Motorpact IEC: Instructions For Use: Instruction Bulletin
Motorpact IEC: Instructions For Use: Instruction Bulletin
Motorpact IEC: Instructions For Use: Instruction Bulletin
Instruction Bulletin
46032-700-09G
4/2016
Retain for future use.
™
Hazard Categories and Special Symbols
Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service, or maintain it. The
following special messages may appear throughout this bulletin or on the
equipment to warn of hazards or to call attention to information that clarifies or
simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates
that an electrical hazard exists which will result in personal injury if the
instructions are not followed.
This is the safety alert symbol. It is used to alert you to personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or
death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol is not used with this signal word.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel. No responsibility is assumed by Schneider Electric
for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the
construction, installation, and operation of electrical equipment and has
received safety training to recognize and avoid the hazards involved.
Table of Contents Motorpact IEC: Instructions for Use
Table of Contents
ENGLISH
Padlocking the Disconnector .............................................................66
Padlocking the Cable Earthing Switch ...............................................67
Padlocking the Incoming Cable Section Doors ..................................67
Locking Using Keylocks (Optional) ....................................................68
Number of Possible Locks per Section Type .....................................68
Keylocking the Disconnector .............................................................68
Locking the Disconnector Open or Closed with 1 Keylock ................68
Locking the Disconnector Open or Closed with 2 Keylocks ....................68
Locking the Cable Earthing Switch Open or Closed ..........................69
FVR (Full Voltage Reversing Bidirectional) .......................................70
Description................................................................................... 70
FVS (Dual Voltage Transfer Starter) ..................................................71
Description................................................................................... 71
FVSD (FVS–Dual Box) ......................................................................72
Description................................................................................... 72
Redundant Smart Sequence Starter ..................................................73
Description .........................................................................................73
DDS (Dual Disconnect Section) .........................................................74
Description .........................................................................................74
2-Speed, 1-Winding ...........................................................................76
Description .........................................................................................76
2-Speed, 2-Winding ...........................................................................77
Description .........................................................................................77
Star Delta ...........................................................................................78
Description .........................................................................................78
RVAT (Reduced Voltage Autotransformer) .......................................79
Description .........................................................................................79
Limited Duty Cycle Rating .................................................................79
Keylocks on an RVAT ........................................................................80
Keylocking with Disconnector (without cable earthing switch) ...........80
Keylocking (with cable earthing switch) .............................................80
RVAT Operation ................................................................................81
Autotransformers ...............................................................................81
Relay Setting .....................................................................................82
Tap Setting ........................................................................................82
Steps to change tap settings ....................................................... 82
Steps to CLOSE ................................................................................83
Steps to OPEN ..................................................................................83
Reduced Voltage Soft Starter (RVSS) Soft Start Section ..................83
Description .........................................................................................83
Keylocks on an RVSS Soft Start Section ...........................................85
Keylocking with Disconnector (without cable earthing switch) ...........86
Keylocking with Cable Earthing Switch ..............................................86
Keylocking with S3 Line-Ups .............................................................86
Keylocking for S3 Line-Up with Dual Disconnect Section (DDS) .......86
FVS Key Locking ...............................................................................86
Removing a Contactor from an RVAT Section or RVSS Soft Start
Section ...............................................................................................87
Preliminary Steps ...............................................................................87
Steps to Remove a Start, Run, or Bypass Contactor ........................88
Installing a Contactor in an RVAT Section or RVSS Soft Start
Section ...............................................................................................89
Preliminary Steps ...............................................................................89
Steps to Install a Start, Run, or Bypass Contactor ............................90
Using a Lift Truck ...............................................................................91
MDT107 Thermal Diagnostic System (Optional) ...............................92
Description .........................................................................................92
Functions ...........................................................................................93
Monitoring of Temperature Buildup in 2 Zones............................ 93
Triggering of a Pre-alarm............................................................. 93
Triggering of an Alarm ................................................................. 93
Self-Monitoring of the Module...................................................... 94
Self-Monitoring of Sensors .......................................................... 94
Wiring .................................................................................................95
Wiring and Operation for MDT107 .....................................................95
Ratings ...............................................................................................95
MDT107 Module Location ..................................................................96
MDT107 Sensors Location ................................................................97
Setting the Temperature Rise Thresholds .........................................97
Steps to Set the Temperature Rise Thresholds........................... 97
Setting the Ambient Temperature Correction ....................................98
Steps to Set the Ambient Temperature ....................................... 98
Troubleshooting .................................................................................98
SECTION 6:MAINTENANCE ............................................................................ 99
Preventative Maintenance .................................................................99
Environmental Conditions ....................................................................... 100
Ideal Conditions ............................................................................... 100
Standard Conditions ........................................................................ 100
Aggressive Conditions ..................................................................... 100
Inspecting the Equipment .................................................................... 101
SECTION 7:REPLACEMENT PARTS ............................................................ 102
SECTION 8:TROUBLESHOOTING ................................................................ 103
SECTION 9:GLOSSARY ................................................................................ 105
ENGLISH
It is strictly forbidden to remove the parts bearing this marking when the
equipment is energized:
Application Methods The conical washers placed on the external sides of the busbars ensure better
distribution of stress regarding bolts tightened to the recommended torques.
M O
N
Starter Type M N
FVR Bidirectional Forward contactor Reverse contactor
FVS Dual Voltage Transfer Starter Run contactor Start contactor
2S1W Slow-speed contactor Shorted contactor
Star Delta Star-connection contactor Delta-connection contactor
M O
N
Starter Type M N
2-speed, 2-winding Fast-speed contactor Slow-speed contactor
FVSD (FVS–Dual Box) Run contactor Start contactor
D K
E
L
G
H
I
J
G M
F G
Identification
FVNR
A. Name of starter or section
B. Viewing port, disconnector A
C. Characteristics, designations, and serial
number
D. Interlock shuttle
E. Status window, blown fuse indicator
(see Blown Fuse Indicator)
F. Status window, cable earthing switch
(see Cable Earthing Switch Operating
Condition)
G. Status window, contactor
Contactor
C
H. Characteristics, designations, and serial B
number D
I. Status indicator
E
Contactor
C
H. Characteristics, designations, and B
serial number D
I. Status indicator
Procedure Pictogram
Steps for Closing of Circuit
1. MV compartment door position, close and latch
2. If the cable earthing switch is not supplied, skip to step 5. If
the cable earthing switch is supplied, move the cable
earthing switch access port from the locked to unlocked
position. This requires the interlock shuttle to be in the
right-hand position. See Cable Earthing Switch
Operation (Optional).
