Webpower Help: User'S Guide
Webpower Help: User'S Guide
Webpower Help: User'S Guide
WebPower Help
Configuration Program
DC Power Supply System
356807.063
Information in this document is subject to change without notice and does not
represent a commitment on the part of Eltek.
FAQs 31
Frequently Asked Questions, FAQs ........................................................................................ 31
Generic FAQs ............................................................................................................ 31
WebPower FAQs ....................................................................................................... 32
PowerSuite FAQs ...................................................................................................... 43
Functionality Description 45
Functionality Overview ........................................................................................................... 45
About Power System Configuration .......................................................................... 46
Menu Options - Smartpack2 Master Controller ........................................................ 47
Power System Functions.......................................................................................................... 62
Networking the Controller - Access Methods ........................................................... 62
Power System Configuration & Monitoring – Methods ............................................ 71
DC Plant Information ................................................................................................ 79
Location – Map Coordinates ..................................................................................... 79
System Configuration ~ General ............................................................................... 81
System Voltages Levels ............................................................................................ 81
System Commands .................................................................................................... 82
System Calibration .................................................................................................... 83
Types of System Logs ............................................................................................... 95
Alarm Messages, (Log) ........................................................................................... 106
Alarm Reset ............................................................................................................. 107
Power System’s Operation Mode ............................................................................ 107
About AC, DC Earthing Systems ............................................................................ 108
Earth Fault Detection ............................................................................................... 109
About Negative & Positive DC Distribution Systems ............................................. 111
CAN bus Termination ............................................................................................. 111
Climate Control Functions - Outdoor Cabinets ....................................................... 114
Mains Functions..................................................................................................................... 121
Mains Phase Assignment versus Rectifier ID.......................................................... 121
Generator Functions............................................................................................................... 123
AC Generator as AC Mains ..................................................................................... 123
Configuration of Generator Functionality ............................................................... 127
Generator Control Logic – Flowchart...................................................................... 140
Rectifier Functions................................................................................................................. 143
Plug-and-Play Rectifiers .......................................................................................... 143
Index 261
Welcome to WebPower
WebPower Online Help System, 356943.063, 4v5a, 2012-02-08
Copyright (page 237)
WebPower Online Help is designed to help you get started using WebPower, the
web-based user interface (GUI). It also contains overview information and
procedural steps for performing common configuration tasks.
How to Find Topics
Use following buttons on the toolbar
Context button: a complete list of all topics, in a logical order, like a book’s
table of content
Index button: a complete list of all topics, in alphabetical order, like a book’s
index
Search button: enter the word or term you want to find, and a list of topics
containing the term are displayed
Favorites: click this button when you have found a topic that you should want to
come back to at a later stage
Online Help Main Sections
WebPower Online Help is divided into the following sections:
“Getting Started” on page 2
Provides introductory information about WebPower. It also includes
explanation of important concepts, system requirements, about the
controllers, how to log in, the program’s access levels, etc.
“Understanding the WebPower Interface” on page 6
Describes the location of the different elements in the WebPower user
interface, the home page window, the window panes, icons, toolbar, etc.
“Using WebPower” on page 10
Provides detailed information about the web-based user interface, the
configuration web pages, subpages and commands. It also explains
procedures to accomplish common system configuration tasks using
WebPower
Getting Started
This section provides introductory information about the WebPower firmware. It
also includes an explanation of important concepts, system requirements, about
the controllers, how to log in, the program’s access levels, etc.
Server
Compack
controller Ethernet Local Area Network
(LAN)
WebPower also provides you with a graphical interface for local or remote
monitoring and control of the DC power system.
Notice:
The WebPower firmware is tested and approved for MS Windows with
the latest versions of the following Web browsers:
Microsoft Internet Explorer and Mozilla Firefox.
Other browsers and operating systems may also be used, though
faultless behaviour cannot be guaranteed.
Compack Controller
The Compack controller is a DIN rail mounted monitoring and
control unit used in the Micropack DC power systems. The
controller is also used in larger Eltek’s Compack-based power
systems.
It monitors and controls the whole system, and implements several
network protocols for local and remote system configuration via Web browser
and existing network management system (NMS).
Using the UDP tunneling protocol, the powerful PowerSuite application may
also be used for system configuration from a local or remote Internet connected
personal computer.
Smartpack Controller
The Smartpack controller is a monitoring and control unit
used as the vital nerve center of the DC power plant. You
operate the system directly from the elegant front panel,
using three front keys and the LCD-display; they represent
the main interface between you and the system.
You can also operate the system remotely via modem, Ethernet and the Web.
The module then utilizes the USB or RS232 ports to interface with NMS or Web
adapters.
The Smartpack controller’s standard front panel consists of a three-button
keypad, a graphic display, an USB port and 3 LED lamps.
The Smartpack controller has the following LED indications:
Alarm (red) indicates an alarm situation (major alarm)
Warning (yellow) indicates an abnormal situation (minor alarm)
“Power” (green) indicates that the power supply is ON or OFF
You can operate the DC power system from the Smartpack controller, by means
of display menus and sub-menus.
For more advanced operation, you can use the WebPower GUI from a computer,
or install and run the PowerSuite application.
Read more about the controller, networking and monitoring methods in the
Control System Functions (page 188) topic, in the Functionality Description
section.
You can find the Access Level assigned to the User Login Account you used to
log in, by looking at the Power Summary pane (top right). Refer also to the topic
“WebPower Home Page” on page 6.
6
5
4
3
7
8
2
1
Note that the web browser must have the Pop-ups function enabled, as the
configuration web pages employ Java script navigation. Read topic How to
Enable Pop-ups in the browser -- Internet Explorer (page 32) in the FAQs
section.
7
8
7
8
1
11
4
3
14 15
13 16 12
The “LoadCurrent” alarm monitor (12) does not really measure the
load current. It raises alarms based on the calculation of the load current
(the difference between the rectifier current “RectifierCurrent” and the
battery current “BatteryCurrent”). Read also the Load Current
Calculation (page 157) topic in the Functionality Description section.
In addition to the Power Summary pane, these alarm monitor are also
displayed in the “Battery web page” on page 29.
The “RectifierCurrent” alarm monitor (16) does not really measure
the rectifier current. It raises alarms based on the addition of all the
rectifier currents.
Using WebPower
This section provides detailed information about the web-based user interface,
the configuration web pages, subpages and commands. It also explains
procedures to accomplish common system configuration tasks using WebPower.
WebPower has 2 main functional areas, where you open configuration web pages
and subpages to interact and configure the DC power supply system.
o Toolbar
o Power Explorer pane
System Configuration
WARNING: To register and edit the data you must log in using an
account with Access Level Factory (Admin).
The global position data is stored in the controller, and used by the MultiSite
Monitoring PC Application software to dynamically display the position of
power system installations in maps.
o If required, select the desired data format and register the parameters
by clicking on the text fields and typing appropriate values
o Click on the Save button, to save the changes
Password tab
The Password tab (2) -- in the System Configuration web page -- enables you to
change the access level, the user name and password of up to 10 logging
accounts.
NOTICE:
To register and edit the data you must log in using an account with
Factory (or Admin) Access Level.
Otherwise, you are only able to change your account’s password
(requires also the administrator’s password).
You can find the Access Level assigned to the User Login Account you used to
log in, by looking at the Power Summary pane (top right). Refer also to the topic
“WebPower Home Page” on page 6.
Current Access Level:
“admin”
System Configuration 2
1 3
4
7 6
o If required, select the desired user name, access level and password (3,
4 and 5) for the displayed account number, by clicking on the text
fields, radio buttons and typing appropriate values.
The configuration web page displays the User Login Account you used to log in;
e.g. “...account #1”. If this account’s access level is “administrator / factory”,
then you can edit the following:
Current User Name (3):
click on the text field and type a new user name for this account
Access Level (4):
click on the radio button for the Access Level you want to assign to this
account, e.g. the radio button for “administrator / factory”.
Read more about available access levels and default accounts in topic
“Accessing the Controller and Logging In to WebPower” on page 5
Password (5) fields:
click on the text fields and type the login account’s current password
(case sensitive) and twice the password you want to change to
If you are logged in using an account with Factory (or Admin) Access Level,
you will also see the “Account Overview” button (7). Click on this button will
enable you to edit existing logging accounts and create new ones.
For information about how to create new User Login Accounts and how to edit
existing User Login Accounts, read topic “How to Create New User Login
Accounts in WebPower” (page 35)
1
View links
3
2 4
Sorted column
A row
per Battery Test
The configuration web page displays a result table, where each row (2) of data
represents a battery test. The battery quality, calculated by completed battery
tests, is also displayed in one of the columns.
If required, you can
-- Sort the table, by clicking on one of the column’s heading (3) that
you want to sort after; e.g. the “Start Time” heading. An arrow head
indicates the actual sorted column
-- View more details of each battery test and export the test data to a
file in your hard disc, by clicking on the “View” links (4). Refer to topic
“Battery Test Log subpage” on page 16
Click on the Close button (5), to close the window
For more information about how to carry out battery tests, read topic “Battery
Test subpage” on page 29. If required, read also about types of battery tests in
topic Battery Tests (page Error! Bookmark not defined.) .
3 2
4
The configuration web page displays the detailed test results (2), (3) for a
specific battery test, e.g. “...Data for test id: 07”.
You can do the following with the battery test results:
o Click on the “Select Unit” drop-down arrow (4) and select the battery
bank that you want to see test results for.
o Click on the data check boxes (checked) to enable the battery test data
types to display in the table.
Click again to (unchecked) to disable the data types you do not want to
display.
o Click on the “Get the Data” button (4), to display the selected types of
data in the table
AND
o Click on the “Extract csv data to new window” (5), to display the
battery test results in a new browser window, where you then can save
the data as a simple file, CVS- structured (Comma Separated Values),
easy to be imported to other computer applications
For more information about how to carry out battery tests, read topic “Battery
Test subpage” on page 29. If required, read also about types of battery tests in
topic Battery Tests (page Error! Bookmark not defined.) .
Event Log
2
3
The configuration web page displays the Event Log, which is a log of power
system events automatically registered by the system controller. The log is stored
in the system’s control unit(s).
Read more about “events” in the topic Alarm Monitors (page Error! Bookmark
not defined.), in the Functionality Description section.
The configuration web page enables you to do the following:
o Click on the Next Page and First Page buttons (2) to display the next
page of system events, and return to the first page respectively
o If required, click on the “Click here” link (3) to display a dialog box,
where you can click in the Open or Save buttons (4) to open or save an
XLM file containing the complete log of system events (5)
2
Network Config
eMail tab
The eMail tab (2) -- in the Network Config web page -- enables you to
configure the parameters for an external SMTP E-mail server that the controller
may use to send warning and alarm e-mails to specified e-mail addresses.
WARNING: To register and edit the data you must log in using an
account with Access Level Factory (Admin).
WARNING: To register and edit the data you must log in using an
account with Access Level Factory (Admin).
2
Network Config 7 3
4
5
1 6
8
WARNING: The system controller may restart, when any of the TCP/IP
parameters are changed.
The TCP/IP parameters are determined by entering or changing the controller’s
IP address and Subnet Mask. The Default Gateway and DNS Server addresses
are usually “0.0.0.0”.
DHCP enable: (7)
click on the check box to enable (checked) or disable (unchecked) the
controller’s Dynamic Host Configuration Protocol (DHCP).
When enabled, the controller can automatically obtain necessary access
data to operate in an existing Local Area Network (LAN), and you can
only enter data in the Device Name field.
By default, the controllers have DHCP enabled.
Read more in topic Controller’s Default IP Address (page 62), in the
Functionality Description section.
WARNING!
Never enter Network Mask (Subnet masks) <0.0.0.0> or
<255.255.255.255> as they are not valid masks, and in the worst case
may render the controller or LAN device inaccessible.
SNMP tab
The SNMP tab (2) -- in the Network Config web page -- enables you to see and
configure the controller’s SNMP agent.
WARNING: To register and edit the data you must log in using an
account with Access Level Factory (Admin).
5 6
7
8
11 10
9
The controllers implement an SNMP agent which interfaces with the Network
Management System (NMS), enabling remote monitoring via the standard
SNMP messaging commands SET, GET and TRAP.
The SNMP agent responds to SNMP’s GET and SET commands, and forwards
TRAPs to designated recipients when critical conditions occur to the DC power
system, as configured in the controller.
The GET commands provide the NMS with remote monitoring status — e.g.
Battery status, etc. — of the power system.
The SET commands enable the NMS to remote control the power system, e.g.
changing the output voltage.
The TRAP commands are unsolicited alarm messages that the power system
sends to the NMS, when critical situations occur.
Read more in topic Monitoring -- via Network Management System (page
Error! Bookmark not defined.), in the Functionality Description section.
WARNING!
Address “255.255.255.255” is not allowed on the traps’ address fields.
NOTICE:
Community Strings or passwords can be max 19 characters long. Valid
characters are A-Z, a-z, 0-9 and special characters ~@#%^&_-+=:,. Do
not use any other characters
NOTICE:
Community Strings or passwords can be max 19 characters long. Valid
characters are A-Z, a-z, 0-9 and special characters ~@#%^&_-+=:,. Do
not use any other characters
WARNING: To register and edit the data you must log in using an
account with Access Level Factory (Admin).
Network Config
2
1 3
4
o If required, click on the text field (3) and type a new web address
o Click on the Save button, (4) to save the changes
NOTICE!
Contact your closest Eltek representative to get the active log in details
(user name and password).
AO Group number
AO Group status
AO Group name
1 2
3
4
The configuration web page displays an overview of the status of all alarms
(Alarm Output Groups, AOG) in the power system.
The overview lists two sections of AOGs: one used to group alarm relay outputs
(2) and another used to group LVD latching contactors (3).
System events trigger alarm conditions in the corresponding Alarm Monitors,
which then activate the assigned Alarm Output Groups.
Read more about “events” and how alarms are generated, in the topics Alarm
Monitors (page Error! Bookmark not defined.) and Alarm Output Groups, in
the Functionality Description section.
The configuration web page enables you to do the following:
o Click on the Reset Active Alarms button (4) to reset the system’s
alarm monitors, and refresh the overview of Active Alarm Output
Groups.
If the events that caused the alarms are still present, the corresponding
AO Groups will again be in alarm condition
To change the WebPower Online Help default web address, if required, read
topic “Online Help Files tab” on page 24.
Power System
Following configuration web pages are used to interact with DC power supply
system, and configure it with parameters that apply to the system in general.
Mains
Following configuration web pages are used to interact with DC power supply
system, and configure it with AC Mains related parameters.
Rectifiers
Load
Following configuration web pages are used to interact with DC power supply
system, and configure it with parameters related to the system’s DC load.
Battery
Following configuration web pages are used to interact with DC power supply
system, and configure it with battery related parameters.
Read about Overview Battery Measurements (page 160), in the Functionality
Description section.
LVBD subpage
Outputs
Following configuration web pages are used to interact with DC power supply
system, and configure its output parameters.
Control System
Following configuration web pages are used to interact with DC power supply
system, and configure its parameters.
Generic FAQs
PowerSuite and WebPower
Question:
What’s the difference between PowerSuite and WebPower?
Answer:
PowerSuite is a program to be installed and run on a personal computer, while
WebPower is a graphical user interface (GUI) based on HTML pages that the
controller serve to a standard web browser for viewing. No program installation
required.
WebPower implements the most common configuration task, while PowerSuite
enables full configuration of the power system.
Type of Logs
Question:
What’s the difference between the types of logs or data records displayed by
Eltek’s power systems, and where do I find them?
Answer:
The control system implements following types of logs:
Event Log (system events)
Data Log (key system data)
Data Logging (key system data)
Measurement Logs
o Energy Log
o Load Monitor Energy Log
o Mains Outage Log
o Generator Run Hours Log
o Generator Fuel Consumption Log
o Battery Discharge Cycles Log
WebPower FAQs
How to Enable Pop-ups in the browser -- Internet Explorer
Question:
How do I enable Pop-ups in the Internet Explorer browser?
Answer:
You must allow the Web browser to show pop-ups from the controller’s
configuration web pages, as the pages’ navigation buttons, etc. employ Java
script-based navigation.
Internet Explorer and other Web browsers usually have the Pop-Up Blocker
feature enabled, thus stopping annoying pop-up ads and pop-up windows while
“surfing” the Internet.
This topic explains how to configure the Pop-up Blocker to allow pop-ups from
the controller’s configuration web pages (e.g. IP address <172.16.5.221>), using
Internet Explorer.
Carry out the following steps, if the browser’s Information bar displays that the
Pop-up Blocker has blocked the page, after clicking on one the buttons on the
Power Explorer tool bar:
1. Click on the Information bar
2. Select command “Always Allow Pop-ups from This Site”,
from the drop-down menu
3. Click “Yes”,
in the “Allow pop-ups from this site?” dialog box
Information Bar
(Pop-up blocked…)
Power Explorer
Tool Bar
(Configuration
buttons)
Compack
controller’s IP
address
(Example)
Answer:
To view the controller’s configuration pages (GUI) in your Web browser and be
able change the “admin” account’s user name and password, you have to log in
using the “admin” login account.
Following table shows the WebPower’s default, factory set User Login
Accounts.
“Enter” link
Note that the Web browser must have the Pop-ups function enabled, as the configuration web pages employs Java
script navigation.
Read the topic “How to Enable Pop-ups in the browser -- Internet Explorer” on page 32.
