RC Design U 2017 v13.2

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 74

INDEX (Quick reach)

Reinforced Concrete Design©


Using the Ultimate Limit Design Method
according to ECP 203-2018

Ver. 13.2

Please send your comments & suggestions to improve this tool on


melkateb@hotmail.com

https://www.facebook.com/MelkatebDesignsheets

by
Mahmoud M. El-Kateb, Ph.D

Structural Engineering Dept.


Faculty of Engineering - Ain Shams University
GENERAL
Calculation of T & L Section Inertia
Calculation of Loads and Coefficients
Fire Rating Requirements
Capacity of Sections

SLABS
Empirical Analysis of Solid Slabs
Design of Slabs
Empirical Design of Flat Slab
Check Punching for Flat Slab Columns "Approximate"
Check Punching for Flat Slab Columns "Exact"
Calculation of Punching RFT

DEEP BEAMS
Design of Simple Deep Beams
Design of Continuous Deep Beams
Design of Corbel

SERVICEABILITY
Deflection of Cantilever
Deflection of Simple R-Section
Deflection of Simple T-Section
Calculation of Crack Width

Design of Retaining Walls


Development & Splice of Reinforcement
Design of Water Section
BEAMS
Design of Beams
Design of Beams with Compression RFT
Design of Sec. under M & N
Check Shear in Beams
Design of Torsion

COLUMNS
Design of Rectangular Columns
Design of Circular Columns

FOUNDATIONS
Design of Isolated Footing
Design of isolated Footing under Moment
Design of isolated Footing under Double Moment
Design of Fence Footing
Design of Combined Footing
Design of Strap Beam Footing
Design of Pile Cap
Design of Pile Cap under Moment
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.2

* Calculation of T & L Section Inertia

* Project :

1200 mm
250 mm

700 mm

300 mm

I R-sec = 8.58E+09 mm4


yc.g = 234 mm from flange edge
I T-sec = 1.52E+10 mm4 = 1.8 I R-sec
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 9.6

* Calculation of Loads & Coefficients

* Project :

Load Distribution of Solid Slabs:

Long span Short span Code of practice Marcus Grashoff


Area
Span (m) contin. Span (m) contin. a b a b a b
1 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
2 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
3 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
4 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
5 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
6 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
7 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
8 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
9 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
10 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291

Load Distribution on Beams:

Load on Long Short Load coeff. Load distribution for


Area
slab (kN/m2) span (m) span (m) shear moment shear (kN/m`) moment (kN/m`)
1 8.5 5 4 0.600 0.787 10.2 13.4
2 8.5 5 4 0.600 0.787 10.2 13.4
3 8.5 5 4 0.600 0.787 10.2 13.4
4 8.5 5 4 0.600 0.787 10.2 13.4
5 8.5 5 4 0.600 0.787 10.2 13.4
6 8.5 5 4 0.600 0.787 10.2 13.4
7 8.5 5 4 0.600 0.787 10.2 13.4
8 8.5 5 4 0.600 0.787 10.2 13.4
9 8.5 5 4 0.600 0.787 10.2 13.4
10 8.5 5 4 0.600 0.787 10.2 13.4

Load of Hollow Slabs:

Web breadth Spacing Thick Slab th F.C L.L Block One way Two way
Area
b (mm) e (mm) t (mm) ts (mm) (kN/m ) (kN/m ) Wt. (kN)
2 2 Wu (kN/m2) Wu (kN/m2)
1 120 400 270 70 1.5 2.0 0.15 11.4 12.2
2 120 400 270 70 1.5 2.0 0.15 11.4 12.2
3 120 400 270 70 1.5 2.0 0.15 11.4 12.2
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 9.6

* Calculation of Loads & Coefficients

* Project :

4 120 400 270 70 1.5 2.0 0.15 11.4 12.2


5 120 400 270 70 1.5 2.0 0.15 11.4 12.2
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.0

* Fire Rating Requirements

* Project :

Design fire rating period: 2 hours


Type of aggregate: ‫متوسط الوزن‬

Traditional slabs: Pre-stressed slabs:


min. Thick = 120 mm min. Cover = 40 mm
min. Cover = 25 mm

Traditional simple beams: Traditional cont. beams:


min. Breadth = 250 mm min. Breadth = 180 mm
min. Cover = 35 mm min. Cover = 30 mm

Columns:
min. Dim. = 250 mm
min. Cover = 40 mm

Walls:
RFT ratio m 0.4 % < < 1 %
min. Dim. = 200 mm
min. Cover = 25 mm
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.2

* Capacity of Sections

* Project :

Concrete fcu = 30 MPa


Steel fy = 400 MPa

Breadth Thick Depth Tension RFT As Comp. RFT As` Moment


Sec. Comp. RFT case
b (mm) t (mm) d (mm) no. f (mm ) 2
no. f (mm2) capacity (kN.m)
1 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
2 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
3 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
4 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
5 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
6 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
7 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
8 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
9 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
10 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
11 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
12 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
13 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
14 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
15 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
16 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.2

* Capacity of Sections

* Project :

Concrete fcu = 30 MPa


Steel fy = 400 MPa

Breadth Thick Depth Tension RFT As Comp. RFT As` Moment


Sec. Comp. RFT case
b (mm) t (mm) d (mm) no. f (mm ) 2
no. f (mm2) capacity (kN.m)
17 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
18 250 700 650 4 18 1018 4 12 452 Ignore comp. RFT 211.4
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.6

* Empirial Analysis of Solid Slabs

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Long span Short span min. Slab Slab thick F.C L.L Wsu Code of practice Moments (kN.m) Rft. /m Rft. /m
Area
Span (m) contin. Span (m) contin. thick (mm) (mm) (kN/m 2
) (kN/m 2
) (kN/m 2
) a b Ma Mb short dir. long dir.
1 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
2 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
3 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
4 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
5 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
6 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
7 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
8 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
9 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
10 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
11 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
12 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
13 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
14 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
15 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
16 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
17 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.6

* Empirial Analysis of Solid Slabs

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Long span Short span min. Slab Slab thick F.C L.L Wsu Code of practice Moments (kN.m) Rft. /m Rft. /m
Area
Span (m) contin. Span (m) contin. thick (mm) (mm) (kN/m 2
) (kN/m 2
) (kN/m 2
) a b Ma Mb short dir. long dir.
18 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Design of Slabs

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa
###
###
Ult. Moment Breadth Depth Thick. As Asmin Used ###
Sec. C1 J Rft. /m Notes
Mu (kN.m) b (mm) d (mm) t (mm) (mm ) (mm )
2 2
As ###
1 15 1000 120 150 4.90 0.826 378 225 378 5 f 10 Safe
###
2 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
3 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
4 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
5 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
6 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
7 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
8 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
9 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
10 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
11 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
12 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
13 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
14 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
15 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
16 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
17 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
18 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
19 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
20 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
21 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
22 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
23 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
24 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
25 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
26 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
27 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
28 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
29 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
30 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
31 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
32 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Design of Slabs

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa
###
###
Ult. Moment Breadth Depth Thick. As Asmin Used ###
Sec. C1 J Rft. /m Notes
Mu (kN.m) b (mm) d (mm) t (mm) (mm ) (mm )
2 2
As ###
33 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
34 15 1000 120 150 4.90 0.827 378 225 378 5 f 10 Safe
###
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.5

* Empirical Design of Flat Slab

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa
cmax/d
Slab Module: Long span L1 = 7 m Short span L2 = 6 m ###
Marginal beams: Yes ###
Column dim.: with long span 500 mm with short span = 500 mm ###
Slab thickness: 220 mm ###
Live load: 4.0 kN/m2 Floor cover + Walls: 2.5 kN/m2
Slab load Wsu = 17.6 kN/m2

