Bureau of Design: Schedule of Loads and Computations: General Notes

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

GENERAL NOTES: SCHEDULE OF LOADS AND COMPUTATIONS:

DISTRIBUTION PANELBOARD " DPC " (FOURTH FLOOR)


DISTRIBUTION PANELBOARD " DPA " (GROUND FLOOR)
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES, RULES AND REGULATIONS OF THE LOCAL GOVERNMENT AND WITH BRANCH BRANCH
THE REQUIREMENTS OF THE LOCAL POWER COMPANY. CKT. VA PER CKT. BREAKER SIZE OF HOMERUN CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT ) NO. CKT. ( WIRES IN CONDUIT )
2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE SINGLE-PHASE, 2-WIRE, 230V, 60 HERTZ, A.C AF P AT AF P AT

3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE 1 LIGHTING OUTLETS 1260 230 100 2 20 2 - 3.5mm² THHN IN 15mm Ø C 1 LIGHTING OUTLETS 1260 230 50 2 20 2 - 3.5mm² THHN IN 15mm Ø C
POWER COMPANY SERVICE POINT.
2 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C 2 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C
4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL CONDUIT TO BE USED SHALL BE
3.5mm²,THHN AND 15mm NOMINAL DIAMETER, RESPECTIVELY. LIKEWISE ALL ELECTRICAL WIRES SHALL BE COLOR-CODED.
3 LIGHTING OUTLETS 1070 20 2 - 3.5mm² THHN IN 15mm Ø C 3 LIGHTING OUTLETS 1080 20 2 - 3.5mm² THHN IN 15mm Ø C
5. ALL LIGHTING CIRCUIT HOMERUNS AND CONVENIENCE OUTLETS SHALL BE WIRED WITH NOT LESS THAN 3.5 mm² IN SIZE.
4 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 4 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
6. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION BOXES SHALL BE INSTALLED AT CONVENIENT AND
INCONSPICUOUS LOCATION, ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLAN NOR MENTIONED IN THE SPECIFICATIONS.
5 CONVENIENCE OUTLETS 1440 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 5 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
7. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ACCORDANCE
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. 6 CONVENIENCE OUTLETS 1800 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 6 CONVENIENCE OUTLETS 2160 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C

8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND PURPOSE. 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 3HP, 1Ø, BOOSTER PUMP 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C
7 COMPUTER OUTLETS 1250 20 7 3910 40
9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTENANCES FOR THE ENTIRE
ELECTRICAL INSTALLATION SHALL BE USED. 8 COMPUTER OUTLETS 1250 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 8 SPARE 1500 20

10. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED FLOOR LEVEL UNLESS NOTED IN 9 COMPUTER OUTLETS 1250 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 9 SPARE 1500 20
THE PLAN.
10 COMPUTER OUTLETS 1250 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 10 SPARE 1500 20
a) WALL SWITCHES @ 1300mm
b) WALL CONVENIENCE OUTLETS @ 300 mm
11 COMPUTER OUTLETS 1250 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 11 SPARE 1500 20
11. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY REGISTERED
ELECTRICAL ENGINEER. 12 COMPUTER OUTLETS 1250 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 12 SPARE 1500 20

13 COMPUTER OUTLETS 1250 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C TOTAL 14340 MAIN ACB: 100AF, 2P, 100AT, 250V, 18KAIC

ELECTRICAL SYMBOLS: 14 COMPUTER OUTLETS 1250 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C TOTAL CONNECTED LOADS: 14340 VA

