PASSENGER ELEVATORS
General and MRL(Machine-Room-Less) Type

Development Innovation Technology Quality

HEAD OFFICE & FACTORY


San 136-1, Ami- ri, Bubal- eup, Ichon-shi, Kyonggi-do 467-734, Korea
Tel : 82-31-644-5160 Fax: 82-2-745-4227
Homesite : http://www.hyundaielevator.co.kr
E-mail : e-biz@hyundaielevator.co.kr
SEOUL OFFICE(INT’L SALES DIV.)
1-83 Dongsoong- dong, Jongro-ku, Seoul 110-510, Korea
Tel: 82-2-3670-0659 Fax : 82-2-3672-8763~4

� HYUNDAI ELEVATOR INTERNATIONAL SALES & SERVICE NETWORK


U.S.A. INDIA SAUDI ARABIA
Hyundai Elevator Co., Ltd. Kinetic Escalator & Elevator Ltd. M/S. Electromechanical & Technical Associates-Eta,
L.A Office D1 Block, Plot No.18/1, Chinchwad, Al-Marjan Tower, 11th Floor,
879W. 190th St. Suite 580 Pune 411 019, India Hail Street & Waly ahd Street Intersection,
Gardena, CA 90248 U.S.A. Tel: 91-20-2747-6624 Fax: 91-20-2747-7056 Ruwais District, P. O. Box 6591,
Tel: 1-310-538-4770 Fax: 1-310-538-4745 Jeddah-21452, Saudi Arabia
PAKISTAN Tel: 96-62-652-9000 Fax: 96-62-652-9090
JAPAN Islamabad Industrial & Trading Corp.
Hyundai Elevator Co., Ltd. 304 Amber Estate Shahra-e-faisal, CHINA
11F, Yamato Life Bldg. 1-1-7, Uchisaiwai-cho, Karachi - 75350, Pakistan �China Operation Head Office
Chiyoda-ku, Tokyo, Tel: 92-21-452-3237~8 Fax: 92-21-454-7405 Hyundai Elevator Co., Ltd.
100-0011, Japan 27F, Jinxuan Bldg., No.238 Nandan RD.(East),
Tel: 81-3-3519-6125 Fax: 81-3-3519-6126 EGYPT Shanghai, China, 200030
International Eng. & Trade Tel: 86-21-6427-6616 Fax: 86-21-6427-4428
PHILIPPINES 10 El Hakam St., Helmeyt Ei Zayton Cairo, Egypt
Hyco Industrial Sales Corp. Tel: 20-2-241-8542 Fax: 20-2-639-2672 �Beijing Office
#81 Kapiligan Cor. Bayani St., Hyundai Elevator Co., Ltd.
Dona lmelda, Quezon City, Philippines U.A.E Beijing Office
Tel: 63-2-716-0905/0923 Fax: 63-2-714-8896 Arabian Elevators & Engineering Co.,Ltd. Golden Land Bldg. Rm506 No.32 Liang Ma Bridge Road,
P. O. Box : 26031, Sharjah, U.A.E Chaoyang District Beijing, China
INDONESIA Tel: 971-6-561-4533 Fax: 971-6-561-5532 Tel: 86-10-6464-3483/3485/3509 Fax: 86-10-6464-3394
PT. Superhelindo Jaya
JL. KH. Moch. Mansyur No 19B, KUWAIT � Shenyang Hyundai Elevator Co., Ltd.
Jakarta 10140, Indonesia Deal General Trading & Contracting Co. No. 43 Shenda Road, Yuhong District,
Tel: 62-21-631-8444 Fax: 62-21-632-6288 P. O. Box 27956 Safat, 13140 Kuwait Shenyang, China, Post Code : 110141
Tel: 965-245-7925 Fax: 965-242-3510 Tel: 86-24-2530-0108 Fax: 86-24-2583-2321
THAILAND
Loxley Public Co., Ltd. JORDAN � Shanghai Hyundai Elevator Manufacturing Co., Ltd.
Construction Materials Department Bseiso Engineering Materials Corp. �Head Office(Factory)
102 Na Ranong Rd, Klongtoey, P. O. Box 830681 Amman 11183, Jordan Xiaozheng Qingpu Xian, Shanghai, China 201716
Bangkok 10110, Thailand Tel: 962-656-99012 Fax: 962-656-99014 Tel: 86-21-5981-3981/3990/3961/3971 Fax: 86-21-5981-3982
Tel: 66-2-348-8000 Fax: 66-2-240-3127/3128
IRAN �Shanghai Office
BANGLADESH Mehfakhr Flat No. 84 8th Flr. No. 23 Corner of 13th St. 27F, Jinxuan Bldg., No.238 Nandan Rd(East),
Regional Traders Ltd. Asadabadi Ave. Tehran Iran Shanghai, China, 200030
Karim chamber(3rd Floor)99, Tel: 98-21-872-6082 Fax: 98-21-855-3741 Tel: 86-21-6427-6616 Fax: 86-21-6427-4428
Motijheel Commercial Area
Dhaka-1000, Bangladesh
Tel: 880-2-956-3122 Fax: 880-2-956-7377

PASSENGER ELEVATORS - We reserve the right to change designs and specifications for the product development without prior notice. Printed in Korea
CATALOG CODE : C-VPE-E1108 / 2005. 5 / Revision 11
General Type MRL(Machine-Room-Less) Type
The most economical option for residential or midrise commercial building. The highest An innovative new elevator which does not require a separate machine room. Applicable to
efficiency is achieved through the optimal combination of voltage and frequency, the latest and residential or mid-to high rise commercial buildings.
most advanced technology VVVF, of electric power supply to the induction motor.