Long direction 117.3 1 293.3 3


Column strip 4 176.0 2 146.7

Long direction 58.7 5 117.3 7


Field strip 8 117.3 6 88

Short direction 91.8 9 233.1 11 Modified


Column strip 12 134.2 10 113

Short direction 56.5 13 113.0 15 Modified


Field strip 16 113.0 14 84.8

Page 14 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.5

* Empirical Design of Flat Slab

Design of sections:

Ult. Moment Breadth Depth As Asmin Used


Sec. C1 J Rft. /m Notes
Mu (kN.m) b (mm) d (mm) (mm ) (mm )
2 2
As
1 176.0 3000 190 3.92 0.801 963 330 963 5 f 16 Safe
###
2 293.3 3000 190 3.04 0.747 1722 330 1722 9 f 16 Safe
###
3 146.7 3000 190 4.30 0.814 791 330 791 4 f 16 Safe
###
4 117.3 3000 190 4.80 0.826 623 330 623 4 f 16 Safe
###
5 117.3 3000 190 4.80 0.826 623 330 623 6 f 12 Safe
###
6 117.3 3000 190 4.80 0.826 623 330 623 6 f 12 Safe
###
7 88.0 3000 190 5.55 0.826 467 330 467 5 f 12 Safe
###
8 58.7 3000 190 6.79 0.826 312 330 330 3 f 12 Safe
###
9 134.2 3000 190 4.49 0.819 719 330 719 7 f 12 Safe
###
10 233.1 3000 190 3.41 0.776 1317 330 1317 7 f 16 Safe
###
11 113.0 3000 190 4.89 0.826 600 330 600 6 f 12 Safe
###
12 91.8 3000 190 5.43 0.826 488 330 488 5 f 12 Safe
###
13 113.0 4000 190 5.65 0.826 450 330 450 4 f 12 Safe
###
14 113.0 4000 190 5.65 0.826 450 330 450 4 f 12 Safe
###
15 84.8 4000 190 6.53 0.826 338 330 338 3 f 12 Safe
###
16 56.5 4000 190 7.99 0.826 225 330 330 3 f 12 Safe
###

Page 15 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Check Punching for Flat Slab Columns using approximate b factor

* Project :

Concrete fcu = 40 MPa

Internal columns:

b critical perimeter (bo)

Ult. Load Col. Dims. Slab Cover Critical bo qcpu qpu


Col. D/C
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) (N/mm ) 2
(N/mm2)
1 600 300 600 250 30 Auto 2680 1.63 1.17 0.72
2 600 300 600 250 30 Auto 2680 1.63 1.17 0.72
3 600 300 600 250 30 Auto 2680 1.63 1.17 0.72
4 600 300 600 250 30 Auto 2680 1.63 1.17 0.72
5 600 300 600 250 30 Auto 2680 1.63 1.17 0.72
6 600 300 600 250 30 Auto 2680 1.63 1.17 0.72
7 600 300 600 250 30 Auto 2680 1.63 1.17 0.72
8 600 300 600 250 30 Auto 2680 1.63 1.17 0.72
9 600 300 600 250 30 Auto 2680 1.63 1.17 0.72

D critical perimeter (bo)

Ult. Load Col. Dims. Slab Cover Critical bo qcpu qpu


Col. D/C
Qu (kN) D (mm) Thick (mm) (mm) Perimeter (mm) (N/mm2) (N/mm2)
1 450 400 250 30 Auto 1948 1.63 1.21 0.74
2 450 400 250 30 Auto 1948 1.63 1.21 0.74
3 450 400 250 30 Auto 1948 1.63 1.21 0.74

Page 16 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Check Punching for Flat Slab Columns using approximate b factor

4 450 400 250 30 Auto 1948 1.63 1.21 0.74

Edge columns:

b
critical perimeter (bo)

Ult. Load Col. Dims. Slab Cover Critical bo qcpu qpu


Col. D/C
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) (N/mm2) (N/mm2)
1 300 300 600 250 30 Auto 1640 1.63 1.08 0.66###
2 300 300 600 250 30 Auto 1640 1.63 1.08 0.66###
3 300 300 600 250 30 Auto 1640 1.63 1.08 0.66###
4 300 300 600 250 30 Auto 1640 1.63 1.08 0.66###
5 300 300 600 250 30 Auto 1640 1.63 1.08 0.66###
6 300 300 600 250 30 Auto 1640 1.63 1.08 0.66###
7 300 300 600 250 30 Auto 1640 1.63 1.08 0.66###

Corner columns:

b
critical perimeter (bo)

Ult. Load Col. Dims. Slab Cover Critical bo qcpu qpu


Col. D/C
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) (N/mm2) (N/mm2)
1 200 300 600 250 30 Auto 1120 1.63 1.22 0.75
2 200 300 600 250 30 Auto 1120 1.63 1.22 0.75
3 200 300 600 250 30 Auto 1120 1.63 1.22 0.75
4 200 300 600 250 30 Auto 1120 1.63 1.22 0.75
5 200 300 600 250 30 Auto 1120 1.63 1.22 0.75
6 200 300 600 250 30 Auto 1120 1.63 1.22 0.75
7 200 300 600 250 30 Auto 1120 1.63 1.22 0.75

Page 17 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.1

* Check Punching for Flat Slab Columns taking unbalanced moment effect

* Project :

Concrete fcu = 30 MPa

Internal rectangular columns:


unbalanced moment
Mft

unbalanced moment
b Mfb

critical perimeter (bo)


t

Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb


Col.
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m
600 300 600 250 30 Auto 2680 30 40
t+d b+d d CABt CABb Jct Jcb qcpu qave qb+qt qpuAB
1 gqt gqb D/C
Output: (mm) (mm) (mm) (mm) (mm) (mm ) 4
(mm ) 4
(N/mm ) 2
(N/mm ) 2
(N/mm ) 2
(N/mm2)
820 520 220 410 260 6.01E+10 3.05E+10 0.456 0.347 1.41 1.02 0.21 1.23 0.87
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb
Col.
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m
600 300 600 250 30 Auto 2680 30 40
t+d b+d d CABt CABb Jct Jcb qcpu qave qb+qt qpuAB
2 gqt gqb D/C
Output: (mm) (mm) (mm) (mm) (mm) (mm ) 4
(mm ) 4
(N/mm ) 2
(N/mm ) 2
(N/mm ) 2
(N/mm2)

Page 18 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.1

*2Check Punching for Flat Slab Columns taking unbalanced moment effect
Output:
820 520 220 410 260 6.01E+10 3.05E+10 0.456 0.347 1.41 1.02 0.21 1.23 0.87

Internal circular columns:


unbalanced moment
Mfy

unbalanced moment
D Mfx

critical perimeter (bo)

Ult. Load Col. Dims. Slab Cover Critical bo Mfx Mfy


Col.
Qu (kN) D (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m
450 400 250 30 Auto 1948 30 30
D+d d CABx CABy Jcx Jcy qcpu qave qx+qy qpuAB
1 gqx gqy D/C
Output: (mm) (mm) (mm) (mm) (mm ) 4
(mm ) 4
(N/mm ) 2
(N/mm ) 2
(N/mm ) 2
(N/mm2)
620 220 310 310 2.17E+10 2.17E+10 0.400 0.400 1.41 1.05 0.34 1.39 0.99
Ult. Load Col. Dims. Slab Cover Critical bo Mfx Mfy
Col.
Qu (kN) D (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m
450 400 250 30 Auto 1948 30 30
D+d d CABx CABy Jcx Jcy qcpu qave qx+qy qpuAB
2 gqx gqy D/C
Output: (mm) (mm) (mm) (mm) (mm ) 4
(mm ) 4
(N/mm ) 2
(N/mm ) 2
(N/mm ) 2
(N/mm2)
620 220 310 310 2.17E+10 2.17E+10 0.400 0.400 1.41 1.05 0.34 1.39 0.99
Ult. Load Col. Dims. Slab Cover Critical bo Mfx Mfy
Col.
Qu (kN) D (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m
450 400 250 30 Auto 1948 30 30
D+d d CABx CABy Jcx Jcy qcpu qave qx+qy qpuAB
3 gqx gqy D/C
Output:
Page 19 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.1