— Clicking in the “Current User Name” field (3), and typing the login account’s new user name
— Selecting the Access Level for the login account; e.g. the “administrator/factory” (4)
— Clicking in the Password fields (5), and typing
the login account’s current password (case sensitive) and twice the password you want to change to
— Then clicking on the “Save” button (6), to activate the new password
Access Level 3
radio buttons
4
System Configuration
5
1
6
Answer:
To view the controller’s configuration pages (GUI) in your Web browser and be
able to create new User Login Accounts or change registered user names and
passwords, you have to log in using one of the login accounts with Factory (or
ADMIN) Access Level, either the default “admin” account or an already created
account with the Factory (or ADMIN) Access Level.
Following table shows the WebPower’s default, factory set User Login
Accounts.
“Enter” link
Note that the Web browser must have the Pop-ups function enabled, as the configuration web pages employs Java
script navigation.
Read the topic “How to Enable Pop-ups in the browser -- Internet Explorer” on page 32.
3. Create the new Login Account – or edit existing account – by carrying out the following:
— Click on the “System Configuration” button (1), on the Power Explorer toolbar
— Click in the Current User Name field (9), and type the user name for the new account,
or edit the name of the existing account.
— Select the radio button for the Access Level for the new login account; e.g. the “control/service” (10)
— Then click on the “Save” button (12), to activate the new login account data.
System Configuration 2
3
4
1
7 8
9
10
11
12
Note that the Web browser must have the Pop-ups function enabled, as the configuration web pages employs Java
script navigation.
Read the topic “How to Enable Pop-ups in the browser -- Internet Explorer” on page 32.
TCP/IP tab
Device Name’s field
Save button
Now the Eltek Network Utility window will display the new device name.
Answer:
In MS Windows, you can always check the IP address, subnet mask, status, etc.
of your personal computer’s network card (NIC), by opening the “Network
Connections” window and looking at the Detail pane on the left side of the
window.
(Example)
OR
If this command is not displayed in the computer’s “Start” menu,
— Making a note of the IP address and Subnet mask displayed in the Details panel, on the left side of the window.
E.g. IP address: <172.16.5.192>, Subnet mask: <255.255.252.0>
(Example)
(Example)
NOTICE:
You might need to change the IP address of your computer, for example if you want to connect the computer to a
controller or network device with fixed IP address.
WARNING!
Never enter Network Mask (Subnet masks) <0.0.0.0> or <255.255.255.255> as they are not valid masks, and in the
worst case may render the controller or LAN device inaccessible.
PowerSuite FAQs
Cannot Find the Com Port Number
Question:
Why clicking on the “Find COM Port #” button does not display the COM port
number?
You find the “Find COM Port #” button on dialog box Site Manager dialog box
in PowerSuite Online Help.
Functionality Overview
Functionality Description Online Help System, 350020.073, 1v4, 2012-02-08
Copyright
This section offers a more detailed description of the functionality that Eltek has
implemented in Smartpack2-, Smartpack- and Compack-based DC power supply
systems.
The Smartpack2 Master controller’s menu options are grouped in these task-
oriented logical groups, as described in the topics below.
(lower area L)
Battery Temp 1.1 29 Celsius
Battery Temp 1.2 0 Celsius
Battery Temp 1.3 27 Celsius
NOTICE:
The default Service Access Level password or Pin-Code is <0003>. We
strongly recommend changing the passwords as soon as the power
system is installed.
Read about “Access Levels” on page 188.
The parameters are organized in system-oriented groups: Power System, Mains,
Generator, Rectifier, etc.
Refer to these topics (Power System, Mains, Rectifiers, etc.) for more
information about the System Configuration parameters.
2.2 Mains
Available options in Smartpack2 Master Controller’s submenu:
System Configuration > Mains
2.3 Rectifiers
Available options in Smartpack2 Master Controller’s submenu:
System Configuration > Rectifiers
2.4 Load
Available options in Smartpack2 Master Controller’s submenu:
System Configuration > Load
2.5 Battery
2.6 Generator
Read topic “AC Generator as AC Mains” on page 123, for available options in
Smartpack2 Master Controller’s submenu:
System Configuration > Generator
NOTICE:
The default Service Access Level password or Pin-Code is <0003>. We
strongly recommend changing the passwords as soon as the power
system is installed.
Read about “Access Levels” on page 188.
3.1 Mains
Available options in Smartpack2 Master Controller’s submenu:
Alarm Configuration > Mains
>> Read also the topic “Typical Parameters for Alarm Monitors” on page 191.
3.2 Rectifiers
Available options in Smartpack2 Master Controller’s submenu:
Alarm Configuration > Rectifiers
>> Read also the topic “Typical Parameters for Alarm Monitors” on page 191.
3.3 Load
Available options in Smartpack2 Master Controller’s submenu:
Alarm Configuration > Load
>> Read also the topic “Typical Parameters for Alarm Monitors” on page 191.
3.4 Battery
Available options in Smartpack2 Master Controller’s submenu:
Alarm Configuration > Battery
>> Read also the topic “Typical Parameters for Alarm Monitors” on page 191.
3.5 Inputs
Available options in Smartpack2 Master Controller’s submenu:
Alarm Configuration > Inputs
>> Read also the topic “Typical Parameters for Alarm Monitors” on page 191.
3.6 Outputs
Available options in Smartpack2 Master Controller’s submenu:
Alarm Configuration > Outputs
>> Read also the topic “Typical Parameters for Alarm Monitors” on page 191.
3.8 Generator
Available options in Smartpack2 Master Controller’s submenu:
Alarm Configuration > Generator
>> Read also the topic “Typical Parameters for Alarm Monitors” on page 191.
>> Read also the topic “Typical Parameters for Alarm Monitors” on page 191.
Commands options
The options in this logical group let you issue or activate specific commands,
such as resetting manual alarms, deleting the event log, starting battery tests, etc.
Issuing commands is allowed at this level, using a Pin-Code.
NOTICE:
The default Service Access Level password or Pin-Code is <0003>. We
strongly recommend changing the passwords as soon as the power
system is installed.
Read about “Access Levels” on page 188.
Event Log
The Event Log is a record of system related events automatically registered by
the system controller.
Example of Event Log in Smartpack2 Master Controller’s submenu:
Logs/Report > Event Log
# Date and Time Description Event Note
yyyy.mm.dd hh:mm:ss RectifierError MinorAl:On
yyyy.mm.dd hh:mm:ss SymmVolt 1.4 MajorAl:On
yyyy.mm.dd hh:mm:ss LVD close Info:On
yyyy.mm.dd hh:mm:ss Door alarm MajorAl:Off
yyyy.mm.dd hh:mm:ss OutdoorTemp 81.1 Info:Off
----
You can also save the Even Log to a storage media -- read about “Up/Download
options” on page 61 – or use WebPower or PowerSuite to delete, print and save
the log to a file in your computer.
Read about “Types of System Logs” on page 95.
----
Inventory Report
The Inventory Report presents information that describe the power system, the
site’s name , serial number, installation and service dates, software name, etc.
Example of Inventory Report table in Smartpack2 Master Controller’s submenu:
Logs/Report > Inventory Report
# Description Note
Company
Site
Model
Install Date
Serial N
Service Date
Responsible
Message 1
Message 2
(Installed HW and SW info, part #, serial #, version #, etc.)
Statistics options
This logical group collects and presents relevant system data and calculated
statistics, such as average results, peak values, etc.
Example of the Statistics table available in Smartpack2 Master Controller’s
submenu:
Statistics
# Description Reset Average Peak Note
BatteryVoltage No 52,48 52,61
BatteryCurrent No -35 0
Battery Temp No 41 0
Load Current No 35 50
Rectifier Current No 75 120
Mains Volt 1 No 225 235
Commissioning options
This logical group presents a generic description of the steps required to carry
out the power system’s commissioning.
Up/Download options
The options in this logical group let you upload firmware to connected
controllers and control units, as well as download or save system related logs,
etc.
In addition to firmware, this group’s options offer you the possibility of
uploading and saving system configuration files.
NOTICE:
Using the controller’s front panel keypad, you can only upload &
download to the controller’s SD card. Using the WebPower or
PowerSuite GUI, you can also upload & download to other storage
media, such as a computer’s hard drive or similar.
The Up- and Download options are organized in following groups:
Save Event Log
A command that saves to a storage media the system related log of
power system events, automatically registered by the system controller.
Read about “Logs and Reports options” on page 59, or about “Types of
System Logs” on page 95
Save Data Log
A command that saves to a storage media the control unit related log of
key system data (voltages, current and temperature values) registered by
the system controllers, or by other connected control units (e.g. I/O
Monitor, Mains Monitor).
Read about “Types of System Logs” on page 95
Save Energy Log
A command that saves to a storage media the system related log that
presents the power system’s energy usage, (Wh).
Read about “Types of System Logs” on page 95
Save /Load Config
A command that saves to a storage media the System Configuration file
<*.XML>, with all the specific parameters and settings.
Also, you can upload a similar, specific System Configuration file
<*.XML> to the controller, e.g. for automatic configuration of specific
functions
Software Upgrade
which offers you to upgrade the firmware in connected controllers and
control units, by uploading files stored in the Smartpack2 Master
controller’s SD card.
After accessing the controller, you can read a short description about available
methods to configure and monitor the DC power supply system, which you find
in topic “Power System Configuration & Monitoring – Methods” on page 71.
WARNING:
Some controllers may have the Dynamic Host Configuration Protocol
(DHCP) enabled, instead of static IP address. Thus, they can
automatically obtain necessary access data to operate in an existing
Local Area Network (LAN), based on the Ethernet communication
technique and the TCP/IP protocol suite.
NOTICE:
In short, two LAN devices (e.g. a controller and a computer) can
communicate with each other, if they have different IP addresses and
are in the same subnet.
A Subnet Mask is used to determine what subnet an IP address or
device belongs to.
For example, all devices with IP address <169.254.52.XXX> and
subnet mask <255.255.255.0> (where XXX can be 1 to 255) belong to
the same subnet, and can “talk” to each other.
WebPower
Configuration via web
browser
Ethernet cable
Compack
controller (Standard straight through
cable OR crossover cable)
**NOTICE:
You need an Ethernet crossover cable, if the controller is a Smartpack
with hardware version 1.x (SB70) or previous.
Contact your IT Department, if your computer has difficulties while installing or
configuring the network card.
Requirements
Computer equipped with a standard Ethernet Network Interface Card
(NIC) with RJ-45 socket. Wireless NICs may not be used to access the
controller.
The NIC’s necessary network components have to be correctly
installed, specially the Internet Protocol (TCP/IP). Also, the DHCP
function must be enabled.
Ethernet cable to connect the controller to the LAN
(straight-through** or crossover cable, as the controller’s port
implements HP Auto MDI/MDI-X detection and correction)
“Eltek Network Utility” program,
that you can download with the controller’s firmware from
www.eltek.com
**NOTICE:
You need an Ethernet crossover cable, if the controller is a Smartpack
with hardware version 1.x (SB70) or previous.
Network components are software clients, services and protocols that the NIC
uses to communicate with servers in the network.
In Short
To get access to the controller via a stand-alone computer, just connect the
controller directly to the computer’s NIC, using a standard Ethernet straight-
through** or crossover cable.
NOTICE:
If the controller has DHCP enabled when you connect it to the
computer’s NIC, then the controller and the computer will assign
themselves a random IP address, e.g. the controller may get <0.0.0.1>
and the computer <169.254.52.132>.
In this case, change the controller’s IP address from e.g. <0.0.0.1> to
e.g. <169.254.52.133> to enable them to “talk” to each other.
Then, access the controller via your web browser, and change its LAN device
name, to facilitate later identification.
The “Controller Access — Via Stand-alone PC” procedure involves following
steps (as described in more detail in the topic “More Detailed” on page 64):
1. Start the “Eltek Network Utility” program
2. Connect the computer to the controller and check its MAC address
3. Find the NIC’s IP address and subnet mask used by the computer
4. Change the controller’s IP address to the same subnet as the computer’s
5. Access the controller’s configuration pages in your web browser
6. Log in with the <admin> account,
7. Change the controller’s Device Name
**NOTICE:
You need an Ethernet crossover cable, if the controller is a Smartpack
with hardware version 1.x (SB70) or previous.
More Detailed
Carry out the following steps to access the controller via a stand-alone computer:
Notice that if the computer has installed wireless Ethernet Network Interface Cards, they should not be active;
otherwise the Eltek Network Utility may display LAN devices accessed wireless.
The Eltek Network Utility displays the controller as a connected LAN device (may take up to 1 minute to display)
with the default static IP address <192.168.10.20>
Notice that -- if the controller has the DHCP enabled instead of static IP address -- the controller automatically gets
an IP address, e.g. <0.0.0.1>, as displayed in the Eltek Network Utility below.
Check that the displayed MAC address corresponds to the MAC address label on the controller.
3. Find the NIC’s IP address and subnet mask used by the computer by,
— Opening the computer’s Network Connections window
— Selecting the actual network card (NIC) and
— Making a note of the IP address and Subnet mask displayed in the Details panel, on the left side of the window.
E.g. IP address: <169.254.52.132>, Subnet mask: <255.255.0.0>
Read the topic How to Check or Change the Computer’s IP Address (page 40) in the FAQs section
Notice that you can also get this information by opening a DOS window and running the command “IPCONFIG”.
Now, the controller’s and the computer’s IP addresses are in the same subnet and both devices can “talk” to each
other.
Computer’s: <169.254.52.132> <255.255.0.0>
Controller’s: <169.254.52.133> <255.255.0.0>
Configuration button
WARNING!
Never enter Network Mask (Subnet masks) <0.0.0.0> or <255.255.255.255> as they are not valid masks, and in the
worst case may render the controller or LAN device inaccessible.
Note that the web browser must have the Pop-ups function enabled, as the configuration web pages employ Java
script navigation. Read topic How to Enable Pop-ups in the browser -- Internet Explorer (page 32) in the FAQs
section
For security reasons, it is advisable to change the default passwords with your own passwords.
Read the topic How to Change WebPower’s Default Log in Passwords (page 33) in the FAQs section
Read topic How to Change the Controller’s Device Name (page 38) in the FAQs section
Now the Eltek Network Utility window will display the new device name.
NOTICE:
If later you connect your computer’s NIC (while DHCP is enabled) to a
LAN, the network server will automatically assign a new IP address to
your NIC, so that your computer may access the LAN.
It may take up 1 or 2 minutes, but you can select the command “Repair
this connection” — in the computer’s Network Connections window —
and Windows will right away automatically assign the new IP address.
Compack
controller Ethernet Local Area Network
(LAN)
Contact your LAN administrator, if your computer has difficulties accessing the
network.
Requirements
Computer correctly configured and connected to the LAN
Standard Ethernet cable (straight through cable),
to connect the controller to the LAN
“Eltek Network Utility” program,
that you can download with the controller’s firmware from
www.eltek.com
In Short
To get access to the controller via your LAN networked computer just connect
the controller to the LAN using a standard Ethernet straight-through** or
crossover cable.
NOTICE:
By default, the controllers are shipped with a unique MAC address, e.g.
[00-0A-19-C0-00-13] and a fixed, static IP address <192.168.10.20>.
Some controllers may have DHCP enabled (automatically obtain
necessary access data to operate in an existing LAN).
For the computer to be able to access the controller via the LAN network, both
devices need to have different IP addresses, but in the same LAN subnet. If the
networked computer’s NIC IP address is e.g. <172.16.5.29>, so changing the
controller’s IP address from <192.168.10.20> to e.g. <172.16.5.30> will enable
them to “talk” to each other via the LAN network.
NOTICE:
If the controller has DHCP enabled when you connect it to the LAN
network, then the LAN network will automatically assign the controller
with a spare IP address in the LAN subnet, e.g. the controller may get
<172.16.6.130>, which will enable the networked computer to “talk” to
controller.
More Detailed
Carry out the following steps to access the controller via the Ethernet LAN:
Notice that if the computer has installed wireless Ethernet Network Interface Cards, they should not be active;
otherwise the Eltek Network Utility may display LAN devices accessed wireless.
Now, the controller’s and the computer’s IP addresses are in the same LAN subnet and both devices can “talk” to
each other via the LAN network.
Computer’s: <172.16.5.29> <255.255.0.0>
Controller’s: <172.16.5.30> <255.255.0.0>
Notice that you do not have to change the controller’s IP address -- if the controller has the DHCP enabled instead
of static IP address. The controller then automatically gets an IP address from the LAN, e.g. <172.16.5.221>, as
displayed in the Eltek Network Utility below.
Note that the web browser must have the Pop-ups function enabled, as the configuration web pages employs Java
script navigation. Read topic How to Enable Pop-ups in the browser -- Internet Explorer (page 32) in the FAQs
section
For security reasons, it is advisable to change the default passwords with your own passwords.
Read the topic How to Change WebPower’s Default Log in Passwords (page 33) in the FAQs section
Now the Eltek Network Utility window will display the new device name.
For more information about how to access the configuration web pages,
read topic How to Change WebPower’s Default Log in Passwords
(page 33) in the FAQs section
Via PowerSuite application.
The powerful PowerSuite application must be installed in the computer,
and enables advanced monitoring and configuration features.