Main Specifications Main Specifications


Control
�Innovative energy-savings & reduced electric power Control
�More flexible architectural design
VVVF(Inverter)Microprocessor Control requirements VVVF(Inverter)Microprocessor Control �Benefit in north side slanting line limitation and sunshine
System System
Speed 60, 90, 105, 120m/min �Extremely smooth riding comfort & accurate landing Speed 45~120m/min right regulation
Capacity 6~24 persons/450~1600kg �Minimized motor size & minimized noise / vibration Capacity 8~17 persons/550~1150kg �Minimized power equipment and power consumption
1Car/2Cars : Selective Collective �Enhanced system reliability �Reduction of building costs
1Car : Selective Collective (1C 2BC)
Operation (1C/2C 2BC) �Minimum space requirements Operation �Smoother and superior riding comfort
2Cars : Group Operation
3~8Cars : Group Operation �Environment-friendly products
�Applicable up to 32 floors (96m)
www.hyundaielevator.co.kr

Car Design

SE34 SE36
�Ceiling �Ceiling
CD516B (Indirect lighting)/ CD451B/ Acryl / Acryl Lens /
Convective Air Sterilization System Painted Steel (P022)
�W all �W all
Hairline Etched Stainless Steel (SE739), Hairline Etched Stainless Steel (SE1169)
Galaxy Art(AF-G-246)
�Car Doors
�Car Doors Hairline Etched Stainless Steel (SE1169)
Galaxy Art(AF-G-246)
�Operating Panel
�Operating Panel OPP-N240A
OPP-N240A,
�Indicator
OPP-N240W (For the disabled)
Deluxe Type(PI-D600)
�Indicator �Handrail
Deluxe Type(PI-D600)
Stainless Steel 1Pipe(1A)
�Handrail �Entrance Column
Stainless Steel 1Pipe(1A)
Hairline-Finished Stainless Steel
�Entrance Column �Flooring
Hairline-Finished Stainless Steel
Polyvinyl Tile
�Flooring (TN2401C, TN2406C)
Polyvinyl Tile
(TN2211C, TN2401C, TN2412C)

SE35 SE37
�Ceiling �Ceiling
CD249C/ Acryl / Acryl Lens / CD291C/ Lumasite /
Painted Steel (P021) Painted Steel (P021)
�W all �W all
Hairline Etched Stainless Steel (SE1168) Hairline Etched Stainless Steel (SE1177)
�Car Doors �Car Doors
Hairline Etched Stainless Steel (SE1168) Hairline Etched Stainless Steel (SE1177)
�Operating Panel �Operating Panel
OPP-N240A, OPP-N240A,
OPP-N240W (For the disabled) OPP-N240W (For the disabled)
�Indicator �Indicator
Deluxe Type(PI-D600) Deluxe Type(PI-D110)
�Handrail �Handrail
Stainless Steel 1Pipe(1A) Stainless Steel 1Pipe(1R)
�Entrance Column �Entrance Column
Hairline-Finished Stainless Steel Hairline-Finished Stainless Steel
�Flooring �Flooring
Polyvinyl Tile (DTF5311, DTF5906) Polyvinyl Tile ( TN2411C, TN2412C)

Note : Finished product may vary slightly from these prints. Note : Finished product may vary slightly from these prints.

4 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 5


www.hyundaielevator.co.kr

Car Design

SB20 SB23
�Ceiling �Ceiling
CD451B / Acryl / Acryl Lens / CD513E(Indirect lighting)/
Painted Steel (P021) Painted Steel / Down Light
�W all �W all
Polyvinyl Sheet (ME04 / ME5011) / Hairline Etched Stainless Steel
Aluminium Di-Casting Trim (SE739/SE798/SE799)
�Car Doors �Car Doors
Polyvinyl Sheet (ME04) Hairline Etched Stainless Steel (SE739)
�Operating Panel �Operating Panel
OPP-D240A, OPP-N240,
OPP-N240W (For the disabled) OPP-N240W (For the disabled)
�Handrail �Indicator
Stainless Steel 1Pipe (1A) Deluxe Type(PI-D600)
�Entrance Column �Handrail
Hairline-Finished Stainless Steel Stainless Steel 1Pipe (1R)
�Flooring �Entrance Column
Polyvinyl Tile (86516) Hairline-Finished Stainless Steel
�Flooring
Polyvinyl Tile (RN33019)

SB21 SB24
�Ceiling �Ceiling
CD469B / Acryl / Painted Steel (P017) CD439B / Acryl / Painted Steel (P016)
�W all �W all
Hairline Etched Stainless Steel (SE439) Polyvinyl Sheet (FW234) /
Hairline Etched Stainless Steel (SE1167)
�Car Doors
Hairline Etched Stainless Steel (SE439) �Car Doors
Hairline Etched Stainless Steel (SE1167)
�Operating Panel
OPP-N240, �Operating Panel
OPP-N240W (For the disabled) OPP-D240A,
OPP-N240W (For the disabled)
�Indicator
Deluxe Type(PI-D600) �Handrail
Stainless Steel 1Pipe(1A)
�Handrail
Stainless Steel 1Pipe(1R) �Entrance Column
Hairline-Finished Stainless Steel
�Entrance Column
Hairline-Finished Stainless Steel �Flooring
Polyvinyl Tile (LM3602)
�Flooring
Polyvinyl Tile
(TN2202C, TN2203C, TN2211C)

Note : Finished product may vary slightly from these prints. Note : Finished product may vary slightly from these prints.