3. OPEN or un-earth the cable earthing switch
4. Move the cable earthing switch access port from the
unlocked to locked position; then move the interlock shuttle
from the right-hand to left-hand position. See Disconnector
Operation.
5. Move the disconnector access port from the locked to
unlocked position
6. CLOSE the disconnector
7. Move the disconnector access port from the unlocked to
locked position
8. CLOSE the contactor
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Avoid disconnecting any wire connections before removing the bus compartment access panel.
Failure to follow this instruction can result in equipment damage.
Steps to Access the Busbar Compartment from the Rear of the Enclosure
1. Remove the upper MV cable compartment
cover. 4 M10x20 screws.
2. Remove the rear main busbar cover.
4 M10x20 screws.
3. The busbar compartment is now accessible.
1 2 3
Steps to Access the Busbar Compartment from the Front of the Enclosure
1. Remove the main busbar access cover in the
floor of the LV cabinet. 8 M10x20 screws.
2. The busbar compartment is now accessible.
NOTE: After installation or maintenance, ensure all covers are replaced using
the original hardware. Tightening torque: 26 lb-ft (35 N•m).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
NOTE: Motorpact™ motor starters are shipped with the disconnector in the
earthed/OPEN position.
The disconnector must be in the earthed/OPEN position to open the medium
voltage compartment door.
See Disconnector Operation.
NOTE: The cable earthing switch (optional) must be in the earthed/CLOSED
position to open the medium voltage compartment door.
See Cable Earthing Switch Operation (Optional).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Steps to Access the Cable 1. Always remove all power from the section and use a properly rated testing
Compartment of an FVNR device to confirm there is no voltage present.
Section 2. Always look through the rear viewing window to verify that the MV
compartment door is OPEN, before removing the MV cable compartment
cover.
3. Verify through the rear viewing window that the MV compartment door is
OPEN, the power has been removed from the section, and the load
connections have been properly earthed.
4. Remove the lower MV cable compartment cover. 4 M10x20 screws.
Rear view
After installation or maintenance, ensure all covers are replaced using the
original hardware. Tightening torque: 26 lb-ft (35 N•m).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Operating handle
Operating handle
Release
button
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The RVAT or RVSS soft start section main busbar compartment can be
accessed only from the front due to the cable arrangement in the rear of these
sections.
Steps to Access the Busbar Compartment from the Front of the Enclosure
1. Remove the M6x10 screws holding the main busbar access covers.
NOTE: The RVAT shown will have 2 covers. RVSS soft start section will have
only 1 cover.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA
70E, NOM-029-STPS-2011, or CSA Z462.
• Only qualified personnel familiar with medium voltage equipment are to perform work described in this set of
instructions. Workers must understand the hazards involved in working with or near medium voltage circuits.
• Perform such work only after reading and understanding all of the instructions contained in this bulletin.
• Turn off all power supplying this equipment before working on or inside equipment.
• Use a properly rated voltage sensing device to confirm that the power is off.
• Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of
electric power. Assume that all circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of
power, including the possibility of backfeeding.
• Do not make any modifications to the equipment or operate the system with the interlocks removed. Contact
your local field sales representative for additional instruction if the equipment does not function as described
in this manual.
• Carefully inspect your work area and remove any tools and objects left inside the equipment.
• Replace all devices, doors, and covers before turning on power to this equipment.
• All instructions in this manual are written with the assumption that the customer has taken these measures before
performing maintenance or testing.
Failure to follow these instructions will result in death or serious injury.
The DDS main busbar compartment can be accessed only from the front due to
the busbars being enclosed in a busbar tunnel.
1. Remove the M10x20 screws holding the main busbar access covers.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Steps to Access the Reduced Voltage Soft Starting MV Cable Connector Compartment
from the Front of the Enclosure
Operation
It is strongly advised to periodically carry out (minimum every 2 years) a
few operation cycles on operating devices.
Outside normal conditions of use (between - 5 °C and 40 °C, absence of dust,
corrosive gas, etc.), it is recommended to verify the steps to be taken in
order to ensure correct functioning of the installation. Contact the Schneider
Electric Service Center for help to do so.
The Service Center is able to assist you at any time to offer you:
• installation diagnostics
• suitable maintenance operations
• maintenance contracts
• adaptations
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only qualified electrical personnel should perform this testing.
• During testing, maintain a minimum clearance of 6 feet (1829 mm) from the
equipment.
Failure to follow these instructions will result in death or serious injury.
Safety Precautions
Carry out electric tests in compliance with the standards in force. All operations
described hereafter must be carried out in compliance with the safety standards
in force, under the responsibility of a competent person.
It is recommended that prior to start-up and after maintenance on this
equipment, the 1 minute dielectric test is always performed. See "steps to be
taken for test and inspections" in the installation instruction guide.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only qualified electrical personnel should perform this testing.
• During testing, maintain a minimum clearance of 6 feet (1829 mm) from the
equipment.
• If any operation checks provide unacceptable results, DO NOT ENERGIZE
THE EQUIPMENT. Contact your local field sales office or distributor.
Failure to follow these instructions will result in death or serious injury.
Disconnector Operation
Description
The disconnector is the isolation means between the main busbar and the line
side of the primary fuses. When the disconnector is in the earthed or OPEN
position, it disconnects or isolates the contactor from the supply voltage.
Moving the disconnector to the OPEN position earths the switch blades and the
load side power circuit down to the line side of the contactor.
NOTE: In the earthed/OPEN position, the disconnector does not earth the load
side of the contactor, cables, or any other components that are connected to
the load side of the contactor.
switch blades
Interlock Shuttle
An interlock shuttle is provided on all FVNR starters with a cable earthing
switch.
This shuttle must be in the left-hand position to operate the disconnector.
NOTE: Always look through the viewing window to verify the actual position of
the disconnector switch blades.
Open position
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• VPIS must not be used as a VDS (Voltage Detecting System).
• Always use a properly rated testing device to confirm there is no voltage
present.
Failure to follow these instructions will result in death or serious injury.
The indication of a VPIS alone will not ensure the system is de-energized. If the
operation rules require this, then suitable voltage detectors in compliance with
IEC 61243 must be used.
