Analysis of Integral Snubber Circuit Design For Transformers in Urban High Rise Office Building
Analysis of Integral Snubber Circuit Design For Transformers in Urban High Rise Office Building
Analysis of Integral Snubber Circuit Design For Transformers in Urban High Rise Office Building
Abstract- Transformer failures have in recent years transient or the transient recovery voltage (TRV) of
led to the development of Resistor-Capacitor snubber a switching device, is within the capabilities of the
circuits for the protection of the transformer and transformer insulation system to withstand. This
winding insulation from the damaging effects of high insulation capability is defined as the Basic
voltage high-frequency transients. Transformer Insulating Level, ElL, and is part of the
insulation may be damaged if the Basic Insulation manufacturer's specifications for the transformer,
Level (BIL) is exceeded, turn-to-turn insulation when
and the subject of factory tests. For these
there is excessive rate of change of voltage with time
transformers, typical transient voltages may be 1 0
(dv/dt), and to switching devices by restrikes when
kV higher than the system voltage peak, thus, with
the Transient Recovery Voltage (TRV) is exceeded.
a 1 3 . 8 kV system, at a possible 5 % overvoltage, the
These transients are most often observed when dry
peak line-ground transient voltage would be
type transformers are close coupled to vacuum
switching devices. Some manufacturers are now
approximately 1 3 . 8 x 1 .05 x + 1 0 = 2 1 . 8 kV. This
including snubbers in their transformer designs.
is well below the 95 kV ElL. The transient
This paper provides a thorough review of the causes overvoltages caused by switching events may,
of the transients, methods of analysis, and mitigation however, be much higher, and may damage the
of the effects of these transients. An example is transformer insulation.
provided of transformers to be installed in the
The problem of switching transients, primarily from
basement of an urban high rise office building, where
vacuum interrupters, damaging dry-type (and other)
the space is limited and the available fault current is
high, where the transformer enclosure includes built
transformers with low insulation strength has been
in snubber circuits. The strengths and weaknesses of
known since the invention of vacuum interrupters,
current methods are examined. Recommendations as described in the late Professor Greenwood's
are made for improvements in snubber circuit design book Vacuum Switchgear [3] . The analysis of the
and analysis. transient overvoltages which have resulted in the
application of snubber circuits has been given in
Index Terms-Snubbers, Transformer snubber detail in Greenwood's classical textbook Electrical
circuits, Transformer protection, Transient analysis, Transients in Power Systems [4] . The ailed analysis
Transient overvoltages, Transient rate of rise of of the internal windings and insulation systems of
voltage, Transformer failure. transformers is generally only possible with
information on the construction of the transformer
I. INTRODUCTION
which is usually manufacturer's proprietary
The purpose of a snubber study is to determine information. This makes some of the techniques
the need for and ratings of snubbers necessary to discussed in the draft IEEE standard and in
protect the subject transformers from over-voltages Greenwood's Transients book difficult to apply.
due to switching transients. [ 1 ] Snubber studies are
One technique which has been successfully applied
often conducted in accordance with the
is to perform "black-box" sweep frequency
recommendations of the draft standard IEEE
impedance measurements of transformers and
PC57. 142 [2]
cables [5] [6] . Measurements over a range of 50 Hz
When a transformer is subjected to high-frequency to 2 MHz were performed on a de-energized
voltages from switching transients, there is a transformer using a network analyzer, which
possibility that these frequencies may excite a provided a frequency sweep and .
resonance in the transformer windings. This
A snubber study was performed for four 2500/3333
resonance may cause a high turn-turn voltage to be
kVA 1 3 . 8 kV - 0.48 kV transformers at a
developed internally to the transformer. This may
Manhattan office tower. The purpose of the
be true even in the situation where the transient
Snubber Study was to evaluate the design of the
voltage itself, whether from a cable energization
integral snubber circuit as shown in the drawings
$
978-1-4673-0651-5/12/ 31.00 © 2012 IEEE
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 2 of 17
[--��L���-�:�M���---'
II. SYSTEM DATA
A. System Configuration
CABLEC2
A simplified one-line diagram is shown in
Figure 1 . Four three-phase 750 kcmil utility
service cables (Cable Cl), of which one is shown,
enter the first basement (B 1) of the building
through a set of steel conduits . Out of the four
cables, Cl, two each enter one of two Splice
Chambers, of which one is shown. In the Splice
Chambers, each single 750 kcmil conductor is
spliced to a pair of 750 kcmil conductors (Cable
C2), so that four (4) cables leave each Splice
Chamber. These leave the Splice Chambers in
paired steel conduits which pass down to the third
basement (B3) level. The Cables C2 enter the
service equipment vault, where there is a bank of
vacuum switchgear units called primary
CABLEC3
TRANSI
BOXTION
distribution centers (PDCs).
