PP-A1 - WACU - 1 Phase

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 21

LOAD SCHEDULE / CABLE SIZING / VOLTAGE DR

PROJECT: DAVAO CITY BY PASS CONSTRUCTION PROJECT/ PA


PANEL NAME: PP-A1 (GROUND FLOOR)-WACU PANEL
LOCATI0N: ENGINEER'S OFFICE AND LIVING QUARTERS (GROU
MEETING ROOM

CKT. NO. LOAD DESCRIPTION

1 1.5 HP, 230V, WACU


2 1.5 HP, 230V, WACU
3 1.5 HP, 230V, WACU
4 1.5 HP, 230V, WACU
5 SPARE
6 SPARE
7 SPARE
8 SPARE

TOTAL
TOTAL PANEL LOAD
DEMAND FACTOR
TOTAL DEMAND LOAD
TOTAL CURRENT LOAD

COMPUTATION:

FULL LOAD CURRENT:


= 5.52 kVA
1.000 X 230 V
FLC = 24 A

Page 1 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
CB RATING: = 20 +6+6+6 = 38 A

USE: 40 AT
50 AF
CABLE SIZE AMPACITY:
(1.25)6 +6+6 +6 = 25.5 A
SEE ARTICLE 3.10 . CONDUCTORS FOR GENERAL WIRING TA
45.10 ≤ 38.0 WITH CORRE
USE: 1 SET/S -2

VOLTAGE DROP CALCULATION:


VD = 35.6 X 24.00 X
1000 X 14.0 X
VD = 4.27 Volts

%V = 4.27
230
%V = 1.86 IF ≤ = 2 %
USE: 12 SET/S
FOR SERVICE WIRE:
USE: 1 SET/S 2
FOR GROUND WIRE:
SEE ARTICLE 2.50 . MINIMUM SIZE OF EQUIPMENT GROUND
USE: 1- 5.5 mm²
FOR CONDUIT SIZING:
SEE APPENDIX C, TABLE C.4 PEC 1, 2017 PAGE 985
USE: 40 mmø IMC

For Reference:

VOLTAGE DROP CALCULATION


1Ø, VD CALCULATION: 3Ø, 3W VD CALCULATION
35.6 x L x I 30.8 x L x I
eV = eV =
1000 x S 1000 x S

% VD =
Page 2 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
e (V) = Voltage Drop, (volts)
% VD = Voltage Drop, (%)
L = Single Length of Conductor, (meters)
I = Current, (amperes)
S = Single Conductor Cross Section multipl
V = System Voltage, (volts)

Page 3 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
OLTAGE DROP

PROJECT/ PACKAGE I-2


VOLTAGE SYSTEM :
RTERS (GROUND FLOOR) WIRE :
ENCLOSURE :

RATING
k
VA QTY Ø System Voltage
W kVA
kW
1380 1 1 230 1.38
1380 1 1 230 1.38
1380 1 1 230 1.38
1380 1 1 230 1.38
230 ### 0.00
230 ### 0.00
230 ### 0.00
230 ###
0.00
0.00
0.00
0.00
0.00
5.52
EL LOAD 5.52
ACTOR 100
MAND LOAD 5.52
RENT LOAD 24

Page 4 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
PHASE: 1 WIRE: 2
MCB

L WIRING TABLE 3.10.2.6 PEC 1, 2017 PAGE 174


WITH CORRECTION FACTOR (0.82) @ 40°C
14 mm² TW (FIRE PROOF)

70 LM
1 SET/S

14.0 mm² TW

14.0 mm² TW

NT GROUND TABLE 2.50.6.13, PEC 1, 2017 PAGE 124


TW

PAGE 985

ALCULATION:
ALCULATION: 3Ø, 4W VD CALCULATION:
30.8 x L x I 17.8 x L x I
eV =
1000 x S 1000 x S

eV / V x 1000
Page 5 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
ctor, (meters)

Section multiplied by the number of sets, (mm²)

Page 6 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
230 V, 1-Phase
2W + G
NEMA 1 with Ground Terminal

LOAD DISTRIBUTION, KVA CIRC


% Full Loa
AB BC CA AN
CN 1ø Pole
Multiplier Current
1.38 1.38 1.75 2 6.00
1.38 1.38 1.75 2 6.00
1.38 1.38 1.75 2 6.00
1.38 1.38 1.75 2 6.00
0.00 0.00
0.00 0.00
0.00 0.00

0.00 0.00 5.52 ### 5.52


kVA Phase 1
% System Voltage (V) 230
kVA Transformer (kVA)
A

Page 7 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
Page 8 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
Page 9 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
CIRCUIT BREAKER SIZE GROUND WIRE
Full Load
MCB Rating AT AF mm² Type
Current
6.00 10.50 20 50 3.5 TW
6.00 10.50 20 50 3.5 TW
6.00 10.50 20 50 3.5 TW
6.00 10.50 20 50 3.5 TW
20 50
20 50
20 50
20 50

MAIN P
MAIN

Page 10 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
Page 11 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
Page 12 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
D WIRE CONDUIT
Full Load
PF DF K L
Type mmØ Type Current
TW 20 IMC 1 1 35.6 60 6.00
TW 20 IMC 1 1 35.6 60 6.00
TW 20 IMC 1 1 35.6 60 6.00
TW 20 IMC 1 1 35.6 60 6.00

