificial pollution tests on high-voltage insulators to be used on a.c.
IEC 60507
systems
Selection and dimensioning of high-voltage insulators intended for use in
IEC 60815-3
polluted conditions
Bushings above 1 kV up to 52 kV and from 250 A to 3,15 kA for liquid
EN 50180
filled transformers
Plug-in type bushings above 1 kV up to 52 kV and from 250 A to 2,50
EN 50181
kA for equipment other than liquid filled transformers
4. TESTING AND INSPECTION
4.1. GENERAL
All cable accessories shall be tested in accordance with the respective latest applicable standards
mentioned in Chapter 3 – Applicable codes and standards.
6
12-SDMS-01 REV.04
4.2. TYPE TESTS
The vendor shall provide certified test reports from independent / approved laboratory along with
the bid for the materials offered to show that product has been qualified according to the
applicable test sequence as mentioned in the respective standards.
A new type test has to be done in full conformance with the requirements of the latest version of
IEC standard if changes in the materials, the structure or the production process take place, which
could have an effect on the operating characteristics. SEC has to be informed about planned or
implemented changes (e.g. use of new materials, use of new manufacturing processes,
commissioning of new production plants or production sites) in order to coordinate the further
procedure in a particular case.
SEC reserves the right to review and / or verify the compliance with the standards, guidelines and
regulations as well as this Technical Specification, including the required type test.
4.3. TYPE TESTS DOCUMENTS
The test documents have to be in electronic format (readable with freely available PC software
such as Acrobat Reader), so that they can be provided by the manufacturer. The manufacturer
shall provide the test documents in hard-copy if requested.
5. MARKING
All components of the kits shall be clearly marked with the manufacturer's name and reference
numbers. The marking shall be done before coating the adhesive onto the component.
Electrically conducting components shall be marked 'conducting' clearly and permanently unless
they are very small to accommodate respective marking.
All components shall be capable of being stored without deterioration within the temperature
range of -10 ºC to +55 ºC. Components or materials, if subjected to a shelf life limitation, shall
have the final date of use prominently and permanently shown on all packages.
The electrical relevant components of cable accessories must be marked with the following data:
Company name or logo
Production indicator for traceability
In the case of joints, cross-section, diameter, or application range should be marked as
well
Packaging for each cable accessory has to be printed with the following information:
Manufacturer's name
Manufacturer’s Type No. / catalog number
Purchase order number/tender
7
12-SDMS-01 REV.04
Cable size/diameter
Nominal Voltage
Year of manufacture
Date of expiry
SEC item number
Possibly changed materials (look at chapter: Product change)
On the outer packaging which contains the cable accessories, following information should be
printed:
Gross weight in kilograms (pounds)
Position of slinging points and other relevant handling instructions
It has to be possible to read all information directly.
8
12-SDMS-01 REV.04
6.2. DELIVERY, PACKING, AND SHIPPING
The joint/termination kits and accessories shall be delivered ready for service. All components in
the kit should be individually packed and labeled in the main packaging. Each group of same
material can be packed in one bag. Mastics and sealant tapes are to be packed in polybags. Stress
control mastics should be packed in aluminum foil to prevent moisture absorption.
Each kit along with appropriate installation instructions in English and Arabic languages shall be
packed separately in card board box. The kit should also contain a complete kit content list and a
manufacturer certificate guaranteeing the completeness of the kit content agreed with SEC.
Maximum 10 boxes shall be packed in properly palletized non-returnable wooden boxes or as per
specified requirements.
Packing shall be designed to protect against ingress of dust, moisture, and mechanical damage.
The kits shall not be packed in perishable material.
All components shall be capable of being stored without deterioration within the temperature
range of 0°C to + 55°C. Components or materials, if subject to a shelf life limitation, shall have
the final date of use prominently and permanently shown on all packages.
9
12-SDMS-01 REV.04
10
12-SDMS-01 REV.04
8.3. MEDIUM VOLTAGE CABLE ACCESSORIES REQUIREMENTS UP
TO 36 KV
The existing or used cables comply with IEC 60502-2 and the conductor cross-sections will be
from 50 mm² to 500 mm².
Technology of the cable accessories are either pre-molded or cold-shrink.
Creepage distance for outdoor termination shall be also according to the latest revision of SEC
General Specification 01-SDMS-01 applicable for coastal areas.
The stress control grader or grading joint is to be designed in an easy-to-assemble design. The
stress grading via connectors can be integrated in the joint body.
As requested in the inquiry, the outer sealing can be made by either one of the following:
a.) two-single sleeves (parking position on one side mounting position)
b.) wrap around sheath so that the assembly is possible even in tight conditions
c.) injected cast-resin
The wrap around sheath repair sleeve for medium voltage shall be of the heat shrink type and
shall be coated with an adhesive which becomes activated on the application of heat and will
form a bond with cable jacket when shrunk.
Metal shields, such as copper tape or copper wire, should be connected by a solderless
connection system such as roll springs or mechanical connectors in combination with copper
mesh.
An inner jacket installed over the joint-body prior to reinstatement of the mechanical protection
of armored cables shall be provided in the joint kits.
For tape armored cables, all items required for connection (such as worm drive clamps) are to be
provided in the kit content. Moreover, inner sleeve shall be provided between the metallic screen
and the galvanized steel wraparound cover.
Reinstatement of mechanical protection for armored cables shall be in the form of galvanized
steel wire or sheet wraparound cover, not steel tubing. Ends of steel armor forming wraparound
shall not be sharp. The armor shall be protected by outer heat shrinkable sealing sleeves.
For identification of medium voltage joint and termination kits, identification marker shall be
supplied with blank, white-colored, adhesive-baked, wrap-around polyolefin, capable of
operating temperature minus 55°C to plus 135°C and recovery temperature of plus 100 °C.
Details are given in Figure 1.
11
12-SDMS-01 REV.04
8.4. GENERAL REQUIREMENTS FOR SPECIFIC ACCESSORIES
8.4.1. CABLE JOINTS
For heat shrink joints (LV cables only):
For the central joint body, the minimum insulation thickness of the primary cable
insulation has to be replaced across the connector.
The adhesive shall have a softening temperature not less than 90 ºC.
For pre-molded and cold shrink joints:
Joints should be manufactured from EPDM rubber or high performance silicone.
Connectors shall be of water-blocking type.
13
12-SDMS-01 REV.04
8.4.8. REPAIR SLEEVES
Wrap around sheath/repair sleeve for MV cables shall be heat shrink type and shall be coated
with adhesive that becomes activated on the application of heat and when shrunk will form a
bond with cable jacket.
Repair sleeves for LV cables shall be supplied in length of 1.5 meters complete with channels
and clips in proper packing.
The diameter of sleeve (as supplied and retainable/recovered after shrinkage) shall be marked on
the sleeve.
8.4.9. TRANSITION JOINTS
Transition joints shall be suitable for different types of cables specified in the tender/inquiry.
Connectors used for transition joints shall be of tinned copper or tinned aluminum alloy
compatible to both copper and aluminum conductors. The minimum thickness of tin coating is
20µm.
14
12-SDMS-01 REV.04
9. GUARANTEE
The supplier shall guarantee the kits against all defects arising out of faulty design or
manufacturing defects or defective material for a period of five years from the date of delivery or
one year from installation date, whichever comes first.
15
12-SDMS-01 REV.04
Joints and Terminations
Manufacturer of
Description Vendor/Supplier
Material/Equipment
Name of Company
16
12-SDMS-01 REV.04
11. APPENDIX
Figure 1: Identification marker
17