* Check Punching for Flat Slab Columns taking unbalanced moment effect

3 gqx gqy D/C


Output: (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm2) (N/mm2) (N/mm2) (N/mm2)
620 220 310 310 2.17E+10 2.17E+10 0.400 0.400 1.41 1.05 0.34 1.39 0.99

unbalanced moment
Mft
Edge columns:

unbalanced moment
b Mfb

critical perimeter (bo) t

Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb


Col.
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m
300 300 600 250 30 Auto 1640 30 70
t+d b+d/2 d CABt CABb Jct Jcb qcpu qave qb+qt qpuAB
1 gqt gqb D/C
Output: (mm) (mm) (mm) (mm) (mm) (mm ) 4
(mm ) 4
(N/mm ) 2
(N/mm ) 2
(N/mm ) 2
(N/mm2)
820 410 220 410 102.5 4.12E+10 7.05E+09 0.485 0.320 1.41 0.83 0.47 1.30 0.92
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb
Col.
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m
300 300 600 250 30 Auto 1640 30 70
t+d b+d/2 d CABt CABb Jct Jcb qcpu qave qb+qt qpuAB
2 gqt gqb D/C
Output: (mm) (mm) (mm) (mm) (mm) (mm ) 4
(mm ) 4
(N/mm ) 2
(N/mm ) 2
(N/mm ) 2
(N/mm2)
820 410 220 410 102.5 4.12E+10 7.05E+09 0.485 0.320 1.41 0.83 0.47 1.30 0.92
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb
Col.
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m
300 300 600 250 30 Auto 1640 30 70

3 Page 20 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.1

* Check Punching for Flat Slab Columns taking unbalanced moment effect

t+d b+d/2 d CABt CABb Jct Jcb qcpu qave qb+qt qpuAB
3 gqt gqb D/C
Output: (mm) (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm2) (N/mm2) (N/mm2) (N/mm2)
820 410 220 410 102.5 4.12E+10 7.05E+09 0.485 0.320 1.41 0.83 0.47 1.30 0.92

unbalanced moment
Corner columns: Mft

b unbalanced moment
Mfb
critical perimeter (bo)

Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb


Col.
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m
150 300 600 250 30 Auto 1120 50 50
t+d/2 b+d/2 d CABt CABb Jct Jcb qcpu qave qb+qt qpuAB
1 gqt gqb D/C
Output: (mm) (mm) (mm) (mm) (mm) (mm ) 4
(mm ) 4
(N/mm ) 2
(N/mm ) 2
(N/mm ) 2
(N/mm2)
710 410 220 225.04 75.04 1.44E+10 4.03E+09 0.467 0.336 1.41 0.61 0.68 1.29 0.91
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb
Col.
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m
150 300 600 250 30 Auto 1120 50 50
t+d/2 b+d/2 d CABt CABb Jct Jcb qcpu qave qb+qt qpuAB
2 gqt gqb D/C
Output: (mm) (mm) (mm) (mm) (mm) (mm ) 4
(mm ) 4
(N/mm ) 2
(N/mm ) 2
(N/mm ) 2
(N/mm2)
710 410 220 225.04 75.04 1.44E+10 4.03E+09 0.467 0.336 1.41 0.61 0.68 1.29 0.91
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb
Col.
Qu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m

Page 21 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.1

* Check Punching for Flat Slab Columns taking unbalanced moment effect

150 300 600 250 30 Auto 1120 50 50


t+d/2 b+d/2 d CABt CABb Jct Jcb qcpu qave qb+qt qpuAB
3 gqt gqb D/C
Output: (mm) (mm) (mm) (mm) (mm) (mm )
4
(mm ) 4
(N/mm ) 2
(N/mm ) 2
(N/mm ) 2
(N/mm2)
710 410 220 225.04 75.04 1.44E+10 4.03E+09 0.467 0.336 1.41 0.61 0.68 1.29 0.91

Page 22 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Calculation of Punching RFT

* Project :

Concrete fcu = 30 MPa


Steel fy = 350 MPa

Internal columns:
bb

no. of bra.
parallel to b
no. of bra.
parallel to t
bt

tcol

Ult. Load Equiv. Col. Dims. Slab Req. no. of Branch Spcaing bb no. of bra. bt no. of bra. no. of RFT
Col. Notes
Qu (kN) b factor b (mm) t (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) parallel to b (mm) parallel to t Rows qpu
1 950 1.17 300 600 250 11 12 100 250 2 250 4 3 Safe ###
2 950 1.17 300 600 250 11 12 100 250 2 250 4 3 Safe ###
3 950 1.17 300 600 250 11 12 100 250 2 250 4 3 Safe ###
4 950 1.17 300 600 250 11 12 100 250 2 250 4 3 Safe ###
5 950 1.17 300 600 250 11 12 100 250 2 250 4 3 Safe ###
6 950 1.17 300 600 250 11 12 100 250 2 250 4 3 Safe ###
7 950 1.17 300 600 250 11 12 100 250 2 250 4 3 Safe ###

Page 23 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Calculation of Punching RFT


8 950 1.17 300 600 250 11 12 100 250 2 250 4 3 Safe ###

Ult. Load Equiv. Col. Dims. Slab Req. no. of Branch Spcaing b no. of no. of
Col. Notes
Qu (kN) b factor D (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) branches Rows qpu
1 630 1.2 400 250 7 12 100 200 4 2 Safe ###
2 630 1.2 400 250 7 12 100 200 4 2 Safe ###
3 630 1.2 400 250 7 12 100 200 4 2 Safe ###
4 630 1.2 400 250 7 12 100 200 4 2 Safe ###

Edge columns:

tcol

bcol

Ult. Load Equiv. Col. Dims. Slab Req. no. of Branch Spcaing bb no. of bra. bt no. of bra. no. of RFT
Col. Notes
Qu (kN) b factor b (mm) t (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) parallel to b (mm) parallel to t Rows qpu
1 450 1.51 300 600 250 7 12 100 250 2 250 4 4 Safe ###
2 450 1.51 300 600 250 7 12 100 250 2 250 4 4 Safe ###
3 450 1.51 300 600 250 7 12 100 250 2 250 4 4 Safe ###
4 450 1.51 300 600 250 7 12 100 250 2 250 4 4 Safe ###

Page 24 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Calculation of Punching RFT


5 450 1.51 300 600 250 7 12 100 250 2 250 4 4 Safe ###
6 450 1.51 300 600 250 7 12 100 250 2 250 4 4 Safe ###

Corner columns:

Ult. Load Equiv. Col. Dims. Slab Req. no. of Branch Spcaing bb no. of bra. bt no. of bra. no. of RFT
Col. Notes
Qu (kN) b factor b (mm) t (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) parallel to b (mm) parallel to t Rows qpu
1 220 1.84 300 600 250 4 12 100 250 2 250 4 3 Safe ###
2 220 1.84 300 600 250 4 12 100 250 2 250 4 3 Safe ###
3 220 1.84 300 600 250 4 12 100 250 2 250 4 3 Safe ###
4 220 1.84 300 600 250 4 12 100 250 2 250 4 3 Safe ###
5 220 1.84 300 600 250 4 12 100 250 2 250 4 3 Safe ###
6 220 1.84 300 600 250 4 12 100 250 2 250 4 3 Safe ###

Page 25 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Design of Beams

* Project :

Concrete fcu = 30 MPa


Steel fy = 400 MPa

Ult. Moment Breadth Comp.fl. Depth Asmin Used


Sec. C1 J Rft. Notes
Mu (kN.m) b (mm) B (mm) d (mm) (mm2) As
1 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
2 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
3 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
4 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
5 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
6 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
7 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
8 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
9 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
10 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
11 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
12 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
13 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
14 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
15 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
16 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
17 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
18 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
19 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
20 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
21 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
22 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
23 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
24 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
25 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
26 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
27 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
28 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
29 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
30 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
31 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
32 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Design of Beams

* Project :

Concrete fcu = 30 MPa


Steel fy = 400 MPa

Ult. Moment Breadth Comp.fl. Depth Asmin Used


Sec. C1 J Rft. Notes
Mu (kN.m) b (mm) B (mm) d (mm) (mm2) As
33 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
34 150 250 250 650 4.60 0.821 501 703 4 f 16 Safe
###
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Design of Beams with Compression Rft.