The 1 3 . 8 kV, 1 200 A PDCs have a main service
breaker (52-S) and four feeder breakers (52-Fl
through 52-F4). Electrical power from the PDCs is
CABLEC4
SPOT:RK n
then fed (Cable C3) from the four feeder breakers
NETW
to Transition Boxes. From here cables (Cable C4)
go to an array of Spot Networks in basement level
2 (B2) and electrical rooms in upper floors . Each
Spot Network contains four (4) 2500/3325 kVA
LL 2500KVA
transformers. The Cables C4 are connected to the
2500/3325 kVA 1 3 . 8-277Y1480V spot network
transformer primary windings through fused
grounding switches. The spot network transformer
u
-i 'r 13.8KV-480V
secondary windings are connected together through
�
4000 A Network Protectors and Network Fuses at
an 8000 A Spot Network Bus. However, this paper
is only concerned with the system up to the
8000A BUS
primary windings of the Spot Network
transformers. ------------- ---------------------
B. Utility Data
I
The Utility contribution for three-phase, first Figure 1 Simplified one line diagram.
cycle symmetrical short-circuits is used in this
study, shown in Table 1 . There are eight 1 3 . 8 kV
services, divided up between the two Splice
Chambers, any one of which could be used to Table 113.8 kV Utility Short Circuit Data
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 3 of 17
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 4 of 17
oCt) = J �
1tf OIT m (1)
For the second case, where the skin effect is
Where: operative, the ac resistance is a function of the
Ii(f) is the skin depth, in m square root of the frequency. The factor ran can ;>!
f = frequency, in Hz, be used to calculate the ac resistance:
7
flo = 41t X 1 0- HIm i s the permeability o f free space.
racw _ rw.jff/lOIT
The skin depth of a conductor is inversely - rdc
w 2 �or r
w
> 20 (5)
11
proportional to the square root of frequency. For a
copper conductor: The breakpoint in equation (5) occurs when the
radius of the conductor equals twice the skin depth:
oct) = 0.0655
m (2)
11 rw = USC!) m, (7)
as shown in Figure 3 and Table 4 . Combining (2) and (7), the conductor may be said
to be at the skin depth transition frequency:
1.E-Ol
4
F = -- Hz •
Jtw 1',21[1l (j (8)
1.£-02 ....... .......
W ,.. 0
E
:;;
"
�I'-.. The skin depth transition frequency for copper
! 1.£-03 conductors with a circular cross-section is:
�
1.£-04
�....... F
Jtw
- 0.01695 HZ
- 2 (9)
rw
'� Skin depth transition frequencies, dc resistance and
1.£-05
lEtOI lEt02 tE+03 lEt04 tEfOS lEt06 lEt07 >!
the factor rae,; are shown in Table 5 for some
Frequency (HI)
common sizes of copper conductors.
Figure 3 Skin depth, B, of a copper conductor This approximation is not used in calculating
Table 4 Skin depth, B, of a copper conductor the power frequency resistance of conductors for
power system studies such as short circuit and load
Frequency.! Skin Depth, B Frequency, f Skin Depth, B
flow analysis. However, it can be used for transient
(Hz) (m) (Hz) ( m)
1E+01 2.06E-02 1E+04 6.S1E-04
studies above the transition frequency.
2E+01 1.46E-02 2E+04 4.60E-04 For snubber studies, the frequency of interest
SE+01 9.21E-03 SE+04 2.91E-04 may vary between 10 kHz and several MHz,
1E+02 6.S1E-03 1E+OS 2.06E-04 depending upon the mode of the oscillation. Once
2E+02 4.60E-03 2E+OS 1.46E-04 the frequency of oscillation is determined, then the
SE+02 2.91E-03 SE+OS 9.21E-OS resistance for the simulation may be calculated
1E+03 2.06E-03 1E+06 6.S1E-OS
using (5). This is plotted in Figure 4 (a) .
