SM100-A (B) Hart Intelligent Converter User Manual: Jiaxing Songmao Electronic Co. Ltd. China
SM100-A (B) Hart Intelligent Converter User Manual: Jiaxing Songmao Electronic Co. Ltd. China
SM100-A (B) Hart Intelligent Converter User Manual: Jiaxing Songmao Electronic Co. Ltd. China
HART INTELLIGENT
CONVERTER
USER MANUAL
http://www.smdznet.com
http://www.hart-rs232.com
-0-
Contents
1 SM100-A (B) Introduction .................................................................................................................... - 4 -
1.1 Product Introduction .................................................................................................................. - 4 -
1.2 Product Features........................................................................................................................ - 4 -
1.3 Key Parameters.......................................................................................................................... - 4 -
2 SM100-A (B) Diagram and LED Functions ...................................................................................... - 5 -
2.1 Diagram ....................................................................................................................................... - 5 -
2.2 Product Selection ....................................................................................................................... - 5 -
2.3 Introduction of Interfaces .......................................................................................................... - 6 -
2.4 LED Indications .......................................................................................................................... - 6 -
3 Connecting Diagram and Precautions .............................................................................................. - 7 -
3.1 Connecting Diagram with Different Instruments.................................................................... - 7 -
3.2 Differences between Two-Wiring and Four-Wiring HART Protocol Intelligent Instruments
-8-
3.3 The Debugging Procedures of the Intelligent Converter Connecting with Multiple HART
Protocol Instruments ........................................................................................................................ - 8 -
4 Configuration Software Function Introduction and Operation Steps ............................................ - 9 -
4.1 System Parameter Interface Function Introduction .............................................................. - 9 -
4.2 Transmission Mode Interface Function Introduction............................................................. - 9 -
4.3 General HART Protocol Interface Function Introduction ................................................... - 10 -
4.4 Introduction of Special HART Protocol Interface Function ................................................ - 10 -
4.5 Introduction to Customized HART Protocol Interface Features ........................................ - 11 -
4.6 Reading Data with ModScan32 Test Software.................................................................... - 11 -
5 Data Register Address ...................................................................................................................... - 12 -
6 Service and Warranty Information ................................................................................................... - 13 -
-1-
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
Statement:
Copyright © 2018 SMDZNET. All Rights Reserved.
Please read the manual intensively before using the product. .First please confirm which type of Instruments is used with the
HART protocol, and then find out the appropriate using method in the manual. Before switching on the power, please confirm all
interfaces are correctly connected. The company will not be liable for any damage caused by this product unless following the
instructions.
SMDZNET provides the manual for instructions. Specifications and information contained in this manual are furnished for
informational use only, and are subject to change at any time without notice, and should not be construed as a commitment by
SMDZNET. SMDZNET assumes no responsibility or liability for any changes or invalidation that may appear in this manual, due
to the upgrading for the products or software described in it. Please notice the version and update it timely.
Please visit the support website www.hart-rs232.com for the latest information. If any confusion towards the specifications and
information contained in this manual, please contact us or the local supplier directly. Please E-mail :smdz2007@smdznet.com or
contact QQ: 2850687718 , tel:86-4007-803-803 if encountering problems.
Copyright statement:
No part of this manual, including the products and software described in it, may be reproduced, transmitted, transcribed, stored in
a retrieval system, or translated into any language in any form or by any means, except documentation kept by the purchaser for
backup purposes, without the express written permission of SMDZNET.
-2-
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
SM100-A (B) HART Intelligent Converter connect the Instruments
Radar Level Gauge 3300 Transmitter 1700 (2700) Electromagnetic Flowmeters of 8700 Series
Radar level Gauges of 5400 Series Integrated Temperature Transmitter Multivariable Transmitter
248
2) Siemens Series
3) KROHNE Series
Flowmeter UFC500
4) ABB Series
5) E+H Series
Flowmeter of NMS 53X Series Level Meter of FMR 53X Series Material Level Meter of FMU 40X Series
Differential Pressure Transmitter PDM Liquid Level Meter of FMR 23X (24x) Mass Flowmeter PROWIRL
23X (26X) Series
6) Yokogawa Series
Intelligent Pressure Gauges of LD301 Ultrasonic Liquid Level Transmitter FISHERMETER Vortex Shedding Flowmeter
series MSP400R VT5000
Metal Tube Float Flowmeters of F56 Metal Tube Float Flowmeters of HT50 Radar Material Level Meter VAG
Series Series
-3-
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
1 SM100-A (B) Introduction
1.1 Product Introduction
The SM100-A (B) is HART intelligent converters designed by JIAXING SONGMAO. It is researched and developed by ARM
microprocessor, HART protocol modulation and demodulation ASIC, and experienced with a lot of practical applications. The
design is in accordance with the requirements of industrial products with high reliability and stability. The intelligent converter is
equipped with standard RS232 and RS485 interfaces, which can be transparently transmitted to the intelligent instruments with
HART protocol or converted to MODBUS_RTU Protocol to read data, ensuring the live transmission.