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Ult. Moment Breadth Depth Thick Main Comp.


Sec. Main Rft. Comp. Rft. Notes
Mu (kN.m) b (mm) d (mm) t (mm) As As
1 400 250 650 700 2101 6 f 22 339 4 f 12 ok
2 400 250 650 700 2101 6 f 22 339 4 f 12 ok
3 400 250 650 700 2101 6 f 22 339 4 f 12 ok
4 400 250 650 700 2101 6 f 22 339 4 f 12 ok
5 400 250 650 700 2101 6 f 22 339 4 f 12 ok
6 400 250 650 700 2101 6 f 22 339 4 f 12 ok
7 400 250 650 700 2101 6 f 22 339 4 f 12 ok
8 400 250 650 700 2101 6 f 22 339 4 f 12 ok
9 400 250 650 700 2101 6 f 22 339 4 f 12 ok
10 400 250 650 700 2101 6 f 22 339 4 f 12 ok
11 400 250 650 700 2101 6 f 22 339 4 f 12 ok
12 400 250 650 700 2101 6 f 22 339 4 f 12 ok
13 400 250 650 700 2101 6 f 22 339 4 f 12 ok
14 400 250 650 700 2101 6 f 22 339 4 f 12 ok
15 400 250 650 700 2101 6 f 22 339 4 f 12 ok
16 400 250 650 700 2101 6 f 22 339 4 f 12 ok
17 400 250 650 700 2101 6 f 22 339 4 f 12 ok
18 400 250 650 700 2101 6 f 22 339 4 f 12 ok
19 400 250 650 700 2101 6 f 22 339 4 f 12 ok
20 400 250 650 700 2101 6 f 22 339 4 f 12 ok
21 400 250 650 700 2101 6 f 22 339 4 f 12 ok
22 400 250 650 700 2101 6 f 22 339 4 f 12 ok
23 400 250 650 700 2101 6 f 22 339 4 f 12 ok
24 400 250 650 700 2101 6 f 22 339 4 f 12 ok
25 400 250 650 700 2101 6 f 22 339 4 f 12 ok
26 400 250 650 700 2101 6 f 22 339 4 f 12 ok
27 400 250 650 700 2101 6 f 22 339 4 f 12 ok
28 400 250 650 700 2101 6 f 22 339 4 f 12 ok
29 400 250 650 700 2101 6 f 22 339 4 f 12 ok
30 400 250 650 700 2101 6 f 22 339 4 f 12 ok
31 400 250 650 700 2101 6 f 22 339 4 f 12 ok
32 400 250 650 700 2101 6 f 22 339 4 f 12 ok
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Design of Beams with Compression Rft.

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Ult. Moment Breadth Depth Thick Main Comp.


Sec. Main Rft. Comp. Rft. Notes
Mu (kN.m) b (mm) d (mm) t (mm) As As
33 400 250 650 700 2101 6 f 22 339 4 f 12 ok
34 400 250 650 700 2101 6 f 22 339 4 f 12 ok
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.5

* Design of Sec. under M & N

* Project :

Concrete fcu = 30 MPa


Steel fy = 400 MPa

Ult. Moment Normal Breadth Depth Thick As Asmin Used


Sec. ecc. C1 J Rft.
Mu (kN.m) Nu (kN) b (mm) d (mm) t (mm) (mm ) (mm2)
2
As
1 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
2 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
3 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
4 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
5 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
6 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
7 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
8 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
9 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
10 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
11 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
12 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
13 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
14 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
15 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
16 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
17 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
18 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
19 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f 16
###
20 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
21 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
22 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
23 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f 16
###
24 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
25 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
26 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
27 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
28 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
29 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
30 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
31 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
32 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.5

* Design of Sec. under M & N

* Project :

Concrete fcu = 30 MPa


Steel fy = 400 MPa

Ult. Moment Normal Breadth Depth Thick As Asmin Used


Sec. ecc. C1 J Rft.
Mu (kN.m) Nu (kN) b (mm) d (mm) t (mm) (mm ) (mm2)
2
As
33 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
34 150 -200 250 650 700 Big 3.88 0.800 435 501 501 3 f ###
16
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Check Shear in Beams

* Project :

Concrete fcu = 30 MPa


Concrete qcu cracked = 0.54 MPa
Stirrups fy = 240 MPa

Ult. Shear Breadth Depth qu As min. no. of


Sec. Stirrups /m Notes
Qu (kN) b (mm) d (mm) (N/mm ) 2
S stirrups bran. ###
1 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
2 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
3 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
4 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
5 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
6 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
7 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
8 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
9 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
10 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
11 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
12 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
13 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
14 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
15 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
16 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
17 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
18 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
19 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
20 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
21 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
22 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
23 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
24 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
25 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
26 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
27 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
28 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
29 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
30 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
31 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Check Shear in Beams

* Project :

Concrete fcu = 30 MPa


Concrete qcu cracked = 0.54 MPa
Stirrups fy = 240 MPa

Ult. Shear Breadth Depth qu As min. no. of


Sec. Stirrups /m Notes
Qu (kN) b (mm) d (mm) (N/mm ) 2
S stirrups bran. ###
32 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
33 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.3

* Design for Torsion

* Project :

Concrete fcu = 25 MPa

Stirrups fy = 240 MPa

Horizontal bars fy = 400 MPa ###

###
Ult. torsional moment Sec. dim. Ult. shear force ###
Sec. Mu (kN.m) b (mm) t (mm) Qu (kN)
1 20 300 700 150
qcu
qtu Notes qsu Notes qumax
0.94 N/mm 2
need rft. 0.77 N/mm 2
use min Aoh
Ao
qtcu = 0.24 N/mm2 Ph
qcu = 0.98 N/mm2
qumax = 2.86 N/mm2

Calculation of Rft.

Stirrups due to shear no. f as/s


4.0 8 /m inner
astr/s
Stirrups due to torsion no. f
4.4 10 /m outer
###
or use total stirrups no. f ###
7 10 /m Asl min
Asl
Horizontal Rft. no. f ###
6 12

5 f 10 /m

7 f 10 /m
0.70 m 0.70 m

4 f8 /m

OR
0.30 m 0.30 m
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.3

* Approximate Design of Rectangular Columns

* Project :

