RLC04 - Manual
RLC04 - Manual
RLC04 - Manual
Protection Relay
RLC04
Operating & Instruction Manual
Document History
2
RLC04-B
Capacitor and Filter Bank Protection Relay
Complete Operating and Instruction Manual
3
4
Table of Contents
INTRODUCTION....................................................................................................................................................... 9
PRODUCT OVERVIEW .......................................................................................................................................... 10
Application ........................................................................................................................................................... 10
Main Product Features ........................................................................................................................................ 10
Protection Functions ........................................................................................................................................ 10
Test functions................................................................................................................................................... 10
Inputs ............................................................................................................................................................... 10
Outputs............................................................................................................................................................. 11
Enclosure ......................................................................................................................................................... 11
User Interface .................................................................................................................................................. 11
Data Communications...................................................................................................................................... 11
Application Software ........................................................................................................................................ 11
Product Evolution Information ............................................................................................................................. 11
FUNCTIONAL DESCRIPTION ............................................................................................................................... 12
Protection Functions............................................................................................................................................ 12
Normal Mode ................................................................................................................................................... 12
Repetitive Peak Overvoltage Protection ...................................................................................................... 12
Programmable vc>reset Time ...................................................................................................................... 13
Thermal Overcurrent Protection................................................................................................................... 14
Fundamental Frequency Star Point Unbalance Protection..........................................................................15
Fundamental Frequency Line Current Unbalance Protection...................................................................... 15
Fundamental Frequency Earth Fault Protection .......................................................................................... 16
Fundamental Frequency Overvoltage and Overcurrent Protection ............................................................. 16
RMS Overcurrent Protection ........................................................................................................................ 16
Fundamental Frequency Undercurrent Protection....................................................................................... 16
Breaker Fail Protection................................................................................................................................. 17
Capacitor Bank Re-switching Protection...................................................................................................... 17
Event Trip ..................................................................................................................................................... 17
H-Bridge Mode................................................................................................................................................. 18
Fundamental Frequency H-Bridge Unbalance Protection ...........................................................................18
Inputs and Outputs .............................................................................................................................................. 19
Element Inputs ................................................................................................................................................. 19
Output Relays .................................................................................................................................................. 19
Relays K1 to K5............................................................................................................................................ 19
Relay K6 Self-supervisory Output ................................................................................................................ 19
Contact Forms.............................................................................................................................................. 19
Relay Checksum .......................................................................................................................................... 20
Digital Input ...................................................................................................................................................... 20
Breaker-Bon ................................................................................................................................................. 20
Event Tripping .............................................................................................................................................. 20
Remote Reset .............................................................................................................................................. 20
Other Facilities..................................................................................................................................................... 20
Password Protection ........................................................................................................................................ 20
Test Facilities ................................................................................................................................................... 20
PC Based Software Package........................................................................................................................... 21
Modbus Protocol .............................................................................................................................................. 21
5
Enclosure and Draw-out Unit............................................................................................................................... 22
Terminals ......................................................................................................................................................... 22
User Interface .................................................................................................................................................. 22
Five button keypad. ...................................................................................................................................... 23
Status LEDs ................................................................................................................................................. 23
LCD Display ................................................................................................................................................. 23
LCD Display ................................................................................................................................................. 24
Serial Data Port ............................................................................................................................................ 24
Auxiliary Power Supply........................................................................................................................................ 24