6 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 7


www.hyundaielevator.co.kr

Entrance Design

JP050PP JP200ESS-01
�Landing Doors �Landing Doors
Painted Steel Sheet (P003) Etched Stainless Steel (EE008)
�Jambs �Jambs
Narrow Jambs in Painted Steel Sheet Full-Wall Jambs in Hairlined Stainless Steel
�Hall Button with Position Indicator �Transom Panel
To be Selected Separately, HIP-D442 (Shown) Hairline-Finished Stainless Steel
�Position Indicator & Hall Button
To be Selected Separately, PI-D110, HPB-442 (shown)

JP100SS JP200ESS-02
�Landing Doors �Landing Doors
Hairline-Finished Stainless Steel Etched Stainless Steel (EE007)
�Jambs �Jambs
Full-Wall Jambs in Hairlined Stainless Steel Full-Wall Jambs in Hairlined Stainless Steel
�Hall Button with Position Indicator �Transom Panel
To be Selected Separately, HIP-D640 (Shown) Hairline-Finished Stainless Steel
�Position Indicator & Hall Button
To be Selected Separately, PI-D600, HPB-240 (Shown)

Material Selection Guide


�Landing Doors
�Jambs
�Transom Panel

JP200
P : Painted Steel Sheet
L : Plastic-Laminated Steel Sheet (*)
S : Hairline-Finished Stainless Steel (*)
E : (Hairline) Etched Stainless Steel (*) Note *: optional

8 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 9


www.hyundaielevator.co.kr

Signal Fixtures

CAR OPERATING PANELS POSITION INDICATORS

AUTO
AUTO FULL HYUNDAI
FULL

PI-S100 (LED Segment Type) PI-D600 (Dot Matrix Type) PI-D200 (Dot Matrix Type)
(LED Segment Type : PI-S200)

PASSENGER
28 PERSONS
1800 kg
AUTO
FULL

AUTO
AUTO FULL HYUNDAI
EMERGENCY FULL
CALL

PI-D300 (Dot Matrix Type)


*PI-D100 (Dot Matrix Type) *PI-D110 (Dot Matrix Type) (LED Segment Type : PI-S300)
Note *: optional

HALL BUTTONS

HPB-230 HPB-240 HPB-530 HPB-442 HPB-423 HPB-640


(Boxless Type) (Boxless Type) (Boxless Type)

OPP-D230A OPP-D240A OPP-N240 OPP-N230A OPP-N240A

TYPE OF BUTTONS

30 Type 40 Type HIP-D230 HIP-D240 HIP-D530 HIP-D442 HIP-D423 HIP-D640


(Boxless Type) (Boxless Type) (Boxless Type)
Notes : Above buttons are available for OPP-D230A, OPP-N230A, OPP-N240, Notes : 1. Finished product may vary slightly from these prints.
HIP-D230, HIP-D423, HIP-D530, HPB-230, HPB-423, and HPB-530. 2. The price will vary depending on the customer’s specification.

10 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 11


www.hyundaielevator.co.kr

Material Patterns
ETCHING POLYVINYL TILE

RE12014 RN33013 RN33016


SE403 SE406 SE409 SE424

RN33019 RS10017 RS15001


SE439 SE785 SE859 SE928

SE1168 SE1169 SE1171 SE1172 RT22011 TN2202C TN2227C

Note : � : � Emboss � : � Intaglio

PAINT COLOR
TN2211C TN2601C TN2604C
Note : Finished product may vary slightly from these prints.

P003 (2.3Y 8.5/2.5) P006 (2.5GY 7/12) P008 (8.5YR 7.1/12.5) P009 (4.5B 7.8/2.0)
HANDRAIL W ood designs are available.

1R (1 Pipe Stainless Polished) *2R (2 Pipe Stainless Polished)


P011 (4.1R 4.3/12.8) P012 (2.3PB 4.5/9.6) P016 (9.9YR 5.0/3.1) P017 (6.7Y 8.7/2.0)

1A (Aluminium Di-Casting /1 Pipe Stainless Polished) *FL (Flat Bar Stainless)


P019 (5.1Y 7.6/1.1) P020 (Metallic Gold) P021 (Metallic Silver) P022 (Black)
Notes : *: optional

Note : Finished product may vary slightly from these prints.

12 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 13


www.hyundaielevator.co.kr

Material Patterns
ENTRANCE(ETCHING) CEILING

CD291C (P017) CD200A (P022)

CD469B (P019) CD451B (P017)


EE001 EE002 EE003 EE005

CD249C (P019) CD249B (P009)

EE006 EE007 EE008 EE009 CD519D CD516C


Aluminium Silver Stainless Steel, Polyvinyl Sheet
Indirect Lighting Indirect Lighting
Convective Air Sterilization System Convective Air Sterilization System

Note : � : � Emboss � : � Intaglio


Note : Finished product may vary slightly from these prints.

14 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 15


www.hyundaielevator.co.kr

Layout Plan
Machine-Room-Less(MRL)Type 60 ~ 105m/min Machine-Room-Less(MRL)Type 60 ~ 120m/min

SPACE SAVERⅢ-T SPACE SAVERⅡ-T


(Permanent Magnet Synchronous Motor) (Permanent Magnet Synchronous Motor)
Plan of Hoistway Section of Hoistway
Lighting
Plan of Hoistway Section of Hoistway
X Hook(By others)

A Min.1100

Traction 2-Hook(By others)


Min.1100 X
Machine
Vent Fan A
(By others) Gallery window
CA

Min.2000
Maintenance Door (By others)

Overhead (OH)
(By others) Control Traction
900(W)×1900(H) Panel Machine
Floor with CA
CB
Y

Entrance Height (EH)


Control Panel

Overhead (OH)
CB

Y
B

The Floor Height at


Control
Control

Entrance Height (EH)


Control

Top Floor(FH)
Control
Control

Min.2600
Panel
Panel
Panel
Panel
Panel
OP
OP

Total Height (TH)


Power Distribution
Board(By others)

Total Height (TH)


Control
Control
Floor without (Unit : mm)
Control
Control
Control
Panel
Panel
Panel Control Panel

Travel (TR)
Panel
Panel
Speed Overhead Pit
530 OP (m/min) (OH) (PP)
Power Distribution
60 FH+2000 1500

Travel (TR)
Board(By others)
90 FH+2000 1800
(Unit : mm) 105 FH+2000 2100
Receptacle
Notes : 1, Above dimensions are applied in (By others)
Speed Overhead Pit case car height is 2500mm. 120 FH+2000 2100
(m/min) (OH) (PP) (Car internal height is 2300mm.)
60 3800 1500 2, Above shown is minimum size.

Pit Depth (PP)


Ladder Notes : 1, Above dimensions are applied in
(By others) case car height is 2500mm.
90 3900 1800
(Car internal height is 2300mm.)