The HART protocol is complied with the standard of Bell202 Frequency Shift Keying (FSK), and modulate digital signals on a
basis of 4~20mA, which leads the HART protocol instruments to bidirectional data communication without interfering the analog
signal of 4-20mA. The intelligent converters of SM100 series are for bidirectional modulation and demodulation with digital
signals and analog signals.
-4-
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
2 SM100-A (B) Diagram and LED Functions
2.1 Diagram
Model Application
The RS232 interface is suitable for the DATA RTU between collector and the SM100-A converter in
SM100-A close distance. It does not need to adopt the bus way, the DATA RTU (or PLC ) + multiple SM100-A
intelligent converters + one or more HART protocol intelligent instruments
The RS485 interface is suitable for the communication between DATA RTU and the SM100-B converter
SM100-B in long distance. You can adopt the bus mode to organize network, the DATA RTU (or PLC ) + multiple
SM100-B intelligent converters + one or more HART protocol intelligent instrument
The RS232 interface and RS485 interface are separate communication channels. The same HART
converters can be used for data communication with different DATA RTU, two DATA RTU with different
SM100-A(B)
system (or PLC ) + SM100-A(B)intelligent converters + one or more HART protocol intelligent
instrument
+DC24v mainly used for the HART instruments with power supply less than DC 24V and connecting with DC 24V
Built-In Power two-line-meter.
Supply
-5-
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
2.3 Introduction of Interfaces
● GND, POW: power interface terminals, POW connects the power supply with the positive pole while GND connects with the
negative pole.
● GND, R232RX, R232TX: RS232 communication interface terminals.
● BR485D-, BR485D+: RS485 communication interface terminal A.
● AR485D-, AR485D+: RS485 communication interface terminal B.
● Loop1+, Loop1-~Loop4+, Loop4-: four sets of HART communication interface terminals
-6-
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
3 Connecting Diagram and Precautions
3.1 Connecting Diagram with Different Instruments
(1) Connecting Diagram with Single and Multiple Tow-line-Meter
(3) Connecting Diagram with Two and Four-line-Meter ( Single & Multiple)
-7-
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
(4) Connecting Diagram with HART Converter of Built-In DC24V and Two-Wiring HART Protocol Intelligent Instrument
● -1 is connecting with one HART Protocol intelligent Instrument, the default value of HART is 0, no need modification.
● -4 is connecting with four HART Protocol intelligent Instruments, the HART address needs to be modified to 1,2,3 ,4, then all
the output currents from the HART sensors are 4mA, and only a 250Ω resistance is needed.
● -8 is connecting with eight HART Protocol intelligent Instruments, the HART address needs to be modified to 1,2,3 ,4,5,6,7,8,
then all the output currents from the HART sensors are 4mA, and only a 250Ω resistance is needed.
● If connected with the USB/RS232 Converter, the RS232/RS485 Converter needs to connect with the DC5V power supply.
● when using Siemens PLC programming cord, USB-PPI (USB-RS485 cord), the 3 pin is D+, the 8 pin is D-.
-8-
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
4 Configuration Software Function
Introduction and Operation Steps
4.1 System Parameter Interface Function Introduction
-9-
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
4.3 General HART Protocol Interface Function Introduction
- 10 -
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
4.5 Introduction to Customized HART Protocol Interface
Features
- 11 -
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
5 Data Register Address
Instrument number Variable Variable Variable Variable
Current 40001 40003 40005 40007 40009
0 1 2 3 4
- 12 -
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao
6 Service and Warranty Information
SM100 Series HART Intelligent Converter Quality Assurance
1. The warranty period for the product is 36 months with normal operation conditions from the date of purchase by
end-customers.
2. The company warrants the Product to be free from defects in workmanship and technology for the Warranty Period.
3. This Free Warranty does not include such as but not limited to:
a. The Product has been tampered with, repaired and/or modified without the consent of the company;
b. Damage caused by external force and other natural disasters.
4. When the warranty service is needed, please contact us with calling the service hotline. We would maintain the warranty
service and deliver the product back as soon as possible.
5. This warranty liability limits to the warranty period for the breakdown maintenance of the product, and do not assume other
responsibilities.
- 13 -
SONGMAO Electronic co.ltd Address: Room 1-201, Kechuang Centre, NO. 1369 Chengnan RD, Jiaxing, China
Tel:86-573-82623038
http://www.hart-rs232.com Email:smdz2007@smdznet.com QQ: 2850687718 Skype:smdzyao