Concrete fcu = 30 MPa Braced

Steel fy = 400 MPa Unbraced


###
Type of structure: Unbraced ###
Ult. Load Desired Dim of column As Clear Madd
Col. Reinforcement (K) l critical Notes m min (%) d (mm)
Nu (kN) m (%) b (mm) t (mm) (mm ) 2 Height (m) (kN.m)
1.0 250 250 625 4 f 16 14.4 Safe 1.00 25.9 18.1
1.3 250 250 813 5 f 16 14.4 Safe 1.00 25.9 18.1
C1 700 3.00 1.20
1.6 250 250 1000 5 f 16 14.4 Safe 1.00 25.9 18.1
1.05 250 250 656 4 f 16 14.4 Safe 1.00 25.9 18.1
1.0 250 350 875 5 f 16 14.4 Safe 1.00 25.9 25.9
1.3 250 350 1138 6 f 16 14.4 Safe 1.00 25.9 25.9
C2 1000 3.00 1.20
1.6 250 350 1400 7 f 16 14.4 Safe 1.00 25.9 25.9
1.1 250 350 963 5 f 16 14.4 Safe 1.00 25.9 25.9
1.0 250 450 1125 6 f 16 14.4 Safe 1.00 25.9 31.1
1.3 250 400 1300 7 f 16 14.4 Safe 1.00 25.9 31.1
C3 1200 3.00 1.20
1.6 250 400 1600 8 f 16 14.4 Safe 1.00 25.9 31.1
1.15 250 400 1150 6 f 16 14.4 Safe 1.00 25.9 31.1
1.0 250 550 1375 7 f 16 14.4 Safe 1.00 25.9 38.9
1.3 250 500 1625 9 f 16 14.4 Safe 1.00 25.9 38.9
C4 1500 3.00 1.20
1.6 250 500 2000 10 f 16 14.4 Safe 1.00 25.9 38.9
1.2 250 500 1500 8 f 16 14.4 Safe 1.00 25.9 38.9
1.0 250 650 1625 9 f 16 14.4 Safe 1.00 25.9 46.7
1.3 250 600 1950 10 f 16 14.4 Safe 1.00 25.9 46.7
C5 1800 3.00 1.20
Page 36 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.3

* Approximate Design of Rectangular Columns

* Project :

Concrete fcu = 30 MPa Braced

Steel fy = 400 MPa Unbraced


###
Type of structure: Unbraced ###
Ult. Load Desired Dim of column As Clear Madd
Col. Reinforcement (K) l critical Notes m min (%) d (mm)
Nu (kN) m (%) b (mm) t (mm) (mm ) 2 Height (m) (kN.m)
C5 1800 3.00 1.20
1.6 250 550 2200 11 f 16 14.4 Safe 1.00 25.9 46.7
1.2 250 600 1800 9 f 16 14.4 Safe 1.00 25.9 46.7
1.0 250 750 1875 10 f 16 14.4 Safe 1.00 25.9 54.4
1.3 250 700 2275 12 f 16 14.4 Safe 1.00 25.9 54.4
W1 2100 3.00 1.20
1.6 250 650 2600 13 f 16 14.4 Safe 1.00 25.9 54.4
1.3 250 700 2275 12 f 16 14.4 Safe 1.00 25.9 54.4
1.0 250 850 2125 11 f 16 14.4 Safe 1.00 25.9 62.2
1.3 250 800 2600 13 f 16 14.4 Safe 1.00 25.9 62.2
W2 2400 3.00 1.20
1.6 250 750 3000 15 f 16 14.4 Safe 1.00 25.9 62.2
1.2 250 800 2400 12 f 16 14.4 Safe 1.00 25.9 62.2
1.0 250 4650 11625 31 f 22 14.4 Safe 1.00 25.9 352.5
1.3 250 4350 14138 38 f 22 14.4 Safe 1.00 25.9 352.5
W3 13600 3.00 1.20
1.6 250 4150 16600 44 f 22 14.4 Safe 1.00 25.9 352.5
1.55 250 4200 16275 43 f 22 14.4 Safe 1.00 25.9 352.5
1.0 250 4550 11375 57 f 16 14.4 Safe 1.00 25.9 344.7
1.3 250 4250 13813 69 f 16 14.4 Safe 1.00 25.9 344.7
W4 13300 3.00 1.20
1.6 250 4050 16200 81 f 16 14.4 Safe 1.00 25.9 344.7
1.35 250 4200 14175 71 f 16 14.4 Safe 1.00 25.9 344.7

Page 37 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.3

* Approximate Design of Rectangular Columns

* Project :

Concrete fcu = 30 MPa Braced

Steel fy = 400 MPa Unbraced


###
Type of structure: Unbraced ###
Ult. Load Desired Dim of column As Clear Madd
Col. Reinforcement (K) l critical Notes m min (%) d (mm)
Nu (kN) m (%) b (mm) t (mm) (mm ) 2 Height (m) (kN.m)
1.0 250 1050 2625 14 f 16 14.4 Safe 1.00 25.9 77.8
1.3 250 1000 3250 17 f 16 14.4 Safe 1.00 25.9 77.8
W5 3000 3.00 1.20
1.6 250 950 3800 19 f 16 14.4 Safe 1.00 25.9 77.8
1.55 250 950 3681 19 f 16 14.4 Safe 1.00 25.9 77.8

Page 38 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.2

* Approximate Design of Circular Columns

* Project :

Concrete fcu = 25 MPa Braced

Steel fy = 400 MPa Unbraced


###
Type of structure: Unbraced ###
Ult. Load Desired Diamter As Clear Madd
Col. Reinforcement (K) l critical Notes m min (%) d (mm)
Nu (kN) m (%) D (mm) (mm2) Height (m) (kN.m)
1.0 300 707 4 f 16 16.0 Safe 1.08 38.4 26.9
1.3 300 918 5 f 16 16.0 Safe 1.08 38.4 26.9
1 700 4.00 1.20
1.6 300 1130 6 f 16 16.0 Safe 1.08 38.4 26.9
1.1 300 777 4 f 16 16.0 Safe 1.08 38.4 26.9
1.0 400 1256 7 f 16 12.0 Safe 0.87 28.8 37.4
1.3 400 1633 9 f 16 12.0 Safe 0.87 28.8 37.4
2 1300 4.00 1.20
1.6 400 2010 11 f 16 12.0 Safe 0.87 28.8 37.4
1.2 400 1507 8 f
16 12.0 Safe 0.87 28.8 37.4
1.0 500 1963 10 f
16 9.6 Safe 0.75 23.0 43.8
1.3 500 2551 13 f
16 9.6 Safe 0.75 23.0 43.8
3 1900 4.00 1.20
1.6 450 2543 13 f
16 10.7 Safe 0.80 25.6 48.6
1.4 500 2748 14 f
16 9.6 Safe 0.75 23.0 43.8
1.0 600 2826 15 f 16 8.0 Safe 0.67 19.2 55.7
1.3 600 3674 19 f 16 8.0 Safe 0.67 19.2 55.7
4 2900 4.00 1.20
1.6 600 4522 23 f 16 8.0 Safe 0.67 19.2 55.7
1.5 600 4239 22 f 16 8.0 Safe 0.67 19.2 55.7
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.5

* Design of Isolated Footing

* Project :

Concrete fcu = 25 MPa

Steel fy = 400 MPa

Bearing capacity qall = 150 KPa

Column working load Column dim. Extension


foot Nw (kN) b (mm) t (mm) of P.C (mm)
F1 1000 300 500 300 Working P.C

Dims. of P.C : B (mm) L (mm) t (mm)


2,550 2,750 300

Dims. of R.C : B (mm) L (mm) t (mm)


1,950 2,150 600

Actual soil stress (kPa) Notes


146 safe

Stress above P.C (kPa)


254

Shear stress (N/mm2) qcu (N/mm2) Notes


0.37 < 0.65 safe

Punching stress (N/mm2) qcup (N/mm2) Notes


0.61 < 1.29 safe

Calculation of Rft. : Asmin


900 mm2

Long Direction : Mu /m As /m no. f total no.


122 695 8 12 /m 16

Short Direction : Mu /m As /m no. f total no.