Pit Depth (PP)


Waterproof Finish
105 4000 2100 (By others) 2, Minimum overhead dimensions is FH+1500mm.
(FH: the floor height at top floor.) Waterproof Finish
3, Above dimensions are based on Korean Code. (By others)

Standard Dimensions (Unit : mm)


When dimensions are required to
meet the local code, cousult Hyundai.
Receptacle
Ladder (By others)
(By others)
Clear Car Hoistway
Speed Capacity Motor
Opening Internal External 1 Car Depth
(m/min) (kW)
Persons kg OP CA × CB A×B X Y
60 3.4
90 8 550 800 1400 × 1030 1460 × 1185 2100 1650 5.1
105
60
5.9
3.7
Standard Dimensions (Unit : mm)
90 9 600 800 1400 × 1100 1460 × 1255 2100 1700 5.6 Car Hoistway Car Hoistway
Clear Clear
105 6.5 Speed Capacity Motor Speed Capacity Motor
Opening Internal External 1 Car Depth Opening Internal External 1 Car Depth
60 4.3 (m/min) (kW) (m/min) (kW)
90 10 700 800 1400 × 1250 1460 × 1405 2100 1750 6.5 Persons kg OP CA × CB A×B X Y Persons kg OP CA × CB A×B X Y
105 7.5 60 3.4 60 5.6
60 4.6 90 8 550 800 1400 × 1030 1460 × 1185 2100 1650 5.1 90 8.3
13 900 900 1600 × 1350 1660 × 1505 2300 1800
90 11 750 800 1400 × 1350 1460 × 1505 2100 1800 6.9 105 5.9 105 9.7
105 8.1 60 3.7 120 11.1
60 5.6 90 9 600 800 1400 × 1100 1460 × 1255 2100 1700 5.6 60 6.2
90 13 900 900 1600 × 1350 1660 × 1505 2300 1800 8.3 105 6.5 90 9.2
15 1000 900 1600 × 1500 1660 × 1655 2300 1900
105 9.7 60 4.3 105 10.8
60 6.2 90 10 700 800 1400 × 1250 1460 × 1405 2100 1750 6.5 120 12.3
90 15 1000 900 1600 × 1500 1660 × 1655 2300 1900 9.2 105 7.5 60 7.1
105 10.8 60 4.6 90 10.6
17 1150 1000 1800 × 1500 1900 × 1670 2600 2100
60 7.1 90 11 750 800 1400 × 1350 1460 × 1505 2100 1800 6.9 105 12.4
90 17 1150 1000 1800 × 1500 1900 × 1670 2600 2100 10.6 105 8.1 120 14.1
105 12.4 Notes : The capacity in persons is calculated at 68kg/person. (EN81 75kg/person)
Notes : 1. The capacity in persons is calculated at 68kg/person. (EN81 75kg/person)
2. For applicable dimensions on the speed of 90 m/min, 105m/min or 17 persons, consult Hyundai.

16 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 17


www.hyundaielevator.co.kr
� �
Layout Plan Typical Entrance Layouts
Machine-Room-Less(MRL)Type 45 ~ 60m/min Only for Floor with Control Panel of the Machine-Room-Less Elevators

SPACE SAVERⅠ-T
(Permanent Magnet Synchronous Motor)
Plan of Hoistway Section of Hoistway Entrance Design Structural opening of Entrance
Hook(By others)
X cL OF CAR
A

30
Overhead(OH)

700
Steel Bar for 150
CA Fixing Jambs
� 9×6EA (By others)
Y

Hall Button
CB

Concrete Opening : 2200


Entrance Height(EH) : 2100
B

with

Jamb Height(JH)

500
Indicator

700
Control
Control
Control
Control
Control
Floor with
Panel
Panel
Control Panel

Total Height(TH)
Panel
Panel
Panel
Power Distribution OP
Board(By others) 530

1000
CP Clear Opening (OP) 30 Concrete Opening
530

700
Clear Opening Clear Opening
Finished +CP+100 +100

Travel(TR)
Floor Level 2 2
(By others)

Ent. Height(EH)
Traction
Floor without Machine

Control Panel CP110 Type (Standard) CP110 Type (Standard)


OP

ABOUT 600
Pit Depth(PP)

(Unit : mm)
Notes : Above dimensions are applied
Speed Overhead Pit cL OF CAR
(m/min) (OH) (PP) Travel in case car height is 2500mm.
Transom Panel
(Car internal height is 2300mm)
Drainage (∅ 50)
45 3800 1400 MAX Ladder Waterproof
(By others)
Position
41000 Receptacle (By others) Finish(By others) Indicator
60 3800 1500
(By others)

Standard Dimensions (Caved Wall Type)

700
Steel Bar for
(Unit : mm)
Fixing Jambs

Concrete Opening : JH+50


Car Hoistway � 9×6EA (By others) 150
Clear
Capacity

Jamb Height(JH)
Speed Motor

Entrance Height(EH) : 2100


Opening Internal External 1 Car Depth Hall Button
(m/min) (kW)
Persons kg OP CA × CB A×B X Y

300
700
45 2.6
8 550 800 1400 × 1030 1460 × 1185 1900 1700
60 3.4

45 2.8
9 600 800 1400 × 1100 1460 × 1255 1900 1750
CP Clear Opening (OP) 30
60 3.7

1000
530 Concrete Opening

700
45 3.3 Finished Clear Opening Clear Opening
10 700 800 1400 × 1250 1460 × 1405 1900 1950 Floor Level +CP+100 +100
2 2
60 4.3 (By others)

45 3.5
11 750 800 1400 × 1350 1460 × 1505 1900 2050
60 4.6

45 4.2 CP210 Type (Optional) CP210 Type (Optional)


13 900 900 1600 × 1350 1660 × 1505 2150 2050
60 5.6

45 4.6
15 1000 900 1600 × 1500 1660 × 1655 2150 2200
60 6.2
Notes : 1. The capacity in persons is calculated at 68kg/person. (EN81 75kg/person)
2. For applicable dimensions on the speed of 90 m/min, 105m/min or 17 persons, consult Hyundai.

