Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Real-Time Monitoring For Peak Effi Ciency

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Real-Time Monitoring

For Peak Efficiency


Power Monitoring For more than 25 years, STARLINE® Track Busway has provided
mission critical facilities with the most flexible, reliable and

You Can Rely On. customizable power distribution systems on the market today.
Now, because of the market’s growing need for energy efficiency,
energy monitoring systems are more important than ever. The
STARLINE Critical Power Monitor (CPM) offers an enhanced
monitoring package that will allow you to monitor, integrate and
display more data center power information easily and reliably.

The STARLINE CPM offers:


• Revenue grade metering functionality
• Monitors multi-circuit configurations
• End feed and branch circuit models
• Display and non-display versions available
• Wired Ethernet and serial communications are standard,
optional 802.11n Wi-Fi connectivity
• Ability to use both Modbus and SNMP protocols simultaneously
• Telnet, BACnet IP and Modbus TCP/IP are also standard
protocols
• Now offering daisy-chain Ethernet
STARLINE’s CPM is part of the STARLINE Track Busway System,
and is uniquely designed to provide the functionality required for
busway applications.

The STARLINE CPM is calibrated to meet ANSI Revenue Grade


Standards for power usage, and a variety of communications
interfaces facilitate seamless integration with BMS and
DCIM packages.

Monitors are factory-built into STARLINE power feeds and


plug-ins, providing a clean and seamless integration of monitoring
with power distribution.

The STARLINE CPM creates value for data center power


distribution systems by providing the critical information
needed to optimize management and efficiency.
Universal Electric Corporation (UEC), the
Measured Parameters Accuracy
manufacturer of STARLINE, has been a
Voltage rms Line - Neutral 0.5 % of Reading leader in power distribution since 1924. The
company’s founders led the way for many
Voltage rms Line - Line 0.5 % of Reading
new technologies in the power distribution
Line Current rms 0.5 % of Reading equipment industry. Today, this family tradition
of innovation continues to pave the way for
Active Power, Watts ANSI 12.20 Class 0.5
safer, more innovative and more reliable
Energy, Watt-hours ANSI 12.20 Class 0.5 electrical power distribution systems.

+/- Reactive Power, VARs ANSI 12.20 Class 0.5


Other UEC products include STARLINE
Apparent Power, VA ANSI 12.20 Class 0.5 Plug-In Raceway, STARLINE DC
Solutions and U-S Safety Trolley.
+/- Power Factor 1.0 % of Reading
Visit www.uecorp.com for your Flexible
Frequency +/-0.1Hz Power Solutions.

Measured Values Real-Time /Phase Total Average Max Min For installation details, RS Means Electrical
Estimating cost comparisons, and actual
Feed Voltage L-N X X X case histories of projects where savings with
Feed Voltage L-L X X X X X STARLINE have been documented, contact
UEC’s Customer Service Department at
Feed Line Currents* X X X X X +1 724-597-7800.
Feed Line Current Demand X X X

Feed Watts X X X X

Feed Watts Demand X X

Feed +/- VAR X X X

Feed VAR Demand X X

Feed VA X X X

Feed VA Demand X X 168 Georgetown Road


Canonsburg, PA 15317
Feed Watt-hour X X X +1 724-597-7800
www.StarlinePower.com
Feed Power Factor X X X info@uecorp.com
Outlet Line Currents X X X X

Outlet Line Current Demand X X X

Outlet Watts X X X

Outlet VAR X X

Outlet VA X X

Outlet Watt-hour X X

Outlet +/- Power Factor X X

Frequency X