122 695 8 12 /m 18
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.6

* Design of Isolated Footing under Moment

* Project :

Concrete fcu = 25 MPa

Steel fy = 400 MPa

Bearing capacity qall = 125 KPa Secondary case

Column working load Moment Column dim. Extension


foot Nw (kN) Mw (kN.m) b (mm) t (mm) of P.C (mm)
F1 250 200 300 500 300 Working P.C

Dims. of P.C : B (mm) L (mm) Lno tens (mm) t (mm)


Choose dim of P.C 2,950 3,150 3,107 300

Dims. of R.C : B (mm) L (mm) t (mm)


2,350 2,550 500

Max. Stress (kPa) = 83 Safe Secondary case


Min. Stress (kPa) = 1 No tension
Max. Stress (kPa) = 83 Safe Secondary case
After Redistribution
Min. Stress (kPa) = 1

Shear stress (N/mm2) qcu (N/mm2) Notes


0.33 < 0.65 safe

Punching stress (N/mm2) qcup (N/mm2) Notes


0.21 < 1.29 safe

Calculation of Rft. : Asmin


750 mm2

Long Direction : Mu /m As /m no. f total no.


89 623 7 12 /m 17

Short Direction : Mu /m As /m no. f total no.


51 357 7 12 /m 18

Page 41 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.6

* Design of Isolated Footing under Moment

Results:
Nw = 250 kN

Mw = 200 kN.m

0.50 m

0.30 m

0.57
kPa

83
kPa

2.55 m

0.50
/m
2.35 m

2.95 m
0.30

12

0.50
7 f

7 f 12 /m

3.15 m

F1

Page 42 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.5

* Design of Isolated Footing under Double Moment

* Project :

Concrete fcu = 25 MPa ###

Steel fy = 400 MPa ###

Bearing capacity qall = 150 KPa Secondary case ###

###
###
Column working load Moment Moment Column dim. Extension
foot Nw (kN) Mwx (kN.m) Mwy (kN.m) b (mm) t (mm) of P.C (mm)
F1 400 150 300 300 500 300 ###

###
Dims. of P.C : B (mm) L (mm) t (mm) ###
1,700 3,400
Choose dim of P.C 3,000 3,200 300

Dims. of R.C : B (mm) L (mm) t (mm)


2,400 2,600 500

LRC
3 1

Mwx

BRC bcol Mwx Mwy BPC

tcol

4 2
LPC

Eccentricities:
ex = 0.28 m ey = 0.55 m
P1 Stress (kPa) = 146 Safe Secondary case
P2 Stress (kPa) = 84
P3 Stress (kPa) = 29

Page 43 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.5

P4 Stress (kPa) = -33 Tension on soil

Using chart:
ex/B = 0.09 ey/L = 0.17 K= 2.67

Max. Stress (kPa) = 150 Safe Secondary case

Using Approximate method:


Beff (mm) = 2446 Leff (cm) = 2092
###
Average Stress (kPa) = 106 Safe primary case ###
###
Shear stress (N/mm2) qcu (N/mm2) Notes
0.36 < 0.65 safe

Punching stress (N/mm2) qcup (N/mm2) Notes ###


0.42 < 1.29 safe
###
Calculation of Rft. : Asmin ###
750 mm2 ###
###
Long Direction : Mu /m As /m no. f total no. ###
82 577 7 12 /m 17 ###
###
Short Direction : Mu /m As /m no. f total no.
126 884 8 12 /m 21

Results:

2.60 m 150 kPa


29 kPa 146 kPa

0.50

0.50
F1
/m
2.40 m

3.00 m
0.30

12
8 f

7 f 12 /m

-33 kPa 84 kPa

Page 44 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.5

(0.00 kPa) 3.20 m

Page 45 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.4

* Design of Fence Footing

* Project :

Concrete fcu = 25 MPa

Steel fy = 400 MPa

Bearing capacity qall = 100 KPa

Column working load Moment Column dim. Ecc. Extension


foot Nw (kN) Mw (kN.m) b (mm) t (mm) e (mm) of P.C (mm)
F1 63 5 250 250 525 200

Dims. of P.C : B (mm) L (mm) Lno tens (mm) t (mm)


1,150 1,150 2013
Choose dim of P.C 1,500 1,300 200

Dims. of R.C : B (mm) L (mm) t (mm)


1,100 1,100 400

Max. Stress (kPa) = 109 Safe secondary case


Min. Stress (kPa) = -24 Tension on soil on 0.18 L
Max. Stress (kPa) = 110 Safe secondary case
After Redistribution
Min. Stress (kPa) = 0

Shear stress (N/mm2) qcu (N/mm2) Notes


0.17 < 0.65 safe

Punching stress (N/mm2) qcup (N/mm2) Notes


0.36 < 1.29 safe

Calculation of Rft. : Asmin


600 mm2

Long Direction : Mu /m As /m no. f total no.


48 424 6 12 /m 7

Short Direction : Mu /m As /m no. f total no.


9 83 6 12 /m 7

Page 46 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.4

* Design of Fence Footing

Results:
Nw = 63 kN

Mw = 5 kN.m

0.40 m

0.20 m

0
kPa

110
kPa

1.10 m

0.40
/m
1.10 m

1.50 m
0.25

12

0.25
6 f

6 f 12 /m

1.30 m

F1

Page 47 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.3

* Design of Combined Footing

* Project :

Concrete fcu = 25 MPa

Steel fy = 400 MPa

Bearing capacity qall = 150 KPa

F9
Column working load Column dim. (mm) Extension
Col Nw (kN) trans. long. of P.C (mm)
Smaller 600 250 500 300
Larger 840 250 700 300

Distance from c.g to c.g: 2 m

Resultant of 2 loads is at: 1.17 m from smaller column

Dims. of P.C : B (mm) L (mm) Soil stress (kPa)


minimum 3,100 3,450
chosen 2,400 5,000 137 safe

Dims. of R.C : B (mm) L (mm) t (mm)


1,800 4,400 600

LR
C

Distance c.g to
c.g
BRC Dtransverse Dtransverse BPC

Dlong Dlong

LP
C

Punching stress (N/mm ) 2 qpu (N/mm2) qcup (N/mm2) Notes


Samller column 0.54 < 1.29 safe

Page 48 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.3

* Design of Combined Footing


Larger column 0.68 < 1.11 safe

Longitudinal direction:

Shear stress (N/mm2) qu (N/mm2) qcu (N/mm2) Notes


max. shear stress 0.35 < 0.65 safe

Top Rft. : Mu /m As /m no. f total no.


NA 900 8 12 /m 15

Bottom Rft. : Mu /m As /m no. f total no.


141 900 5 16 /m 10

Transverse direction:

Shear stress (N/mm2) qu (N/mm2) qcu (N/mm2) Notes


max. shear stress 0.34 < 0.65 safe

Top Rft. : no. f total no.


5 12 /m 23

Bottom Rft. : Mu /m As /m no. f total no.


106 900 8 12 /m 36

Results:

4.40 m

8 f 12 /m

0.60
/m

/m
1.80 m

2.40 m
12

12

1.17 m
f

f
5

5 f 16 /m

Page 49 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.3

* Design of Combined Footing

5.00 m

Page 50 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.3

* Design of Strap Beam Footing

* Project :
cmax/d
Concrete fcu = 25 MPa ###

Steel fy = 400 MPa ###

Bearing capacity qall = 150 KPa ###

###

Column working load Column dim. (mm) Extension Thickness


Col Nw (kN) trans. long. of P.C (mm) of P.C (mm)
Exter. 685 300 500 0 300
Inter. 1270 300 900 300 300
Rex
Distance from c.g to c.g: 4.9 m ###

Take eccentricity = 0.85 m ###

Dims. of P.C : B (mm) L (mm) Soil Stress (KPa)


External footing 2,700 2,200 143
Internal footing 2,550 3,150 144
###
Dims. of R.C : B (mm) L (mm) t (mm)
External footing 2,100 1,900 500
Internal footing 1,950 2,550 500