MV Cable Test
Steps to Test Conditions
1. Open the cable earthing switch.
2. The cables are connected to injection tools.
Voltage Injections on MV Outgoing Cable Heads
2. Close the cable earthing switch. See Closing the Cable Earthing
Switch.
CAUTION
STATIC VOLTAGE
• All operations described hereafter must be carried out in compliance with the
safety standards in force, under the responsibility of a competent person.
• Do not replace indicator box while equipment is energized. Static voltage
will be present.
Failure to follow these instructions can result in death or serious injury.
Contact fingers
Truck handle
Control terminal
blocks
Vacuum interrupter
Description
Reset
button
CAUTION
HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE
• Use extreme caution while handling the contactor (25 kg) during this process.
See "Using a Lift Truck."
Failure to follow these instructions can result in personal injury and
equipment damage.
2. Pull the contactor rail down. This 3. Roll the contactor out of the
will disengage the contactor from enclosure. Use extreme
the line and load busbar caution while handling the
connections. contactor (25 kg) during this
process. See Using a Lift
Truck.
Wheel stop
1. Seat the contactor truck wheels 3. Lift the contactor rail to the
onto the contactor rail. vertical position, engaging the
2. By gripping the handles (A) contactor.
shown, slowly roll the contactor
into the enclosure until it reaches
the wheel stop.
Operator panel
Back light pushbutton
Operator cover
A
Tie
channel
Battery Replacement The batteries should be replaced every 4 years to maintain proper
operation. Two AA alkaline batteries are required.
Steps for Removal
1. Remove all power from the section. See Operating Instructions.
2. After opening the MV compartment door, remove 2 screws holding
the bottom of the operator cover to the tie channel.
Left
Negative 3. Open the LV door, and remove the 2 screws holding the top of the
battery
operator cover to the operator panel. Remove the cover.
4. The back light assembly can now be accessed to replace the batteries.
5. Remove the batteries by pulling them straight down from their spring
Front
clips.
6. When replacing batteries, insert the left-side battery with the negative
Right end nearest to the operator and the right-side battery with the
battery Positive positive end nearest to the operator.
Steps to Place Back into
Operation
Operating
handle
Status
window
Earthing
bar
Un-earthed Earthed
position position ?
The indicator for the cable earthing switch can be viewed The cable earthing switch
through a status window in the MV compartment door. operating handle is stored on the
right- or left-hand end sheet.
Description
The cable earthing switch is used to earth the customer load connection cables
when the switch is in the CLOSED or discharged position. It is mechanically
interlocked with the disconnector and is actuated by using the same operating
handle.
Connection to earth is accomplished when the spring operated earthing bar is
connected across all three phases of the customer load terminals.
Instructions for Use
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The cable earthing switch has no interrupting capability and is not capable of
closing on the full fault current available on the system.
When used with a power transformer, key interlocks must be used between
the main secondary disconnect device and the cable earthing switch to ensure
proper sequencing of operation.
Failure to follow these instructions will result in death or serious injury.
Interlock Shuttle An interlock shuttle is provided on all FVNR starters with a cable earthing
switch. This shuttle must be in the right-hand position to operate the cable
earthing switch.
The interlock system requires the following conditions to be met before the
cable earthing switch can be operated:
• The interlock shuttle must be in the right-hand position.
• The contactor must be in the OPEN position.
• The disconnector must be in the DISCONNECTED and EARTHED
position.
• The MV compartment door must be closed and latched.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
The cable earthing switch will close at approximately eight rotations. Continue
to turn for an additional two rotations. Do not apply excessive force when
resistance is met.
Failure to follow this instruction can result in equipment damage.
Closed position
NOTICE
HAZARD OF EQUIPMENT DAMAGE
When resistance is met at the end of ten rotations, do not apply excessive
force to the handle.
Failure to follow this instruction can result in equipment damage.
Open position
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
NOTICE
HAZARD OF OVERHEATING EQUIPMENT AND FUSE MELTING
Do not substitute any other fuse.
Failure to follow this instruction can result in equipment damage.
An optional fuse tool is available to help in the removal and installation of power
fuses. Contact a field sales representative or distributor. See Fuse Tool
(Optional).
CAUTION
HOT FUSE
• The body of a fuse that has blown or carried load current can be
EXTREMELY HOT and will burn unprotected hands.
• Never try to insert or remove both ends of the fuse at once. The fuse body
can be made of FRAGILE PORCELAIN (glass-like) and can shatter if
handled incorrectly.
• Always remove the lower end first.
Failure to follow these instructions can result in personal injury and
equipment damage.
Fuse Characteristics The fuse characteristics and direction of mounting are printed on the fuse.
When replacing the fuse, turn it so that the label is in the front, and the
striker pin is at the top.
CAUTION
HOT FUSE
• The body of a fuse that has blown or carried load current can be
EXTREMELY HOT and will burn unprotected hands.
• Always install the upper end of the fuse first; then install the lower end.
Always push on the ferrule being inserted.
Failure to follow these instructions can result in personal injury and
equipment damage.
1. Always insert the upper end of the fuse first. Grasp the fuse by the upper
ferrule, insert it into the upper fuse clip, and twist it while pushing upward.
2. Insert the lower end into the lower fuse clip.
3. Rotate the fuse so that the label is facing the front.
To ease installation,
lubricate fuse clips with
red Mobilgrease® 28.
CAUTION
HOT FUSE
Always wear gloves when working with fuses. The fuses could be hot and will
burn unprotected hands.
Failure to follow these instructions can result in personal injury.
The fuse tool is an ergonomic aid for inserting and extracting fuses in
de-energized Motorpact™ motor starters. It does not protect the
operator from contacting live parts.
Hook
Handle
Pusher
Steps to Install Rear and The process is the same for installing fuses in the rear and middle
Middle Fuses fuseholders. Begin by installing the rear fuses.
NOTE: Always wear gloves when 1. Align the fuse tool so that the hook and the pusher are toward the
working with fuses. The fuses could handle end of the tool.
be hot and will burn unprotected
hands. The photos on these pages
are factory demonstrations.
