Alternator Parallel Operation
Alternator Parallel Operation
Alternator Parallel Operation
1. To study the transference of loasd between two alternators running in parrallele, keeping the
load,frequency,and voltage constant.
2. To stiudy the variation of voltamperes with respect to alternator excitation, keeping input power
, output load, voltage and frequency constant.
Theory:
The laod output of ther alterantor is governed by the input power from its prime -mover. Variation
of excitation gives rise to a change in the kVar ouput; the kW output remins unchanged.
Procedure:
1. The alternators are conneted as shown in FIG.1 using two single-phase wattmeters
2. The d.c shunt motors are started and the alternators are brought up to speed.
3. By varying the alternator fields, the terminal voltages are brought up to the rated values(110V).
4. The speeds of the sets are adjusted by means of the motor field rheostat control until
thealternators run at rated frequency
5. The synchronising switch is closed in the middle of a dark period of the lamps. ( The
alterantors should now be working in parallel, but they should not be delivering any load. Also ,
if the voltage and speed have been properly adjusted, there should be no interchange odf current
between the alternators and the ammeters should read zero.
6. For a particular load output at consatnt frequency and voltage, input ot the d.c machine is varied
and the outputs shared by each alternator are noted from the wattmeter readings. Inputs to the
d.c side are also noted.
7. A graph is plotted between the input power and the load shared by each machine, as shown in
FIG.2
8. Keeping the input power , outputload , terminal voltage an dfrequency constant, the current
outut of each alternator is noted for different excitaitons.
9. A graph of output (in VA) versus excitation as shown in FIG.3 is plotted.
Observations:
LOAD SHARING
No. W1 A1 Iac1 Vdc1 W2 A2 Iac2 Vdc2
(watts) (amps) (amps) (Volts) (watts) (amps) (amps) (volts)
Voltage =
Load current =
Frequency =
W1 =
W2 =
No. Machine I Machine II
If1(amp) Iac1(amp) 1.73VIac1(VA) If2(amp) Iac2(amp) 1.73Viac2(VA)
Results:
Remark:
Variation of load angle with cahnge in the output load can be observed with a stroboflash
arrangement
FIG.1 Two D.C motor -alternator sets as follows are used.
Ifpm
A
Rf1=0-185 ohm
S1 Ra Ia
A
0-60A
Starter A1 F1 F1
110 V
D.C R
Supply M Y
0-150V Vt B
D.C N
A2 F2 F2 Star-connected
alternator
130 V,13.9 A,
3 kVA,50Hz
Rf2 =0-35 ohm 1000 rpm
A
0-6 A D.C
L1
B1 B2
A 0-60A
L2 To 3-phase load
L3
FIG.2
800 Machine I
600 Machine II
400
200
MachineI Machine II
Volt- amperes