INSTALLATION AND COMMISSIONING.............................................................................................................. 25
Unpacking, Storage and Handling....................................................................................................................... 25
Enclosure and Draw-Out Unit.............................................................................................................................. 25
Configuring the Hardware Prior to Installation..................................................................................................... 26
Output relay contact form................................................................................................................................. 26
Mounting .............................................................................................................................................................. 26
Wiring................................................................................................................................................................... 27
Auxiliary power supply ..................................................................................................................................... 27
Current transformer circuits ............................................................................................................................. 27
Output Relay Circuits ....................................................................................................................................... 27
Digital Input ...................................................................................................................................................... 28
Serial Communication Port .............................................................................................................................. 28
Earth Connection ............................................................................................................................................. 28
Noise Isolation ..................................................................................................................................................... 28
1st Level Menus ................................................................................................................................................... 30
2nd Level Menus................................................................................................................................................... 31
Changing or Selecting Parameters.................................................................................................................. 31
Some Exceptions ......................................................................................................................................... 31
Some Exceptions ......................................................................................................................................... 32
Scrolling ........................................................................................................................................................... 32
The Exit Process.............................................................................................................................................. 32
PROGRAMMING THE RLC04-B............................................................................................................................ 33
Configuring the Hardware.................................................................................................................................... 33
Setting the Password........................................................................................................................................... 33
Serial Port Options .............................................................................................................................................. 33
Serial Port Options .............................................................................................................................................. 34
Parameter Setup - Normal Mode ........................................................................................................................ 35
Set Element 1, 2, 3 Variables .......................................................................................................................... 35
Set Element 4 Variables .................................................................................................................................. 36
Set Element 5 Variables .................................................................................................................................. 36
Set Other Functions ......................................................................................................................................... 36
Compensate for Star Unbalance ..................................................................................................................... 37
Clear Trip History ............................................................................................................................................. 37
Output Relay Setup – Normal Mode ................................................................................................................... 37
Parameter Setup – H-Bridge Mode ..................................................................................................................... 38
Set Element 2, 3, 4 Variables .......................................................................................................................... 38
Set Other Functions ......................................................................................................................................... 39
Compensation for xIub..................................................................................................................................... 39
Clear Trip History ............................................................................................................................................. 39
Output Relay Set-up - H-Bridge Mode ................................................................................................................ 40
6
OPERATING THE RLC04-B .................................................................................................................................. 41
Healthy Condition ................................................................................................................................................ 41
The LED Indicators .......................................................................................................................................... 41
The Running Displays...................................................................................................................................... 41
Normal Mode Displays ................................................................................................................................. 42
H-Bridge Displays......................................................................................................................................... 42
Default Display ............................................................................................................................................. 43
Fault Condition .................................................................................................................................................... 43
The LED Indicators .......................................................................................................................................... 43
The Running Display........................................................................................................................................ 43
Post-trip Fault Annunciation Displays .............................................................................................................. 43
Typical Post-Trip Annunciation Displays...................................................................................................... 44
Information Retrieval ........................................................................................................................................... 44
Trip History List ................................................................................................................................................ 44
Status Information............................................................................................................................................ 45
Relay configured in Normal Mode................................................................................................................ 46