System Configuration
(Via PowerSuite)
Ethernet LAN
(UDP Tunnelling)
System Configuration
(Via Web browser)
System Monitoring
Ethernet Local Area Network (Via NMS)
(LAN)
Ethernet LAN
(Network Manager System)
Compack
controller Ethernet Local Area Network
(Network Management System)
Requirements
Computer correctly configured, connected to the LAN and with access
to the NMS
Standard Ethernet cable (straight through cable),
to connect the controller to the LAN
Eltek’s specific SNMP MIB files (Management Information Base)
In Short
The power system’s controllers implement an SNMP agent which interfaces with
the Network Management System (NMS), enabling remote monitoring via the
standard SNMP messaging commands SET, GET and TRAP.
The SNMP agent is compatible with all major NMS on Ethernet, such as “HP
Open View”, “Sun NetManager”, etc.
The SNMP agent responds to SNMP’s GET and SET commands, and forwards
TRAPs to designated recipients when critical conditions occur to the DC power
system, as configured in the controller.
The GET commands provide the NMS with remote monitoring status — e.g.
Battery status, etc. — of the power system.
The SET commands enable the NMS to remote control the power system, e.g.
changing the output voltage.
The TRAP commands are unsolicited alarm messages that the power system
sends to the NMS, when critical situations occur.
You can regard SNMP agents (network devices) that send TRAPs as “clients”,
and network devices that receive TRAPs and poll devices (issue GETs and
SETs) as “servers”.
NMS configuration:
1. Compile the Eltek’s device specific MIB files into the NMS database
(Read chapter “About Eltek’s SNMP MIB Files”, page 77)
Note that the web browser must have the Pop-ups function enabled, as the configuration web pages employ Java script
navigation. Read topic How to Enable Pop-ups in the browser -- Internet Explorer (page 32) in the FAQs section.
“Send Off
Traps” check
“NMS Trap box
Receiver IP (Sends a TRAP
Address” fields when an alarm
(Up to 10 NMS IP is reset)
addresses that
will receive the “Authentication and
alarm messages) Warmstart …” field
(NMS IP address to
receive start-up
messages)
“Trap Repeat Rate” field
(How often an active
alarm is resent)
“Heartbeat…” field
(How often a “control”
message is sent)
“Read Community String”
field
(A password for SNMP “Write Community
GET commands) String” field
(A password for SNMP
SET commands)
“Save” button
NOTICE:
You can visit www.eltek.com to download Eltek’s device specific MIB
files, or contact Eltek’s Service Dep.
The MIB files are in the plain-text, DOS End-of-Line format, and conform to the
ASN1 coding syntax.
Eltek’s SNMP compliant devices are described in one or several MIB files,
which are required for configuration of the Network Management System
(NMS).
There are 3 types of Eltek SNMP MIB files:
The “First-Time Installation Type” MIB files.
Describe a complete MIB tree structure (root and a branch) for Eltek
SNMP devices.
Use this type of MIB file if your NMS MIB tree does NOT already
contain an Eltek SNMP MIB tree structure.
The “Root Type” MIB files.
Describe the Eltek MIB tree base or root (no branches for SNMP
devices).
Use this type of MIB file if you want to use several Eltek Branch MIB
files simultaneously as branches in the NMS MIB tree.
The “Branch Type” MIB files.
Describe the Eltek MIB tree branches for SNMP devices (no root).
Use this type of MIB file if you already have the Eltek MIB tree root
compiled in the NMS MIB tree.
You can compile several Eltek Branch MIB files in the NMS MIB tree,
thus describing different Eltek’s SNMP compliant devices (equipment).
Following table is an overview of some of the Eltek SNMP MIB files, their MIB
file type and the equipment they describe:
Selected Object
(“batteryBreakerStatus”)
DC Plant Information
The DC Plant configuration pages of WebPower and PowerSuite enables you to
enter information that describe the power system, the site’s name , serial number,
installation and service dates, software name, etc.
Read also the “General tab” topic Power System dialog box in the PowerSuite
Help section.
Data Format
Usually, the data format for entering the 3 coordinates: latitude, longitude and
elevation is
Sexagesimal Notation: DDº MM’ SS.ss’’ N or S
Degrees (º), minutes (’) and seconds (’’).
For greater precision, use the decimal fraction of seconds: SS.ss.
North (N) or South (S) of the equator.
E.g.: 66º 33’ 38.95’’ N
Latitude
Latitude is the angular distance, measured north or south from the equator, of a
place on the Earth's surface, usually expressed in degrees. Parallels are
imaginary lines along all the places on the Earth with the same latitude.
Latitude: (<DD>º<MM>’ <SS.ss>’’ N/S)
Latitude ranges from 0º at the equator to 90ºN (or +90º) at the North Pole; and to
90ºS (or -90º) at the South Pole.
Longitude
Longitude is used to denote the location of a place on the Earth's surface east or
west of the prime meridian.
A meridian is an imaginary line from the North Pole to the South Pole that
connects all locations with the same longitude. The position of a point on the
meridian is given by the latitude.
The Prime Meridian is, by international convention, one passing through the
Royal Observatory, Greenwich, in east London, United Kingdom, known as the
International Meridian or Greenwich Meridian.
Longitude: (<DD>º<MM>’ <SS.ss>’’ E/W)
Longitude is given as an angular measurement ranging from 0° at the Prime
Meridian to +180° eastward (or 180°E) and −180° westward (or 180°W).
Elevation
Elevation, or altitude, is used to indicate how high a place on the Earth's surface
is from sea level (above mean sea level, AMSL).
The power system’s elevation is entered in meters above sea level (AMSL).
Read also the “Location tab” topic Power System dialog box in the PowerSuite
Help section.
Option Description
NomVolt Nominal output voltage
BoostVolt Battery boost-charging voltage
LowBatt1 Voltage limit for Low Battery Alarm 1
From PowerSuite
By clicking on the “System Voltage Levels” button, on the PowerSuite toolbar,
you can also display and change important system voltages, such as:
Nominal or Reference voltage (float)
Boost voltage
Battery Test End Voltage
Rectifier standby voltage
Battery disconnect voltage
Battery reconnect voltage
Rectifier OVS trip voltage
Refer also to PowerSuite’s System Voltage Levels dialog box topic.
System Commands
This logical subgroup lets you issue or activate specific commands related to
the whole system. For example, following commands might be available in
Smartpack2 Master Controller’s submenu:
Commands > System Commands
NOTICE:
The default Service Access Level password or Pin-Code is <0003>. We
strongly recommend changing the passwords as soon as the power
system is installed.
System Calibration
The Eltek’s DC power systems are factory calibrated.
Normally, the power system will NOT require additional calibration, except
when the system’s controller or control units are re-installed in other power
systems.
Definition
The power system calibration is the process of establishing the relationship
between a measuring device (system inputs) and the units of measure
(displayed measurements).
The accuracy of the displayed measurements depends on how god calibration
data is entered in the control units (calibration quality).
What to Calibrate
Following types of inputs and measuring functions can be calibrated in Eltek’s
DC power systems:
Current Sense Inputs
-- Load Current calibration
-- Battery Current calibration
Voltage Monitoring Inputs
-- Battery Voltage calibration
-- Symmetry Voltage calibration
Temperature Sense Inputs
-- Battery Temperature calibration
Earth Fault Detection Function
-- Calibration of Earth Fault Detection
Read following topics for information about available inputs and outputs and
related functions:
“The Smartpack2 Basic Controller - Overview” on page 218
“The Smartpack Controller - Overview” on page 220
“The Compack Controller - Overview” on page 223
“The Smartnode Control Unit - Overview” on page 225
“The Battery Monitor Control Unit - Overview” on page 225
“The Load Monitor Control Unit - Overview” on page 226
“The I/O Monitor Control Unit (T1) - Overview” on page 226
How to Calibrate
The Eltek’s DC power systems are factory calibrated at 2 calibration points: at a
Low Calibration Point and at a High Calibration Point.
The two calibration points’ units of measurement can be Ampere, Volt, degree
Celsius, Ohms, etc.
In short, the calibration process consists of setting the power system in the
suitable calibration stage, measuring the actual parameter and entering the
parameter in PowerSuite.
Which is the power system’s most suitable calibration stage depends on the
type a calibration to perform. For example, a suitable calibration stage could be
to load the system with 50-60% of the system’s maximum output power, or
turning off the rectifiers, or load the battery bank so that the battery current is at
least 30% of the current shunt rating, etc.
NOTICE: When calibrating current shunts, you must also enter the
current shunt rating, in addition to the low and high calibration
measurements.
Refer to the topic Alarm Monitor Scale tab (current shunt) in
PowerSuite Help.
NOTICE: When calibrating current shunts, you must also enter the
current shunt rating, in addition to the low and high calibration
measurements.
Refer to the topic Alarm Monitor Scale tab (current shunt) in
PowerSuite Help.
AND
-- Click on the Apply button, (D) in the dialog box
C D
Block Measurements
Block Measurements
Battery Monitor ID#33 for battery string 1 (lowest)
Symmetry 1.1:
measure between point V0 and V1 (~12V)
Symmetry 1.2:
measure between point V0 and V2 (~24V)
Symmetry 1.3:
measure between point V0 and V3 (~36V)
Symmetry 1.4:
measure between point V0 and V4 (~48V)
Symmetry2.1:
measure between point V0 and V1 (~12V)
Symmetry 2.2:
measure between point V0 and V2 (~24V)
Symmetry 2.3:
measure between point V0 and V3 (~36V)
Symmetry 2.4:
measure between point V0 and V4 (~48V)
Mid-point Measurements
NOTICE:
Always connect Battery Monitor with ID#<33> to battery strings 1 (lowest), 2, 3 and 4. Then Battery Monitor with
ID#<34> to string 5, 6, 7 and 8. And so on. PowerSuite will then refer to the correct battery string.
Mid-point Measurements
Battery Monitor ID#33 for battery string 1 (lowest), 2, 3 and 4
Symmetry 1.1:
measure between point V0a and V1a (~24V)
Symmetry 1.2:
measure between point V0b and V1b (~24V)
Symmetry 1.3:
measure between point V0c and V1c (~24V)
Symmetry 1.4:
measure between point V0d and V1d (~24V)
Mid-point Measurements
Symmetry 1.1:
measure between point V0 and V1 (~24V)
Block Measurements
Symmetry 1.1:
measure between point V0 and V1 (~12V)
Symmetry 1.2:
measure between point V1 and V2 (~12V)
Symmetry 1.3:
measure between point V2 and V3 (~12V)
Symmetry 1.4:
measure between point V3 and V4 (~12V)
Double-point Measurements
Symmetry 1.1:
measure between point V0 and V1 (~24V)
Symmetry 1.2:
measure between point V1 and V2 (~24V)
Example of measurement points for symmetry voltages, for the Battery Monitor’s Block or Mid-point Measurement
Method in 24V DC power systems. String 1, 2, 3 and 4
NOTICE:
Always connect Battery Monitor with ID#<33> to battery strings 1 (lowest), 2, 3 and 4. Then Battery Monitor with
ID#<34> to string 5, 6, 7 and 8. And so on. PowerSuite will then refer to the correct battery string.
Symmetry 1.1:
measure between point V0a and V1a (~12V)
Symmetry 1.2:
measure between point V0b and V1b (~12V)
Symmetry 1.4:
measure between point V0d and V1d (~12V)
Notice that in +24V power systems using 12V battery blocks, the Mid-Point
Measurement Method and the Block Measurement Method are equal, as the
strings consist of only two battery blocks.
Symmetry 1.1:
measure between point V0a and V1a (~12V)
WARNING:
To be able to use the Earth Fault Detection functionality, the power
system must be implemented with “floating earth”, which means that
“Telecom Earth” (TE) or DC Earth must NOT be connected to the
power system’s DC output rail (+ or –).
Read more in topic “About AC, DC Earthing Systems” on page 108
This figure shows examples of PowerSuite dialog boxes for Event Log, Data Log and Data Logging.
Event Log
The Event Log is a system related log of power system events automatically
registered by the system controller.
You can access the log either using the controller’s front keypad or other GUI.
E.g., available options in Smartpack2 Master Controller’s submenu:
Logs/Report > Event Log
Read more in topic Control System Event Log tab in the PowerSuite Help
section
Data Log
A log of key system data (voltages, current and temperature values) registered
by the system controllers, or by other connected control units (e.g. I/O
Monitor, Mains Monitor) at the intervals specified by e.g. in PowerSuite.
You can access the log either using the controller’s front keypad or other GUI.
Read more in topic Control Unit Data Log tab in the PowerSuite Help section
Data Logging
Data Logging is a log of key system data (voltages, current and temperature
values) that PowerSuite registers or saves in a file in your computer, not in the
controller.
PowerSuite acquires the key system data by interrogating the system controller
at the specified intervals.
You can access the log via the PowerSuite application.
Read more in topic Data Logging dialog box in the PowerSuite Help section
Measurement Logs
Logs of specific measurements or calculations (consumed energy, time duration,
volume, counter) registered by the system controller.
Read more in topic “Measurement Logs” on page 97.
Measurement Logs
Measurement Logs are records of specific measurements or calculations
(consumed energy, time duration, volume, counter) registered by the system
controller.
The control system implements following types of measurement logs:
Energy Logs (Wh)
(for Mains, Battery, Load, Rectifiers, Generator, Solar Chargers)
Load Monitor Energy Logs (Wh)
Mains Outage Log (time duration)
Generator Run Hours Log (time duration)
Generator Fuel Consumption Log (volume)
Battery Discharge Cycles Log (counter)
C D E I
B
A
G
This figure shows an example of PowerSuite dialog box with the battery banks’ Energy Log.
NOTICE:
The Energy Log for the battery bank may display positive and negative
values. Positive values represent energy provided by the battery to the
load, while negative values represent energy used by the battery via
recharging.
Power system is
switched OFF from
Sep 24th to Oct 1st
This table shows an example of Measurement Log entries displayed on October 31st .
If the monitored devices (e.g. rectifiers, generator, etc.) are not running
for longer periods of time, the log will display “0” for the last hour, last
day, last week.
See the table in the example above.
If the power system is switched OFF for a period of time, no data is
entered for the down-time, and the previous log entries are kept.
See the table in the example above.
Energy Log
The Energy Log is a measurement log, and represents an efficient way of
logging the power system’s energy usage, (Wh).
For each of them, the controller logs the energy provided during the last hour,
the energy used the last day and the last week and the total energy provided
(used) since the first system start-up.
The system controller stores the latest 52 sets of measurements or calculations,
which can be displayed by the Energy Log.
NOTICE:
To monitor the energy provided to the system by the grid (AC mains), a mains
monitor must be connected to the system.
Read more in topic Mains Monitor nn dialog box in the PowerSuite Help
section.
NOTICE:
To monitor the energy provided through a specific load fuse, a load monitor
must be connected to the system.
Read more in topic “Load Monitor Energy Log” on page 101, and in topic Load
Primary nn dialog box in the PowerSuite Help section.
51 20 3 12
Oldest calculation 52 55 2 15
The table above shows an example of Energy Log for the system batteries. The
same Energy Log can also be displayed in PowerSuite interface, see an example
in topic “Generic about Measurement Logs”, page 97.
While the total energy provided (used) since the first system start-up is
continuously updated, the controller calculates the values for the energy
delivered or supplied every hour, every day and every week.
For example, the “Day kWh” value for the latest calculation represents the
energy consumption for the latest 24 hours (calculations).
Read more in topic “Generic about Measurement Logs”, page 97.
I
C D E
This figure shows an example of PowerSuite dialog box with the Mains Outage Log.
The Mains Outage Log displays how long time the power system’s AC Mains
feed has been OFF during the last day, in minutes (C); and during the last week
(D) and the last month (E), in hours.
It also displays how many hours the AC Mains feed has been OFF since the
first system start-up (F)
The system controller stores the latest 52 sets of measurements or calculations
(A), which can be displayed by the Mains Outage Log. By dragging the split box
(I) down to the middle (H), you can browse the log in two different panes.
C D E
This figure shows an example of PowerSuite dialog box with the Generator Run Hours Log.
The Generator Run Hours Log displays how long time the gen-set has being
ON, or running during the last day, in minutes (C); and during the last week
(D) and the last month (E), in hours.
It also displays how long time the gen-set has being ON, or running since the
first system start-up (F).
The system controller stores the latest 52 sets of measurements or calculations,
which can be displayed by the Generator Run Hours Log.
Clicking on the “Export to file” button, enables to save the log in XML format
to a computer.
Read also topic Generator Run Hours tab in the PowerSuite Help section.
Read more in topic “Generic about Measurement Logs”, page 97.
I
C D E
This figure shows an example of PowerSuite dialog box with the Generator Fuel Consumption Log.
The system stores a fuel consumption log for each fuel tank (J), based on the
entered tank configuration data. The fuel consumption is displayed in liters,
gallons or any other suitable volume unit.
As recommended, the used units should be included in the tank description
name. See topic “Step 9- Configure the fuel tank” on page 138.
The Generator Fuel Consumption Log displays how much fuel the gen-set has
consumed during the last day (C), during the last week (D) and during the last
month (E).
It also displays how much fuel the gen-set has consumed since the first system
start-up (F).
The system controller stores the latest 52 sets of measurements or calculations,
which can be displayed by the Generator Fuel Consumption Log.
By dragging the split box (I) down to the middle (H), you can browse the log in
two different panes.
Clicking on the “Export to file” button, enables to save the log in XML format
to a computer.
Read also topic Generator Fuel Consumption tab in the PowerSuite Help section.