Pusher
Handle
Hook
2. Insert the hinge in the narrow vertical space in front of the fuseholder,
between the fuse holder and the fuse tray. In some cases, this may be
a tight fit. The handle should be horizontal and extend towards the
door.
fuse
hinge holder
fuse
lifting
tray
rod
handle
3. Bring the fuse into the enclosure. With the upper end of the fuse
behind the upper fuse holder, bring the lower end of the fuse to rest
on the lifting rod.
Upper
fuse
Fuse Lower
holder
clip end of
fuse
Upper
end of
fuse
4. Visually align the upper end of the fuse with the upper fuse clip, and
raise the tool handle to push the fuse into the upper clip. Verify that
the fuse is fully inserted into the upper clip.
Handle
5. Lower the handle. If the fuse was fully inserted at the top, the lower
end will naturally swing into place against the opening of the lower
fuse clip.
Lower
end of
fuse
Lower
fuse clip
Pusher
Hinge
7. Raise the handle again to push the fuse into the lower fuse clip.
Handle
Fuse
Steps to Install Front 1. Align the fuse tool so that the hook is toward the handle end and the
Fuses pusher is in the opposite position, toward the hinge.
2. Insert the hinge in the narrow vertical space in front of the
fuseholder, between the holder and the fuse tray. In some cases,
NOTE: Always wear gloves when
this may be a tight fit. The tool should rest on the fuse tray, and the
working with fuses. The fuses could
be hot and will burn unprotected handle should hang down.
hands. The photos on these pages
are factory demonstrations.
Handle
3. Bring the fuse into the enclosure. With the upper end of the fuse
behind the upper fuseholder, bring the lower end of the fuse to rest
on the V-notch in the pusher. The bulk of the fuse should be on the
hinge side of the pusher.
Fuse end
resting on
V-notch
Pusher
4. Visually align the upper end of the fuse with the upper clip, and raise
the tool handle to push the fuse into the upper clip. Verify that the
fuse is fully inserted into the upper clip.
5. Lower the handle. If the fuse was fully inserted at the top, the lower
end will naturally swing into place against the opening of the lower
fuse clip.
Fuse
Lower
fuse clip
Fuse tool
6. Raise the handle again to push the fuse into the lower fuse clip.
Handle
Steps to Remove Fuses This process is the same for all fuses.
1. Align the fuse tool so that the hook is toward the hinge end of the
tool and the pusher rests in the opposite direction, toward the
NOTE: Always wear gloves when
working with fuses. The fuses could handle.
be hot and will burn unprotected 2. Insert the hinge in the narrow vertical space in front of the
hands. The photos on these pages fuseholder, between the holder and the fuse tray. In some cases,
are factory demonstrations. this may be a tight fit.
3. Support the handle in one hand, and place the hook around the
back of the fuse as low as possible.
Hook
4. Lower the handle to extract the fuse from the lower fuse clip.
5. Manually pull the fuse from the upper fuse clip.
Flag indicator
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
CAUTION
HOT FUSE
• The body of a fuse that has blown or carried load current can be
EXTREMELY HOT and will burn unprotected hands.
• Never try to insert or remove both ends of the fuse at once. The fuse body
can be made of FRAGILE PORCELAIN (glass-like) and can shatter if
handled incorrectly.
• Always remove the lower end first.
Failure to follow these instructions can result in personal injury and
equipment damage.
NOTE: Always wear gloves when working with fuses. The body of a fuse that
has blown or carried load current can be extremely hot and will burn
unprotected hands.
Steps to Remove Fuses Remove and replace each fuse individually to avoid swapping wires.
NOTE: IEC standard 60282-1:8.4.2 1. Remove and retain the screw from the top of the connector.
states that all of the MV fuses should 2. Remove and retain the washer.
be changed whenever one fuse is
3. Remove and retain the connector from the top of the fuse.
blown.
4. Loosen the jam nut at the bottom of the fuse.
5. Unscrew the fuse from the PFCC threaded rod.
Screw
Washer
Wire lug
Connector
Fuse
Jam nut
PFCC
Steps to Install Fuses 1. Screw the fuse onto the PFCC threaded rod. Torque the fuse
following fuse supplier specifications.
2. Torque the jam nut against the fuse according to the fuse supplier
specifications.
3. Screw the connector on the fuse. Torque the connector according to
the fuse supplier specifications.
4. Install the wire lug, the washer, and the screw at the top of the
connector as shown in the figure.
5. Torque the screw to 2 lb-ft (3 Nm).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Steps to Replace Fuses 1. Remove the load from the contactor. See Operating the Contactor.
2. OPEN the disconnector to the earthed position. See Opening the
Disconnector.
3. CLOSE the cable earthing switch, if supplied, to the earthed
position. See Closing the Cable Earthing Switch.
4. Open the MV compartment door. See Opening the Medium
Voltage Compartment Door.
C
B
Steps to Place Back into 1. Complete these operations in the reverse order of removal. See
Operation Operating Instructions.
2. Complete these electric tests in compliance with the standards in
force.
Padlocking the
Disconnector
Description The full voltage reversing (FVR) starter is a full voltage, bidirectional
motor starter with an operating range of 2300–7200 V. This product will
deliver the highest starting torque (about 150% of full load torque) to the
motor terminals in either direction: forward or reverse. This starter bases
interrupting ratings on fused applications.
Forward contactor
Reverse contactor
Run contactor
Full voltage bus Soft start flexible connector (450 A max.)
Start contactor
Soft start
protection
relay Sepam Sepam Sepam
protection protection protection
relay relay relay
Run contactor
Start contactor
Description The redundant smart sequence starter application takes the smart
sequence starter and adds a second RVSS soft start section. The
second RVSS section can be used as a back up to the first RVSS section
or motor starting can be toggled between the two RVSS soft start sections
to allow one to cool down while the other is starting motors.
The second RVSS section also allows for one remote line-up of dual
voltage transfer starters (FVS) to be connected in addition to the close
coupled FVS line-up.
2-Speed, 1-Winding
Description The 2-speed, 1-winding starter (2S1W) is designed for the control of
two-speed AC motors that have a single winding. Since the motor is
single winding, the speed change is accomplished by changing the
wiring configuration using a third contactor.
The 2S1W is part of a line-up that also includes a full voltage
non-reversing starter (FVNR).
Slow-speed contactor
Shorted contactor
2-Speed, 2-Winding
Description The 2-speed, 2-winding starter (2S2W) is designed for the control of AC
motors that have separate windings for high- and low-speed operation.
Two interlocked contactors are used, with overload protection included
for each motor winding.