2E+03 1.46E-03 2E+06 4.60E-OS
SE+03 9.21E-04 SE+06 2.91E-OS
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 5 of 17
0.004238
F = HZ
E >Of . Jts t2
.
' ( 1 3)
1.E.Q2
s
£
�
e
For a typical copper shield of 5 mils thickness or
1;;
� 1.E.Q3
Frequency (Hz)
1E+05 1E+06 1E+07
with the skin depth by /1:
- . -750
{
······· 250 ----350 - - 500
rdes if ts < 0 n
raes=
rdes ts y�
( 14)
m
fJrJioa if ts >
-Shield 250 -Shield 350-Shield SOO_Shield 750
0
(a) Resistance of conductors and shields
1.E+OO
Then:
l.E.Ql racs
11 = rdestsyJr JioaI;-::; . f ts >
r;;:-; J:
u (15)
....""'101
�
�
1.E.Q2
1l
1.E-03
.�
the ac resistance is shown in Table 6 for the shields
'"
1.E-04
of some common sizes of copper conductors.
1.E-05 Table 6 Resistance o f 5 mil (0.127 mm) copper shield.
lE+Ol lE+02 1E+03 lE+04 lE+05 lE+06 1E+07
Frequency (Hz)
- - -
Size
······· • rs fls rdcs Tacs/fl
(AWGI
250 ----350 500 -750
At high frequencies, the cable acts as a coaxial 2/0 0.01204 2.63E+05 1.73E-03 3.38E-06
cable and the return current flows through the 3/0 0.01267 2.63E+05 1.65E-03 3.21E-06
shield. The currents being considered are 4/0 0.01337 2.63E+05 1.56E-03 3.05E-06
capacitive ground currents through the cable and 250 0.01407 2.63E+05 1.48E-03 2.90E-06
transformer capacitances, and not the load currents, 350 0.01540 2.63E+05 1.36E-03 2.65E-06
which are phase to phase and do not involve 500 0.01699 2.63E+05 1.23E-03 2.40E-06
ground. If the shield consists of a conducting tape 750 0.01937 2.63E+05 1.08E-03 2.10E-06
of fixed thickness, its dc resistance may be 1000 0.02121 2.63E+05 9.86E-04 1.92E-06
calculated:
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 6 of 17
I.E-05
The shield resistances are plotted in Figure 4(a),
and are seen to be constant up to the shield skin l.E-06 .p._-I__"__"_�__"_...-j
depth transitIOn frequency. The conductor
resistance goes to the load, and the shield resistance
is the ground return, so that the total resistance is
the sum of the two. The total resistance is plotted in
Figure 4(b), and is dominated by the shield
resistance.
1.E·ll +-����--I-��4---�....-j����..j
Frequencv(Hz)
b) Cable Inductance lE+Ol lE+02 lE+03 lE+04 lE+05 lE+06 lE+07
- - 500lnl - -7501nl
-500E)(1 _7SOExt
Inductance is the sum of the internal inductance ·•·· .. ·2SOlnt ----350lnl
.. ---- 350Shld
- - 500Shld - -7SOshld
-250E)(1 -350Et K
·•·
of the wire, the external inductance between the ··2SOShld
- ---- -------
.
f --------
-
-- -
-
--------
--- --
e 2n: rw m
( 1 6) ��� � - -- -- f------
For normal phase currents, the distance between
I 5.0E-07 +-----+--+-----1
conductors would be substituted for the radius of
the shield. The dc internal inductance of the wire O.DE+DO +-����--I-��+-����....j
Frequency (HZ)
1.0E+01 1.0E+02 1.0E+03 1.0E+04 1.0E+OS 1.0E+06 1.0E+07
for low frequencies is constant:
_
[dew - J.lo � ·······250 ----350 - - 500 - -750
( 1 7)
Sn: m (b) Total internal and external inductance of wire and
shield.
At higher frequencies, the internal inductance liw
has characteristics similar to resistance, as shown in Figure 5 Internal and external inductance vs frequency for
several common cable sizes (in kcmil)
Figure 5 (a), exhibiting a skin effect also. [3]
[dew if rw < 28 The third inductance in the cable is that of the
I
H
[.tw "'" [ 1 1 - internal inductance of the shield. Paul [9] has
- dew � ( 1 8)
2rw n:J.lo(J v17t if rw > 28 m
given the calculation of this inductance by both the
energy method and the method of flux linkages.