Read more in topic “Generic about Measurement Logs”, page 97.
The controller counts and logs the number of performed battery cycles during the
last day, during the last week and during the last month.
Also, the controller counts the total number of battery cycles performed since
the first system start-up.
The system controller stores the latest 52 calculations, which can be displayed by
the “Battery Discharge Cycles Log”.
Read more in topic Discharge Cycles tab in the PowerSuite Help section, and in
topic “Generic about Measurement Logs”, page 97.
Battery Cycles
(a discharge and recharge sequence)
SOC
a b c d
100%
96%
75%
72%
40%
20%
0% t
Ignored discharge- Cycle1 Cycle2 Cycle3
recharge of 4% (A)
Configured Discharge
Ignored recharge Cycle Threshold 5%
of 3% (B)
This diagram shows that the controller counts 3 cycles during this period of time, with a configured Discharge Cycle
Threshold of 5%
Alarm Reset
The DC power system can be configured with automatic or manual alarm reset.
When Manual Alarm Reset is enabled -- and the alarm condition no longer
exists -- the operator must reset the alarm manually, via the power systems
user interface (web GUI or controller’s front keys).
When the Manual Alarm Reset is disabled, then the Automatic Alarm Reset is
enabled (default). In this case, when an alarm condition no longer exists, the
main controller will automatically reset the alarm, by deactivating the alarm
lamps and relays to indicate that normal operation is established.
At factory, AC Earth (PE) and DC Earth (TE) are connected to chassis. Remove
“Link 2” (“floating earth”) for compliance with other local earthing systems.
TN networks
The TN earthing system, where one of the points in the generator or transformer
is connected with earth, usually the star point in a three-phase system. The body
of the electrical device is connected with earth via this earth connection at the
transformer.
TT networks
In a TT earthing system, the protective earth connection of the consumer is
provided by a local connection to earth, independent of any earth connection at
the generator.
The big advantage of the TT earthing system is the fact that it is clear of high
and low frequency noises that come through the neutral wire from various
electrical equipment connected to it. This is why TT has always been preferable
for special applications like telecommunication sites that benefit from the
interference-free earthing. Also, TT does not have the risk of a broken neutral.
In locations where power is distributed overhead and TT is used, installation
earth conductors are not at risk should any overhead distribution conductor be
fractured by, say, a fallen tree or branch.
In pre-RCD era, the TT earthing system was unattractive for general use because
of its worse capability of accepting high currents in case of a live-to-PE short
circuit (in comparison with TN systems). But as residual current devices mitigate
this disadvantage, the TT earthing system becomes attractive for premises where
all AC power circuits are RCD-protected.
IT networks
In an IT network, the distribution system has no connection to earth at all, or it
has only a high impedance connection. In such systems, an insulation monitoring
device is used to monitor the impedance
WARNING:
To be able to use the Earth Fault Detection functionality, the power
system must be implemented with “floating earth”, which means that
“Telecom Earth” (TE) or DC Earth must NOT be connected to the
power system’s DC output rail (+ or –).
Read more in topic “About AC, DC Earthing Systems” on page 108
The Earth Fault Detection functionality requires no external wiring, but it is
disabled by default, and must be activated in the controller via the PowerSuite
configuration program.
The Earth Fault Detection function is based in a device that compares the ground
(chassis) voltage (VEarth) with a reference voltage (VRef).
When no earth fault is present (RFault1 and RFault2 ≈ ∞), then VEarth = VRef and the
device output VEFI = 0.
When an earth fault is present (and RFault1 or RFault2 < RLimit) — there is a current
leakage from the supply conductor (from + or – or both) to ground.
Consequently, VEarth ≠ VRef and the device output VEFI ≠ 0, causing the controller
to activate an earth fault alarm.
Notice that even if there is an earth fault, the controller will not raise an alarm, as
long as RFault1 and RFault2 are higher than RLimit, which you must configure in e.g.
PowerSuite.
WARNING:
When the power system is implemented with more than one
Smartpack2 Basic controllers, you must remove the jumper “Link” (see
diagram) from inside ALL the Smartpack2 Basic controllers but one.
For example, you cannot use the Earth Fault Detection functionality to raise an
alarm when the earth current leakage exceeds exactly 30mA.
— +
DC Load
DC Load
+
wires
wires
— + +
— — + + +
Negative DC Positive DC
Distribution Distribution
The figure below shows a Flatpack2 DC power system expanded with a slave
controller to implement additional digital inputs, relay outputs or similar
functionality. The CAN bus is terminated with a 120Ω resistor on both line ends
(60Ω bus impedance).
Master and Slave controllers’
DIP switch configuration
120
120 n n+1 n+2 m End-of-Line Resistor
End-of-Line Resistor 01 02 03 04
Flatpack2 DC Power System
The figure below shows a Flatpack2 DC power system expanded with a slave
controller and 3 CAN bus Nodes to implement additional relay outputs and
digital inputs (for current and fuse monitoring, temperature and fan speed control
& monitoring or similar functionality). The CAN bus is terminated with a 120Ω
resistor on both line ends (60Ω bus impedance).
The 3 CAN Bus nodes connected are: a Battery Monitor (ID#33), an I/O Monitor
(ID#81) and a Load Monitor (ID#49).
Flatpack2
DC Power System
WebPower
(web-based user interface)
ID Number
Fuses
Flatpack2
DC Power System
When connecting more CAN nodes to the bus, you have to remove the CAN bus
termination plug from one of the CAN bus ends, and plug it in one of the CAN
ports on the last connected CAN node.
More Detailed:
Alarm Monitors
The measured temperatures on these two inputs are continuously monitored by
PowerSuite’s alarm monitors “OutDoorTempX.1” and “OutDoorTempX.2”.
Refer also the “Control Unit Outdoor tab” topic in PowerSuite Help.
Warning:
To prevent damaging the I/O Monitor’s Speed Control Outputs, do not
connect clamping diodes directly on the fans’ control inputs. Also, the
input impedance of the fans’ control inputs must be 10K or greater.
The two inputs “Tachometer Input 1” and “Tachometer Input 2” are
developed to monitor the rotational speed of two individual fans.
The block diagram shows the I/O Monitor inside a fan-cooled outdoor cabinet, controlling the fan speed via “Speed
Control Output 1”, monitoring the fan speed via “Tachometer Input 1” and the internal temperature via
“Temperature Sense 1”
The outputs can be configured to give a linear control signal from 0V (0% fan
speed) to 10V (100% fan speed).
The I/O Monitor is configured with the low and high fan speed values, that you
want the fan to run at the specified temperatures.
For example, setting the Low and High Calibration Points to 20°C-10% and
70°C-100% will make the fan to run at 10% speed until the temperature reaches
20°C, then the speed will increase linear for increasing temperatures, and run at
100% speed when the temperature reaches 70°C and above.
NOTICE:
To avoid that a factory reset may cause the fans to rotate too slow, the
fan speed is configured from factory with the same speed for the low
and high speed values (20°C -50% speed) (70°C -50% speed).
Alarm Monitors
Refer also the “Control Unit Outdoor tab” topic in PowerSuite Help.
Refer also the “Control Unit Outdoor tab” topic in PowerSuite Help.
NOTICE:
Do not select the I/O Monitor’s programmable input 1 (ProgInput X.1)
for the Pressure Test, when the Humidity Reduction function also is
enabled.
How it works
When enabled, the I/O Monitor will run a Pressure Test at the date and time
specified. The test will be run repeatedly at the specified time intervals (a
number of days).
Refer also the “Control Unit Outdoor tab” topic in PowerSuite Help.
Requirements
When using the Humidity Reduction function, you must carry out the following:
Connect a humidity sensor inside the cabinet, and configure it so that
the sensor’s relay output is in alarm, when the humidity inside the
cabinet is above an accepted level HON, at which you want the
I/O Monitor to start attempting to reduce the humidity in the air
Connect and configure in PowerSuite the I/O Monitor’s programmable
input 1 (ProgInput X.1) to monitor when the humidity sensor’s output
is activated
Install a heater device inside the cabinet, and connect it so that it is
controlled (turned ON and OFF) by the I/O Monitor’s alarm relay
output 1
How it works
THEN
the I/O Monitor will reduce the fan’s speed with 10% every 5
minutes,
UNTIL
either the humidity sensor is deactivated (HOFF)
OR
the internal temperature increases to 50°C
(TINT°C>= TDEF°C)
OR
the fan’s speed has been reduced to 20% speed level.
THEN
the I/O Monitor will start the heater, using the Alarm Relay Output
X.1
THEN
the I/O Monitor will stop the heater, using the Alarm Relay Output
X.1
AND
restore the fan speed to normal (V1%)
Refer also the “Control Unit Outdoor tab” topic in PowerSuite Help.
Mains Functions
This section describes functions related to the DC power system’s AC Mains
input.
AC Generator as AC Mains
The control system’s Generator functionality is a set of software functions that
enables efficient monitoring and controlling of generator-fed, hybrid DC power
systems.
See a diagram of a hybrid DC power system in topic “Configuration Criteria” on
page 125.
The control system’s Generator functionality implements following main
features:
Generator Start & Stop Control
Automatic generator start/stop, based on the discharge level of the
system’s battery bank
Automatic generator start/stop, based on the system’s battery voltage
Daily and monthly periodical start & stop, based on configurable data
Generator Management
Reduced battery charging current limitation
Optimized implementation with adjustable parameters for: Mains delay,
Stop delay, Boost charging, etc
Fuel tank monitoring
Log of fuel consumption
Log of generator run time
Log of generated and consumed energy
Optional generator monitoring via digital inputs
Smoother rectifiers start-up with Walk-in Time feature
Optional delay for rectifiers start-up
You can use the controller’s keypad or other GUI to configure the Generator
functionality.
For example, following are the available options in the Smartpack2 Master
Controller’s submenu:
System Configuration > Generator
AC Generator DC Load
Battery
Bank
Solar PV Panels
Flatpack2 Hybrid Solar DC Power System
DC Load
Solar PV Panels
Battery
Bank
Example diagram of two systems: a Flatpack2 Hybrid Solar Power System (fed from AC generator and Solar panels) and a
Flatpack2 Autonomous Solar Power System (fed Solar panels)
See also the diagram in topic “Configuration Criteria” on page 125.
Configuration Criteria
Following criteria is required in the configuration of the example of the hybrid
system below:
Example diagram for a Smartpack2-based Flatpack2 Hybrid Power System (fed from AC generator and PV solar
panels) implemented with Flatpack2 HE rectifiers and Flatpack2 HE Solar converters
Diesel Engine Considerations
Ideally, diesel engines should run at 70-90% of the engine’s maximum rated
capacity, thus achieving highest efficiency. The gen-set efficiency is measured
by the delivered energy per consumed litre of diesel (kWh/l).
When running with too small loads, the engine combustion is poorer, causing
soot and clogging, which results in frequent servicing and increased operating
cost (OPEX).
The gen-set should be dimensioned so that the sum of the total DC load current
and the maximum battery charging current loads the gen-set to 70-90% of its
capacity.
The lifetime of a battery (cycle life) is a function of the executed number of
battery cycles, discharge level (DOD), temperature, etc., as specified in the
battery’s datasheet.
Select to start the gen-set at a combination of the below described criteria that
gives the best total cost of ownership (TCO).
Capacity Criteria
The hybrid system is supplied from the photovoltaic solar panels (PV panels)
during the daytime.
Based on this hybrid system’s type of batteries, we want the controller to
automatically start the generator, if the batteries discharge level has reached
the limit (e.g. 50% DOD), which could happens during cloudy days. The
engine-generator set (gen-set) will then help out supplying the hybrid system.
The controller will stop the generator, when the batteries are almost fully
recharged (~85-90% SOC), thus avoiding that the gen-set keeps on running
inefficiently.
Daily Criteria
At night, the hybrid system is supplied from the generator set.
The controller will daily and periodically start the generator at 20:00 hours and
stop it at 06:00 hours.
Monthly Criteria
Twice a month, the 1st and the 15th, the controller will periodically start the
generator at 22:00 hours, and will run for 16 hours.
Generic Criteria
Based on the size of the connected gen-set, and to prioritize the DC load over the
battery recharging time, the “Generator-feed battery charging current” is to be
limited to 10A. Read more about “Battery Charging Current Limitation” on page
182.
In addition to the battery discharge level criteria (e.g. 50% DOD), the controller
will also automatically start the gen-set if the battery voltage is lower than
LVBD level plus 1 volt (a safety start trigger, if the battery heath is very bad, and
the voltage drops before the DOD value is calculated). E.g. 45V, if LVBD level
is 44V.
In addition to the battery recharge level criteria (~85-90% SOC), the controller
stops the gen-set when the charging current is lower than 1A (Generator Stop
Current Limit), thus avoiding that the generator keeps on running inefficiently.
The system’s AC input is supplied by the gen-set, but to prevent the controller
from restarting the gen-set repeatedly during short mains outages, the controller
will start the generator e.g. 5 min after a mains outage is detected (Mains
Delay).
To be able to charge the battery bank a bit longer, after reaching the assigned
recharge level (~85-90% SOC), the generator will run extra 5 min, after all the
criteria to stop the generator are reached (Stop Delay).
To reduce the required recharging time, battery boost charging (increase of
charging voltage) must be enabled.
To limit the load transient “seen” by the generator and avoid generator hick-up --
the “Rectifiers Walk-in Time” is to be configured for “Long Time” (60s).
If the Rectifiers Long Walk-in-Time is not enough, then you can enable the
generator dependent “Rectifiers’ Start-up Delay”, for example to 5 minutes.
The hybrid system must monitor and log the fuel consumption. The hybrid
system’s gen-set is implemented with two 5000 liters diesel tanks. The
supplier’s tank strapping tables are available with 10cm increments. The Fuel
Level Transducers have a level offset of 5cm.
More Detailed:
NOTICE:
When the power system is fed from 2 gen-sets, one at a time, you must
define 2 different “generator start” Alarm Output Groups, one for each
generator.
A B
Rename the spare Alarm Output Group “Alarm Group 08” to e.g.
“Gen-set Start” (A)
Assign the relays “Alarm Output 5” and “Alarm Output 6” to the group
“Gen-set Start”; checked boxes (B).
Relay 5 will start the generator, and relay 6 will turn ON an external
lamp to indicate when the gen-set is running.
Click on the Apply button to activate the changes, then on the OK
button
For detailed information, refer to topic “Alarm Output Groups” on page 193, and
to the tutorial “How to Configure Alarm Output Groups” on page 232
A
B
NOTICE:
When the power system is fed from 2 gen-sets, one at a time, you must
define 2 different “generator start” Alarm Output Groups, one for each
generator, e.g. “Gen-set Start” and “Gen-set Start2”.
You could then select “Gen-set Start2” (B) to start the second gen-set.
F
E
G
A
50
B
C
D
Check the “Enable boost during charging” box (G) to allow e.g.
automatic battery boost charging (reduces recharging time).
Refer to topic “Battery Boost Charging” on page 180, for configuration
of boost charging method, parameters, etc.
Click on the Apply button to activate the changes, then on the OK
button
Battery Charging Max. Current Criteria
In addition to configuring the 1A “Generator stop current limit”, carry out the
following to configure the 10A max “generator-feed battery charging current
limit”.
L
P
Open the Battery dialog box, click in the Configuration tab, then in
the Current Limitation sub tab (L)
Check the “Enable” box (P) to enable the “generator-feed battery
charging current” criteria
Type e.g. <100> amp in the Mains Feed “Current limit value [A]” field
(M), and
<10> amp in the Generator Feed “Current limit value [A]” field (N)
Click on the Apply button to activate the changes, then on the OK
button
Q
T
R
S
NOTICE:
When the power system is fed from 2 gen-sets, one at a time, you must
define 2 different “generator start” Alarm Output Groups, one for each
generator, e.g. “Gen-set Start” and “Gen-set Start2”.
You could then select which generator to start every weekday. E.g.
selecting “Gen-set Start2” to start the second gen-set on Tuesdays,
Wednesdays and Thursdays; and selecting “Gen-set Start” the rest of
the weekdays.
A
B
C D
A B
C
E
15 D
A B
C G
D
F
E
NOTE:
The volume values displayed in the dialog box are just default entries in
this example.
Click in the “Change” button, (H)
and in the displayed “Input Configuration” section,
select the I/O Monitor3 CAN Node and its corresponding digital input,
used to monitor the Fuel Level Transducer.
E.g. Select “I/O unit 1” in the “Select Unit” field,
and “Outdoor Temp 81.1” in the “Select Input” field.
Read below about “Level Sensor and Digital Input”
Click then on the Apply button, right under the “Select Input” field
Click on the Apply button to activate the changes
NOTICE:
The volume data may be entered in liters, gallons or any other suitable
volume unit. It is recommended to include the used units in the tank
description name, as there is no reference to the units any other place
in the dialog box.
For information about the Energy tab, the Run Hours tab and the Fuel
Consumption tab, read topics “Energy Log” on page 100, “Generator Run Hours
Log” on page 103 and “Generator Fuel Consumption Log” on page 103. Or the
“Generator dialog box” topic in PowerSuite Help.
Plug-and-Play Rectifiers
WARNING:
It is important to insert the Flatpack2 rectifiers in the correct position in
the power shelves.
This fact is not so important in systems using Micropack rectifiers.
When a rectifier is hot plugged in a power shelf for the first time, the main
controller assigns the next available ID number to the rectifier, starting with
“01”. This ID number (or CAN bus address) and the rectifier’s serial number are
stored in both modules.