15 FACP 1500 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 14340


I L @ 85% D.F. = (0.85) + 0.25 (17) = 57.25 AMPERES
230
USE : 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C
16 CCTV 1500 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C (57.25 A / 115 A )
CEILING LIGHT OUTLET
REFER TO SCHEDULE OF
17 SPARE 1500 20 POWER PANELBOARD "PPH"
CEILING LIGHT OUTLET LIGHTING FIXTURES AND LAMPS
BRANCH
18 SPARE 1500 20
CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
CF CEILING FAN, 60 WATTS, 230V, 60Hz LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT )
19 3.0 TR, 1Ø, SPLIT TYPE ACU 4850 60 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C AF P AT
SCF CEILING FAN CONTROL SWITCH
20 3.0 TR, 1Ø, SPLIT TYPE ACU 4850 60 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C 1 2.0HP, 1Ø, 230V, WATER PUMP MOTOR 2760 230 50 2 30 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
S SINGLE POLE WALL SWITCH IN ONE SWITCH PLATE
(10 AMP., 230 VOLTS)
21 3.0 TR, 1Ø, SPLIT TYPE ACU 4850 60 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C 2 2.0HP, 1Ø, 230V, WATER PUMP MOTOR 2760 230 50 2 30 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
S² 2 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE
(10 AMP., 230 VOLTS)
22 SPARE 4850 60 TOTAL 5520 MACB : 50AF, 2P, 250V, 50AT, 10KAIC
S³ 3 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE
(10 AMP., 230 VOLTS)
TOTAL 42710 MAIN LUGS ONLY: 200AMPS, 2P, 250V, 22KAIC
TOTAL CONNECTED LOADS: 4600 VA
S3W THREE WAY WALL SWITCH (10 AMP., 230 VOLTS)
TOTAL CONNECTED LOADS: 42710 VA
DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE, 20A, 250VOLTS 5520
I L @ 100% D.F. = (1.0) + 0.25 (12) = 27 AMPERES
"WP" DENOTES WEATHERPROOF OUTLET 42710 230 USE : 2 -8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C
I L @ 90% D.F. = (0.90) + 0.25 (21.09) = 172.40 AMPERES
230 USE : 2 - 80mm² THHN + 1 - 22mm² THHN (G) IN 50mm Ø C
SINGLE CONVENIENCE OUTLET, GROUNDING TYPE
(172.40 A / 205 A )
EF "EF" DENOTES EXHAUST FAN (15 AMP., 230 VOLTS) MAIN DISTRIBUTION PANELBOARD "MDP "
CONCEALED OR EMBEDDED CONDUIT RUN DISTRIBUTION PANELBOARD " DPB " (SECOND & THIRD FLOOR) BRANCH
CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
UNDERGROUND OR UNDERFLOOR CONDUIT RUN BRANCH LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT )
CKT. VA PER CKT. BREAKER SIZE OF HOMERUN AF P AT
LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT )
CIRCUIT HOMERUN AF P AT
1 "DPA" 42710 230 225 2 200 2 - 80mm² THHN + 1 - 22mm² THHN (G) IN 50mm Ø C

ENCLOSED CIRCUIT BREAKER 1 LIGHTING OUTLETS 1260 230 50 2 20 2 - 3.5mm² THHN IN 15mm Ø C
RATING AS SHOWN ON THE PLAN 2 "DPB" 19580 230 225 2 100 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C

2 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C


PB PULLBOX 3 "DPC" 14340 230 225 2 100 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C

3 LIGHTING OUTLETS 1030 20 2 - 3.5mm² THHN IN 15mm Ø C


4 "PPH" 5520 230 225 2 50 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C
MAIN DISTRIBUTION PANELBOARD
4 LIGHTING OUTLETS 1260 20 2 - 3.5mm² THHN IN 15mm Ø C
TOTAL 82150 MACB : 400AF, 2P, 250V, 400AT, 42KAIC

DISTRIBUTION PANELBOARD 5 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C


TOTAL CONNECTED LOADS: 82150 VA
M ELECTRIC SERVICE METER 6 LIGHTING OUTLETS 1030 20 2 - 3.5mm² THHN IN 15mm Ø C
82150 (0.90) + 0.25 (21.09) = 326.73 AMPERES
7 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C I L @ 90% D.F. = USE : 2 -250mm² THHN + 1 - 50mm² THHN (G) IN 90mm Ø RSC
230 (326.73 A / 400 A )
ELECTRIC SERVICE ENTRANCE
8 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C

GROUNDING SYSTEM CAPACITY OF TRANSFORMER:


9 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
KVA = EI @ D.F. = 80%, DIVERSITY FACTOR = 1.10 DECKROOF
10 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 1000
FACP FIRE ALARM CONTROL PANEL = (230) (357.17) (0.80) = 59.74 kVA
NOTE:
11 CONVENIENCE OUTLETS 2160 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 1000 (1.10)
ALL SIZES OF SERVICE FEEDER (WIRES IN CONDUIT)
USE: ONE (1) SET - 65 kVA, 34.5 kV/230V, 1Ø, 60Hz, AC, OISC, POLE MOUNTED, REFER TO SCHEDULE OF LOADS AND COMPUTATIONS
12 CONVENIENCE OUTLETS 2160 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
DISTRIBUTION TRANSFORMER
4TH FLOOR
13 SPARE 1500 20
"DPC"
14 SPARE 1500 20
SERVICE LATERAL PROVIDED WITH 90mmØ
"TYPE F" CONDULETS FOR 230V, 2-WIRE,
SCHEDULE OF LIGHTING FIXTURES AND LAMPS 15 SPARE 1500 20 60Hz, A.C. TO CONNECT TO AVAILABLE
POWER LINES.
INSTALLATION/ "MDP"- 3 3RD FLOOR
SYMBOLS DESCRIPTION 16 SPARE 1500 20
MOUNTING REINFORCED CONCRETE ELECTRIC
PEDESTAL 5.00m X 0.30m X 0.30m "DPB"
SURFACED CEILING