18 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 19


www.hyundaielevator.co.kr

Layout Plan
General Type 45 ~ 120m/min

Plan of Hoistway & Machine Room Section of Hoistway Standard Dimensions & Reactions
(Unit : mm)
MX1

X1 Suspension Hook Car Hoistway M/C Room


Clear

Height(MH)
M/C Room
A Cinder
(By others)
Speed Capacity M/C Room
Concrete Min.150 Opening Internal External 1Car 2Cars 3Cars Depth 1Car 2Cars 3Cars Depth Reaction(kg)
R1 (By others) (m/min)
Persons kg OP CA×CB A×B X1 X2 X3 Y MX1 MX2 MX3 MY R1 R2
window
window
window
window
Gallerywindow

R2 R1
others)
others)
others)
others)
others)
(Byothers)

6 450 800 1400× 850 1460×1005 1800 3700 5600 1480 2000 4000 6000 3200 3600 2000
(By others)
Gallery

Vent Fan
Gallery
Gallery
Gallery
(By
(By
(By
(By
(By

Overhead (OH)
Y

CB

8 550 800 1400×1030 1460×1185 1800 3700 5600 1660 2000 4000 6000 3400
B

4050 2250
CA
1400×1100 1460×1255 1800 3700 5600 1730 2000 4000 6000 3500
MY

9 600 800 4100 2450


OP
1400×1150 1460×1305 1800 3700 5600 1780 2000 4000 6000 3550
R2
45 700
Control 10 800 1400×1250 1460×1405 1800 3700 5600 1880 2000 4000 6000 3600 4200 2700
Panel

11 750 800 1400×1350 1460×1505 1800 3700 5600 2000 2000 4000 6000 3700 4550 2800

Total Height (TH)


Distribution Board 1600×1350 1660×1505 2050 4200 6350 2000 2300 4400 6800 3750
(By others) Machine Room
13 900 900 5100 3750

Travel (TR)
Access Door(By others) 60
Min. 900(W)×2000(H) 1600×1400 1660×1555 2050 4200 6350 2050 2300 4400 6800 3800

1600×1500 1660×1655 2050 4200 6350 2150 2300 4400 6800 3850
15 1000 900 5450 4300
1600×1550 1660×1705 2050 4200 6350 2200 2300 4400 6800 3900
90

Ent. Height (EH)


Notes : Machine room temperature should be maintained below
1000 1800×1500 1900×1670 2350 4800 7250 2280 2600 4900 7500 3900

2100
40℃ with ventilating fan and /or air conditioner(if necessary)
and humidity below 90%. 17 1150 6600 5100
1100 2000×1350 2100×1520 2550 5200 7850 2130 2800 5250 8300 3800
Pit Depth (PP)

1800×1700 1900×1870 2350 4800 7250 2480 2600 4900 7500 4200
105 1000
1800×1730 1900×1900 2350 4800 7250 2510 2600 4900 7500 4300
20 1350 7800 6000
Ladder Waterproof Finish
(By others) (By others) 2000×1500 2100×1670 2550 5200 7850 2280 2800 5250 8300 4000
Receptacle 1100
(By others) 2000×1550 2100×1720 2550 5200 7850 2330 2800 5250 8300 4100
120
2000×1750 2100×1920 2550 5200 7850 2530 2900 5400 8300 4300

MX2 2000×1800 2100×1970 2550 5200 7850 2580 2900 5400 8300 4400
X2 MX3 24 1600 1100 8500 6800
X3 2150×1600 2250×1770 2700 5500 8300 2380 3000 5650 8700 4200
X1
X2
A 2150×1670 2250×1840 2700 5500 8300 2450 3000 5650 8700 4300
X1
R1 R1
Min. 100

A
R1 R1 R1
others)
others)
others)
others)
Fan(Byothers)
Gallery window(By others)

Notes : 1. White colored dimensions shall be applied for Malaysia & Singapore market.
Gallery window(By others)

Beam (By others)


Vent Fan(By others)

2. Above hoistway dimensions are based on 15-storied buildings. For application to over 16-storied buildings,
Fan(By
Fan(By
Fan(By
VentFan(By

Beam
(By others) the hoistway dimensions shall be at least 5% larger considering the sloping of the hoistways.
3. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai.
Vent
Vent
Vent
B Vent

4. When non-standard capacities and dimensions are required to meet the local code, consult Hyundai.
CB

CB

Y
B

CA 5. The capacity in persons is calculated at 68kg/person.


CA

(Unit : mm)
MY

OP OP OP
MY
Gallery window(By others)

Speed Overhead Pit M/C Room Height


Gallery window(By others)

OP OP R2 R2 R2
Vent Fan(By others)

(m/min) (OH) (PP) (MH)


R2 R2
Control Control Control Control Control 45 4400 1200 2200
Panel Panel Panel Panel Panel
60 4600 1500 2200
Distribution Board Distribution Board
(By others) (By others) 90 4800 1800 2400
105 5000 2100 2400
Machine Room
Machine Room Access Door(By others) 120 5000 2100 2600
Access Door(By others) Min. 900(W)×2000(H)
Min. 900(W)×2000(H)
Notes : Above is minimum size.