To achieve a more controlled ID assignment, you should always insert & hot-
plug new rectifiers in the power shelves, one module at a time, starting with
shelf position 1, 2, 3 and so on. The sequence is indifferent after positions 9.
The power shelf position numbers vary with the type of AC mains and the type
of power shelves installed in your system. Refer to your system’s quick start
guide and specific documentation for more information.
Rectifier Information
You can display information about the rectifiers,
In Compack-based systems, via:
The WebPower configuration web pages
Option Description
NoOfRects. Number of rectifiers installed in the system.
RectCurrent Rectifier current
RectSerialNumber Rectifier ID and serial number
Rect.PrimaryVolt Rectifier input voltage
Rectifier Status Rectifier status
Rectifier Temp Rectifier temperature
While the controller is accessing information from a specific rectifier, the green
LED on the rectifier’s front panel flashes.
The Smartpack controller sends out status messages every 200ms to all the
Flatpack2 rectifiers connected to the CAN bus, such as:
The Smartpack controller’s status
Current Limit Reference
Measured Output Voltage
Reference Output Voltage
Over-voltage Protection Reference
From PowerSuite
By double-clicking on any of the Rectifier icons, on the PowerSuite Power
Explorer pane, you can also display important parameters about all the rectifiers
in the system, such as:
Rectifier’s ID number
Rectifier’s Status
Rectifier’s Serial Number
Rectifier’s Output Current
Efficiency Management
This feature optimizes the power system’s efficiency loss, when the load current
is less than approx. 50% of the installed rectifier capacity.
C
D
E
NOTICE:
The “Efficiency Manager” section is only displayed when the “Enable
efficiency manager” box is checked.
Also, when the “Enable HE priority” box is checked, there is no need for
configuring the parameters in the “Efficiency Manager” section.
Enabling
You can use the controller’s keypad or other GUI to configure the Efficiency
Management function.
When you enable Efficiency Management, the control system will check if the
total load current is less than approx. 50% of the system’s total capacity, in
which case it will switch OFF redundant rectifiers. Thus, the AC current
requirement is reduced and the remaining running rectifiers operate more
efficiently.
If the load increases, the control system will automatically switch ON more
rectifiers to supply the new load requirements.
Shuffle Time
The rectifier’s Walk-in Time feature helps reduce the current pull when running
on low current supply AC sources (solar panels, AC generators, etc).
This feature helps also reduce battery damage, caused by very large in-rush
currents at AC connection and reconnections to Mains. This is especially critical
if the batteries have reached the battery disconnect point or worse, have been
deep-discharged.
44.0
Short Time
Long Time
T(s)
5s
60s
Read more in the hybrid site example in topic “Step 8- Optionally, configure
rectifiers’ start-up delay” on page 137.
The rectifiers automatically adjust their output currents, so that they are as
close as possible to the mean rectifier output current (rectifiers’ total output
current divided by the number or rectifiers).
The “RectCurrShareErr” alarm monitor observes the rectifiers’ current sharing,
and indicates the worst percentage of deviation from the mean rectifier output
current.
E.g.: A power system implemented with 4 rectifiers delivers 100A to the load
and batteries. The mean rectifier output current is then 25A.
A rectifier delivering 12.5A will be indicated by the “RectCurrShareErr” alarm
monitor with a value of -50%.
Typical current sharing alarm limits are between ± 2.5 % to ± 5% at full load.
But the active current sharing, implemented by digital CAN bus
communication among rectifiers, makes it possible to achieve very accurate
current sharing between rectifiers, even better than ± 2.5 % at full load.
Read also the topic “Battery Charging Current Limitation” on page 182.
Read more in the hybrid site example in topic “Step 8- Optionally, configure
rectifiers’ start-up delay” on page 137.
NOTICE:
Contact the Eltek Service Dep. if you need to upgrade the rectifier’s
firmware or any CAN Bus control units other than controllers.
FWLoader Online Help helps you using the FWLoader graphical user interface
(GUI).
Read more “About the FWLoader Program” on page 202.
Load Groups
Normally, the power system’s total number of Priority and Non-Priority DC load
circuits are considered as one Load Group.
A Load Group consists of one or several priority and or non-priority DC load
circuits. See the diagram in topic “Overview Load Measurements” on page 154.
Usually, one Load Group is monitored by one Smartpack or Smartpack2 Basic
controller (implements LVLD contactors) and one or several Load Monitor
modules (implements current and fuse monitoring). Refer to the topic “System
Inputs and Outputs - Overview” on page 214.
Read also about “Load Groups” on page 154, and the topic “System Inputs and
Outputs - Overview” on page 214.
NOTICE:
In general, the total DC load -- of power systems implemented with one
controller -- represent one Load Group.
The total DC load of larger, multi-cabinet power systems --
implemented with several controllers in interconnected cabinets – are
divided into several Load Groups, as many load groups as there are
controllers.
Solar Panel
50V
LVBD
Cooling System
28ºC
48V
44V
Battery Bank
DC Power System
In the example, the system’s controller trips the LVLD contactor (disconnects
the non-priority load circuits) when the following conditions are met:
AND
The battery voltage has dropped down to e.g. 44V (Disconnect Voltage)
OR
The non-priority load’s backup leasing time has expired (Disconnect
Delay Time)
In the example, the system’s controller reconnects the LVLD contactor when
all the following conditions are met:
A. The AC Mains supply is ON again
(Normal Condition and Mains Dependent)
B. The LVLD contactor has been disconnected longer than the Delay
After Disconnect period of time
C. The rectifier system output voltage has risen to e.g. 48V (Reconnect
Voltage)
ILOAD = 0 – (–IBAT)
ILOAD = IBAT
Example of a 48V battery bank implemented with two 48V battery strings;
each string consists of four 12V battery blocks, each block consists of six 2V-battery cells.
48V battery strings are then implemented with 24 such battery cells.
Example of a 24V battery bank implemented with two 24V battery strings;
each string consists of two 12V battery blocks, each block consists of six 2V-battery cells.
24V battery strings are then implemented with 12 such battery cells.
Similarly, a 60V battery bank could be implemented with one or several 60V
battery strings; each string consists of five 12V battery blocks, each block
consists of six 2V-battery cells.
The 60V battery strings consists then of 30 such battery cells.
Read also about “Battery Banks, Strings and Blocks” on page 159, and the topic
“System Inputs and Outputs - Overview” on page 214.
Battery Commands
This logical subgroup lets you issue or activate specific commands related to
the power system’s battery bank. For example, following commands might be
available in Smartpack2 Master Controller’s submenu:
Commands > Battery Commands
NOTICE:
The default Service Access Level password or Pin-Code is <0003>. We
strongly recommend changing the passwords as soon as the power
system is installed.
Read also about the Smartpack controller’s “Available Inputs and Outputs” on
page 220 and about “The Battery Monitor Control Unit - Overview” on page
225.
Example of terminal connection points for the Smartpack controller’s Symmetry Block, Mid-point and Double Mid-
Point Measurement Methods in 48V DC power systems
You can implement any of these methods using one or two Battery Connection
Kits and the appropriate number of Battery Symmetry Kits, which contain a
single wire with suitable cable lugs, etc.
Refer to the system’s quick start guide for connection details, and for using
fewer wires, setting the switches to ON.
Read also about “The Battery Monitor Control Unit - Overview” on page 225.
Notice:
Always connect Battery Monitor with ID#<33> to battery string 1
(lowest), with ID#<34> to string 2, and so on. PowerSuite will then refer
to the correct battery string.
Read also about “The Battery Monitor Control Unit - Overview” on page 225.
Notice:
Always connect Battery Monitor with ID#<33> to battery strings 1
(lowest), 2, 3 and 4. Then Battery Monitor with ID#<34> to string 5, 6, 7
and 8. And so on. PowerSuite will then refer to the correct battery
string.
Read also about the Smartpack controller’s “Available Inputs and Outputs” on
page 220 and about “The Battery Monitor Control Unit - Overview” on page
225.
You may also find useful reading the topic “About Negative & Positive DC
Distribution Systems” on page 111.
In +24V power systems using 12V battery blocks, the Mid-Point Measurement
Method and the Block Measurement Method are equal, as the strings consist of
only two battery blocks. Only 2 symmetry wires per battery string are required.
Each Smartpack controller is equipped with 8 battery symmetry inputs (on
connectors CON4 and CON3), enabling symmetry measurement of 8 battery
strings using the Mid-Point or Block Measurement Method.
You can implement any of these methods using one or two Battery Connection
Kits and the appropriate number of Battery Symmetry Kits, which contain a
single wire with suitable cable lugs, etc.
Example of terminal connection points for the Smartpack controller’s Symmetry Block or Mid-Point measurement
methods in 24V DC power systems
Refer to the system’s quick start guide for connection details, and to the
PowerSuite Help, for symmetry reconfiguration, or when configuring Battery
Monitor Control Units.
WARNING:
In +24V systems, the Battery Monitors are to be connected to the CAN
bus via a CAN Repeater module and a CAN Power module. Also, the
Battery Monitor’s firmware 402086.009 must be version 1.03 or newer.
In +24V power systems using 12V battery blocks, the Mid-Point Measurement
Method and the Block Measurement Method are equal, as the strings consist of
only two battery blocks.
Each Battery Monitor is equipped with 4 battery symmetry inputs, enabling
symmetry measurement of 4 battery string using the Mid-Point or Block
Measurement Methods.
Read the “Installation Guide Battery Monitor CAN Node”, document number
351507.033.
Refer also to “Installation Guide Battery Monitor – Symmetry Kit”, document
number 351497.033, which is included with the kit. The Battery Fuse and
Battery Current cables are not shipped with the Battery Monitor ~ Symmetry Kit.
Refer to the PowerSuite Help for symmetry configuration of Battery Monitor
Control Units.
Notice:
Always connect Battery Monitor with ID#<33> to battery strings 1
(lowest), 2, 3 and 4. Then Battery Monitor with ID#<34> to string 5, 6, 7
and 8. And so on. PowerSuite will then refer to the correct battery
string.
Refer to the system’s quick start guide for connection details, and to the
PowerSuite Help, for symmetry reconfiguration, or when configuring Battery
Monitor Control Units.
The 8 “SymmDelta x.x” alarm monitors are configured to generate alarms when
the Delta voltage is 1.5V (Major Alarm) and 1.0V (Minor Alarm). Clicking on
the monitors name you can check their configuration.
The calculation is based on following formula:
Battery Tables
PowerSuite enables you to select a specific Battery Definition Table to upload to
the controller.
Refer also to the Battery Table Data dialog box topic, in PowerSuite Help.
In this dialogue box, you can select, edit, export and import battery tables.
OR
o Click the “Apply” button
to upload the Battery Table to the controller
PowerSuite will then use the discharge performance data in the table
Battery Tests
The purpose of battery testing is to estimate the battery capacity, based on
calculations on discharge tests and discharge data preconfigured in a battery
definition table entered via PowerSuite. You find more information about the
“Battery Tables” on page 173.
Read also the “Discontinuance Battery Test” on page 179, as it is a special
battery test with a completely different testing purpose.
To evaluate the state of the battery bank, the controller starts a battery test by
reducing the rectifiers’ output voltage so that the batteries take over the full load
current.
56
Battery
Voltage
54 Rectifier
Standby
Voltage
MajorLow
52
Battery
Alarm
Vdc
50
48
46
44
0
8
10
30
50
70
86
88
90
92
94
96
time [min]
T1 T2 t
PowerSuite implements 3 types of battery tests, and 3 different methods to
initiate the tests.
Read more about the topic in the “Battery” dialog box, on the Test tab in
PowerSuite Help.
NOTICE:
The Interval Battery Test will not start, if any of the following alarm
monitors are in alarm status, caused by a Major Alarm event:
-- RectifierError
-- RectComm_Error
-- BatteryQuality (indicates the result of a battery test)
-- DeltaStringCurr (indicates the result of a discontinuance test.
Requires installation of shunts in all battery strings)
-- SymmVolt X.X (indicates the result of symmetry measurements)
You may schedule to start and stop a Discontinuance Battery Test automatically:
o At a specified date and time (specified in the “Interval Test” sub-tab)
Hardware Requirements
To use the Discontinuance Battery Test, the power system’s battery bank must
be implemented with battery blocks with the same capacity, have at least 2
battery strings, and each string must have an individual shunt.
You find the “DeltaStringCurr” alarm monitor under the “Status” tab, in the
Battery dialog box topic, in PowerSuite Help.
56,64
54,72
52,8
0 10 20 30 °C
Temperature
The following two parameters are specified by the battery manufacturer:
o Reference Voltage (V/Cell)
The charging voltage per battery cell, at a reference temperature of for
instance 20°C, as recommended by the battery manufacturer
o Temperature Slope (mV/°C/Cell)
The slope of the Temperature Compensated Charging Equation is
expressed as the change in millivolts per battery cell per degree
Centigrade (the recommended compensation factor for the type of
batteries)
In order to protect connected load equipment against too high and too low output
voltage, it also is advisable to specify the following parameters:
o Min Compensation Voltage (V/Cell)
Minimum charging voltage per battery cell
o Max Compensation Voltage (V/Cell)
Maximum charging voltage per battery cell
Using the Battery Charging Current Limitation function you may charge the
battery bank while protecting from overcharging.
50V
LVBD
Cooling System
28ºC
47V
43V
Battery Bank
DC Power System
In the example, the system’s controller trips the LVBD contactor (disconnects
the battery bank from the load) when all the following conditions are met:
The AC Mains supply fails (critical condition)
The battery voltage has dropped down to e.g. 43V (Disconnect Voltage)
In the example, the system’s controller reconnects the LVBD contactor when
all the following conditions are met:
A. The AC Mains supply is ON again
(Normal Condition and Mains Dependent)
B. The LVBD contactor has been disconnected longer than the Delay
After Disconnect period of time
C. The rectifier system output voltage has risen to e.g. 47V (Reconnect
Voltage)
D. The battery temperature is lower than e.g. 28ºC (the temperature limit
configured in the “BatteryTemp” alarm monitor) (Temperature
Dependent)
NOTICE: In this example, the fan cooled system stopped due to the
Mains outage, which caused a battery temperature increase above
28ºC.
The LVBD contactor will NOT be reconnected because the battery
temperature is not lower than 28ºC (condition D).
In this situation, the controller may reconnect the LVBD contactor, if
Access Levels
The control system protects system parameters and other configured values with
following three different access levels:
User Access Level
is the default level when you access the menus or GUI.
Log in is not required.
You can read all parameters and values (Read Access), but changing
them is not allowed.
Service Access Level
By logging in to this level you can change most of the system
parameters and values (Write Access).
You can use the controller’s keypad or other GUI to change the access level
password.
E.g. to do this in PowerSuite, read the “Access Levels (page Error! Bookmark
not defined.)” topic in PowerSuite Help.
WARNING:
If you change and forget the control system’s default password, you will
need a Master Password to reset all passwords to default.
E.g. to find the serial number using PowerSuite, read the “Control Unit
Summary tab” topic in PowerSuite Help.
Alarm Monitors
Alarm monitors are software modules used by the system controller to measure
system internal and external input signals or logical states.
When an alarm monitor is enabled, it compares the measured parameter with
pre-programmed values or limits, and raises an alarm in the event of the
measured parameter reaching one of the limits.
When this event occurs, the alarm monitor stores the event in the Event Log,
initiates an internal action and activates an output group.
Internal pre-programmed actions may be battery current limiting, boost
inhibiting or similar. The generated alarm activates a pre-programmed group
of relay outputs (an alarm output group, AOG).
t
Input Signal
Time
delay
In addition, you can configure the alarm monitors with a description of the alarm
monitor and other configuration parameters.
Analogue and numerical alarm monitors compare the measured input with from
one to four user-defined values or limits; two above normal value (Major High
and Minor High) and two below normal value (Minor Low and Major Low).
Logical alarm monitors only compare the measured input signal with a logical
state (normally open or close). The user can define the type of event the monitor
activates when the input signal is not in the normal state.
Using PowerSuite, you can change the default alarm monitor’s name
(Description). This is useful for alarm monitors of the type “ProgInput X.Y”, but
you should be careful changing the name of other system alarm monitors.
Read also the “Alarm Monitor dialog boxes” topic in PowerSuite Help.
The examples below show typical configuration parameters for these alarm
monitors.
Parameters for Logical Alarm Monitors (L1)
Example to monitor logical states such as Open/Close or Yes/No.
# Description Value Unit/Label Note
Monitor – Enable/Disable? Enable Activates or deactivates the alarm monitor
Manual Reset Disabled Or “All Levels” or “MajorHigh Only” (a)
Hysteresis 000 (not applicable)
TimeDelay 7 Seconds Selects among delay time options (b)
MinorHigh AlarmGroup Major Alarm Selects the alarm group to activate
The LVD alarm monitors “observe” that the battery voltage (input signal) is
within limits, otherwise they activate the LVD contactors (alarm group).
(a) Manual Reset
Read also topic “Alarm Reset” on page 107
(b) Hysteresis and Time Delay
Read also topic “Alarm Monitors” on page 189
(c) Mains Independent
Check this option if you want that the LVD alarm monitor will reconnect the
LVD contactor when the rectifier system output voltage reaches the
Reconnect Voltage limit, regardless whether Mains is ON or OFF. For
example, this is possible using an additional primary supply.