Fast-speed contactor
Slow-speed contactor
Star Delta
Description Star Delta starters are designed for the reduced voltage starting of
medium voltage motors by changing the configuration of the motor
windings from a Star to a Delta AC configuration without lowering the
current.
The Star Delta is part of a line-up that also includes a full voltage
non-reversing starter (FVNR).
Star-connection contactor
Delta-connection contactor
Start contactor
Run contactor
Autotransformer
Limited Duty Cycle The reduced voltage starters contain an autotransformer with a limited
Rating duty cycle rating. Unless otherwise noted, these devices are rated per
IEC 60076-11. Longer start times or more frequent starts will shorten
the life of this device.
Keylocks on an RVAT
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E, NOM-029-STPS-2011, or CSA Z462.
• Only qualified personnel familiar with medium voltage equipment are to perform work described in this set of
instructions. Workers must understand the hazards involved in working with or near medium voltage circuits.
• Perform such work only after reading and understanding all of the instructions contained in this bulletin.
• Turn off all power supplying this equipment before working on or inside equipment.
• Use a properly rated voltage sensing device to confirm that the power is off.
• Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of
electric power. Assume that all circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of
power, including the possibility of backfeeding.
• A spare key is supplied with every RVAT section. For safe operation, only 1 key should be used. The spare key
should be stored away from the equipment and only used if 1 key is lost.
• Using both keys could give access to live parts and could cause death or serious injury.
• Handle this equipment carefully and install, operate, and maintain it correctly in order for it to function properly.
Neglecting fundamental installation and maintenance requirements may lead to personal injury, as well as
damage to electrical equipment or other property.
• Do not make any modifications to the equipment or operate the system with the interlocks removed. Contact
your local field sales representative for additional instruction if the equipment does not function as described
in this manual.
• Carefully inspect your work area and remove any tools and objects left inside the equipment.
• Replace all devices, doors, and covers before turning on power to this equipment.
• All instructions in this manual are written with the assumption that the customer has taken these measures before
performing maintenance or testing.
Failure to follow these instructions will result in death or serious injury.
Keylocking with Disconnector The RVAT section is supplied with key interlocks between the
(without cable earthing switch) disconnector in the main contactor section and the start and run
contactor compartments and the autotransformer compartment.
With the disconnector in the CLOSED position, the key is held
captive. During maintenance, the disconnector can be
OPENED/earthed and the key removed for access to the RVAT
section. See Disconnector Operation and Accessing the
Medium Voltage Compartments RVAT or RVSS Soft Start
Section.
Keylocking (with cable When a cable earthing switch is supplied, the RVAT section is
earthing switch) supplied with key interlocks between the cable earthing switch in
the main contactor section and the start and run contactor
compartments, and the autotransformer compartment.
With the cable earthing switch in the OPEN or unearthed position,
the key is held captive. During maintenance, the cable earthing
switch can be CLOSED/earthed and the key removed for access to
the RVAT section. See Cable Earthing Switch Operation
(Optional) and Accessing the Medium Voltage Compartments
RVAT or RVSS Soft Start Section.
RVAT Operation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E, NOM-029-STPS-2011, or CSA Z462.
• Only qualified personnel familiar with medium voltage equipment are to perform work described in this set of
instructions. Workers must understand the hazards involved in working with or near medium voltage circuits.
• Perform such work only after reading and understanding all of the instructions contained in this bulletin.
• Turn off all power supplying this equipment before working on or inside equipment.
• Use a properly rated voltage sensing device to confirm that the power is off.
• Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of
electric power. Assume that all circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of
power, including the possibility of backfeeding.
• Handle this equipment carefully and install, operate, and maintain it correctly in order for it to function
properly. Neglecting fundamental installation and maintenance requirements may lead to personal injury, as
well as damage to electrical equipment or other property.
• Do not make any modifications to the equipment or operate the system with the interlocks removed. Contact
your local field sales representative for additional instruction if the equipment does not function as described
in this manual.
• Carefully inspect your work area and remove any tools and objects left inside the equipment.
• Replace all devices, doors, and covers before turning on power to this equipment.
• All instructions in this manual are written with the assumption that the customer has taken these measures before
performing maintenance or testing.
Failure to follow these instructions will result in death or serious injury.
Autotransformer taps
Relay Setting The current transition relay setting is user selectable with 100% being
the recommended default setting. An incomplete sequence timer will
open the starter if the current relay has not initiated transition before the
timer times out. The timer should be set to a maximum of 30 seconds.
The current relay setting may be increased to its maximum value of
120% if transition does not occur.
Tap Setting If the starter does not transition in 30 seconds with the current relay set
at its maximum of 120%, the motor does not have sufficient starting
torque for the connected load. The motor must be unloaded or the
starting torque increased.
To increase starting torque, the autotransformer must be moved from
the 65% tap setting to the 80% tap setting.
Steps to change tap settings
1. OPEN the main contactor controlling the equipment by pressing the
STOP or OPEN pushbutton on the operating panel of the main
contactor. See Operating the Contactor.
2. OPEN the disconnector in the main contactor to the earthed
position. See Disconnector Operation.
3. If supplied, CLOSE the cable earthing switch to the earthed
position. See Cable Earthing Switch Operation (Optional).
4. Using the key from the main disconnector or cable earthing switch if
supplied, OPEN the keylock allowing access to the MV
compartments. See Accessing the Medium Voltage
Compartments RVAT or RVSS Soft Start Section.
5. Change tap setting cable connections as needed. See
autotransformer cable connections in the installation instruction
guide.
The transition between the start
and run contactors is made
through the electrical control
4# 4" "
as an FVNR.
Steps to CLOSE
1. OPEN or unearth the cable
earthing switch, if supplied. See
Cable Earthing Switch
Operation (Optional).
2. CLOSE the disconnector. See
Disconnector Operation.
3. Press the START or CLOSE
pushbutton on the operator panel. Operator panel
Steps to OPEN
Press the STOP or OPEN pushbutton
on the operator panel.
Main RVAT
contactor
Description The RVSS soft start section is designed with heavy duty components to provide
a soft motor start suitable form most demanding applications. Typical
applications are as follows:
• conveyor motor
• fans
• pumps
• mining equipment
• crushers
• grinders
• chillers
• compressors
Like the RVAT section, the soft start section is always controlled from an FVNR
starter adjacent to the left of the RVSS soft start section. All motor cable
connections are made in this main FVNR. See "loadbox cable connection" in
the installation instruction guide for cable connection information.