300mm
1 ONE (1)-28W, 230V,60Hz AC, FLUORESCENT LIGHTING FIXTURE, BOX TYPE. TOTAL 19580 MAIN ACB: 100AF, 2P, 100AT, 250V, 18KAIC
MOUNTED

3100mm (MIN.) - 5500mm (MAX.)


SURFACED CEILING TOTAL CONNECTED LOADS: 19580 VA
2 TWO (2)-28W, 230V, 60Hz AC, FLUORESCENT LIGHTING FIXTURE , BOX TYPE
MOUNTED
ELECTRIC SERVICE
METER (CTC METERING) PROPOSED: 2.0HP, 1Ø, 230V,
19580 (0.85) = 72.36 AMPERES "MDP"- 2 2ND FLOOR 60Hz., AC, WATER PUMP MOTOR
ONE (1)-18W, 230V, 60Hz AC,COMPACT FLUORESCENT LIGHTING FIXTURE WITH SURFACED CEILING I L @ 85% D.F. = USE : 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C
230
MEDIUM BASE KEYLESS TYPE PORCELAIN RECEPTACLE MOUNTED "PPH"
(72.36 A / 115 A )
M "DPA" "MDP"
ALL FLUORESCENT LIGHTING FIXTURES SHALL BE EQUIPPED WITH A HIGH POWER FACTOR, PRE-HEAT
NOTE: WITH STARTER AND THERMALLY PROTECTED BALLAST, COMPLETE WITH ALL NECESSARY ACCESSORIES, MANHOLE SIZE
WIRED AND READY FOR USE. AS REQUIRED

1800mm
WP WP

FIN. FLOOR LINE A A


FIN. GRADE LINE
MH
TO "MDP"- 4
1-50mm² THHN IN 25mmØ C. -
2- 250mm² THHN + 1-50mm²THHN(G) CLAMPED TO A 25mmØ X
1-5.5mm² THHN IN 15mmØ C.
IN 90mmØ RSC 3000mm COPPERCLAD AUTOMATIC CIRCUIT BREAKER
A - CLAMPED TO A 16mmØ X
GROUNDING ELECTRODE 50AF, 2P, 240VOLTS, 30AT
2400mm COPPERCLAD
IN NEMA 3R ENCLOSURE
GROUNDING ELECTRODE
ELECTRICAL RISER DIAGRAM B
AUTOMATIC CIRCUIT BREAKER
NOT TO SCALE 50AF, 2P, 240VOLTS, 40AT
IN NEMA 3R ENCLOSURE

AUTOMATIC CIRCUIT BREAKER


C 100AF, 2P, 240VOLTS, 60AT
IN NEMA 3R ENCLOSURE

REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED: SIGNED SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO. SHEET NO.
MARU BRYAN T. ZAPLAN
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS GENERAL NOTES
ENGINEER II
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
MODIFIED STANDARD DPWH - DEPED ELECTRICAL SYMBOLS CADD: SIGNED
BUREAU OF DESIGN FOUR (4) STOREY, TWENTY (20) SCHEDULE OF LOADS MARU BRYAN T. ZAPLAN
ENGINEER II
APPROVED WITH SIGNATURE BOD
E - 10
BUILDINGS DIVISION SCHEDULE OF LIGHTING FIXTURES AND LAMPS JOSEPHINE P. ISTURIS LEA N. DELFINADO GILBERTO S. REYES LEONOR M. BRIONES
CLASSROOM SCHOOL BUILDING ELECTRICAL RISER DIAGRAM CHECKED: SIGNED B 12 90
ERIBERTO B. SIOSON OIC, UNDERSECRETARY FOR
BONIFACIO DRIVE PORT AREA, MANILA CHIEF, BUILDINGS DIVISION OFFICER-IN-CHARGE, BOD SECRETARY, DEP ED