20 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 21


� �
Typical Entrance Layouts 2-Panel Center-Opening(co) Layout

Entrance Structural Opening of Entrance Plan of Entrance Section Entrance


10

90
Jamb Width
50
150

700

Thickness
Entrance Height (EH) : 2100

Wall
Steel
Steel
Steel
SteelBar
Steel Bar
Bar for
for
Barfor
Bar for
for

100
Concrete Opening : 2200

Wall Finish
Fixing
FixingJamb
Fixing Jamb
Jamb

Thickness
Fixing
Fixing
Fixing Jamb
Jamb
Jamb
HB With HPI 10 10
����� 9×6
9×6 (By others)
EA
EA
9×6 EAEA
(Byothers)
others)

500
9×6EAEA(By
9×6
EA
EA
EAEA
EA
(By
(By others)
others)
700 (150)
In case of Boxless Type 70 Clear Opening (OP) 70 HB With HPI

Clear
Clear
Clear
Clear
Clear
Buttons and Fire man‘s witch

1000
Opening (OP)
Opening(OP)
(OP) Concrete
10 Opening
Opening
Opening (OP)
(OP)
JP050 Type

Entrance Height (EH) : 2100


700

Opening
OP+140
Finished Floor Level Wiring Inlet :� 50
(By others) (By others)
Jamb Width

Concrete Opening(Jamb Height + 50mm)

90
JP050 Type (Basic)

700

Jamb Width

Thickness
Wall

Wall Finish
200

400

Thickness
700
Indicator
30

1700
Steel
Steel
Steel Bar
Bar for
for 30 (180)
SteelBar
Steel Barfor
Bar for
for 80
Fixing
FixingJamb
Fixing
Fixing Jamb
Jamb
Jamb
250

Fixing Jamb
Emergency Call ����� 9×6
9×6 EA
(By others) Hall

1050
9×6
9×6
EA
EAEA EA
(Byothers)
9×6EAEAEAEAEAEA(By
(By
(By others)
others)
others) 150 Clear Opening (OP) 150

50
150 Button
700

Switch

700
(For emergency call,
only rescus floor is Steel
Steel
Steel
SteelBar
Steel Bar
Bar for
for
Barfor
Bar for
for
Entrance Height (EH) : 2100

Fixing
Fixing Jamb
Jamb
Concrete Opening : 2200

applied)
Fixing
FixingJamb
Fixing Jamb
Jamb JP100, JP200 Type
Jamb Height (JH)

����� 9×6
9×6 (By others)
EA
EA
9×6
9×6
EAEA
EAEA (Byothers)
9×6EAEAEAEA(By
EA
(By
(By others)
others)
others) 90
HB
700

Concrete Opening Finished Floor Level Building Structure


300

(By other Contractors)


1650

(By others)
JP050 Type
Wall and Floor Finishing
(By other Contractors)
Clear
Clear
Clear
Clear
Clear
Clear
1000

30 Opening
Opening
Opening
Opening (OP)
Opening(OP)
(OP)
(OP)
(OP) Concrete
700

Opening

50
OP+300

50
Finished Floor Level

50
(By others)
Ceiling Line
Upper

100
JP100 Type (Optional) frame

10 10

Finished Ceiling Level


50
30

(By others)

Jamb Height (JH)

Jamb Height (JH)


Entrance Height (EH) : 2100
Entrance Height (EH) : 2100

Entrance Height (EH) : 2100


Ceiling Height
Transom Transom
Panel Panel
Steel
SteelBar
Steel
Steel
Steel Bar
Bar
Bar for
Barfor
for
for
for
Hall Position Hall Position Fixing
Fixing
FixingJambJamb
Jamb
Jamb
Fixing
Fixing
Fixing Jamb
Jamb
Indicator Indicator
����� 9×6
9×6 (By others)
EA
EA
9×6
9×6
EAEA
EA
EA (Byothers)
9×6EAEAEA(By
EA
(By
(By others)
others)
others) Jamb Width
250

Jamb Width Jamb Width


700

Emergency Call Emergency Call


150
Concrete Opening:JH+50

Switch Switch
(For emergency (For emergency
Jamb Height (JH)

call, only rescus call, only rescus


Jamb Height (JH)
Ceiling Height
Entrance Height (EH) : 2100

floor is applied) floor is applied)


Entrance Height (EH) : 2100

300

HB HB
700

1650

50

50

50
1000

Clear
Clear
Clear
Clear
Clear Clear
Clear
Clear
Clear
Clear Concrete
Opening
Opening (OP)
Opening(OP)
(OP) Opening (OP)
Opening(OP)
Opening (OP) Opening 90 90 90
30 Opening
Opening (OP)
(OP) 30 Opening
Opening (OP)
(OP)
700

OP+300

Finished Floor Level


(By others)

JP100 Type JP200 Type JP200 Type


JP200 Type (Optional) (with upper frame) (without upper frame)
22 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 23
www.hyundaielevator.co.kr

Standard &Optional Features

Items Descriptions Marks Items Descriptions Marks

The first call determines the direction of the elevator. All calls opposing the respective 14) Multi-beam door Multi-beam from the top to the bottom of the door senses any obstruction caught in the door.
1) Selective collective � ★
direction are serviced after carrying out by the calls of the respective direction. protection It makes the door reopen, or keep open/close before the door is touched such obstruction.

2) Duplex selective
2 units of elevator provide the effective service for the common hall calls ★ When a fire breaks out, all cars activated by the switch or fire detector are immediately
collective 15) Fire emergency service ★
called to a specified rescue floor for the passenger’s safety.

When a car is 80% loaded, it will automatically bypass all hall calls as the bypass load
3) Automatic bypass weighing device is activated.

Evaluates the number of people on the car and compares that value to the number of the car
calls registered. If the number of car calls exceeds the number of people in the car by the load
16) Anti-nuisance ★
4) Chime bell It provides an audible indication in the car that an elevator is about to arrive. � sensor, the car call exceeding the number of passengers will be cancelled after service
nearest all only.

Digital(Segment) type �
5) Signal fixtures Dot matrix type(moving direction) ★ A voice synthesizer with microprocessor makes announcements to inform passengers of
Hall lantern ★ 17) Voice synthesizer ★
various conditions, including landing floor and operation direction, etc.

Contact with a passenger or inanimate object causes the doors to stop and
6) Single-side safety During normal power failure, elevator service continues with building’s
reopen automatically. � 18) Emergency power ★
edge of door The elevator doesn’t start if the door is completely not closed.
emergency power source.