For specific detailed instruction on ratings, operation, programming, control
connections, start-up, maintenance, replacement parts and troubleshooting,
see Schneider Electric bulletin 46032-700-10_.
Each RVSS soft start section is equipped with the following:
• bypass contactor
• silicon starter rectifier
• microprocessor-based control system
• digital display
46032-700-09G © 2003–2016 Schneider Electric All Rights Reserved 83
Motorpact IEC: Instructions for Use Section 5—Operating Instructions
Bypass contactor or
PLC (depending on
application)
Digital
display
Door latch
Microprocessor keylock
based control SCR
system assembly
RVSS soft start section exterior RVSS soft start section interior
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E, NOM-029-STPS-2011, or CSA Z462.
• Only qualified personnel familiar with medium voltage equipment are to perform work described in this set of
instructions. Workers must understand the hazards involved in working with or near medium voltage circuits.
• Perform such work only after reading and understanding all of the instructions contained in this bulletin.
• Turn off all power supplying this equipment before working on or inside equipment.
• Use a properly rated voltage sensing device to confirm that the power is off.
• Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of
electric power. Assume that all circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of
power, including the possibility of backfeeding.
• A spare key is supplied with every RVAT section. For safe operation, only 1 key should be used. The spare key
should be stored away from the equipment and only used if 1 key is lost.
• Using both keys could give access to live parts and could cause death or serious injury.
• Handle this equipment carefully and install, operate, and maintain it correctly in order for it to function properly.
Neglecting fundamental installation and maintenance requirements may lead to personal injury, as well as
damage to electrical equipment or other property.
• Do not make any modifications to the equipment or operate the system with the interlocks removed. Contact
your local field sales representative for additional instruction if the equipment does not function as described
in this manual.
• Carefully inspect your work area and remove any tools and objects left inside the equipment.
• Replace all devices, doors, and covers before turning on power to this equipment.
• All instructions in this manual are written with the assumption that the customer has taken these measures before
performing maintenance or testing.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E, NOM-029-STPS-2011, or CSA Z462.
• Only qualified personnel familiar with medium voltage equipment are to perform work described in this set of
instructions. Workers must understand the hazards involved in working with or near medium voltage circuits.
• Perform such work only after reading and understanding all of the instructions contained in this bulletin.
• Turn off all power supplying this equipment before working on or inside equipment.
• Use a properly rated voltage sensing device to confirm that the power is off.
• Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of
electric power. Assume that all circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of
power, including the possibility of backfeeding.
• Handle this equipment carefully and install, operate, and maintain it correctly in order for it to function properly.
Neglecting fundamental installation and maintenance requirements may lead to personal injury, as well as
damage to electrical equipment or other property.
• Do not make any modifications to the equipment or operate the system with the interlocks removed. Contact
your local field sales representative for additional instruction if the equipment does not function as described
in this manual.
• Carefully inspect your work area and remove any tools and objects left inside the equipment.
• Replace all devices, doors, and covers before turning on power to this equipment.
• All instructions in this manual are written with the assumption that the customer has taken these measures before
performing maintenance or testing.
Failure to follow these instructions will result in death or serious injury.
Preliminary Steps
1. OPEN the main contactor section controlling the equipment by pressing the
STOP or OPEN pushbutton on the operating panel of the main contactor
section. See Operating the Contactor.
2. OPEN the disconnector in the main contactor section to the earthed
position. See Disconnector Operation.
3. If supplied, CLOSE the cable earthing switch to the earthed position. See
Cable Earthing Switch Operation (Optional).
4. Using the key from the main disconnector or cable earthing switch if
supplied, OPEN the keylock allowing access to the MV compartments. See
Accessing the Medium Voltage Compartments RVAT or RVSS Soft
Start Section.
CAUTION
HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE
Use extreme caution while handling the contactor (25 kg) during this process. See Using a Lift Truck.
Failure to follow these instructions can result in personal injury and equipment damage.
1. Pull the contactor rail down. This will disengage the contactor
from the line and load busbar connections.
2. Roll the contactor slowly out of the section until it rests in the
wheel slot at the end of the contactor rail.
3. Carefully lift the contactor out of the guide holding the rear
wheel, and off of the contactor rail.
Contactor Guide
rail Wheel slot
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E, NOM-029-STPS-2011, or CSA Z462.
• Only qualified personnel familiar with medium voltage equipment are to perform work described in this set of
instructions. Workers must understand the hazards involved in working with or near medium voltage circuits.
• Perform such work only after reading and understanding all of the instructions contained in this bulletin.
• Turn off all power supplying this equipment before working on or inside equipment.
• Use a properly rated voltage sensing device to confirm that the power is off.
• Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of
electric power. Assume that all circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of
power, including the possibility of backfeeding.
• Handle this equipment carefully and install, operate, and maintain it correctly in order for it to function properly.
Neglecting fundamental installation and maintenance requirements may lead to personal injury, as well as
damage to electrical equipment or other property.
• Do not make any modifications to the equipment or operate the system with the interlocks removed. Contact
your local field sales representative for additional instruction if the equipment does not function as described
in this manual.
• Carefully inspect your work area and remove any tools and objects left inside the equipment.
• Replace all devices, doors, and covers before turning on power to this equipment.
• All instructions in this manual are written with the assumption that the customer has taken these measures before
performing maintenance or testing.
Failure to follow these instructions will result in death or serious injury.
Preliminary Steps
1. OPEN the main contactor section controlling the equipment by pressing the
STOP or OPEN pushbutton on the operating panel of the main contactor.
See Operating the Contactor.
2. OPEN the disconnector in the main contactor to the earthed position. See
Disconnector Operation.
3. If supplied, CLOSE the cable earthing switch to the earthed position. See
Cable Earthing Switch Operation (Optional).
4. Using the key from the main disconnector or cable earthing switch if
supplied, OPEN the keylock allowing access to the MV compartments. See
Accessing the Medium Voltage Compartments RVAT or RVSS Soft
Start Section.
CAUTION
HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE
• A locking plate is used to prevent a contactor from being installed in the wrong section. If insertion is blocked, verify
that the amperage and contactor type are correct.
• Use extreme caution while handling the contactor (25 kg) during this process. See Using a Lift Truck.
