LS-VINA - MV - Catalogue
LS-VINA - MV - Catalogue
LS-VINA - MV - Catalogue
Hi-Power V series
Safety Design
Compartments are divided by grounded metal
partitions.
Quick-make earthing switches are used for
earthing and withstand of making capacity.
Type tested in accordance with IEC 60298,
IEC 62271-200.
Removable circuit breaker with mechanical
interlocks to prevent mal-operation.
Pressure relief device is available on request.
Normal Service
Standard characteristics of Hi-Power V-series Switchgear
comply with condition as below (IEC standard)
•Ambient temperature : -5℃ ~ +45℃
•Maximum altitude : 1000m
Standard
IEC 62271-200 for switchboard.
IEC 60694 for general purpose
IEC 60298, Annex AA. for
internal arc test.
(Classification IAC : BFLR)
IEC 60529 for the degree of
protection.
IEC 62271-100 for the circuit
breakers.
Applicable standard is
available.
Standard Characteristics
Model Name Unit Hi-Power V12 Hi-Power V17 Hi-Power V24
Rated voltage kV 12 17.5 24
Rated insulation voltage kV 12 17.5 24
Rated power frequency withstand voltage kV 1min 28 38 50
Rated lightning impulse withstand voltage kV 75 95 125
Rated frequency Hz 50/60 50/60 50/60
Rated short-time withstand current kA/s 25/3, 31.5/3 40/3 25/3
Peak current kA 63 100 63
Internal arc withstand current kA/s 25/0.1 40/0.1 25/0.1
Degree of protection IP 4X 4X 4X
Main busbar rated current A 2000 3150 2000
Branch connection rated current A 2000-1250-630 3150-2000-1250 2500-2000-1250-630
Rated current A 2000 * 1250 * 630 * 3150 2000 1250 2500/2000 1250 630
Wide mm 800 650 650 950 800 800 1000 800 800
Height mm 2350 2350 2350 2350 2350 2350 2350 2350 2350
Depth mm 1700 1700 1700 1900 1800 1800 1800 1800 1800
C.B. compartment
BusBar compartment
Cable compartment
V.T. compartment
CB compartment
Can be drawn in and out
C.B. without opening the door.
Installment of viewing window.
Stable structure of hinge and locker.
Shutter padlock facility is available Cable compartment
Installment of IP cover in front of C.B. Sufficient spaces are provided for
cable termination and entry.
Current transformer, cabling and
supporting brackets are
composed at cable compartment.
Optional Accessories
Earthing switch
- (for G class draw-out type only)
For the safety during the maintenance
of a VCB panel, discharge the
charging current in the load side
of a VCB with this earthing switch.
Section View
Skeleton Diagram
• For your safety, please read user's manual thoroughly before operating.
• Contact the nearest authorized service facility for examination, repair, or adjustment.
• Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions • Any maintenance and inspection shall be performed by the personnel having expertise concerned.