Relay configured in H-Bridge Mode: ............................................................................................................ 46
Clearing the Counters .................................................................................................................................. 46
TESTING AND TROUBLESHOOTING .................................................................................................................. 48
Automatic Self-testing.......................................................................................................................................... 48
User-performed Diagnostic Tests........................................................................................................................ 48
Injection Testing .................................................................................................................................................. 49
Trouble Shooting ................................................................................................................................................. 50
APPENDIX 1 ........................................................................................................................................................... 51
Table 1 - Step-By-Step Installation Instructions .................................................................................................. 51
Table 3: Nomenclature & Definitions for H-Bridge Mode .................................................................................... 54
Table 4: General Characteristics......................................................................................................................... 55
Table 5: Technical Specifications........................................................................................................................ 56
Table 6: Settable Parameters and Ranges – Normal Mode ............................................................................... 57
Table 7 – Settable Parameters and Ranges – H-Bridge Mode........................................................................... 58
APPENDIX 2 ........................................................................................................................................................... 59
Example 1: Calculation of Checksums for Output Relays 1 To 5 ....................................................................... 59
Typical Examples of Output Relay Settings and Resulting Checksums ......................................................... 59
One of 5 Output Relays in Normal Mode Operation .................................................................................... 59
One of 5 Output Relays in H-Bridge Mode ...................................................................................................... 59
Example 2: RLC04-B Setting Calculations.......................................................................................................... 60
20 Mvar harmonic filter with a double star capacitor bank .............................................................................. 60
Settings ............................................................................................................................................................ 61
Notes on Settings............................................................................................................................................. 61
Example 3: Calculation of the Reactor Heating and Cooling Time Constant (τ)................................................. 64
Appendix 3........................................................................................................................................................... 65
Figure 1: Relay Case and Panel Cut-out Dimensions......................................................................................... 65
Figure 3: Repetitive Peak Overvoltage vs. Trip Time Curves ............................................................................. 66
Figure 3: Repetitive Peak Overvoltage vs. Trip Time Curves ............................................................................. 67
Figure 4: Thermal Trip Time Curves ................................................................................................................... 67
Figure 4: Thermal Trip Time Curves ................................................................................................................... 68
Figure 5: Typical Application Examples .............................................................................................................. 69
Figure 6: Typical Wiring Diagram For A Double Star Capacitor / Filter Bank ..................................................... 69
7
Figure 6: Typical Wiring Diagram For A Double Star Capacitor / Filter Bank ..................................................... 70
Figure 7: Element Failure in a Double Star Connected Capacitor Bank............................................................. 71
Figure 8: Typical Wiring Diagram for an H-Bridge Capacitor / Filter Bank.......................................................... 72
Figure 9: Element Failure in an H-Bridge Connected Capacitor Bank................................................................ 72
Figure 9: Element Failure in an H-Bridge Connected Capacitor Bank................................................................ 73
Figure 10: Output Relay 1 to 5 Configuration...................................................................................................... 74
8
Introduction
The RLC04-B is a capacitor and filter bank protection relay. It has been built on the foundation of years of
continued development through previous successful models. The RLC04-B has quality embedded into every
stage of its design and it has been manufactured to the strictest quality standards. Combining state of the art
hardware technology and software techniques it provides the most convenient functionality in its sphere.
This manual contains an overview, functional description, and specification of the RLC04-B, as well as detailed
instructions on installation, commissioning, setting up, operation, and maintenance.
Whilst it provides a wealth of information, this manual does not replace the need for anyone installing, operating,
or maintaining the equipment to be suitably qualified and/or trained. Such a person should have a prior
knowledge of power system protection, power system measurements, and power system safety procedures.
Before installing, setting up or operating the RLC04-B, the user should study the applicable sections of this
manual, taking particular note of WARNINGS, CAUTIONS and NOTES included for the safety and protection of
both personnel and equipment.
Before attempting to troubleshoot the equipment, the user should thoroughly understand the entire manual. For
troubleshooting and commissioning the following equipment is required:
- Digital multimeter with clip-on current tong for measuring 1A or 5A current transformer secondary.
- Preferably a three-phase, alternatively a single-phase, primary or secondary injection test set, which is
included in the product range offered by Strike Technologies.
Due to the nature of the RLC04-B relay, it is not recommended that the user should attempt repairs other than
the removal and replacement of the draw-out unit that houses all electrical and electronic parts. Any faulty
RLC04-Bs should be returned to Strike Technologies (Pty) Ltd. for testing, and if necessary, for repair or
replacement of faulty parts, re-calibration and re-testing.
Thank you for purchasing the RLC04-B protection relay, please contact Strike Technologies (Pty) Ltd for further
details should they not be covered within this manual
9
Product Overview
Application
The RLC04-B Protection Relay provides comprehensive protection for the capacitive, inductive and resistive
elements of three phase medium voltage and high voltage shunt capacitor banks and harmonic filter circuits. The
capacitor banks consist of several individual capacitors in a series – parallel arrangement. Each individual
capacitor within a bank may be internally fused, externally fused or unfused. A number of banks are constructed
as a single star, double star, delta or H-bridge configuration.
In normal conditions these banks are balanced, i.e. each leg draws the same current as near as practically
possible. Should one or more of the capacitor elements fail, the system will become unbalanced and the RLC04-
B will sense this and can be used to trip any necessary circuit breakers.
The RLC04-B has additional protection features such as for fundamental and harmonic overcurrent and
overvoltage, as well as over temperature conditions and residual earth currents.