Uncheck this option (Mains dependent) if you want that the LVD alarm
monitor will NOT reconnect the LVD contactor until Mains is ON again.
(d) Temperature Dependent
Used with LVD contactors that disconnect the battery bank (LVBD). Check
this option if you want that the LVD alarm monitor will reconnect the
LVBD contactor when the battery temperature is lower than the temperature
limit configured in the “BatteryTemp” alarm monitor.
(e) Disconnect Voltage
Enter a numeric value for the battery voltage drop-down limit. When -- after
a Mains failure -- the battery voltage gradually drops down to this limit; then
the alarm monitor raises the alarm and trips the LVD contactor.
(f) Reconnect Voltage
Enter a numeric value for the battery voltage reconnection limit. When the
Mains supply is ON again, the rectifier system output voltage increases to
this limit; then the alarm monitor will reconnect the LVD contactor.
(g) Delay Time after Disconnect
Enter the Time delay or number of seconds the LVD contactor has to be
tripped or disconnected, before the alarm monitor is allowed to reconnect
the LVD contactor
The Output Test functionality enables to test and verify the circuits connecting
external equipment to the power system’s alarm relay outputs.
The Output Test command will toggle the alarm relay contacts -- regardless of
the position they are at the moment -- for a certain period of time (entered in the
“Output Test Timeout (sec)” in PowerSuite).
Issuing commands is allowed using a Pin-Code.
NOTICE:
The default Service Access Level password or Pin-Code is <0003>. We
strongly recommend changing the passwords as soon as the power
system is installed.
NOTICE:
The LVD contactors are not affected by the “OutpBlocked” command.
Also, this command will reset possible active alarm relay outputs to
their normal status.
The “OutpBlocked” command uses the Alarm Output Group 18 to facilitate
external warning of this function being active (output relays activation is
blocked).
If an external warning is necessary, you can assign output relays to the
“OutpBlocked, AOG” alarm output group, e.g. to activate a lamp or alarm bell
when the alarm output relays are blocked.
Firmware Upgrade
To upgrade the firmware of controllers and LAN devices you have to use a
specific program to upload the correct firmware file to the controller or device
(target).
Read topic
“Firmware Upgrade - Smartpack Controller” on page 200
Smartpack2 Master
controller (locked)
SD card
Handle in open position
Smartpack2 Master
controller (open)
NOTICE:
All firmware upgrade and configuration files stored in the SC card must
have specific file names.
Do following:
1. Open the controller
using your fingers or a pen, see steps (1), (2) and (3)
2. Insert an SD card
containing the correct controller’s firmware source file, e.g.
<SP2MAST.BIN> for the Smartpack2 Master controller, or
<SP2BAS.MHX> for the Smartpack2 Basic controller.
While the firmware is loaded to the Smartpack2 Basic controller, the FWLoader
program displays a progress bar.
Smartpack2 Master
Controller
Smartpack2 Basic
Controller
Rectifiers
Firmware
Source File 120 1 01 02 n
End-of-Line 120
Resistor End-of-Line
FW Loader
ID Number Resistor
81
(Example of the
1 2 “FWLoader” program
3 4
6
5 7
NOTICE:
Contact the Eltek Service Dep. if you need to upgrade the rectifier’s
firmware or any CAN Bus control units other than controllers.
Using an external PC and the USB-to-CAN Converter (art. 208565) you can
upgrade the firmware installed in the Flatpack2 rectifiers and any of the control
units connected the system’s CAN Bus.
ID Number 01 02 n
33 81 49
Battery
Monitor
I/O Monitor Load Monitor
Flatpack2
DC Power System
The example above shows a Flatpack2 power system with 3 CAN Bus nodes
connected: a Battery Monitor, an I/O Monitor and a Load Monitor.
NOTICE:
USB-to-CAN Converter is not required to upgrade the firmware of the
Smartpack controller. You connect the USB cable directly to the
controller’s USB port.
NOTICE:
If you are upgrading the SB70 hardware platform, you have to carry out
steps 2 - 7 below twice, due to the platform’s memory restrictions.
The first time you select file “FreeRAM_V2_APP.s19” in step 5, and the
second time you select the file “Webpower_SB70_xx_APP.s19”.
1. Connect a PC to the controller or LAN device
Read topic “Networking the Controller - Access Methods” on page 62
2. Start the program “EVIPSetup.exe”,
on the computer;
To learn more about firmware files, you can read topic “Firmware Files and
LAN Devices” on page 205, and ”Content of WebPower Firmware ZIP
File” on page 209
6. Check the “Reboot when complete” check box (marked)
7. Click the “Update” button
the utility will download and update the firmware to the controller or LAN
device with the selected IP address
“Update” button
Controller’s IP Address (Downloads the
(169.254.52.133) firmware file to the
Compack controller
“Reboot when with IP address
completed” <169.254.52.133>)
button
LAN Devices
While the firmware is downloaded to the controller or LAN device, the utility
program displays a progress bar.
Once the firmware has loaded, the controller must restart. It will restart
automatically, because you left the “Reboot when complete” check box checked
(marked).
NOTICE:
The Smartpack controller’s firmware and the firmware in the controller’s
embedded Web adapter are different files, and require different
upgrade procedures.
LAN Devices:
- SB72 and SB72-512 (Stand-alone WebPower Adapter)
- SB70, MCF5208 and MCF5235 (Embedded in Smartpack controller)
- Compack (Embedded in Compack controller)
- Smartpack2 Master (Embedded in Smartpack2 Master controller) not
displayed
The program’s “Update Software” button enables you to upgrade the firmware
of the selected LAN device, by transferring a firmware file (s19-format) from a
LAN connected computer to the device (or hardware platform).
The figures below show examples of firmware files and available type of LAN
devices (or hardware platforms).
Firmware Update
Controller and embedded Web adapter Smartpack2 Master controller
Example file: (Embedded Web adapter)
“SP2MAST_1.00_APP.s19” Flatpack2
Power System
This example firmware file above is used to upgrade the Smartpack2 Master
controller (LAN device) in a Smartpack2-based power system.
Eltek Network
Utility LAN Devise Compack
program
Ethernet cable (LAN)
Firmware Update
Controller and embedded Web adapter Compack controller
Example file: (Embedded Web adapter)
“ComPack_1.01_APP.s19” Micropack
Power System
This example firmware file above is used to upgrade the Compack controller
(LAN device) in a Micropack power system.
LAN Device:
SB70 (Smartpack controller, Part 242100.113) or
MCF5208 (Smartpack controller, Part 242100.118 HW v2) or
MCF5235 (Smartpack controller, Part 242100.118 HW v3)
Eltek Network
Utility
program
Ethernet cable (LAN)
Example firmware files above are used to upgrade the Web adapter (LAN
device) embedded in the controller of a Flatpack2 power system. Each file
corresponds to one of the LAN devices (or hardware platforms).
This example firmware file above is used to upgrade the stand-alone WebPower
Adapter (LAN device) in a Flatpack2 power system.
LAN Devise
Eltek Network SB72 or SB72-512
Utility
program
WebPower
Adapter
Ethernet cable (LAN) Aeon Gold
controller
Firmware Update WebPower Adapter
Example files:
“Rev2.0_SB72Webpower_APP.s19” Aeon
Or Power System
“Webpower_SB72-512_20_APP.s19” (Stand-alone WebPower adapter)
The example firmware files above are used to upgrade the stand-alone
WebPower Adapter (LAN device) in an Aeon power system. Each file
corresponds to one of the LAN devices (or hardware platforms). Note that
version 2.0 is always the highest version available for these firmware files.
LAN Devise
Eltek Network SB72 or SB72-512
Utility
program
WebPower
Adapter
Ethernet cable (LAN)
MCU
Firmware Update WebPower Adapter controller
Example files:
“Rev2.0_SB72Webpower_APP.s19” Flatpack
Or Power System (Stand-alone
“Webpower_SB72-512_20_APP.s19” WebPower adapter)
The example firmware files above are used to upgrade the stand-alone
WebPower Adapter (LAN device) in a Flatpack power system. Each file
corresponds to one of the LAN devices (or hardware platforms). Note that
version 2.0 is always the highest version available for these firmware files.
WARNING: The upgrade will be aborted, if the selected LAN device (or
software platform) and the firmware file do not match.
NOTICE:
All firmware upgrade and configuration files stored in the SC card must
have specific file names.
The SD card uses the 8.3 file name format. Before using the files stored SD card,
you must rename them, so that they conform to the specific file names described
below.
For example, if you receive the file “SmartPack2_Basic_405007.009_V1.1.mhx”
to upgrade your Smartpack2 Basic controller firmware to version 1.1, you must
first rename the file to exactly “SP2BAS.MHX”, then copy the file to the
SD card and finally insert the SD card in the Smartpack2 Master controller to
start the firmware upgrade process.
When upgrading the firmware of controllers and control units — if several units
of the same type are connected to the CAN bus — the Smartpack2 Master
controller will request you to specify the CAN bus ID number of the unit to
upgrade.
Notice:
Some WebPower firmware ZIP files may only content firmware files for
some targets, instead of for all targets, e.g. file “WebPower Rev4.5
hexfiles and MIB, Targets-MCF5208, MCF5235.zip” will only display
folders for these targets; folders for the SB70 and SB72 are then not
included.
NOTICE:
Compack controllers have no DIP switches, as they are configured
from factory with CAN bus ID number <1> (not changeable).
Smartpack2 Master controllers have no DIP switches, as they are
configured from factory with CAN bus ID number <11> (not
changeable).
WARNING:
To replace installed rectifiers with new ones, remove the installed
rectifiers and wait for the controller to notify communication error with
the extracted rectifiers. Push the new rectifiers firmly inwards -- one
module at a time, allowing a 2s delay -- to plug them in the power shelf.
Start with the shelf position with lowest ID number. Lock their handles.
NOTICE:
Compack controllers have no DIP switches, as they are configured
from factory with CAN bus ID number <1> (not changeable).
Smartpack2 Master controllers have no DIP switches, as they are
configured from factory with CAN bus ID number <11> (not
changeable).
For example, in a distributed DC power system with several Smartpack
controllers, the master is configured with ID # <1>, the slave with ID # <2> and
so on. Refer to “CAN Bus Address Range -- Control Units” on page 211.
NOTICE:
Compack controllers have no DIP switches, as they are configured
from factory with CAN bus ID number <1> (not changeable).
Smartpack2 Master controllers have no DIP switches, as they are
configured from factory with CAN bus ID number <11> (not
changeable).
The table below shows the DIP switch position on Smartpack and Smartpack2
Basic controllers:
DIP switch position for Smartpack & Smartpack2 Basic controllers
Smartpack & ID DIP Switch Position
Smartpack2 Basic # 1 -- 2 -- 3 -- 4
Controller
Controller 1 1 OFF--OFF--OFF--OFF
Controller 2 2 ON--OFF--OFF--OFF
Controller 3 3 OFF-- ON--OFF--OFF
Controller 4 4 ON-- ON--OFF--OFF
Note that the controller’s ID number corresponds to the DIP switch’s binary
value plus 1.
The table below shows the DIP switch position on Smartnode control units:
DIP switch position for Smartnode control units
Smartnode ID DIP Switch Position
Control Unit # 1 -- 2 -- 3 -- 4
Smartnode 1 17 OFF--OFF--OFF--OFF
Smartnode 2 18 ON--OFF--OFF--OFF
Smartnode 3 19 OFF-- ON--OFF--OFF
Smartnode 4 20 ON-- ON--OFF--OFF
Smartnode 5 21 OFF--OFF-- ON--OFF
Smartnode 6 22 ON--OFF-- ON--OFF
Smartnode 7 23 OFF-- ON-- ON--OFF
Smartnode 8 24 ON-- ON-- ON--OFF
Note that the control unit’s ID number corresponds to the DIP switch’s binary
value plus 17.
The table below shows the DIP switch position on Battery Monitor CAN nodes:
DIP switch position for Battery Monitors
Battery Monitor ID DIP Switch Position
CAN Node # 1 -- 2 -- 3 -- 4
Node 1 33 OFF--OFF--OFF--OFF
Node 2 34 ON--OFF--OFF--OFF
Node 3 35 OFF-- ON--OFF--OFF
Node 4 36 ON-- ON--OFF--OFF
Node 5 37 OFF--OFF-- ON--OFF
Node 6 38 ON--OFF-- ON--OFF
Node 7 39 OFF-- ON-- ON--OFF
Node 8 40 ON-- ON-- ON--OFF
Node 9 41 OFF--OFF--OFF-- ON
Node 10 42 ON --OFF--OFF-- ON
Node 11 43 OFF-- ON --OFF-- ON
Node 12 44 ON -- ON --OFF-- ON
Node 13 45 OFF--OFF-- ON -- ON
Node 14 46 ON --OFF-- ON -- ON
Note that the node’s ID number corresponds to the DIP switch’s binary value
plus 33.
The table below shows the DIP switch position on Load Monitor CAN nodes:
DIP switch position for Load Monitors
Load Monitor ID DIP Switch Position
CAN Node # 1 -- 2 -- 3 -- 4
Node 1 49 OFF--OFF--OFF--OFF
Node 2 50 ON--OFF--OFF--OFF
Node 3 51 OFF-- ON--OFF--OFF
Node 4 52 ON-- ON--OFF--OFF
Node 5 53 OFF--OFF-- ON--OFF
Node 6 54 ON--OFF-- ON--OFF
Node 7 55 OFF-- ON-- ON--OFF
Node 8 56 ON-- ON-- ON--OFF
Node 9 57 OFF--OFF--OFF-- ON
Node 10 58 ON --OFF--OFF-- ON
Node 11 59 OFF-- ON --OFF-- ON
Node 12 60 ON -- ON --OFF-- ON
Note that the node’s ID number corresponds to the DIP switch’s binary value
plus 49.
The table below shows the DIP switch position on I/O Monitor and I/O Monitor2
CAN nodes:
DIP switch position for I/O Monitor and I/O Monitor2
I/O Monitor & ID DIP Switch Position
I/O Monitor2 # 1 -- 2 -- 3 -- 4
CAN Node
Node 1 81 OFF--OFF--OFF--OFF
Node 2 82 ON--OFF--OFF--OFF
Node 3 83 OFF-- ON--OFF--OFF
Node 4 84 ON-- ON--OFF--OFF
Node 5 85 OFF--OFF-- ON--OFF
Node 6 86 ON--OFF-- ON--OFF
Node 7 87 OFF-- ON-- ON--OFF
Node 8 88 ON-- ON-- ON--OFF
Node 9 89 OFF--OFF--OFF-- ON
Node 10 90 ON --OFF--OFF-- ON
Node 11 91 OFF-- ON --OFF-- ON
Node 12 92 ON -- ON --OFF-- ON
Node 13 93 OFF--OFF-- ON -- ON
Node 14 94 ON --OFF-- ON -- ON
Note that the node’s ID number corresponds to the DIP switch’s binary value
plus 81.
The table below shows the DIP switch position on Mains Monitor CAN nodes:
DIP switch position for Mains Monitor
Mains Monitor ID DIP Switch Position
CAN Node # 1 -- 2 -- 3 -- 4
Node 1 97 OFF--OFF--OFF--OFF
Node 2 98 ON--OFF--OFF--OFF
Node 3 99 OFF-- ON--OFF--OFF
Node 4 100 ON-- ON--OFF--OFF
Node 5 101 OFF--OFF-- ON--OFF
Node 6 102 ON--OFF-- ON--OFF
Node 7 103 OFF-- ON-- ON--OFF
Node 8 104 ON-- ON-- ON--OFF
Node 9 105 OFF--OFF--OFF-- ON
Node 10 106 ON --OFF--OFF-- ON
Node 11 107 OFF-- ON --OFF-- ON
Node 12 108 ON -- ON --OFF-- ON
Node 13 109 OFF--OFF-- ON -- ON
Node 14 110 ON --OFF-- ON -- ON
Note that the node’s ID number corresponds to the DIP switch’s binary value
plus 97.
Example:
In a DC power system with following control units: 2 Smartpack controllers, 1
Smartnode and 2 Load Monitors, you have to set their DIP switches as follows:
First Smartpack controller:
ID# 1 (All DIP switches OFF)
Second Smartpack controller:
ID# 2 (Only DIP switch 1 ON)
”Enter” key
“Cancel” key
Arrow keys
Handle in locked position
The Smartpack2 Master controller is based upon a 3.2” TFT 32k color display
for local monitoring and configuration. The display has QVGA (320 x 240)
resolution and high contrast, for excellent reading from long distances and
angles. For easy screen navigation, it is equipped with a large touchpad, based on
the widely used “capacitive sense” principle.
SD card
Handle in open position
Smartpack2 Master
controller (open)
For information about the Smartpack2 Basic controller’s Earth Fault Detection
function, read topic “Earth Fault Detection” on page 109.
Block Diagram
You can also operate the system locally via a PC using Eltek’s PowerSuite
application, or remotely via modem, Ethernet and the Web. The module then
utilizes the USB- or RS-232 ports to interface with a local PC, SNMP or Web
adapters.
Read also topics about methods of accessing the controller “Networking the
Controller - Access Methods” on page 62, and methods of configuring the power
system “Power System Configuration & Monitoring – Methods” on page 71.
Block Diagram
Service Options
Example of the Service Options software menus and submenus implemented in
the Smartpack controller with 3.05 firmware.