Failure to follow these instructions can result in personal injury and equipment damage.
Using a Lift Truck Use a breaker lift truck or similar device for removing or installing
contactors in an RVAT section or RVSS soft start section.
Contactor
Lift truck
MDT107 Thermal The MDT107 Thermal Diagnostic System is mounted in the equipment
at the factory for shipping. Wiring connections must be completed and
Diagnostic System tested on site before putting the equipment into service.
(Optional)
Self-Monitoring of the Module The MDT107 module has internal self-tests and is equipped with an
indicator that indicates availability:
Self-Monitoring of Sensors The module provides continuous monitoring of the connected sensor(s).
An “Off” position is included in the settings for each zone for the various
situations that can occur:
• If no sensors are connected to the module, the:
— indicator is on and flashes
— pre-alarm output contact is activated
— 6 sensor identification indicators are off
• If 1 of the 3 points of each sensor is detected as being outside the
product specifications (cut or damaged fibers, malfunction of
sensor-embedded electronics, etc.), the:
— indicator is on and flashes
— pre-alarm output contact is activated
— indicator linked to the detected measurement point flashes
• When only 1 zone is connected, the unused zone should be set to
“Off”. If this is not done, the 3 points of the related zone are detected
as outside the product specifications.
Wiring
Wiring and Operation for MDT107
5 relay output, dry contact, Module grounding terminal 24–250 Vdc and 110–240
connection terminals via green/yellow wire Vac power supply
Pre-alarm (1NO, 20-21) Alarm (ground) connection terminals
(1NCNO; 22-23-24)
Terminals
25 and 26 6 red indicators identifying
not used the sensor (zone A or B)
G
off A Zone B Zone A and the circuit/sensor at
B 7 L3 the origin of the alarm
Zone B F
C
E D
Temperature DT° build-up
setting
off -16
-18 -4
-6
L2
A Ambient T°
rise threshold Zone A
G
B
correction
(°C)
-14 -8
L1
F -12 -10
setting E D
C
Ratings
MDT107 module
Temperature rise setting factory set
- 25 °C to +70 °C
Operating and storage temperature
(-13 °F to +158 °F)
NOTICE
HAZARD OF SENSOR DAMAGE
Use caution when working in the enclosure near the MDT107 sensors. The
sensor heads can be damaged easily.
Failure to follow these instructions can result in equipment damage.
Field Load
shapers box
MDT107 Sensors
Location
Field Shapers
Load Box
Setting the Temperature The module is equipped with 2 mechanical selector switches for setting
Rise Thresholds the temperature rise threshold for each zone. Each switch has 8
possible setting positions. The factory settings are shown in the table
off A below.
G B The selector switches are accessible from the front panel. They are
Zone B
F C protected by a sealed cover. To change the setting for a zone:
ΔT° build-up E D Steps to Set the Temperature Rise Thresholds
setting
off A 1. Remove the protective cover.
G B
Zone A 2. Insert the tip of a screwdriver into one of the arrow-shaped slots.
F C
NOTE: Use a flathead screwdriver with a tip width of 0.15 in. (4 mm).
E D
3. Turn the switch to the desired setting.
4. Replace the protective cover.
Zone A Zone B
Contactor rated current (A)
field shapers connection load box connection
200 C B
400 E D
450 F D
720 G C
Setting the Ambient The module contains a mechanical selector switch for correcting the
Temperature Correction ambient temperature measured on the MDT107 module. The switch has
8 possible setting positions. It is accessible from the front panel and is
protected by a sealed cover. To change a setting:
Steps to Set the Ambient 1. Measure the temperature in the LV cabinet where the MDT107
Temperature module is located, then measure the ambient temperature outside
the switchgear. Note the difference in temperature between the two
locations.
2. Remove the protective cover.
3. Insert the tip of a screwdriver into the arrow-shaped slot.
NOTE: Use a flathead screwdriver with a blade width of 0.15 in.
(4 mm).
4. Turn the switch to the setting closest to the temperature difference
measured in step 1.
5. Replace the protective cover.
-18 -4
Ambient T° -16 -6
correction
(°C) -14 -8
-12 -10
Section 6— Maintenance
Preventative Inspect the equipment periodically to determine the conditions to which
the units are subjected. After determining the environmental conditions
Maintenance according to the guidelines in this section (see Environmental
Conditions below), perform inspections and maintenance according to
the following table.
Standard Aggressive
Component Ideal conditions
conditions conditions
Polyester disconnector housing
Housing interior (busbar and mechanism) Every 5 years Every 2 years Once per year
Housing
See Environmental Conditions for definitions.
Environmental Conditions
Ideal Conditions • Unit is installed and commissioned in accordance with the
manufacturer’s instructions.
• Humidity is below 40%, and there is no dripping water
• Indoor, protected from the weather
• Minimum of dust and air circulation
• Ambient temperature is between - 5 °C and 40 °C
• Altitude less than or equal to 1000 m, if above 1000 m, a derating
coefficient will be applied (please consult your local Schneider
Electric representative)
• No contact with any chemical agents (salt, H2S, etc.)
• No infestation of any animal life (rodents, insects, etc.)
• No contact with any plant life (mold, etc.)
• No earth movements (for example, seismic events)
• No damage to the unit of any kind
• No operating problems of any kind
• No abnormally high number of operations
• No abnormally high number of faults
• No overvoltage or overcurrent (above ratings)
• Thermal scanning of the joints (where possible) at least once a year,
or optional thermal diagnostics unit is installed
Standard Conditions Same as "ideal conditions" with the following exceptions:
• Humidity below 60%
• The unit must not be subjected to regular extremes of temperatures
greater than 40 °C or less than - 30 °C
• No regular thick covering of leaves or other debris
Aggressive Conditions Any environmental conditions that have:
• Humidity above 60%
• Unit subjected to temperatures greater than 40 °C or less than - 30 °C
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E, NOM-029-STPS-2011, or CSA Z462.
• Only qualified personnel familiar with medium voltage equipment are to perform work described in this set of
instructions. Workers must understand the hazards involved in working with or near medium voltage circuits.
• Perform such work only after reading and understanding all of the instructions contained in this bulletin.
• Turn off all power supplying this equipment before working on or inside equipment.
• Use a properly rated voltage sensing device to confirm that the power is off.