Due to its accuracy and short response times, the relay provides the optimum protection for a system. By only
operating when absolutely necessary it prevents unnecessary trip outs thereby preventing unnecessary financial
losses and other detrimental consequences. In addition, after a system fault or equipment failure, the RLC
Protection Relay trips the associated circuit breaker timorously, to ensure maximum personnel safety, and to
minimize further equipment and other consequential damage.
Protection Functions
Repetitive peak overvoltage
Thermal overcurrent
Fundamental frequency overvoltage and overcurrent
RMS overcurrent
Fundamental frequency star point unbalance
Fundamental frequency line current unbalance
Fundamental frequency H-bridge configuration unbalance
Fundamental earth fault current
Fundamental frequency undercurrent
Breaker Fail detection
Capacitor bank re-switching
Event tripping
Test functions
Both on-line and user activated hardware diagnostic testing
Inputs
4 Dual Current Measuring Elements - Individually programmable for either 1A or 5A
Optically isolated digital blocking input - User configurable for active low/active high
Wide range AC/DC Auxiliary Power Supply (30 – 250V AC/DC)
10
Outputs
5 Trip/Alarm output relays (K1 to K5), programmable with regard to energisation and latching functionality,
hardware configurable NO/NC contact form
1 Dedicated self-supervisory output relay (K6), hardware configurable NO/NC contact form
Enclosure
Flush mount and 19” rack compatible
Draw-out facility, with automatic shorting of CT input connections
User Interface
3 LED Status Indication: Healthy (Green); Alarm/Start (Yellow); Trip (Red)
Alpha-numeric, backlit, Liquid Crystal Display (2 lines x 16 characters)
Menu driven user interface with 5 button interactive keypad
Data Communications
Two serial interfaces for programming and interrogation
Remote communication by means of RS232 or RS485, either via a dedicated line or via a modem (PSTN or
GSM).
Both Strike protocol and Modbus RTU protocol co-reside in the product
Application Software
Windows 95/98/2000/NT/XP Software Package, for local programming/data uploading, as well as remote
communication via modem
11
Functional Description
Protection Functions
Shunt capacitor and filter banks are used in medium and high voltage systems to provide power factor correction
and reduce unwanted harmonics being fed back onto the mains grid. Any one of a number of standard circuitries
can be used to provide capacitor or filter bank protection in a system. With its 4 Analogue Input Elements, 1
Digital Input, 5 output relays for system protection, and 1 output relay for self-supervision purposes, the RLC04-B
can be programmed to handle any of these configurations.
The measured currents themselves, or several other values calculated from them, are compared to threshold
values entered into the RLC04-B by the user. These can be alarm, low-set, or high-set thresholds, although not
all threshold types are relevant to all functions. If a threshold value is exceeded, a start signal is immediately
generated, which in itself can be used to activate one or more output relays, and a timer linked to that function
starts running. Should the threshold remain exceeded for a specified time-out period, normally also entered by
the user, an alarm or trip signal will be generated. The RLC04-B can be programmed to respond by switching
any permutation of the output relays for each particular signal/threshold combination.
The relay’s functionality and programmable options adapt according to the type of circuitry being protected. We
therefore need to describe the two major circuit groups separately in the following sections.
Normal Mode
This mode is applicable to star, delta, and double star circuits.
Iub
or
12
The alarm threshold VC>al/vcr, with an associated adjustable definite time-out period, VC>al: xt; if VC exceeds
the threshold for the time set, the alarm signal VC>alarm is generated.
The low-set threshold, VC>/VCR. For voltages above this threshold, a starter signal, vc>start starts a trip timer.
The ANSI inverse time curve defines the time before the low-set trip signal, vc>trip, is generated, and providing
that the voltage still exceeds the threshold.
The high-set threshold, vc>>/vcr, with an associated adjustable definite time-out period vc>>:xt, is available to
provide a high-set trip output vc>>trip, if the associated threshold is exceeded for the definite time set.
The graphs show a sequence of intermittent overvoltages in a monitored circuit, with two different consequences
for the relay condition dependent upon the vc>reset value chosen:
The vc/vcr voltage ratio, occasionally exceeding the low-set trip threshold value.