The internal inductance is generally a small The shield transitIOn frequency, its, was
percentage of the external inductance, and is often calculated using ( 1 2) to be 263 kHz. For
ignored. frequencies above it" the effective thickness of the
shield goes from ts to is.
The internal dc inductance and the internal ac
inductance of the shield above it" are approximated
as :
( 1 9)
(20)
Below the transition frequency, where the skin inductance is plotted in Figure 5, and some of the
depth is greater than the thickness of the shield, factors used in the calculations are listed in Error!
current distribution in the shield is uniform, and the Not a valid bookmark self-reference.. Because
dc shield inductance may be used. The shield the internal inductances of the wire and shield are
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 7 of 17
100
over an order of magnitude smaller than the
90 t----+--�--_+--+_--�
external inductance of the wire, le in equation ( 1 6), 80 ............ ............ ............ ............ ............ ............
-----
that can be used as a good approximation for the £ 70
-----
- ----- ------ ----- ------
� ------ ---1-------
cable inductance. -ll ...... ---- r- ------
60
x.
-
50
� 40 t----+--�--_+--+_--�
l t == l e = 110 In 2i.:!. r T----+----�--r_--_+--+_--�
30
(2 1 )
2rr Tw m 20 T----+----�--r_--_+--+_--�
10 t----+----�--_+--+_--�
Frequency (Hz)
Table 7 Inductance of 5 mil (0.127 mm) copper shield.
...... ·250 ---·350 - - 500 - -750
Size
rs rs+ts fts Ides
(AWGI 6
(m) (m) (Hz) Him
Figure Surge impedance vs frequency of for several
kcmil) common cable sizes (in kcmil).
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 8 of 17
--r.---C'-- 2 � •
•
CHL: The high side to low side capacitance:
CHL = CLH = 2060 pF
I
The high side input capacitance:
(. + CHLXCLG
ID
= C HG = 2448 F
CHL +CLG P
Table 13 Manufacturer's No Load Loss
Measurements Converted to Primary Side.
These measurements are made on the low side, with
the high side open circuited. The three-phase
Figure 7 Equivalent Circuit of a Single Phase of Cable.
voltages shown are applied in turn from X" X2 and
D. Transformer Data X3 to Xo and the three-phase power measured. The
The four delta-wye grounded 2500/3333 kVA measured no-load losses on the low side are
AAfFA 1 3 . 8kV-480YJ277V, 7 . 1 5 % IZ cast coil converted to three equal phase currents on the high
transformers are all of the same manufacturer and side.
construction, so that only one transformer model is PL-3</>measured
IL-NLL-line -
- (20)
required. These transformers have integral surge 3VL-line-line
arresters and snubber circuits mounted within the
Because the high side is connected in delta, line
transformer enclosure. The winding configuration
current values must be converted to winding
is shown in Figure 9. Transformer data is listed in
currents :
the following tables:
lL-NLL-line VL
IH-NLL-winding =
VH
(2 1 )
Table 11 Transformer Data. This Table lists the .,f3
transformer data as obtained from the nameplate This high side winding current i s modeled a s a
and the manufacturer's drawings. nonlinear resistive branch Re, which accounts for
Table 12 Manufacturer's Capacitance the fR, hysteresis and eddy current losses. The
Measurements and Calculated Capacitances. current through the resistor Re is modeled as a
The table lists the results of the manufacturer's piecewise linear approximation, shown in Figure
capacitance measurements. These are as follows : 11.
CHL+CHG: The capacitance from the high side to the
low side in parallel with the capacitance from the
high side to ground is obtained by shorting and Table 14 Transformer Saturation Current
grounding the low side windings and injecting a test Measurements Converted to Primary Side.
signal from the high side to ground. These measurements are made on the low side, with
CHG: The capacitance from the high side to ground the high side open circuited. The single phase
is obtained by open circuiting the low side windings voltages shown are applied in turn from Xl to Xo,
and injecting a test signal from the high side to X2 to Xo and X3 to Xo and the currents are measured
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 9 of 17
vlz s
il(t) = - Vrm cos(wt)
--
w
x
(31)
Figure 8 Magnetic Flux Density Across a Surface.