7) Ventilation fan Car ventilation is smooth with ventilation fan built-in the ceiling. � When the fireman’s switch located at the main floor lobby and operating panel on the car is
19) Fireman’s emergency
activated during a fire or other emergency, a designated car can be called back to a specified ★
service floor for fire fighting service.
8) Emergeny car lighting In case of the power failure, it lights automatically in the car. �

9) Automatic interruption of 20) HELMON (Hyundai


The lights and ventilation fan are automatically turned off to save energy if there is This system has a various function like elevator monitoring and control by the personal
� Elevator Computer ★
light and ventilation fan no call registered for a period of time. If there is a call registered again, it works again. computer and modem.
Monitoring) System

When the door is opened, the switch installed at the door operator is activated and keeps In the event of the power failure, the elevator power automatically switches to a rechargeable
10) Door interlock switch the car from moving. During the operation of car, it locks the door completely so as not to � 21) Emergency landing battery built-in controller that moves the car to the nearest floor and allows passengers to
safely exit. ★
open the door from out side. device(ELD)
This can be used when no emergency power source in the building is available.

11) Interphone & emergency In case of emergency, the passenger can communicate with the personnel in control room It is activated when the attendant turns on the ATT switch in the car operating
� 22) Attendant service ★
call button or in prevention center of disasters by pushing the emergency call button. panel to“ON”position.

When the seismic sensor detects and earthquake that exceeds a predetermined level,
To protect the overload of elevator, this device sounds a buzzer and the elevator remains 23) Earthquake operation all cars promptly proceed to land at the nearest floor and park with the doors open to allow ★
12) Overload features stopped at that floor when the number of passengers exceeds the rated capacity. When the � passengers to exit out safely.
excess number of passengers get out of the car, the buzzer stops and the elevator door closes.

The car can be parked at a specified floor, during the nights or holidays with operate
24) Parking parking switch on hall button.

During the operation if the car stops between floors, and safety device doesn’t work, the car
13) Safety drive automatically moves to the nearest floor with the low speed. Then, it opens the door to allow �
the passengers to exit off. Notes : 1. � : Standard, ★: Optional
2. Consult Hyundai if you need the specific features except the above items.

24 I PASSENGER ELEVATORS HYUNDAI ELEVATOR I 25


� �
Works to be Done by Other Contractors Electric Power Requirements (By Others)
The following works are not included in the elevator contract, and shall be done by other contractors in
accordance with the Hyundai Elevator’ s drawings and the applicable codes and regulations. 50/60Hz, 380V

NFB Rated Transformer Power Feeder Earth Wire


The reference rules shown are from ANSI A17.1 Code. (The followings are based on the general type. Persons Speed Motor
Current(A) Capacity(kVA) (mm2) (mm2)
Consult Hyundai for the Machine-Room-Less elevators.) (kg) (m/min) (kW)
1Car 2Cars 1Car 2Cars 1Car 2Cars 1Car 2Cars
60 5.5(2.8) 30(20) 30(20) 5(4) 8(7) 8(5.5) 8(5.5) 5.5(5.5) 5.5(5.5)
6
90 7.5(4.2) 30(20) 30(20) 6(5) 10(9) 8(5.5) 8(5.5) 5.5(5.5) 5.5(5.5)
(450)
120 7.5(4.9) 50 50 7 12 14 14 5.5 8(8)

Building Work � Electrical Work � 8


60
90
5.5(3.4)
11(5.1)
30(20)
50(30)
30(20)
50(40)
6(5)
7(6)
11(10)
12(11)
8(5.5)
14(5.5)
8(5.5)
14(5.5)
5.5(5.5)
5.5(5.5)
5.5(5.5)
8(8)
(550) 105 11(5.9) 50(30) 50(40) 8(7) 14(13) 14(5.5) 14(8) 5.5(5.5) 8(8)
Hoistway Hoistway
120 11 50 50 7 12 14 14(8) 5.5 8(8)
1. Clear, plumb hoistway with fire resistant hatch walls as required by the gover- 1. Light outlet for each elevator, in center of hoistway (or in machine room)as indi-
ning code. (Rule 100.1a) cated by Hyundai Elevator Company. 60 5.5(3.7) 30(20) 30(20) 6(5) 11(10) 8(5.5) 8(5.5) 3.5(5.5) 5.5(5.5)
2. 75。bevel guards on all projections, recesses or setbacks over 50mm except on 2. Convenience outlet and light fixture in pit with switch located adjacent to the 9 90 11(5.6) 50(30) 50(40) 7(6) 12(11) 14(5.5) 14(8) 5.5(5.5) 8(8)
side used for loading or unloading. (Rule 100.6) access door. (Rule 106.1e) (600) 105 11(6.5) 50(30) 50(40) 8(7) 14(13) 14(5.5) 14(8) 5.5(5.5) 8(8)
3. Venting of the hoistway as required by the governing code or authority. 3. Wiring and piping work of emergency bell, interphone, etc. Outside the hoistway
120 11 50 50 7 12 14 14 5.5 8(8)
(Rule 100.4) and the machine room.
4. Supports for rail brackets at each floor, roof, and machine room. (Rule 200.9) 60 7.5(4.3) 30(20) 50(30) 8(6) 15(11) 8(5.5) 14(8) 3.5(5.5) 5.5(5.5)
Maximum allowable vertical spacing of rail supports, without backing. (Rule Machine Room 10 90 11(6.5) 50(30) 50(40) 8(7) 15(13) 14(5.5) 14(8) 5.5(5.5) 8(8)
200.4 and 301.1) 4. Lighting, convenience outlets, ventilation, heating of machine room, and machinery (700) 105 11(7.5) 50(30) 50(40) 10(9) 17(16) 14(5.5) 14(8) 5.5(5.5) 8(8)
Divider beams 100mm between hoistway at each floor and roof, for guide rail space. (Rule 101.5)
120 15 50 75 11 19 14 22 5.5 8(8)
bracket supports.(Rule 200.4, 200.9 and 301.1) 5. Temperature should be maintained below 40。C with ventilating fan and/or air
5. Recesses, supports and patching as required to accommodate hall button conditioner, if necessary, and humidity below 90%. 60 7.5(4.6) 30(20) 50(30) 8(6) 15(11) 8(5.5) 14(8) 3.5(5.5) 5.5(5.5)
boxes, signal fixtures, etc. 6. A fused disconnect switch or circuit breaker for each elevator and light switch 11 90 11(6.9) 50(30) 50(40) 8(7) 15(13) 14(5.5) 14(8) 5.5(5.5) 8(8)
6. All barricades either outside elevator hoistways or between elevators inside located per the governing code and where practicable located adjacent to the (750) 105 11(8.1) 50(30) 50(40) 10(9) 17(16) 14(5.5) 14(8) 5.5(5.5) 8(8)
hoistways as required. door of the machine room. (Rule 210.5 and 306.7)
120 15(9.2) 50(30) 75(50) 11(10) 19(18) 14(8) 22(14) 5.5 8(8)
7. Dry pit reinforced to sustain normal vertical forces from rails and buffers. 7. Feeder and branch wiring to the controller, including mainline switch and con-
(Rule 106.1b and 109) venience outlets. 60 11(5.6) 50(20) 50(30) 10(6) 18(11) 14(5.5) 14(8) 5.5(5.5) 8(8)
Consult Hyundai Elevator Company for rail forces and buffer impacts. Where 8. Suitable power feeder and branch wiring circuits as required for elevators with 13 90 15(8.3) 50(30) 75(50) 11(9) 18(16) 14(5.5) 22(14) 5.5(5.5) 8(8)
there is space below the pit floor which can be occupied, consult Hyundai power operated doors, including disconnect switch or circuit breaker. 105 15(9.7) 50(30) 75(50) 11(10) 19(18) 14(5.5) 22(14) 5.5(5.5) 8(8)
(900)
Elevator Company for special requirements. (Rule 300.4)
8. Where access to the pit is by means of the lowest hoistway entrance, vertical
Emergency Provisions 120 18.5(11.1) 75(30) 100(75) 14(12) 24(22) 22(14) 30(22) 8(5.5) 8(8)

