KYN28-12 Type Metal Armor Container Draw Out Type Switch Equipment

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Product manual of high & low voltage switch cabinet

KYN28-12 type metal armor container draw out type switch


equipment

1. Product overview
KYN28-12 metal armored draw out switch equipment (hereinafter referred to as the switch
cabinet) is a new product designed and developed by domestic and abroad advanced
manufacturing technology, suitable for 3.6 ~ 12 KV three-phase AC 50 Hz power grid, for
receiving and distribution of electrical energy, and for purposes of circuit controlling、monitoring
and protection. Can be used for single busbar, single section busbar system and double busbar
system, handcart type of the circuit breaker, easy maintenance. Mainly used in power plants,
industrial and mining enterprises distribution and hotel area, the urban construction and the
petrochemical sector, etc., for purpose of controlling protection, power distribution monitoring.

6
Product manual of high & low voltage switch cabinet

2. Model explanation:
K Y N 28 - 12 / □ □ □ - □
Rated short circuit breaking current(kA)
Rated short circuit breaking current(kA)
Operating mechanis characteristic
code, D:electromagnetism, T:spring
Primary scheme number
Rated voltage(kV)
Design serial number
Use conditions (indoors)
Shift type
Metal clad enclosed switchgear

3. Working conditions
Ambient temperature: -25℃~+40℃
Altitude: ≤2000m (If it is more than 2000m, please specify, when ordering.)
Relative humidity: ≤95%(25℃)
Earthquake intensity: ≤8 degrees
Installation environment: In the place of no fire, explosion hazards, serious pollution, chemical
corrosion and violent vibration.

4. Main features
 The structure of cabinet is made from several coated aluminum zinc plate which bolted after
multiple bending by CNC processing, complete unit is composed of two main components
which cabinet container and center pull out parts.
 All operations are conducted under state that the cupboard door closed.
 The cabinet sets into four separate compartments, shell protection grade is IP2X, high
protection grade, can prevent the clutter and pest invasion.
 Simply to replace the circuit breaker, handcart has good performance for exchange.

7
Product manual of high & low voltage switch cabinet

 Cabinet can be installed against the wall, maintenance from the front face, reduce the area.
 Cable room has enough space, abundant cable can be connected.
 Circuit breaker room and cable room can be equipped with heater separately to prevent
condensation and corrosion.
 Circuit breaker and cable chambers can respectively install lighting device according to user
requirements for convenience of maintenance and repair.
 With functions of wire lead-out, cable access and other scheme, it can be various forms of
electricity distribution equipment under permutations.

5. Technical parameters of switch equipment

Item Parameter Unit


Rated voltage 3.6, 7.2, 12 KV
Rated frequency 50 HZ
Rated current of breaker 630, 1250, 1600, 2000, 2500, 3150 A
Rated current of switch cabinet 630, 1250, 1600, 2000, 2500, 3150 A
Rated flexible and stable current(4s) 16, 20, 25, 31.5, 40, 50 KA
Rated flexible and stable current(peak) 40, 50, 63, 80, 100, 125 KA
Rated short and open circuit current 16, 20, 25, 31.5, 40, 50 KA
Rated short circuit open and close 40, 50, 63, 80, 100, 125 KA
current(peak)
Rated 1 min power frequency 24 32 42 KV
insulation withstand voltage
level Lightning impulse withstand 40 60 75 KV
voltage
Protection grade Shell IP4X, the compartment door and when the
circuit breaker door open IP2X