The vertical axis quantities can be easily calculated
for plotting saturation according to peak voltage or
Consider the area A, which is the cross-section flux. However, the horizontal axis quantities must
of the magnetic core of a transformer winding: be determined for peak current considering the rms
Is Ioa I: dx . dy
and peak values of the distorted wave shape of
A = dS = m2 (25) saturation current. This may be done by a support
If the flux is perpendicular to a flat surface S routine within EMTP [12], or by other means of
with area A, and the flux density is uniform calculation.
throughout the area, then the magnitudes relate as : The current through the saturable inductor Le,
et> = BA Wb Figure 10, is modeled as a piecewise linear
(26)
approximation, shown in Figure 12.
This is the situation which occurs in a magnetic Table 15 Transformer Series Impedance The
core to which flux is confined, as in a transformer, resistance RT and inductance 4 of the series
where A is the cross-sectional area of the core. The branch, Figure 10, are calculated for the high side
magnetic flux is produced by the current flowing in from the percent impedance, kVA rating and XIR.
the windings wrapped around the transformer core. X2
---\
The magnetic field H,
is a vector in the same H2
B,
B
direction as but with a magnitude which
depends upon the medium through which the flux X1 -XO
is flowing. Here enters the familiar relation:
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 10 of 17
CHL-A
10 71 0.493 0.017 0.010
CHL-B 20 225 0.781 0.027 0.016
CHL-C
30 430 0.995 0.035 0.020
40 722 1.253 0.044 0.025
SO
RT-ALT-A
90
2575
3398
2.235
2.622
0.078
0.091
0.045
0.053
100
�Le-cA ."'
4245 2.948 0.103 0.059
� Re-CA 110 5722 3.612 0.126 0.073
120
'T....f-J CLG-C
CHG-A
CHG-C 15048 8.708 0.303 0.175
CLG-A
CHG-B
CLG-8
20.0
Figure 10 Transformer Equivalent Circuit.
0.0
BIL 95HV/lOLV kV
LV Amp 3007/4009 A
-5.0
HV Amp 104.6/139.4 A
HV Taps 0, ±2.5%,±5.0%
-10.0
Avg'/Max. Amb. 30/40 C
Class AA/FA
Type CAST COIL
-15.0
Windings Copper
Phase 3
Impedance 7.15%
-20.'4--'---'--'----''--
X/R Ratio 9.96 -2 .0-150.0-100.0 -50.0 0.0 50.0 100.0 150.0 200.0
Frequency 60 Hz
Temp. Rise 80/80 C Figure 11 No Load Losses Modeled as a Nonlinear
Resistance Converted to Primary Side.
Table 12 Manufacturer's Capacitance Measurements and
Calculated Capacitances
80.0
Power
Test Current Power Capacitance
ID (rnA) (W)
Factor
(pF) 60.0
(%)
CHL+ CHG 11.808 0.83 0.703 3132 40.0
10
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 11 of 17
Rr Lr
(n) (mH)
(a) overview
0.54 14.38
150
100
I 50
SNUBBER
Simulation results show the energization transient horizontal frequency axis is in values of x, where f = 10'.
11
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 12 of 17
Ie = -INL
VL
= --
480V
- X 5.11A = 0.178A
(a) overview VH 13.8kV
.' Then calculate the resistance:
VLN 13.8kV
Re = -=
Ie ..J3 X 0.178A
= 44.8 kf!
The magnitude of the current chopped is
dependent upon the properties of the cathode
(negative contact) material. Materials with a high
vapor pressure and low thermal conductivity tend
to produce lower chopping currents [3] . The
9.9 10,0
1�1o IIrlJbbor_pIoI; ,.\Of � VS� �SfUlB
10.1
�S�
10.5 [mol 10.6
duration of the arc instability which may result in a
current chop is a statistical phenomenon, with a
(b) detail
consistent average value.
Figure 16 Energization Transient with snubber.
Suppose, for example, that the magnitude of a
70
[kVI current chop is 2.0A. The energy in the inductance
60 from the chopped current is:
-
2
"2 eIo "2Cop Vc
� =IoZo
20
�
Then:
10
0
2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 [sl 6.0
Vc = 10 C
e
(file snubbeLpl4; x-var I) v :SNUBA
op
The surge impedance of the transformer input is
Figure 17 Plot of voltage at Transformer primary with
5.4 kHz. 28H
Zo= � = 5648pF = 70 kf!
snubber showing resonance peak at The horizontal
fre quency axis is in values of x, where f = lOx.