iron ladder extending 1060mm minimum above sill of access door. (Rule 106.1d) 9. Elevator fireman’s and other emergency services’wiring and interconnections 60 11(6.2) 50(30) 50(40) 10(8) 18(15) 14(5.5) 14(8) 5.5(5.5) 8(8)
9. Entrance walls and finished floor are not to be constructed until after door to automatic sprinkler systems or heat and smoke sensing devices furnished by 15 90 15(9.2) 50(30) 75(50) 11(10) 19(17) 14(5.5) 22(14) 5.5(5.5) 8(8)
frames and sills are in place. others and installed to terminal points on the elevator controllers.
(1000) 105 15(10.8) 50(40) 75(50) 12(11) 20(18) 14(5.5) 22(14) 5.5(5.5) 8(8)
Door frames are to be anchored to walls and properly grouted in place to main- 10. When emergency power operation of elevators is required, the electrical con-
120 18.5(12.3) 75(40) 100(75) 14(13) 24(22) 22(14) 30(22) 8(5.5) 8(8)
tain legal fire rating. tractor should coordinate with Hyundai Elevator Company or local distributor
10. Sill supports 64mm minimum floor recesses full hoistway width for entrance for operation requirements. 60 11(7.1) 50(30) 75(40) 12(9) 22(17) 14(5.5) 22(14) 5.5(5.5) 8(8)
sills, with grouting after sills are set in place. 11. Elevator fireman’s and other emergency service requirements may differ from
17 90 15(10.6) 75(40) 100(75) 13(12) 22(21) 14(5.5) 22(14) 5.5(5.5) 8(8)
11. For application as indoor observation elevator, a minimum 3.6m high glass each country. Consult Hyundai Elevator Company or local distributor for other
(1150) 105 18.5(12.4) 50(40) 100(75) 14(13) 24(22) 22(8.0) 30(22) 8(5.5) 8(8)
enclosure above bottom landing is recommended for safety. local requirements.
12. When provisions for earthquake protection are required, consult Hyundai 120 22(14.1) 75(40) 100(75) 15(14) 26(23) 22 30(22) 8(5.5) 8(8)
For application as outdoor observation elevator, full height glass enclosure is
required. Elevator Company for special requirements. 60 15 50 75 14 23 14 22 5.5 8
20 90 18.5 75 100 15 25 22 30 8 8
Machine Room
(1350) 105 22 75 100 16 27 22 30 8 8
12. Enclosed and protected machine room. (Rule 101.1)
13. Access to the machine room and machinery space as required by the governing Heat Emission Of 120 30 100 150 23 39 30 38 14 14

code or authority. (Rule 101.3)


14. Reinforced concrete machine room floor slab or grating, as specified, which
Machine Room 24
60 15 50 75 15 26 14 22 5.5 8
90 22 75 100 16 28 22 30 8 8
must not be placed over the hoistway until elevator machinery is set in position. Q(Kcal/H) = W×V×F×N (1600) 105 22 75 100 19 32 22 30 8 8
(Rule 100.3 for Traction Elevator)
W: Capacity (kg) N: Number of cars 120 30 100 150 23 39 30 38 14 14
15. Hoisting beams, trap doors and other means of access to machine room for
V: Speed
maintenance and equipment removal purposes. (Rule 101.3d) Notes : 1.Above power feeder sizes are for the length of electric wire up to 50m from elevator machine room to transformer.
F: Factor (1/40: VVVF)
16. Cable guards in the machine room or secondary level. (Rule 104.1) For the length being 50m or more, the following formular should be applied: Power feeder length(m)
2. Above power feeder sizes are for copper wires inside electrometallic tubings. Power feeder sizes(mm2) = ×Size in the above(mm2)
17. Supports for machine and sheave beams and reactions including wall pockets 3. For power requirement of 3 cars or more, consult Hyundai. 50
and patching after beams are set in place. (Rule 105.1 to 105.5) 4. Machine room temperature should be maintained below 40℃ with ventilating fan and air conditioner, and humidity below 90%
5. Date shown in ( ) is applied to the Machine-Room-Less elevators. (Gearless type)