Block Diagram
RS232 cable
(to external equipment)
CAN bus
(twisted-pair CAT5 cable)
RS485 cable
(to external equipment)
Smartpack
controller
Smartnode
module
For more information and connection details, refer to the “Installation Guide
Battery Monitor CAN node” (351507-033) or the system’s quick start guide.
Refer also to the PowerSuite Help, for symmetry configuration of Battery
Monitor Control Units.
The fuse monitoring inputs are suitable for monitoring a wide range of breakers
in both positive and negative DC distributions.
For a complete sorted overview of available inputs and outputs, see “System
Inputs and Outputs - Overview” on page 214.
For a complete sorted overview of available inputs and outputs, see “System
Inputs and Outputs - Overview” on page 214.
Warning:
To prevent damaging the I/O Monitor’s Speed Control Outputs, do not
The two inputs “Config. Input 5” and “Config. Input 6” are designed for
accurate analogue current measurements of fuel tank level, wind measurements,
etc. But they can also be used for voltage measurements.
For a complete sorted overview of available inputs and outputs, see “System
Inputs and Outputs - Overview” on page 214.
For a complete sorted overview of available inputs and outputs, see “System
Inputs and Outputs - Overview” on page 214.
Now when an alarm monitor assigned to the “Generator AOG” Alarm Output
Group raises an alarm, the alarm relay outputs 1 and 2 will change from open to
close or vice versa.
For information about how to edit an alphanumeric field or a drop-down list,
refer to the Glossary section.
To configure the alarm monitor to function as described, you must perform the
following steps:
1. Configure the Alarm Output Group
2. Configure the Battery Charging Current Limitation
3. Configure the Alarm Monitor
For information about how to edit an alphanumeric field or a drop-down list,
refer to the Glossary section.
Continue with the tutorial’s “Step 1 - Configure the Alarm Output Group” on
page 234.
Continue with the tutorial’s “Step 2 - Configure the Battery Charging Current
Limitation” on page 234.
You find more information about the Battery Charging Current Limitation (page
182), in the Functionality Description section.
The “ProgInput 1.1” alarm monitor link is now active and in blue text.
For information about how to use the drop-down list, refer to the Glossary
section.
Now you have configured PowerSuite so that when the AC generator supplies
the DC power system, the alarm monitor will limit the battery charging current
and activate several alarm output relays.
Now you are finished with tutorial “How to Configure Alarm Monitors &
Programmable Inputs” on page 233.
Copyright - Eltek
Information in this document is subject to change without notice and does not
represent a commitment on the part of Eltek.
AC
Alternating current (AC) is the electric current whose magnitude and direction
vary cyclically with time.
AFC
Available Fault Current (AFC): The current that flows in a circuit if a short-
circuit of negligible impedance were to occur at a given point
Alarm Monitor
Alarm monitors are software modules used by the controller to measure system
internal and external input signals or logical states.
When an alarm monitor is enabled, it compares the measured parameter with
pre-programmed values or limits, and raises an alarm in the event of the
measured parameter reaching one of the limits.
When this event occurs, the alarm monitor stores the event in the Event Log,
initiates an internal action and activates an output group (AOG).
PowerSuite uses 3 types of alarm monitors:
Analogue Alarm Monitors (usually measure voltage or other analogue input
signals),
Numeric Alarm Monitors (count the number of AC phases, rectifiers or other
integers) and
Logical Alarm Monitors (report the state of relay contacts, open or close, or
other similar status)
Read topic Alarm Monitor in PowerSuite Help section, to find out how to
interact with alarm monitor dialogue boxes in PowerSuite.
Read more about Alarm Monitors (page 189) in the Functionality Description
section.
Alarm State
The state of a voltage output or the position of alarm relay contacts when the
output is NOT in normal condition (the output is activated).
Alphanumeric Field
In standard Windows interface, alphanumeric fields in dialogue boxes are areas
that contain text strings or numeric values that the user may change.
Do following to edit the text strings or numeric values in alphanumeric fields:
1. Click inside the field, to insert the cursor in the text or value.
Use your keyboard’s arrow keys to reposition the cursor
2. Use the keyboard’s standard editing keys (Delete, Backspace and
typing keys) to edit the text or value
Press the ESC key or click on the dialog box’s Cancel button or Close
button, if you want to discard the edited changes.
3. Click on the Apply button, in the dialogue box, to save the changes
Accepting or Rejecting Entered Data
In standard dialog boxes, clicking on the Apply or the OK buttons will activate
the parameters and data you entered or selected in the box’s fields.
Clicking on the Cancel button or the Close button – the cross, in the dialog
box’s title bar – will close the dialog box, and all parameters and data you may
have selected in the box’s fields will be rejected.
Allowed range of values
If you enter values outside a field’s allowed range, a red balloon with an
exclamation mark will appear by the field.
Use the mouse to point at the exclamation mark, and a tool tips text box will
indicate the field’s allowed range.
Alphanumeric Fields
See Alphanumeric field
Ampere-hours (Ah)
A measure of energy that is provided to or drawn from a battery. (A current of
one ampere for one hour equals 1Ah).
Battery Block
Consist of two or more battery cells connected together. Usually, the battery
block consists of a “physical” battery pack, commonly called a “battery”.
Read more about Battery Functions (page 159) in the Functionality Description
section.
Battery Capacity
By accepted convention worldwide, it is described in "AMPERE HOUR" at the
10-hour rate C10 when discharged at 25°C.
i.e.: a battery is 200 Ah at C10, that is the battery will deliver 20 amps current
for 10 hours to a cut off voltage of for example 1.80 volts per cell.
Battery capacity is affected by the discharge rate, end-voltage, temperature and
age.
Read more about Battery Functions (page 159) in the Functionality Description
section.
Battery Cell
An electrochemical system that converts chemical energy into electrical energy.
Battery Cycle
A full charge followed by a full discharge (or the other way around). Cycle life is
measured by the amount of times a battery may be charged and discharged.
Every time a battery is charged and discharged, it uses one cycle. Cycle life is
very important in battery applications such as laptop batteries and emergency
light batteries. A NiCad battery has a cycle life of 500-1000 or more cycles.
Read more about Battery Functions (page 159) in the Functionality Description
section.
Boost Mode
Boost Mode is one of the PowerSuite’s operation modes, where the rectifiers
charge the batteries much faster than while in Float Mode.
Boost Voltage
Indicates the output voltage during fast battery recharge (battery boost charging).
Increased charge voltage will reduce the required recharge time.
Browser
Short for Web browser, a software application used to locate and display Web
pages. The two most popular browsers are Microsoft Internet Explorer and
Mozilla Firefox. Both of these are graphical browsers, meaning that they can
display graphics as well as text. In addition, most modern browsers can present
multimedia information, including sound and video, though they require plug-ins
for some formats.
The WebPower firmware is tested and approved for MS Windows with the latest
versions of the following Web browsers: Microsoft Internet Explorer and
Mozilla Firefox. Other browsers and operating systems may also be used, though
faultless behavior cannot be guaranteed.
CAN Bus
Controller Area Network (CAN or CAN bus) is a serial protocol utilized for
communication between Eltek’s rectifiers, controllers and other control units.
The CAN bus standard was originally designed to allow microcontrollers and
devices to communicate with each other without a host computer.
The CAN specification defines the Data Link Layer, while ISO 11898 defines
the Physical Layer.
The CAN bus is a 2-wire interface running over either a Shielded Twisted Pair
(STP), Un-shielded Twisted Pair (UTP), or Ribbon cable. Each node uses a Male
9-pin D connector.
Capacity
The electrical energy content of a battery as expressed in ampere-hours (Ah).
Capacity is the total number of ampere-hours or watt-hours that can be
withdrawn from a fully charged cell or battery under specific condition of
discharge.
CEC
Canadian Electric Code (CEC), in Canada
Cell mismatch
Cells within a battery pack containing different capacity and voltage levels.
Cell reversal
The stronger cells of a battery (several cells connected in series) impose a
voltage of reverse polarity across a weaker cell during a deep discharge.
Charge
The process of replenishing or replacing the electrical charge in a rechargeable
cell or battery.
Circuit Breaker
A circuit breaker is an automatically operated electrical switch designed to
protect an electrical circuit from damage caused by overload or short circuit.
Its basic function is to detect a fault condition and, by interrupting continuity, to
immediately discontinue electrical flow. Unlike a fuse, which operates once and
then has to be replaced, a circuit breaker can be reset (either manually or
automatically) to resume normal operation.
Compack
A versatile microprocessor based controller for monitoring Micropack DC power
supply systems. The controller is designed for DIN rail mounting.
Control Unit
See Control Units.
Control Units
The control system -- in Eltek DC power systems – consists of control units or
hardware devices connected to the system’s CAN bus.
Several types of control units may be connected, such as:
Smartpack2 Master controllers
Smartpack2 Basic controllers
Smartpack controllers
Compack controllers
Controller
A generic expression for one of the power system’s microcontrollers:
Smartpack2 Master, Smartpack2 Basic, Smartpack or Compack controllers.
Controllers
See Controller
C-rate
Unit by which charge and discharge times are scaled. A battery rated at
1000mAh provides 1000mA for one hour if discharged at 1C. A discharge of 1C
draws a current equal to the rated capacity. The same battery discharged at 0.5C
would provide 500mA for two hours.
Critical Condition
A DC power system’s state caused when one or several serious circumstances
occur. Usually, the DC power supply system is in critical condition when the
battery bank is the only supply source (negative battery current).
Using PowerSuite, you can configure which circumstances (monitors in alarm)
the DC power system has to encounter for the system to be in critical condition.
Crossover Cable
An Ethernet crossover cable is a type of Ethernet cable used to connect
computing devices together directly where they would normally be connected
via a network switch, hub or router, such as directly connecting two personal
computers via their network adapters.
The 10BASE-T and 100BASE-TX Ethernet standards use one wire pair for
transmission in each direction. The Tx+ line from each device connects to the tip
conductor, and the Tx- line is connected to the ring. This requires that the
transmit pair of each device be connected to the receive pair of the device on the
other end. When a terminal device is connected to a switch or hub, this crossover
is done internally in the switch or hub. A standard straight through cable is used
for this purpose where each pin of the connector on one end is connected to the
corresponding pin on the other connector.
Current-limiting chargers
A charger that keeps the charge current constant during the charge process but
allows the voltage to fluctuate.
DC
Direct current (DC) is the constant flow of electric charge with constant polarity.
The electric charges flow in the same direction, distinguishing it from alternating
current (AC)
DC Power System
See DC Power Supply Systems
Delta Voltage
Delta voltage is an absolute calculated value that represents how well balanced
the battery blocks that form a string are. PowerSuite uses this expression when
calculating battery symmetry.
Delta voltage (Vdelta) is the difference between the calculated and the measured
voltages, e.g. (Vbattery / 2) - Vmeasured = | Vdelta |
A Delta voltage of 0V indicates a completely balanced battery string.
DHCP
Dynamic Host Configuration Protocol (DHCP) is a network application protocol
used by devices (DHCP clients) to obtain configuration information for
operation in an Internet Protocol network. This protocol reduces system
administration workload, allowing devices to be added to the network with little
or no manual intervention.
DOD
Depth of Discharge; See Cycle life
Drop-down List
In standard Windows interface, a drop-down list in a dialogue box is a field
containing a down-arrow button at the field’s right side, which displays a list of
text strings or numeric values that the user may select from.
When the list is up, the field displays the selected value.
Do following to select values form the drop-down list:
1. Click on the down-arrow button, to display the list with available
values
2. If the list is longer than displayed, click on the list’s scroll bar buttons
(up or down buttons) to find the value you want to select
3. Click on the value you want to select.
The drop-down list disappears and the selected value is displayed
Accepting or Rejecting Entered Data
In standard dialog boxes, clicking on the Apply or the OK buttons will activate
the parameters and data you entered or selected in the box’s fields.
Clicking on the Cancel button or the Close button – the cross, in the dialog
box’s title bar – will close the dialog box, and all parameters and data you may
have selected in the box’s fields will be rejected.
Drop-down Lists
See Drop-down List
Earthing System
In electricity supply networks, an earthing system defines the electrical
potential of the conductors relative to that of the Earth's conductive surface.
Eltek
Eltek is a global corporation that secures worldwide communication by
providing critical power solutions for telecom infrastructure, as well as for
industrial and solar applications.
End-of-Discharge Voltage
The voltage point to which a battery can be discharged is a function of the
discharge rate. The Recommended End-Voltage Point (REVP) is the voltage at
which a battery should be disconnected from the load.
Discharging the battery below the REVP, or leaving the battery connected to a
load in a discharged state will “over-discharge” the battery, and may impair its
ability to accept charge.
Energy
Voltage multiplied by current expressed in watts.
Equalizing Charge
With time, the charge levels of individual cells of a large battery tend to become
slightly unbalanced. The equalizing charge applies an elevated charge voltage
for a few hours to balance the cells. Used mainly for large lead acid cells.
Ethernet
Local Area Network technology. Ethernet provides data transfer using a
baseband (single-channel) communication technique. Ethernet uses carrier sense
Ethernet, more…
Ethernet is a large, diverse family of frame-based computer networking
technologies that operates at many speeds for local area networks (LANs).
It defines a number of wiring and signaling standards for the physical layer,
through means of network access at the Media Access Control (MAC)/Data Link
Layer, and a common addressing format.
Ethernet has been standardized as IEEE 802.3. The combination of the twisted
pair versions of Ethernet for connecting end systems to the network with the
fiber optic versions for site backbones become the most widespread wired LAN
technology in use from the 1990s to the present, largely replacing competing
LAN standards such as coaxial cable Ethernet, token ring, FDDI, and ARCNET.
In recent years, Wi-Fi, the wireless LAN standardized by IEEE 802.11, has been
used instead of Ethernet for many home and small office networks and in
addition to Ethernet in larger installations.
Event
See Events
Events
In Eltek DC power systems, events are system internal actions used by the
controller’s alarm monitors.
Alarm monitors measure system internal and external input signals or logical
states, and compare the measured parameter with pre-programmed values or
limits. The alarm monitors raise an alarm in the event of the measured
parameter reaching one of the limits.
EVIPSetup.exe
See Eltek Network Utility Program
Firmware
Firmware is software stored permanently on ROM or PROM chips. It can also be
electrically erased and reprogrammed (flashed) when stored in EEPROM chips.
Flatpack
Eltek’s range of Flatpack rectifiers used in Flatpack DC power supply systems.
The systems use the MCU controller and Flatpack rectifiers as their building
blocks. Though the range has been installed worldwide in a variety of system
solutions, and it is now replaced by the compact Flatpack2 range.
Flatpack2
Eltek’s modern of Flatpack2 rectifiers used in Flatpack2 DC power supply
systems. In addition to Flatpack2 rectifiers, the systems use the Smartpack2
Master and Smartpack2 Basic controllers or the Smartpack controller as their
Float charge
Similar to trickle charge. Compensates for the self-discharge on a lead acid
battery.
Float Mode
Float Mode is one of the PowerSuite’s operation modes, where the rectifiers
charge the batteries enough to compensate for self-discharging.
FTP Server
Trivial File Transfer Protocol Server (TFTP). A host to provide services
according to TFTP; a TCP/IP standard protocol for file transfer with minimal
capability and overhead depending on UDP for ts datagram delivery service.
Generator
An engine-generator is the combination of an electrical generator and an engine
(prime mover) mounted together to form a single piece of equipment. This
combination is also called an engine-generator set or a gen-set. In many
contexts, the engine is taken for granted and the combined unit is simply called a
generator.
Gen-Set
See generator
GUI
GUI is pronounced GOO-ee, and is an acronym for Graphical User Interface.
Usually it is a program interface that takes advantage of the computer's graphics
capabilities to make the program easier to use, such as the WebPower browser-
based interface or the PowerSuite Windows application or the graphical menus
in the Smartpack2 Master controller.
Well-designed graphical user interfaces can free the user from learning complex
command languages. On the other hand, many users find that they work more
effectively with a command-driven interface, especially if they already know the
command language.
HTTP
Hypertext Transfer Protocol (HTTP) is a communications protocol for the
transfer of information on intranets and the World Wide Web. Its original
purpose was to provide a way to publish and retrieve hypertext pages over the
Internet.
HUB
A common connection point for devices in a network. Hubs are commonly used
to connect segments of a LAN. A hub contains multiple ports. When a packet
arrives at one port, it is copied to the other ports so that all segments of the LAN
can see all packets.
IEC
The International Electrotechnical Commission (IEC) is a leading organization
that prepares and publishes International Standards for all electrical, electronic
and related technologies. The most familiar guiding organization in Europe;
based in Switzerland.
InstallShield Wizard
A graphical screen interface that guides you through the steps required to install
a Windows based software application, such as PowerSuite.
InstallShield for Windows Installer by InstallShield Software Corporation.
The InstallShield Software Corporation creates products that distribute and
manage digital content by using packaged applications.
IP Address
The Internet Protocol Address
IP version 4 addresses (IPv4) uses 32-bit (4-byte) addresses, which limits the
address space to 4,294,967,296 possible unique addresses. However, IPv4
reserves some addresses for special purposes such as private networks (~18
million addresses) or multicast addresses (~270 million addresses).
IPv4 addresses are usually represented in dot-decimal notation (four numbers,
each ranging from 0 to 255, separated by dots, e.g. 208.77.188.166). Each part
represents 8 bits of the address, and is therefore called an octet.
