SCOUT-S ™ Station Controller

Substation Automation
Station Controllers not only combine the functions
of a traditional RTU with the functionality of a Data
Concentrator, but also includes a Terminal Sever
and a Web Server.
SCOUT-S ™ Extensive communications capabilities are available
over both serial and Ethernet networks. Modular I/O
Station Controller architecture allows the SCOUT-S to be scaled to the
desired point size up to256 I/O points of each type per

features multiple SCOUT-S module up to a database size of 16,000 points.


This innovative architecture allows the SCOUT-S to
IED ports and monitor and control points connected directly to the RTU.
The modular I/O boards are compatible with those used

modular I/O on previous Survalent RTUs, ensuring that the SCOUT-S


unit can replace the main electronic circuits in previous
RTUs such as the XPPB.
architecture This capability also enables a customer to upgrade
to a more feature-rich RTU while leaving the external
wiring untouched. This upgrade capability also applies
to the older 6CPP4 and 6CPP6 RTU models.

Communication Capabilities When connected to an Ethernet LAN, the same


Extensive communications capabilities allow the configuration and diagnostic operations can be
SCOUT-S to connect to IEDs either on multiple ports performed remotely on the RTU via Telnet or a
with multi-drop configurations or over three Ethernet web browser.
ports. Communication to the master(s) can be
A powerful web server is also integrated
configured to occur via serial ports or Ethernet ports.
within the SCOUT-S, allowing operation,
When connected to an Ethernet LAN, one or more
maintenance, and configuration of the
serial ports can be configured to act as terminal
server ports. This allows a remote device (the master RTU without the need of proprietary
or other appropriate computer on the LAN) to access software. Any standard web browser
this port and exchange data with an external device. allows direct access to the web server
As an example, this feature can be used to remotely
built-in within the SCOUT-S.
configure IEDs or upload historical data files.
Simple configuration is provided by the Points Mapping
The SCOUT-S has a dedicated serial port for
Wizard which allows points mapping of third party IEDs
configuration, point monitoring and diagnostics.
and I/O cards in a graphical environment. An extensive
A simple terminal connected to this port will act
library of point maps is available for the most common
as the human interface.
IEDs available on the market, making IED point mapping
a few clicks of the mouse.
SCOUT-S ™ Station Controller

Processing Large Points Database Capacity


▪ NXP P1020 800 MHz Dual Core Processor ▪ Maximum Database Size of 16,000 Points
▪ 64 MB FLASH Memory Analog Inputs (per SCOUT-S module)
▪ 1 GB DDR3 RAM
▪ 256 via 16 I/O expansion boards
▪ Nonvolatile EEPROM for system
▪ Configurable Input ranges: +/-1mA, +/-20mA,
configuration parameters
+/-5V, +/-10V
Communications ▪ Sampling rate 2sec
▪ 11 serial RS232/RS485 for master, IED, ▪ Accuracy ±0.2% of full scale
or terminal server ▪ Configurable dead band per point
▪ 1 serial RS232 for diagnostic and configuration (protocol dependent)
▪ 1 serial RS485 for inter module LAN Digital Outputs (per SCOUT-S module)
▪ 3 Ethernet: 10/100BaseTX and 10/100/1000
▪ 256 Control Outputs
Base-T (Gigabit)
▪ Select — Check — Operate sequence
Environmental ▪ Momentary, pulsed or latched outputs supported
▪ 0°C to 60°C operating ▪ Interposing Relays (Single Form A or dual Form C)
▪ -40°C to 70°C operating (optional) ▪ Form A - Potter & Brumfield Series KUP or KUEP
▪ 0°C to 85°C storage ▪ Form C - Potter & Brumfield Series KUL
▪ Humidity 10-90% relative noncondensing Master Station Protocols
▪ Surge Protection per ANSI C37.90 on all I/Os
▪ DNP3.0
Time Synchronization ▪ DNP3.0 over TCP/IP
▪ Demodulated IRIG-B input ▪ IEC 60870-5-101
▪ Simple Network Time Protocol ▪ IEC 6870-5-104
▪ SCADA system ▪ Modbus