MAIN PROTECTION: 40 AT 50
MAIN FEEDER SIZE: 1 sets - 2 x 14.0 mm²
5.5 mm²

Page 13 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
Page 14 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
Page 15 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
CABLE AMPACITY
System
SERVICE WIRE
Full Load Voltage
CV %
Current Rating Number mm² Type
Multiplier
6.00 1000 1.25 7.5 3.5 TW 230
6.00 1000 1.25 7.5 3.5 TW 230
6.00 1000 1.25 7.5 3.5 TW 230
6.00 1000 1.25 7.5 3.5 TW 230

AF MCB NOTE:
THHN VOLTAGE DROP PE
TW in 0.0 3% FOR BRANCH VOLTAGE (PEC 1, 20
2% FOR FEEDER VOLTAGE (PEC 1, 20

TABLE 3.10.2.6(B)(16) : A
and TABLE 3.10.2.6(B)(2)(a) AMBIENT
TW 60°C
CABLE
CAPACITY
SIZE mm2
2 15
3.5 20
Page 16 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
5.5 30
8 40
14 55
22 70
30 85

38 100
50 115
60 130
80 155
100 185
125 210
150 240
175 260
200 275
250 315

TABLE 3.10.2.6(B)(2)(a): ALLOWA


THW 75°C
CABLE
CAPACITY
SIZE
3.5 25
5.5 35
8 50
14 65
22 85
30 110
38 125
50 145
60 160
80 185
100 220
125 255
150 280
200 330
250 375
Page 17 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
325 435
400 or
Rating 485
Setting
500 of 540
Automatic
Overcurren
TABLE 2.50.6.13: EQUIPMENT GROUNDING CONDU
t Device in
Circuit
Ahead of
Equipment,
Conduit,
etc.,
15
20
30
40
60
100
200
300
400
500
600
800
1000
1200
1600
2000
2500
3000
4000
5000
6000

Page 18 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
PERMITTED VD VOLTAGE DROP REMARKS
Allowable
Voltage
% Voltage e(V) %V
Drop
Drop
3% 6.9 2.93 1.27% OK
3% 6.9 2.93 1.27% OK
3% 6.9 2.93 1.27% OK
3% 6.9 2.93 1.27% OK

VOLTAGE DROP PERMISSIBLE PERCENTAGE


CH VOLTAGE (PEC 1, 2017 PAGE 42, ARTICLE 2.10.2.2 (A) FPN NO.4
ER VOLTAGE (PEC 1, 2017 PAGE 51, ARTICLE 2.15.1.2 (A) FPN NO.2

TABLE 3.10.2.6(B)(16) : ALLOWABLE AMPACITIES OF CABLES,PEC1 page 174


0.2.6(B)(2)(a) AMBIENT TEMPERATURE CORRECTION FACTORS BASED ON 30
60°C 31-40°C INDOOR USE
CAPACITY CORRECTION FACTORS
A 82 % 12.3 A
A 82 % 16.4 A
Page 19 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
A 82 % 24.6 A
A 82 % 32.8 A
A 82 % 45.1 A
A 82 % 57.4 A
A 82 % 69.7 A

A 82 % 82.0 A
A 82 % 94.3 A
A 82 % 106.6 A
A 82 % 127.1 A
A 82 % 151.7 A
A 82 % 172.2 A
A 82 % 196.8 A
A 82 % 213.2 A
A 82 % 225.5 A
A 82 % 258.3 A

2.6(B)(2)(a): ALLOWABLE AMPACITIES OF CABLES,PEC1 page 170


75°C 31-40°C OUTDOOR USE
CAPACITY CORRECTION FACTORS
A 88 % 22.0 A
A 88 % 30.8 A
A 88 % 44.0 A
A 88 % 57.2 A
A 88 % 74.8 A
A 88 % 96.8 A
A 88 % 110.0 A
A 88 % 127.6 A
A 88 % 140.8 A
A 88 % 162.8 A
A 88 % 193.6 A
A 88 % 224.4 A
A 88 % 246.4 A
A 88 % 290.4 A
A 88 % 330.0 A
Page 20 file:///conversion/tmp/activity_task_scratch/538495390.xlsx
A 88 % 382.8 A
A 88 % 426.8 A
A 88 % 475.2 A

OUNDING CONDUCTORS
Size
Aluminum or Copper-
Copper
Clad Aluminum*
AWG/ mm² AWG/
mm²
MCM MCM
2.0 14 3.5 12
3.5 12 5.5 10
5.5 10 8 8
5.5 10 8 8
5.5 10 8 8
8.0 8 14 6
14 6 22 4
22 4 30 2
30 3 38 1
30 2 50 1/0
38 1 60 2/0
50 1/0 80 3/0
60 2/0 100 4/0
80 3/0 125 250
100 4/0 150 350
125 250 200 400
150 350 300 600
200 400 300 600
250 500 400 800
375 700 500 1200
400 800 500 1200

Page 21 file:///conversion/tmp/activity_task_scratch/538495390.xlsx