The accumulating trip timer value with a shorter vc>reset value, allowing an intermediate trip timer reset.
The accumulating timer value with a longer vc>reset value, thus allowing no intermediate reset of the trip timer,
and eventually creating a trip condition.
13
Thermal Overcurrent Protection
All of the components making up a capacitor bank / harmonic filter circuit are stressed thermally by the current
Irms which flows through them. This applies to all of the elements such as circuit breaker, feed cable, damping or
filter reactors, and filter resistors, as well as the capacitors. Irms comprises both the fundamental and harmonic
components. The RLC04-B protects the banks against such excessive temperature rise which would otherwise
lead to damage of the components and cause a breakdown.
According to recognized standards, a capacitor bank, and the capacitor units making up the bank, must be rated
to withstand a continuous current of 130% of the rated current.
For each phase, the RLC04-B protects a capacitor bank / harmonic filter circuit from excessive current stressing,
by modeling the thermal response of the circuit to the total heating current, Irms.
After a system has been running for a short while, it will heat up to a particular temperature, caused by Irms. At
any point before that steady state condition is reached, the lower temperature of the system so far attained could
be said to be caused by a lower effective thermal current, represented as Ith. When the system eventually
reaches the steady state condition, Ith equals Irms. The time constant which determines how quickly this occurs
depends upon the system.
Using advanced digital signal processing techniques Irms is continuously calculated from the measured line
th
currents, both fundamental and harmonics (up to the 50 ). A second order thermal model with an adjustable
heating / cooling time constant , is then used to continuously calculate the thermal current response, Ith, to the
heating current, Irms. Ith is continuously compared to the adjustable low-set and high-set thresholds, Ith> and
Ith>>, each linked to their corresponding trip signals Ith>trip, and Ith>>trip, which are generated, if the
associated thresholds are exceeded for the definite times set.
However, it is possible to set the low-set time-out period Ith>:xt to “Alarm”. The low-set function then acts purely
as an alarm, and only the Ith>start signal is generated, without a subsequent Ith>trip signal.
The trip times can be evaluated using the following formula:
-ln (((I/Ith>)² - 1) / ((I/Ith>)² - (Io/Ith>)²))
t/ =
where I/Ith> = overload current / thermal trip threshold current
and Io/Ith> = pre-load current / thermal trip threshold current
14
Fundamental Frequency Star Point Unbalance Protection
In a double star connected capacitor bank, the failure of internal capacitor elements, and the subsequent blowing
of internal capacitor element fuses or external capacitor unit fuses, is detected by sensitive monitoring of the
unbalance current flowing between the two star ppoints.
Even though efforts may be taken to balance a double star connected capacitor bank, by optimum selection and
positioning of the capacitor units making up the bank, the tolerance in capacitance is such that a “natural”
fundamental frequency star pointt unbalance current flows under normal conditions.
The RLC04-B measures the star point unbalance current and calculates the fundamental frequency component,
Iub. This can then be compensated, in magnitude and phase angle, to zero, to enable further changes, in both
magnitude and phase angle, ∆Iub, from the initial uncompensated value, to be determined. The magnitude of
∆Iub is a measure of the change in capacitance in any leg of a double star capacitor bank arrangement, whereas
the phase angle of ∆Iub indicates the leg in which the change in capacitance has occurred.
The magnitude of (∆)Iub is continuously compared to an adjustable alarm threshold, Iub_al, and trip thresholds,
Iub> and Iub>> each with associated adjustable definite time-out periods, Iub_al:xt, Iub>:xt and Iub>>:xt
respectively. Where (∆)Iub exceeds Iub_al for the definite time set, an alarm signal,
Iub_alarm, is generated. In addition, a starter signal Iub>start as well as low-set and high-set trip signals,
Iub>trip, and Iub>>trip, are generated, if the associated thresholds are exceeded for the definite times set.