Input/Output Boards ▪ Modbus TCP

▪ Compact and rack mountable I/O boards are IED Protocols


available for Digital & Analog Inputs & Digital Outputs ▪ DNP

Digital Inputs (per SCOUT-S module) ▪ DNP over TCP/IP


▪ Modbus RTU
▪ 256 Alarm/Status/Accumulator Inputs via 16 I/O
▪ Modbus TCP
expansion boards
▪ SEL Protocol
▪ Optically Isolated Inputs
▪ Cooper 2179
▪ Scan Time 1ms for SOE, 10 ms for others
▪ IEC 60870-5-103
▪ Configurable for dry or wetted field contacts
▪ IEC 60870-5-101
▪ 24Vdc wetting voltage @ 5mA (12, 48, and 125Vdc)
SCOUT-S ™ Station Controller

Type Tests
Electromagnetic Compatibility Emissions
Conducted Emissions: ▪ IEC 61000-6-4 or EN 61000-6-4 ▪ CISPR 11, EN 55011 Class A, Group 1
Radiated Emissions: ▪ IEC 61000-6-4 or EN 61000-6-4 ▪ CISPR 11, EN 55011 Class A, Group 1
Electromagnetic Compatibility Immunity
Tested in accordance with IEC/EN 61000-6-5: 2015 - Electromagnetic Compatibility (EMC) -
Part 6-5: Generic standards immunity for equipment used in power station and substation environment.
Electrostatic Discharge:
▪ IEC 61000-4-2, EN 61000-4-2 ▪ +6 kV Contact Discharge, +8 kV Air Discharge
Radiated RF Immunity:
▪ IEC 61000-4-3, EN 61000-4-3, ENV 50204 ▪ 10 V/m, 0.8-1 GHz, 3 V/m, 1-6 GHz
Electrical Fast Transient:
▪ IEC 61000-4-4, EN 61000-4-4 ▪ +0.5 kV + 1 kV + 2 kV on AC lines, +0.5 kV + 1 kV + 2 kV on DC, I/O lines
Surge Withstand Immunity:
▪ IEC 61000-4-5, EN 61000-4-5 ▪ +0.5 kV + 1 kV Differential Mode, +0.5 kV + 1 kV + 2 kV Common Mode
Conducted Disturbances Immunity:
▪ IEC 61000-4-6, EN 61000-4-6 ▪ 10 V, 0.15-80 MHz, on AC, DC ▪ 3 V, 0.15-80 MHz, on I/O Lines
Magnetic Field Immunity:
▪ IEC 61000-4-8, EN 61000-4-8 ▪ 100A/m - Continuous, 1kA/m for 1 sec
AC Voltage Dips/Short Interruption:
▪ IEC 61000-4-11, EN 61000-4-11 ▪ 60% UT during 60 cycles, 30% UT during 1 cycle
Conducted RF Immunity, 15-150 KHz:
▪ IEC 61000-4-16, EN 61000-4-16 ▪ 30 Vrms Continuous Disturbance on DC, I/O, 300 Vrms 1 sec Disturbance DC, I/O
Damped Oscillatory Wave Immunity:
▪ IEC 61000-4-18, EN 61000-4-18 ▪ 2.5 kV Common Mode (1 MHz) on AC/DC/I/O line, 1 kV Differential Mode (1 MHz)
on AC/DC/I/O lines
Harmonic Current Emissions:
▪ IEC 61000-3-2, EN 61000-3-2 ▪ Class A (Other), Class B (Portable Equipment), Class C (Lighting Equipment)
Voltage Fluctuation and Flicker:
▪ IEC 61000-3-3, EN 61000-3-3
Environmental
Cold: IEC 61000-2-1, 18 hours at -40°C
Damp Heat, Cyclic: IEC 61000-2-30, 25°C to 55°C, 6 cycles, Relative Humidity: 95%
Dry Heat: IEC 61000-2-2, 18 hours at +70°C
Control your critical network “ We have had no failures to date on
any of these RTUs. The performance is
operations with confidence outstanding. Thank you for creating

With Survalent, you can control your critical network


operations with confidence. We’re the most trusted
such a reliable product.

- Sho-Me Power Electric Cooperative
provider of advanced distribution management systems
(ADMS) for electric, water/wastewater, gas, and transit
utilities across the globe.

Over 600 utilities in 30 countries rely on the SurvalentONE


platform to effectively operate, monitor, analyze, restore,
and optimize operations. By supporting critical utility
operations with a fully integrated solution, our customers
have significantly improved operational efficiencies,
customer satisfaction and network reliability.

Our unwavering commitment to excellence and to


our customers has been the key to our success for
over 50 years.

info@survalent.com ▪ survalent.com ▪ 905-826-5000

© 2018 Survalent Technology Corporation. All rights reserved. Product & company names mentioned herein may be trademarks
or registered trademarks of their respective owners. Errors & omissions excepted.

You might also like