Page 51 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.3

* Design of Strap Beam Footing

Longitudinal direction: shr1


shr2
Dim. of strap beam : b (mm) t (mm) shr3
400 900 shstres1
as/s
Rft. of strap beam : Mu (kN.m) no. f as/s min
Top Rft. 616 7 22 ###
Bottom Rft. 238 4 18 ###
shr1 out
Shear stress (N/mm2) qu (N/mm2) qcu (N/mm2) Notes
max. shear stress inside footing 0.77 > 0.65 cracked

Shear stress (N/mm2) qu (N/mm2) qmax (N/mm2) Notes


max. shear stress on beam 2.36 < 2.86 safe
c1
Stirrups /m : no. f ex
7 10 4 branches in

Transverse direction:
###
Bottom Rft. : Mu /m As /m no. f total no.
External footing 119 840 8 12 /m 17
Internal footing 108 758 7 12 /m 19

Page 52 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.3

* Design of Pile Cap

* Project :

Concrete fcu = 30 MPa


Steel fy = 400 MPa

Pile Diameter = 0.50 m

Pile Capacity = 500 kN

Column working column dim. extension


cap load Nw (kN) b (mm) t (mm) of P.C (mm)
PC1 1500 300 700 100

Estimated no. of piles = 4 piles

Pile spacing is taken from 1.25 to 3.0 m = 1.50 m in long direction

Pile spacing is taken from 1.25 to 3.0 m = 1.50 m in short direction

Short dir. Long dir.


Choosen arrangement of piles = 2 x 2 Piles used = 4

Dims. of P.C cap: B (mm) L (mm) t (mm)


3,200 3,200 200

Dims. of R.C cap: B (mm) L (mm) t (mm)


3,000 3,000 900

Actual pile load (kN) Notes


437 safe

Shear stress (N/mm2) qcu (N/mm2) Notes


0.53 < 0.72 safe

Punching stress (N/mm2) qcup (N/mm2) Notes


0.51 < 1.31 safe

Calculation of Rft. : Asmin


1350 mm2

Long Direction : Mu /m As /m no. f total


175 1350 7 16 /m 22

Short Direction : Mu /m As /m no. f total


262 1350 7 16 /m 22
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 12.3

* Design of Pile Cap under Moment

* Project :

Concrete fcu = 30 MPa ###

Steel fy = 400 MPa ###

Pile Diameter = 0.50 m ###

Pile Capacity = 600 kN

Column working column dim. Working moment extension


cap load Nw (kN) b (mm) t (mm) Mw (kN.m) of P.C (mm)
PC1 2000 800 800 1800 100

Spacing of piles in direction of moment = 1.50 m no. of Piles 4

Spacing of piles in transverse direction = 1.50 m no. of Piles 3


Total no. of piles = 12 ###
###
Dims. of P.C cap: B (mm) L (mm) t (mm) ###
4,700 6,200 100 ###
###
Dims. of R.C cap: B (mm) L (mm) t (mm) ###
4,500 6,000 1200 ###

Max. Load (kN) Min. Load (kN)


1st piles row to center, y1 0.75 m 320 160 ###
2nd piles row to center, y2 2.25 m 480 0 ###
3rd piles row to center, y3 0 m 240 240 ###
4th piles row to center, y4 0 m 240 240 ###
All Safe Tension Appears ###

Shear stress (N/mm2) qcu (N/mm2) Notes


0.71 < 0.72 safe
###
Punching stress (N/mm ) 2 qcup (N/mm2) Notes
0.34 < 1.41 safe ###

Calculation of Rft. : Asmin


1800 mm2 ###
###
Long Direction : Mu /m As /m no. f total ###
999 2676 8 22 /m 37
###
Short Direction : Mu /m As /m no. f total
295 1800 9 16 /m 55
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.5

* Design of Cantilever Retaining Wall

* Project :

Concrete fcu = 25 MPa

Steel fy = 400 MPa 0.25


2.0 kN/m`
Bearing capacity qall = 150 kPa

Retained Soil

Soil above footing: Taken g = 18.0 kN/m3

3.00

2.80
ko = 0.50 C = 0.0 N/mm2

Soil perssure on toe side: f = 30 o


0.50 1.750 0.000
at rest case (conservative) ka = 0.33

0.50 R.C
0.00 P.C

0.00 2.00 0.00

2.00
Foundation soil C= 0.0 N/mm2 f = 30 o

Coefficient of friction (m) = 0.38


Sliding check:
Stabilizing force from: kN Horizontal force from: kN
Weight of wall 18.75 Active earth pressure on wall 23.52
Weight of footing (RC+PC) 25.00 Active earth pressure on footing 9.15
Weight of soil on active side 0.00 Active surcharge pressure 2.20
Weight of soil on passive side 15.75 Passive earth pressure on wall -1.13
Surcharge 0.00 Passive side pressure on footing -3.38
Total weights: S= 59.50 Driving force: S = 30.37

Factor of safety against sliding = 0.75 < 1.5 Not satisfactory

Over-turning check:
Stabilizing moment from: kN.m Over-turning moment from: kN.m
Weight of concrete 60.16 Active earth pressure 35.94
Weight and pressure of soil 15.28 Active surcharge pressure 3.63
S= 75.44 S = 39.57

Page 57 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.5

* Design of Cantilever Retaining Wall

Factor of safety for overturning = 1.91 > 1.5 Satisfactory

Bearing capacity check:


Moment on footing center = 23.63 kN.m
Total weight on footing = 59.50 kN Eccentricity = 0.40 m
Max. stress on soil = 65.2 kPa Safe stress
Min. stress on soil = -5.7 kPa Tension on soil
Max. stress on soil = 65.2 kPa Safe stress
After Redistribution
Min. stress on soil = 0.0 kPa

Calculation of Rft. :
Mu (kN.m) cover (mm) d (mm) As (mm2) As min
For Wall 40.1 50 200 606 375 6 f 12 /m
For Base 55.6 60 440 382 750 7 f 12 /m

Shear on base: qu = 0.08 MPa < qcu = 0.65 MPa Safe

Page 58 of 74
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 2.2

* Design of Simple Deep Beams

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Width (b) = 0.30 m


Span (L) = 4.00 m
Height (H) = 3.40 m
L/H = 1.18 Deep Beam
Empirical analysis accepted

yct = 2.87 m
Ww = 200.0 kN/m
Mw = 400.0 kN.m
Qw = 280.0 kN

As calc = 601 mm2


As min = 1485 mm2
As used = 1485 mm2
8 f 16 Bottom RFT.

Top loaded deep beam

Stirrups = Use min. web RFT


5 f 10 /m 2 Legs Vertical
Safe
5 f 10 /m 2 Legs Horizontal

5 f 10 /m
3.40

5 f 10 /m

8 f 16

4.00
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 2.2

* Design of Continuous Deep Beams

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Width (b) = 0.30 m


Span (L) = 4.00 m
Height (H) = 3.40 m
L/H = 1.18 Deep Beam
Empirical analysis accepted

yct +ve = 1.72 m


yct -ve = 1.48 m
Ww = 80.0 kN/m
Mw +ve = 450.0 kN.m
Mw -ve = 400.0 kN.m
Qw = 250.0 kN

As calc = 1128 mm2 As calc = 1166 mm2


As min = 1485 mm2 As min = 1515 mm2
As used = 1485 mm2 As used = 1515 mm2
5 f 20 5 f 20
Bottom RFT. Top RFT.

