Balanced Faults Part 1
Balanced Faults Part 1
Balanced Faults Part 1
POWER SYSTEMS
LO3
Introduction
Most of the faults on the power system lead to a short-circuit condition.
When such a condition occurs, a heavy current (called short circuit current) flows through the
equipment, causing considerable damage to the equipment and interruption of service to the
consumers.
Therefore, There is probably no other subject of greater importance to an electrical engineer
than the question of determination of short circuit currents under fault conditions.
The choice of apparatus and the design and arrangement of practically every equipment in the
power system depends upon short-circuit current considerations.
Objectives
Define fault level.
Reduce a power circuit with a symmetrical fault to a single
impedance and source.
Derive the fault current and fault level MVA.
Solve problems with symmetrical fault
Fault Analysis
An essential part of the design of a power supply network is the calculation of the
currents which flow in the components when a symmetrical fault occurs.
High currents may cause considerable damage to equipment if they are not immediately
isolated.
High currents may also result in system instability if they are not cleared fast. The system
becomes unbalanced.
Fault calculations provide the values of currents and voltages on a power system during fault
conditions. Why I need this info???
This information is required to design an adequate protection relaying system and to
determine interruption capacity for circuit breakers at each switching location.
Fault Analysis
In an electric power system, a fault or fault current is any abnormal electric current.
For example, a short circuit is a fault in which current bypasses the normal load.
An open-circuit fault occurs if a circuit is interrupted by some failure.
In three-phase systems, a fault may involve one or more phases and ground, or may
occur only between phases.
In a "ground fault“ or "earth fault", current flows into the earth.
The prospective short circuit current of a predictable fault can be calculated for most
situations.
In power systems, protective devices can detect fault conditions and operate circuit
breakers and other devices to limit the loss of service due to a failure.
Types of Faults
In a polyphase system, a fault may affect all phases equally which is a "symmetrical
fault".
If only some phases are affected, the resulting "asymmetrical fault" becomes more
complicated to analyse.
The analysis of these types of faults is often simplified by using methods such as
symmetrical components.
The design of systems to detect and interrupt power system faults is the main objective
of power-system protection.
There are generally two types of faults in power systems:
1- Symmetrical Faults: A symmetric or balanced fault affects each of the three phases
equally, In transmission line faults, roughly 5% are symmetric.
Types of Faults
2- Asymmetrical Faults: An asymmetric or unbalanced fault does not affect each of the
three phases equally.
Common types of asymmetric faults such as
Line-to-Line: Is a short circuit between lines, caused by ionization of air, or when lines
come into physical contact, for example due to a broken insulator.
Line-to-Ground: Is a short circuit between one line and ground, very often caused by
physical contact, for example due to lightning or other storm damage.
Double Line-to-Ground: occurs when two lines come into contact with the ground (and
each other), also commonly due to storm damage.
Assumptions made in fault calculations
The fault per unit impedance ZF PU represents the equivalent impedance. The fault current
flows through it during the fault.
Note: All the resistors and the reactances that ZF represent must found for the same base
apparent power which is the SBASE.
Normally, it is assumed that the generators are operated at rated voltages almost equal to
the base voltages, i.e. EPU = VPU ≈ 1.0 pu. Therefore,
A. Calculation of Fault Current in Amps
A. Calculation of Fault Current in Amps
In a power system, the maximum the fault current (or fault MVA) that can flow into a zero
impedance fault is necessary to be known.
This can either be the balanced three phase value.
The Fault Level defines the value for the symmetrical condition.
The fault level is usually expressed in MVA (or corresponding per-unit value), with the
maximum fault current value being converted using the nominal voltage rating.
b. Fault Level or short circuit Level MVA Calculation