If the natural unbalance has been compensated and the fundamental current in the reference
phase (Element1) drops below 10% of the nominal current In, the star point unbalance protection
functions are suspended, and the compensation vectors are ignored.
If the natural unbalance is not compensated and the fundamental current in the reference phase
drops below 10% of the nominal current In, the star point unbalance protection function operates
only on the amplitude of the measured unbalance current – the phase angle will not be taken into
consideration.
The advantage of star point unbalance protection is that, unlike line current unbalance, the magnitude and phase
angle of (∆)Iub is not influenced by any phase imbalance in the supply voltage. Therefore the sensitivity can be
much higher than line current unbalance measurement, without spurious tripping caused by unbalanced supply
voltages. This sensitivity is often essential for adequate protection of larger capacitor banks with both
internal/external and unfused capacitor units.
In addition, the star point unbalance protection function indicates the leg of the double star bank in which the
change in capacitance has occurred. This is particularly convenient for larger capacitor banks with internally
fused or unfused capacitor arrangements, to speed up the identification of faulty capacitor units. Refer to Figure 7
in Appendix 3 for more details on this.
15
For Ilub greater than Ilub>, a starter signal, Ilub>start, is generated. In addition, low-set and high-set trip
signals, Ilub>trip and Ilub>>trip, are generated if the associated thresholds are exceeded for the definite times
set.
The sensitivity of line current unbalance protection is limited by the effect of supply voltage unbalance on the line
currents. Nevertheless, line current unbalance protection is useful as back-up protection to star point unbalance
protection, as well as for early detection of filter resistor and reactor faults, and for early detection of capacitor
element failures in smaller capacitor banks, in single star or delta connected arrangements, where star point
unbalance protection is not provided.
16
load has been re-established. In certain cases this can help to avoid over correction and excessive voltage rise,
due to load rejection during a mains power dip.
For each phase, the RLC04-B calculates I1, the fundamental frequency component of the line current. I1 is
continuously compared with an adjustable undercurrent threshold, I1<, and associated adjustable definite time-
out period, I1<:xt. With the capacitor bank / harmonic filter circuit breaker on, if the mains power supply fails, as
indicated by a drop in I1 below I1< for longer than the definite time set, then the undercurrent trip signal, I1<trip,
is generated.
If the selected condition is not fulfilled within a programmable time-out period, Bfail1:xt, after the RLC04-B
issues a trip output, a Bfail1 signal is generated which can be allocated to one or more of the output relays.
For selections which involve the digital input, the input function must be set to “Breaker-Bon” or else the release
function will be default to Ifund<10%In.
Bfail2
In addition to the above, if I1 remains above 10% of rated In, for longer than the adjustable definite time-out
period, Bfail2:xt, after the breaker switches off (digital input set to “Breaker- Bon” - indicates the breaker
open/close status), then this indicates a major failure of the capacitor bank / harmonic filter circuit breaker, and
the breaker fail signal, Bfail2, is generated.
Both signals can be used to trip an upstream breaker.
Event Trip
The RLC04-B offers the possibility to trip the relay from an external signal via its digital input. A precondition is
that the digital input must be configured as an Event trip input. If the digital input changes its state from inactive to
active for the definite time-out period Event:xt, the generated function, Event_trip, can be used to operate any
of the output relay(s).
17
H-Bridge Mode
The magnitude of ∆aIub, ∆bIub or ∆cIub is a measure for the change in capacitance, while the phase angle
indicates the leg in which the change in capacitance has occurred.
The magnitudes of (∆)a/b/cIub are continuously compared to adjustable alarm thresholds a/b/cIub_al, low set
trip thresholds a/b/cIub>, and the high set trip thresholds a/b/cIub>>. Each of these thresholds is linked to an
associated adjustable definite time-out period, a/b/cIub_al:xt, a/b/cIub>:xt, and a/b/cIub>>:xt respectively.
For (∆)a/b/cIub greater than a/b/cIub_al for the definite time set, an alarm signal, a/b/cIub_alarm, is generated.