Top loaded deep beam

Stirrups = Use min. web RFT


5 f 10 /m 2 Legs Vertical
Safe
5 f 10 /m 2 Legs Horizontal

5 f 20
3.40

5 f 20

4.00 4.00
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.3

* Design of Corbel

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa
Stirrups fy = 240 MPa

Concrete Dims: L
Thickness at column = 700 mm
Cover = 50 mm
d= 650 mm
Breadth = 300 mm
Cantilever length L = 800 mm
Lateral load height D = 100 mm
Distance of VL load a = 600 mm
Connection between corbel and column:
Monolitic cast concrete
m= 1.2

Loads:
Qu = 200 kN
Nu = 40 kN

As = 702 mm2
Asmin = 366 mm2
Used As = 702 mm2 4 f 16 Main RFT

Ah = 293 mm2 3 f 8 Horizontal stirrups


2 Branches Spacing = 144 mm
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.6

* Deflection of Cantilever

* Project :

Concrete fcu = 30 MPa

Modular ratio (n) = 15

PDL+ PLL
WDL+ WLL

Span

Breadth Depth Thickness Span


Sec. Properties of sec: b (mm) d (mm) t (mm) L (m)
1 1000 220 250 2.5

Top Rft.: no. f area


5 16 1005 mm2

Bottom Rft.: no. f area


5 16 1005 mm2

Working loads: PDL (kN) PLL (kN) WDL (kN/m) WLL (kN/m)
self weights 2.50 0.0 self weights 6.25 3.0
finish+walls 0.00 finish+walls 3.25
Ratio of sustained live load = 0.25
Ec = 24,100 MPa
n= 15.00
Z= 62.1 mm
Ig = 1.30E+09 mm4
Icr = 4.70E+08 mm4
Ieff = 8.29E+08 mm4 due to all loads

Initial deflection = 2.8 mm

Long term deflection = 6.6 mm after 5 years Unsafe, camber may be used
Allowable value = 5.6 mm L / 450

Live load deflection = 0.7 mm Safe


Allowable value = 6.9 mm L / 360

Adding non structural elements after: 1 months of construction


Incremental deflection = 4.4 mm Safe
Allowable value = 5.2 mm L / 480 Brittle cladding
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.6

* Deflection of Simple R-section

* Project :

Concrete fcu = 30 MPa

Modular ratio (n) = 15

PDL+ PLL
WDL+ WLL
###

###
Span/2 Span/2
###
###
Breadth Depth Thickness Span Ig
Sec. Properties of sec: b (mm) d (mm) t (mm) L (m) ###
1 300 650 700 7
z2
z
Top Rft.: no. f area ###
4 16 804 mm2 z
Inv
Bottom Rft.: no. f area
6 22 2280 mm2 Ie tot
Ie d
Working loads: PDL (kN) PLL (kN) WDL (kN/m) WLL (kN/m)
self weights 40.0 50.0 self weights 15.0 10.0 m=
finish+walls 30.0 finish+walls 10.0 a=
Ratio of sustained live load = 0.25 a2=
Ec = 24,100 MPa egzai =
n= 15.00
Z= 266.7 mm
Ig = 8.58E+09 mm4
Icr = 7.45E+09 mm4
Ieff = 7.46E+09 mm4 due to all loads
Ddi
Initial deflection = 10.8 mm ###

Long term deflection = 24.3 mm after 5 years Safe


Allowable value = 28.0 mm L / 250 ###

Live load deflection = 3.7 mm Safe


Allowable value = 19.4 mm L / 360
###
Adding non structural elements after: 6 months of construction ###
Incremental deflection = 15.9 mm Unsafe Flexible
Allowable value = 14.6 mm L / 480 Brittle cladding Brittle c
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.6

* Deflection of Simple T-section

* Project :

Concrete fcu = 40 MPa B

Modular ratio (n) = 15 C As top ts

Z
PDL+ PLL
WDL+ WLL b
h###

###
Span/2 Span/2
C As bottom

###
Breadth Depth Thickness Span
Sec. Properties of sec: B (mm) b (mm) ts (cm) h (mm) t (mm) L (m)
1 1500 300 140 760 900 10
###
Top Rft.: Cov. (mm) no. f area ###
40 6 18 1501 mm2 ###
###
Bottom Rft.: Cov. (mm) no. f area m=
60 12 22 4502 mm2 a=
a2=
Working loads: PDL (kN) PLL (kN) WDL (kN/m) WLL (kN/m) ###
self weights self weights 20.0 8.0 Ie tot
finish+walls finish+walls 10.0 Ie d
Ratio of sustained live load = 0.3
Ec = 27,828 MPa
n= 15.00
Z= 237.3 mm
Ig = 3.35E+10 mm4
Icr = 3.17E+10 mm4
Ieff = 3.18E+10 mm4 due to all loads
Ddi
Initial deflection = 5.6 mm ###

Long term deflection = 13.7 mm after 5 years Safe


Allowable value = 40.0 mm L / 250 ###

Live load deflection = 1.2 mm Safe


Allowable value = 27.8 mm L / 360
###
Adding non structural elements after: 6 months of construction ###
Incremental deflection = 7.7 mm Safe Flexible c
Allowable value = 20.8 mm L / 480 Brittle cladding Brittle cla
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.4

* Design of Water Section

* Project :

Concrete fcu = 30 MPa


Concrete fctr = 3.3 MPa
Steel fy = 400 MPa

Working Moment Normal Force


Sec. Mw (kN.m) Nw (kN)
1 25 20 Tension

Dims of sec: b (mm) t (mm) fct (N/mm2)


1000 250 2.5

Properties of sec: tv (mm) fct all (N/mm2)


258 2.7 Safe

Design of sec: d (mm) C1 J Ascalc Asmin As (mm2)


200 5.83 0.826 620 422 620

use: 9 f 10 bcr = 0.92


Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.7

* Calculation of Crack Width

* Project :

Concrete fcu = 30 MPa

Steel fy = 400 MPa

Comp. side
Thickness

Z
N.A

Tens. side
Breadth

INPUT DATA:
Breadth (B) = 1000 mm
Thickness (t) = 300 mm
Tension RFT. = 10 T 16 = 2011 mm2
Tension RFT. Cover = 50 mm, "to c.g of RFT bars"
Compression RFT. = 10 T 16 = 2011 mm2
Comp. RFT. Cover = 50 mm, "to c.g of RFT bars"
Bars type: Ribbed bars K1 = 0.8
b1 = 0.8
Duration of load: Permanent loads b2 = 0.5
Straining action: Bending moment K2 = 0.5
Mservice = 90 kN.m
Nservice = 30 kN Tension
Exposure category: Second, unprotected tension surfaces
Max. crack width (wkmax) = 0.20 mm

OUTPUT DATA:
Modular ratio (n) = 8.3
Neutral Axis depth (Z) = 70 mm
Tens. Steel stress (fs) = 207 MPa
Cracking stress (fsr) = 110 MPa
Srm = 110.9 mm
esm = 918.5 me
Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 11.7

* Calculation of Crack Width

Crack width (wk) = 0.17 mm Acceptable


Reinforced Concrete design according to ECP 203-2018 By: Dr. Mahmoud El-Kateb
Version 1.0

* Development & Splice of Reinforcement

* Project :

Concrete fcu = 25 MPa

fbu = 1.22 MPa

Steel fy = 400 MPa

Development of bars in tension:


Bar end condition: ‫ مستقيم‬Straight a= 1.00
Bar surface condition: ‫ ذو نتوءات‬Deformed b= 0.75 ‫ جنش بأي شكل‬Hook
Bar position: Horizontal with more than 300mm of concrete underneath
h= 1.30 ‫ ذو نتوءات‬Deform

Development Length, Ld = 70 f , for f 16 = 1120 mm

Lap splice in tension:


As,provided / As,required = <2
Percent of spliced bars = Max. 50%
Splice Length, Ls = 91 f , for f 16 = 1456 mm

Development of bars in compression:


Bar surface condition: ‫ ذو نتوءات‬Deformed b= 0.45
Bar position: Horizontal with more than 300mm of concrete underneath
h= 1.30

Development Length, Ld = 42 f , for f 16 = 672 mm


Splice Length, Ls = 42 f , for f 16 = 672 mm