B.
Current Chopping �c;
The voltage produced is:
Vc = IeZo= 2.0A x 70 kf! = 140 kV
Current chopping occurs when the interrupter
breaks the current flow in an inductive circuit
If the transformer series inductance is
before a current zero . In certain types of vacuum
considered instead :
and SF6 circuit breakers, the current can be
14mH
Zo= � = 3200pF = 1.57 f!
interrupted before the current zero. The magnitude
of the current chopping transient may be estimated
in a number of ways. [4] First, a few constants �c;
The voltage produced is:
Vc = IeZo= 2.0A x 1.57 = 140 kV
need to be calculated:
The transformer excitation current was
approximately 22A at 480V. On the primary side, This is an excessive theoretical value which
the equivalent current is Ie = 0.765A. The does not correspond to observed voltages. In
inductance is: actuality, the voltage is limited by two factors [4] :
=--=
VLN 13.8kV
= 28 H
1 . Due to hysteresis, only a fraction of the energy
Le in the magnetic core is transferred to the
2rr e fI ..J3 x 2rr x 60 x 0.765A
12
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 13 of 17
capacitance. The remainder is trapped within from a value o f 5 .923 kV at t = 14.038 ms, for a
the core as residual magnetism. For grain f't.Vof 5 .753 kV and a rise time of 1 9 /lS. The
oriented steel: overvoltages shown in the simulation are less than
Vc = 0.551eZo = 0.55 x 140 kV = 39 kV the peak voltage of the sinusoidal wave, much less
2. Due to resistances in the circuit damping the BIL.
reduces the magnitude of the voltage peak.
35,------,
The damping constant is: [A[
R e 44.8 kD.
= = = 0.64
25
TJ Zo 70 kD.
As is well known, the circuit response varies with 15
oscillatory decay.
14.3 [ms] 14.4
·25+--�-�--�-�-�-��-�-_J
The time constants of the circuit must be
calculated. The parallel time constant is:
13.6 13.7 13.8 13.9 14.0
(file snubber.pI4; x-val II c:PDCBA S A c:PDCBB S B c:PDCBC S C
14.1 14.2
- W - W - W
Tp = R eCap = 44.8 kD. x 5670 pF = 254 [1.S Figure 19 Chopping of Current at 5 Amperes
Le 28H
Ts = R =
44.8 kD.
= 625 [1.S
e
The period of the undamped circuit is:
T = .jTpTs = .j254[1.s x 625[1.s = 398 [1.S
Using the solutions curves of the second order
differential equations in [4] , the peak voltage is 0.4
per unit or 15.6 kV. ·4
nominal resistor ( 1 000 Q L-N @ 1 3 . 8 kV) was Figure 20 Transformer voltage with current chopping.
placed on the source to prevent the voltage value
from floating by providing a complete circuit for A. Transient Recovery Voltage (TRV)
the source after breaker opening. This is shown in Transient Recovery Voltage (TRV) occurs when
Figure 1 8 . the transformer is being de-energized, and the
CHL
voltage across the just-opening contacts of the
breaker exceeds the breakdown voltage of the
interrupting medium, resulting in a high current
transient.
13
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 14 of 17
o
·12 +--.....--.----1
12 16 [ms[ 20
B.
(file snubber.pI4; x-vart) v:SNUBA v:SNUBB v:SNUBC
Summary of Simulation Results
Figure 22 Reduction of current chopping transients with The withstand capabilities of the transformer
snubber. under investigation consist of:
1. Basic Lightning Impulse Level (BIL) for the
HV winding from transformer nameplate.
This is determined from the 1.2 x 50 f!S Full
Wave Test Value in kV performed by the
manufacturer.
2. dv/dt or rate of rise of the voltage at the
transformer terminal.
14
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 15 of 17
15
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 16 of 17
B. Damping resistor. Should the fuses blow for an arcing fault where the
The resistor should be non-inductive. Typical snubber circuit is not destroyed, then the protection
high power, high voltage non-inductive resistors provided by the snubber circuit will be lost.