Similarly, starter signals a/b/cIub>start and low-set and high-set trip signals, a/b/cIub>trip, and a/b/cIub>>trip,
are generated, if the associated thresholds are exceeded for the definite times set.
If the natural unbalance has been compensated and the fundamental current in the reference
phase (Element1) drops below 10% of the nominal current In, the H-bridge unbalance
protection functions are suspended, and the compensation vectors are ignored.
If the natural unbalance is not compensated and the fundamental current in the reference phase
drops below 10% of the nominal current In, the H-bridge unbalance protection function
operates only on the amplitude of the measured unbalance current – the phase angle will not be
taken into consideration.
The advantage of H-Bridge capacitor bank unbalance protection is that the magnitudes and phase angles of
∆aIub, ∆bIub and ∆cIub are not influenced by any phase imbalance in the supply voltage. Therefore the
sensitivity can be much higher than line current unbalance measurement, without spurious tripping caused by
unbalanced supply voltages. In addition, this sensitive unbalance protection is now provided independently for
each phase of the capacitor bank, thus making it possible to immediately and independently identify the phase
and branch in which a change in capacitance has occurred. This is particularly convenient for larger capacitor
banks with internally fused or unfused capacitor arrangements, to speed up the identification of faulty capacitor
units.
Refer to the figures 5, 8, and 9 in Appendix 3 for further information on this function.
18
Inputs and Outputs
Element Inputs
Four measuring inputs (Elements 1 to 4) are provided. Each can be programmed to measure inputs from current
transformers with nominal currents In of either 1A or 5A.
In Normal Mode the Elements 1, 2 and 3 are used to measure the line currents while Element 4 is used to
measure the star point unbalance current of a double star connected capacitor bank.
In H-Bridge Mode the Element 1 is used to measure the reference phase current, while Elements 2, 3 and 4 are
used to measure the unbalance currents in each of the phases of the H-configured capacitor bank.
Refer to Figure 5 in Appendix 3 for typical configurations.
When programming the RLC04-B it will be noticed that under the Parameter Set-up menu is a sub-menu entitled
Set Element 5 variables. Element 5 is a “virtual” and not a physical element. The currents “measured” by this are
Io and Ilub which are calculated from the line currents measured by elements 1-4.
Output Relays
The RLC04-B has six relay outputs. Five outputs K1 to K5 are for normal protection use, while the sixth K6 is for
the RLC04-B to check its own “health”. To confirm the correct allocation of these output relays a checksum
function is available in the unit.
Relays K1 to K5
Relays K1 to K5 can be programmed, separately and in any permutation, to operate in reaction to any alarm/start
or trip condition.
The relay outputs can be hardwired to N/O or N/C settings by using the selecting the appropriate links on the
RLC04-B’s PC board. See the relevant section under Installation and Commissioning.
Output relays K1 - K5 can be programmed to be de-energised or energised in the operational healthy state, and
to be latching or non-latching.
For relay contact ratings, refer to Table 5 in Appendix 1. Note that in the RLC04-B product, relay K1 has a higher
dc switching capability than K2 to K5, and is intended for the direct tripping of certain switchgear. Caution should
be exercised, however, not to exceed the contact ratings of any relay, as this will eventually result in contact
failure.
Contact Forms
Output relays 1 to 6 each have one changeover (form C) contact. As default, output relays 1 to 6 are supplied
with the normally open (relay de-energized) contacts wired to the terminal block. However, the user may easily
change the contacts of any or all of output relays 1 to 6 wired to the terminal block to be normally closed, as
required by the application. Refer to Section 5 – Installation and Commissioning for more details on this.
19
Relay Checksum
Each relay K1 to K5 has an associated checksum which is calculated automatically according to the allocations
made during set-up. This calculated checksum is displayed as part of the set-up screens. The purpose is for the
user to be able to confirm the correct set-up of K1 to K5, by manually calculating the checksum representing the
desired relay set-up and then comparing this with the calculated checksum, which must agree. Refer to Example
1 in Appendix 2 for more details on this.