• Always look through the rear viewing window to verify that the MV compartment door is OPEN, before removing
the MV cable compartment cover.
• Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of
electric power. Assume that all circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of
power, including the possibility of backfeeding.
• Handle this equipment carefully and install, operate, and maintain it correctly in order for it to function
properly. Neglecting fundamental installation and maintenance requirements may lead to personal injury, as
well as damage to electrical equipment or other property.
• Do not make any modifications to the equipment or operate the system with the interlocks removed. Contact
your local field sales representative for additional instruction if the equipment does not function as described
in this manual.
• Carefully inspect your work area and remove any tools and objects left inside the equipment.
• Replace all devices, doors, and covers before turning on power to this equipment.
• All instructions in this manual are written with the assumption that the customer has taken these measures before
performing maintenance or testing.
Failure to follow these instructions will result in death or serious injury.
Section 8— Troubleshooting
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E, NOM-029-STPS-2011, or CSA Z462.
• Only qualified personnel familiar with medium voltage equipment are to perform work described in this set of
instructions. Workers must understand the hazards involved in working with or near medium voltage circuits.
• Perform such work only after reading and understanding all of the instructions contained in this bulletin.
• Turn off all power supplying this equipment before working on or inside equipment.
• Use a properly rated voltage sensing device to confirm that the power is off.
• Always look through the rear viewing window to verify that the MV compartment door is OPEN, before removing
the MV cable compartment cover.
• Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of
electric power. Assume that all circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of
power, including the possibility of backfeeding.
• Handle this equipment carefully and install, operate, and maintain it correctly in order for it to function
properly. Neglecting fundamental installation and maintenance requirements may lead to personal injury, as
well as damage to electrical equipment or other property.
• Do not make any modifications to the equipment or operate the system with the interlocks removed. Contact
your local field sales representative for additional instruction if the equipment does not function as described
in this manual.
• Carefully inspect your work area and remove any tools and objects left inside the equipment.
• Replace all devices, doors, and covers before turning on power to this equipment.
• All instructions in this manual are written with the assumption that the customer has taken these measures before
performing maintenance or testing.
Failure to follow these instructions will result in death or serious injury.
MV compartment door cannot be • Check that the disconnector is in the OPEN/earthed position.
opened • Check that the disconnector access port is CLOSED.
Disconnector cannot be operated • Check that the MV compartment door is CLOSED and the handle
latched.
• Check that the contactor is in the OPEN position.
• Check that the earthing switch (if supplied) is OPEN and the access
port is CLOSED.
Disconnector access port cannot be • Check that the disconnector is fully OPEN or earthed.
CLOSED • Check that the key interlock keys (if supplied) are in the proper position.
Disconnector access port cannot be • Check that the disconnector is fully OPEN or earthed.
OPENED • Check that the key interlock keys (if supplied) are in the proper position.
Cable earthing switch cannot be • Check that the contactor is in the OPEN position.
operated • Check that the disconnector is in the OPEN/earthed position.
• Check that the MV compartment door is CLOSED and the handle is
latched.
• Check that the disconnector operating access port is OPEN.
Contactor will not CLOSE electrically • Check that the disconnector is CLOSED.
• Check that the disconnector access port is CLOSED.
• Check the control fuses.
• Check the closing coil circuit.
• Check for loose terminal connections.
• Check for a loose plug connection in the LV cabinet.
• Check the electrical interlocks. See equipment drawings provided
with each line-up.
• Check the interlock linkage to the contactor.
Latched contactor will not OPEN • Check the control fuses.
electrically • Check the trip coil circuit.
• Check for loose terminal connections.
• Check for loose plug connections in the LV cabinet.
• Check the electrical interlocks. See equipment drawings provided
with each line-up.
Voltage presence indicator does not • Test for voltage on 2 of the test ports on the indicating box. Verify the
illuminate MV voltage is truly present.
Section 9— Glossary
auxiliary contacts Sets of contacts mechanically operated by the disconnector or
the contactor.
auxiliary section A section that contains either low voltage or medium voltage components
that require a different mounting than a typical starter section.
cable earthing switch A sliding 2-position device (CLOSED position earthed). Designed to
discharge the capacitance to earth up to a 5 kA fault.
capacitive divider A capacitor attached to the phase busbar that is used to send a reduced
voltage signal to a neon light for voltage presence indication.
contactor The mobile vacuum interrupting device used for establishing and
interrupting the medium voltage power in the circuit.
control power transformer (CPT) A transformer that reduces medium voltage to low voltage for control circuit
use.
current transformer (CT) An instrument transformer intended to have its primary winding connected
in series with the conductor carrying the current to be measured or
controlled.
disconnector A rotating, 2-position switch that is used to connect the main power source
in the closed position and to connect to the equipment earth in the open
position.
enclosure The external surface of a section that prevents access to the section’s
internal parts.
full voltage starter A motor starter which connects the line voltage across the motor terminals
in one step.
fuse, medium voltage A medium voltage fuse capable of interrupting all currents from the rated
breaking capacity to the minimum breaking current.
fuseholder An assembly of insulated fuse tubes that house the primary contacts of the
medium voltage fuse connection for the CPT and VT fuses.
insulator A device intended to insulate and give rigid support to busbars throughout
the equipment.
internal arc tunnel An air chamber or compartment attached to the roof of the switchboard line-
up. This compartment is designed for containing or distributing the gases
should an internal arc event occur.
internal arc withstand A description for the added features of the enclosure which help in the
withstand or containment of a gas discharge should an internal arc event
occur.
low power current transformer A device that transforms a medium voltage circuit current into a
(LPCT) proportional low voltage signal.
medium voltage compartment A switchboard compartment which houses any medium voltage devices.
power factor correction capacitor A device that counteracts the undesirable effects of electric loads which
(PFCC) create a power factor less than 1.
starter The combination of all the switching means necessary to start and stop a
motor with suitable overload protection, i.e., a section mounting a contactor
and fuses that is used for starting motors.
voltage presence indication system The VPIS is a light module mounted on the front of the equipment that gives
(VPIS) an indication when voltage is present on the MV cables. Energy is provided
from a capacitive divider (see definition for capacitive divider).
voltage transformer (VT) An instrument transformer intended to have its primary winding connected
in shunt with a power supply circuit for measuring the voltage.
46032-700-09G, 04/2016
Replaces 46032-700-09F, 11/2011