(Figure 26) are constructed of a thick film of
resistive material coated on a ceramic tube,
typically 0.3 - 0.6 m in length and 0.025-0.05 m in
diameter, with a conductive band at each end to
make connection with. The desired RC time
constant is 1 - 1 0 f!s. Thus with a 0.25 capacitor, the
resistance should be between 4 and 400. The
resistance should also attempt to match the surge
impedance of the cable. The surge impedance was
Figure 27 Typical fuse for snubber circuit.
calculated to be approximately 240 at 60 Hz, but
140 at 25 kHz. The existing 20 0 resistor is an D. Arrester.
acceptable value. This resistor has a time constant The characteristics of the existing arresters are
with the 0.25 f!F capacitor of listed in Table 19. The maximum available fault
current is 32.9 kA. The available fault current
T = RC = 20x 0.25 X 1 0- = 5.0 J1S .
6
should be no more than approximately SO% of the
The resistor should have a continuous power
pressure relief rating of the arrester to allow for
rating sufficient for twice the capacitive current (in
inaccuracies in calculating fault currents and for
case of harmonics and overvoltages) . With the
future system expansion. Using the 80% criterion,
capacitive current of 0.75 A, the resistor should be
the pressure relief rating should be 4 1 kA. The
able to dissipate:
existing Distribution Class arresters, having a
P= / 2 R = (0.75AY 200 = 11.25W pressure relief rating 20 kA, should be replaced
If higher current is present due to harmonics and/or with Station Class Arresters, Figure 28, having a
overvoltages, the resistor may dissipate up to : pressure relief rating of at least 40 kA.
Property Value
Rated Voltage 18 kV rms
MCOV 15.3 kV rms
Class Distribution,
heavy-duty
Material Polymer
Pressure relief 20 kA, rms for 12
rating cycles.
Figure 26 Non inductive power resistor.
16
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.
Page 17 of 17
V. CONCLUSIONS [ 15] IEEE Std. C57 .98-1993, IEEE Guide for Transformer
Impulse Tests
A snubber study was performed for the four (4) [ 16] IEEE Std. C62. 11-2005, IEEE Standard for Metal-Oxide
2500/3333 kVA 1 3 . 8 kV - 0.48 kV transformers. Surge Arrestersfor AC Power Circuits (> 1 kV)
The purpose of the Snubber Study was to evaluate
the snubber design as shown in the drawings for
VII. B IOGRAPHY
the transformers. Only one transformer was
analyzed because the all data, including the cable
Peter E. Sutherland (Fellow, IEEE) received the B . S .
lengths are the same for all transformers.
degree in Electrical Engineering from the University o f Maine,
The snubber substantially reduces both peak Orono, and the Ph.D. degree in Electric Power Engineering at
voltage and dVIdt for all cases. The calculated Rensselaer Polytechnic Institute, Troy, NY.
values both with and without the snubber are all In 1987, he joined General Electric Company, Schenectady,
NY, and held a variety of positions, becoming a Senior
well below the limits shown in the applicable Engineer in the GE Power Systems Energy Consulting
standards. Department. In 200 1, he joined SuperPower, Inc., Schenectady,
One change was recommended in the snubber N.Y., where he worked on applications of superconductivity to
electric power systems. Dr. Sutherland then joined EPRI PEAC
design, to replace the distribution class surge Corporation' s (now EPRI Solutions, Inc.), Schenectady, NY
arresters with station class. office as a Consulting Engineer. He is currently a Lead
Consultant with GE Energy Services in Schenectady NY.
VI. REFERENCES Author of numerous technical papers, he is active in the IEEE
Industry Applications Society, and in the IEEE Schenectady
[ 1] Young, B .W., " Snubbers: Protecting medium-voltage Section. Dr. Sutherland is a member of CIGRE and the lET
transformers from electrical transients," Consulting (formerly lEE). He is a Registered Professional Engineer in
Specifying Engineer, March, 2009, pp.4 1-44. Pennsylvania, Maine, New Jersey and New York and is a
[2] IEEE Draft Standard PC57. 142/D8 .2, May 2, 2010. Guide Chartered Engineer in the UK.
to Describe the Occurrence and Mitigation of Switching
Transients Induced by Transformer, Switching Device and
System Interaction.
17
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE ENGENHARIA DE ITAJUBA. Downloaded on April 29,2021 at 21:41:35 UTC from IEEE Xplore. Restrictions apply.