IT
I= isolation; T= earth
See also IEC Earthing System
LAN
Local Area Network
A local area network is a computer network covering a small physical area, like
a home, office, or small group of buildings, such as a school, or an airport.
Current LANs are most likely to be based on Ethernet technology.
Latching Contactor
Magnetically latching contactor
The coil of latching contactors is not energized in any state. They change state
from open to close, or vice versa, when a reversed pulse voltage is applied to its
coil.
LVBD
Low Voltage Battery Disconnect contactor
System internal latching contactor that disconnects the battery bank from the
load, when a certain voltage limit is reached or other battery critical events
occur.
LVD
Low Voltage Disconnect contactor
System internal latching contactor that disconnects the batteries from the load or
the output power from non-priority load, when a certain voltage limit is reached
or a certain event occurs.
LVLD
Low Voltage Load Disconnect contactor
System internal latching contactor that disconnects the output power from non-
priority load, when a certain voltage limit is reached or the mains input fails or
other events occur.
MCB
Miniature Circuit Breaker (MCB)
Originally this term was for a product that met the requirements of IEC 60 898
or IEC 60 947-2, was DIN rail mounted and generally no wider than 25 mm per
pole.
Today MCBs may also refer to devices that also meet North American standards
such as UL 489, UL 1077, CSA 22.2 No. 5 and No. 235.
MIB
Management Information Base, a database of objects that can be monitored by a
network management system. SNMP uses standardized MIB formats that allows
any SNMP tools to monitor any device defined by a MIB
Micropack
Eltek’s modern range Micropack rectifiers used in Micropack DC power supply
systems. The systems use the Compack controller, Micropack rectifiers, Battery
Distribution Base and Load Distribution Bases as their building blocks. All units
are designed for DIN rail mounting.
The range covers low power solutions in telecom and industrial applications.
Mini Hub
A common connection point for devices in a network. Hubs are commonly used
to connect segments of a LAN. A hub contains multiple ports. When a packet
arrives at one port, it is copied to the other ports so that all segments of the LAN
can see all packets
Minipack
Eltek’s range of Minipack rectifiers used in Minipack DC power supply systems.
The systems use either the Smartpack or the Compack controllers and Minipack
rectifiers as their building blocks.
Minipack systems implement a unique system design with extractable system
shelf for easy access and fast installation. Complete 1U high systems offer up to
1.6kW DC output power, while 2U high systems deliver up to 4.8kW.
Modem
A modem (from modulate and demodulate) is a device that modulates an analog
carrier signal to encode digital information, and also demodulates such a carrier
signal to decode the transmitted information.
NEC
National Electric Code (NEC), in the USA, guide electricians in the proper
installation of electrical equipment, and defines among other things the specific
requirements for circuit protection.
Circuit protection is required to prevent fires from occurring, due to overcurrent
faults or short-circuits.
Negative DC Distribution
It is usually implemented in 48V and 60V DC power supply systems, which
have the DC distribution on the negative output (-48VDC or -60VDC), and
the positive on a Common Positive DC Output Rail (0V).
NFPA
National Fire Protection Association (NFPA) in the USA
NIC
Network Interface Controller.
A network card, network adapter, network interface controller, network interface
card, or LAN adapter is a computer hardware component designed to allow
computers to communicate over a computer network. It is both an OSI layer 1
(physical layer) and layer 2 (data link layer) device, as it provides physical
access to a networking medium and provides a low-level addressing system
through the use of MAC addresses. It allows users to connect to each other either
by using cables or wirelessly.
NMS
Network Management Station -An SNMP Manager application which interfaces
with the SNMP Agent and provides communication capabilities through
standard SNMP messaging commands (SET, GET). The NMS also serves to
collect SNMP TRAP events.
A Network Management System (NMS) is a combination of hardware and
software used to monitor and administer a network.
NO-C-NC
Acronym for Normally Open, Common and Normally Closed. The expression
refers to the position of 3 relay contacts, when the relay coil is de-energized.
When the relay coil is energized, the NO-C contacts close, and the C-NC
contacts open.
Nominal voltage
The cell voltage that is accepted as an industrial standard.
Normal Condition
A DC power system’s state when no serious circumstances occur. Usually, the
DC power supply system is in normal condition when no critical condition
occurs.
Normal State
The state of a voltage output or the position of alarm relay contacts when the
output is in normal condition (not activated).
Overcharge
Charging a battery after it reaches full charge. On overcharge, the battery can no
longer absorb charge and the battery heats up.
Overcurrent
The National Electrical Code (NEC) defines overcurrent as any current in excess
of the rated current of equipment or the ampacity of a conductor. It may result
from overload, short-circuit, or ground fault.
OVP
Over Voltage Protection
OVS
Over Voltage Shutdown
When the output voltage of a malfunctioning rectifier reaches a certain limit, the
system automatically shuts down to prevent damages.
pComm
RS232 serial protocol used by Eltek’s controllers for communication with
computers, modems, WebPower adapters and other equipment.
Pop-up
A window that suddenly appears (pops up) when you select an option with a
mouse or press a special function key. Usually, the pop-up window contains a
menu of commands and stays on the screen only until you select one of the
commands. It then disappears. A special kind of pop-up window is a pull-down
menu, which appears just below the item you selected, as if you had pulled it
down.
Powerpack
Eltek’s modern range of Powerpack three-phase rectifiers used in Powerpack DC
power supply systems. The systems use the Smartpack controller and large
Powerpack three-phase rectifier modules as their building blocks.
PowerSuite
Advanced PC application used to configure and operate Micropack, Minipack,
Flatpack2 and Powerpack DC power supply systems. The program is to be run
on computers using the MS Windows operating systems.
Priority Load
Very important telecom equipment or similar supplied from the DC power
system’s load output circuits. The equipment’s continuous operation is essential
and has high backup priority during Mains outages.
PSS
Power Supply System
RCD
Residual Current Device
They are simple fittings designed to help prevent electric shock and other
accidents due to faulty electrical appliances or wiring.
An RCD can detect changes in the proper flow of electric current (when a flex or
cable is cut, for instance, or an electrical tool malfunctions). Within milliseconds
of this happening, the RCD automatically disconnects the power supply to the
equipment before further damage can be done.
REVP
Recommended End-Voltage Point. Read also “_d2h_bmk__Ref228001673_106”
on page Error! Bookmark not defined.
RJ-45
Short for Registered Jack-45, an eight-wire connector used commonly to connect
computers onto local area networks (LAN), especially Ethernets. RJ-45
connectors look similar to the ubiquitous RJ-11 connectors used for connecting
telephone equipment, but they are somewhat wider.
RS232
Serial communication bus or communication port
Serial data port that allows for connection of data devices in accordance with
EIA standards
Shunt
A current shunt is usually a resistor of accurately-known very small resistance
that allows the measurement of current values too large to be directly measured
by a particular ammeter.
The current shunt is placed in series with the load, so that nearly all of the
current to be measured will flow through it. The voltage drop across the shunt is
proportional to the current flowing through it, and since its resistance is known, a
millivolt meter connected across the shunt can be scaled to directly read the
current value.
Shunts are rated by maximum current and voltage drop at that current, for
example, a 500A/75mV shunt would have a resistance of 0.15 milliohms, a
maximum allowable current of 500 amps and at that current the voltage drop
would be 75 millivolts.
By convention, most shunts are designed to drop 75mV when operating at their
full rated current and most "ammeters" are actually designed as voltmeters that
reach full-scale deflection at 75mV.
Smartpack
A versatile microprocessor-based controller used for monitoring Minipack,
Flatpack2 and Powerpack DC power supply systems in a network.
Smartpack2
A modular, microprocessor-based control system used in modern Flatpack2 DC
power supply systems in a network.
The control system is distributed between the Smartpack2 Master controller, the
Smartpack2 Basic controller and the I/O Monitor2 control unit.
SNMP
Simple Network Management Protocol, a set of protocols for managing complex
networks. The first versions of SNMP were developed in the early 80s. SNMP
works by sending messages, called protocol data units (PDUs), to different parts
of a network. SNMP-compliant devices, called agents, store data about
themselves in Management Information Bases (MIBs) and return this data to the
SNMP requesters.
SNMP Agent
An SNMP-compliant device that stores data about itself in Management
Information Bases (MIBs) and return this data to the SNMP requesters.
SOC
State of Charge; See Cycle life
Software
Software are programs for directing the operation of computers,
microprocessors, controllers, etc. or for processing electronic data.
SPD
Surge Protection Device
A surge protector (or surge suppressor) is an appliance designed to protect
electrical devices from voltage spikes. A surge protector attempts to regulate the
voltage supplied to an electric device by either blocking or by shorting to ground
voltages above a safe threshold.
Strapping
Storage tank calibration is also known as Tank Strapping. Consists of
measurement of the tank geometry and calculation of capacity tables or
strapping tables, which provide conversion from depth of product, in linear
units of measurement, to volume of contents.
TCP/IP
Transmission Control Protocol/Internet Protocol
A protocol suite used by more than 15 million users with a UNIX association
and widely used to link computers of different kinds.
The Internet Protocol Suite (commonly known as TCP/IP) is the set of
communications protocols used for the Internet and other similar networks. It is
named from two of the most important protocols in it: the Transmission Control
Protocol (TCP) and the Internet Protocol (IP), which were the first two
networking protocols defined in this standard.
Test Mode
Test Mode is one of the PowerSuite’s operation modes, where the system
controller is performing a specific preprogrammed test of the battery bank.
The Cycle
A process consisting of a single charge and discharge of a rechargeable battery.
TN
T= earth (Latin: terra); N= neutral
See also IEC Earthing System
Trickle charge
Maintenance charge to compensate for the battery's self-discharge.
TT
T= earth (Latin: terra); T= earth
See also IEC Earthing System
UDP
The User Datagram Protocol (UDP) is one of the core members of the Internet
Protocol Suite, the set of network protocols used for the Internet. With UDP,
computer applications can send messages, sometimes known as datagrams, to
other hosts on an Internet Protocol (IP) network without requiring prior
communications to set up special transmission channels or data paths. UDP is
sometimes called the Universal Datagram Protocol.
UL
Underwriters Laboratories Inc. (UL) is an independent product safety
certification organization. Established in 1894, the company has its headquarters
in Northbrook, Illinois, USA. UL develops standards and test procedures for
products, materials, components, assemblies, tools and equipment, chiefly
dealing with product safety.
URL
URL is an abbreviation of Uniform Resource Locator, the global address of
documents and other resources on the World Wide Web.
The first part of the address is called a protocol identifier (ftp, http, etc.) and it
indicates what protocol to use. The second part is called a resource name and it
specifies the IP address or the domain name where the resource is located. The
protocol identifier and the resource name are separated by a colon and two
forward slashes. For example: ftp://sw.eltek.com/powersuite.exe and
http://www.eltek.com/index.html
USB
Universal Serial Bus is a serial bus standard to interface devices to a host
computer. USB was designed to allow many peripherals to be connected using a
single standardized interface socket and to improve plug and play capabilities by
allowing hot swapping, that is, by allowing devices to be connected and
disconnected without rebooting the computer or turning off the device. Other
convenient features include providing power to low-consumption devices
without the need for an external power supply and allowing many devices to be
used without requiring manufacturer specific, individual device drivers to be
installed.
VPN
A virtual private network (VPN) is a computer network in which some of the
links between nodes are carried by open connections or virtual circuits in some
larger network (e.g., the Internet) as opposed to running across a single private
network. The link-layer protocols of the virtual network are said to be tunnelled
through the larger network. One common application is secure communications
through the public Internet, but a VPN need not have explicit security features,
such as authentication or content encryption. VPNs, for example, can be used to
separate the traffic of different user communities over an underlying network
with strong security features.
WebPower
A common name for the firmware installed in Eltek’s controllers – Smartpack2
Master, Compack and Smartpack, web option – and in the external WebPower
adapter module. The firmware provides a communication protocol translator, a
physical layer conversion and Web server software.
WebPower translates the controller’s internal protocol into the HTTP protocol
over TCP/IP, used to communicate in an Ethernet network, LAN, WAN, VPN or
even across the Internet.
The WebPower firmware provides a platform-independent graphical user
interface (GUI), employed to configure and operate Micropack, Minipack,
Flatpack2 and Powerpack DC power supply systems using a standard Web
browser.
In addition, WebPower provides an SNMP Agent, allowing Eltek DC power
systems to be interoperable with SNMP enterprise management solutions, which
are commonly in use within the Telecommunications industry.
Index B
Battery 28
Battery Bank nn subpage 28
Battery Banks, Strings and Blocks 159
Battery Boost Charging 180
Battery Boost subpage 28
Battery Charging Current Limitation 182
Battery Commands 161
Battery Cycles Diagram 105
" Battery Discharge Cycles Log 105
"BatteryLifeTime" Monitor Calculations 184 Battery Functions 159
Battery Monitor's Symmetry Connections, 24V 168
Battery Monitor's Symmetry Connections, 48V Block
+ M 164
+24V Systems ~ Battery Monitor's Symmetry Inputs Battery Monitor's Symmetry Connections, 48V Mid-
92 Point M 165
+24V Systems ~ Smartpack's Symmetry Inputs 93 Battery Symmetry Calculations 170
Battery Symmetry Measurements 161
Battery Tables 173
‒ Battery Temperature Levels ~ "BatteryLifeTime"
‒48V Systems ~ Battery Monitor's Symmetry Inputs monitor 184
88 Battery Test Log subpage 15
‒48V Systems ~ Smartpack's Symmetry Inputs 90 Battery Test Results web page 14
Battery Test Start Methods 177
Battery Test subpage 28
A
Battery Tests 175
About AC, DC Earthing Systems 108 Battery web page 28
About Eltek 237 Block Diagram 219, 220, 224
About Eltek's SNMP MIB Files 77 Block Measurement Calculation -- Example 171
About Hybrid Systems 125
About Negative & Positive DC Distribution Systems C
111
About Power System Configuration 46 Calibration - Battery Current 85
About the FWLoader Program 202 Calibration - Battery Symmetry Voltage 86
About the WebPower Firmware 2 Calibration - Battery Temperature 94
AC Generator as AC Mains 123 Calibration - Battery Voltage 86
Access Levels 188 Calibration - Earth Fault Detection 94
Accessing the Controller and Logging In to CAN Bus Address Range -- Control Units 211
WebPower 4 CAN bus Addressing 210
Active Alarm Groups web page 24 CAN bus Termination 111
Alarm Configuration options 55 Cannot Find the Com Port Number 43
Alarm Messages, (Log) 106 Climate Control Functions - Outdoor Cabinets 114
Alarm Monitors 189 Climate Control Signals ~ I/O Monitor (T1 and T3)
Alarm Output Groups 193 227
Alarm Outputs Isolation (Outputs Blocked) 196 Commands options 58
Alarm Reset 107 Commissioning options 60
All Available System Inputs & Outputs 216 Compack Controller 3
Answer: 31, 32, 33, 35, 39, 40, 44 Compack nn subpage (inputs) 29
Available Inputs and Outputs 219, 220, 224, 225, Compack nn subpage (outputs) 29
226, 227, 229, 230 Compliance to International Standards 237
Available System AC Measurement Inputs 216 Configuration Criteria 125
Available System Alarm Relay Outputs 214 Configuration of Critical Condition 107
Available System Current Sense Inputs 214 Configuration of Generator Functionality 127
Available System Fan Control Inputs & Outputs 215 Configuration subpage (battery) 28
F I
Fan Filter Monitoring - Pressure Test 117 In Short 63, 68, 73
Fan Speed Control - ON/OFF 117 Inputs 29
Fan Speed Control and Monitoring - PWM 115 Inputs web page 29
Firmware Files and LAN Devices 205
Firmware Upgrade 196
L
Firmware Upgrade - Controllers with Ethernet Port
202 Load 28
Firmware Upgrade - Rectifiers 152 Load Bank nn subpage 28
Firmware Upgrade - Smartpack Controller 200 Load Current Calculation 157
Firmware Upgrade - Smartpack2 Controllers 198 Load Functions 154
Firmware Upgrade - Smartpack's Embedded Web Load Groups 154
Adapter 204 Load Monitor Energy Log 101
Firmware Upgrade - Stand-alone WebPower Adapter Load web page 28
204 Location - Map Coordinates 79
Firmware Upgrade from a Computer 199 Logs and Reports options 59
Firmware Upgrade from the SD Card 198 LVBD - Battery Protection 185
Forefront Telecom Power Products 237 LVBD subpage 28
Frequently Asked Questions, FAQs 31 LVLD ~ Non-Priority Load Disconnection 156
From Configuration Web Pages 82, 107, 145
From PowerSuite 82, 107, 144 M
From the Smartpack Controller's Front 81, 106, 144
From the Smartpack2 Master Controller's Front 81, Mains 27
106, 144 Mains Functions 121
Functionality Overview 45 Mains Outage Log 102
Mains Phase Assignment versus Rectifier ID 121
Mains web page 27
G
Map Coordinates tab 11
Generator Control Logic - Flowchart 140 Master Password - Reset All Passwords 188
Generator Fuel Consumption Log 103 Measurement Logs 97
U
Understanding the WebPower Interface 6
Up/Download options 61
Using WebPower 9
W
Web Address Line - WebPower (6) 9
WebPower FAQs 32
WebPower Home Page 6
Welcome to WebPower 1
What to Calibrate 83
Which Program to Use for Upgrading 197