Puddle Flange Thickness Sheet-P2m-R0

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 1

Puddle Flange Thickness

Product GRP/GRV

DN PN Flange thk Layup thk Shear length Width 2 Flange OD Height above pipe
(mm) (Bars) tF(mm) t (mm) W(mm) W2(mm) (mm) H (mm)
300 15 34 7 75 100 411 51
350 15 36 8 88 100 462 51
400 15 39 9 100 100 513 51
450 15 42 10 113 100 564 51
500 15 45 11 125 100 615 50
600 15 55 13 150 100 717 50
700 15 58 15 175 100 869 74
800 15 64 18 200 100 971 74
900 15 74 20 225 100 1073 73
1000 15 79 22 250 100 1175 73
1100 15 83 24 275 100 1277 72
1200 15 89 26 300 106 1379 72
1300 15 95 28 325 115 1531 96
1400 15 100 30 350 125 1633 96
1500 15 106 33 375 135 1735 95
1600 15 111 35 400 145 1837 95
1800 15 125 39 450 163 2041 94
2000 15 136 43 500 182 2245 93
2200 15 148 48 550 201 2449 92
2400 15 159 52 600 221 2653 91
2600 15 176 56 650 237 2857 90
2800 15 186 60 700 257 3061 89
3000 15 197 65 750 277 3265 88
3200 15 207 69 800 297 3469 87
3400 15 218 73 850 317 3673 86
3600 15 228 78 900 336 3877 85
3800 15 239 82 950 356 4081 84
4000 15 249 86 1000 376 4285 83

80 15 30 2 20 100 175 47
100 15 30 3 25 100 195 46
150 15 30 4 38 100 247 47
200 15 30 5 50 100 298 46
250 15 30 6 63 100 350 47
300 15 30 7 75 100 403 47

Notes:
1) Shear stress is assumed 15 N/mm2 and with a factor of safety of 6 the value taken is 2.5 N/mm2
2) OD of puddle flange is assumed to be the same as the flange itself
3) Thickness of the puddle flange is assumed to be the same as the flange thickness
4) The pipe is extended to the flange hub in order to make the pipe biaxial.
In case the pipe used is biaxial then you should have a W2 on the other side of the puddle flange

To be extended to
the flange hub

1 tF
4

H t

Pipe wall

W2
THRUST RESTRAINT PUDDLE FLANGE