Digital Input
In addition to the four measuring elements there is an optically isolated digital input, in which the input signal is
not measured but is simply detected to see if it is active or inactive. It can be set to have a high level or a low
level as being active. A high level must conform to the range 30V - 250V ac or dc and is not polarity sensitive. It
can be configured as one of three possible functions, or disabled.
Breaker-Bon
A signal from an auxiliary contact on the associated circuit breaker is fed into the digital input to signal whether
the breaker is open or closed. This signal is used by the undercurrent protection, and can be used by the Breaker
Fail 1 protection and Bena function of the relay. If the relay does not receive the Breaker On signal, neither of the
mentioned functions will operate.
Event Tripping
The second alternative for the digital input is to create a trip condition based on an active signal on its input. The
same input conditions as described above apply, and similarly to other trip condition configurations, any
combination of output relays K1 to K5 can be allocated to it. To create a trip, the active signal must remain valid
for a pre-set length of time. This Event Input Trip Time (Event:xt) is programmable under the PARAMETER
SETUP – Set OTHER functions menu. Should the signal become inactive during this trip time, further activation
will begin a new timing sequence starting from zero, even if the reactivation occurs within the original trip time. A
suitably descriptive label, downloadable from a computer running the application software, can be programmed
to appear following an event trip.
Remote Reset
The third alternative for the digital input is to reset the RLC04-B from a remote location, e.g. a control room. This
has the same effect as pressing the red button to acknowledge a trip.
Other Facilities
Password Protection
Certain parts of the menu structure can be protected by an optional password. This provides a measure of
security against inadvertent or unauthorized alterations to the relay settings, or clearance of the trip history.
Unrestricted access is still provided to the status and test functions.
Test Facilities
While the RLC04-B Relay is in service, it continuously performs various self-testing functions, and if any errors or
failures are detected, the corresponding error code(s) will be displayed, and the self-supervision output relay will
de-energize, to signal the malfunction. These self-tests include tests of the processors as well as the memory of
the device. All protection functions continue uninterrupted during this process.
20
In addition, a further set of hardware diagnostic tests may be performed on the RLC04-B by the user to test and
check the functionality of the digital input, relay outputs, LCD display and LED’s. Note that some protection
functions may be interrupted during this process.
Modbus Protocol
The RLC04-B supports the MODBUS RTU protocol for integration of the relay into a SCADA environment.
Further information on the implementation can be provided upon request.
21
Hardware Description
Enclosure and Draw-out Unit
The RLC04-B is housed in a draw-out chassis within a fixed case. This housing is particularly suitable for both
flush mounting and 19 inch rack mounting. The case is designed for use in tropical climates, and is designed to
withstand shock, vibration and the ingress of dust and moisture. Two phosphor bronze earth continuity strips
riveted to the draw-out chassis make contact with earthing strips in the fixed case.
Terminals
A terminal block, with 28 recessed terminals, is provided on the rear of the fixed case. Standard M4 screw
terminals (cable lugs with M4 and lug outer diameter < 8 mm), or fast-on connectors (4,8 mm width / 0,8 mm
thickness), can be used on the terminal block for connections to the protection relay. Removing the draw-out
chassis from the fixed case automatically short circuits the current transformer field terminals, before breaking
contact with the draw-out chassis, and ensures that the current transformer circuits are not open circuited during
and after removal.
The RLC04-B incorporates static sensitive devices. However the electronic circuits
are well protected by the fixed metal case. Therefore do not withdraw the draw-out
chassis unnecessarily. Refer to the section on Installation for further details on
handling of the draw-out chassis when removed from the fixed case.
User Interface
A menu driven interface is provided on the front panel. This allows convenient viewing of operational information
as well as programming facilities for relay set-up, and access to certain test aids for verification purposes.
22
LCD Display
Status LEDs
5 button keypad
Status LEDs
There are three status indicators:
Power On (Healthy). This green LED is normally on continuously indicating that power is applied, and the relay
is in a healthy state. A flashing state indicates that the relay is in the process of completing its on-line diagnostic
test.
Alarm/Start. This Yellow LED may be illuminated by an Alarm or a Start condition, depending upon the set-up of
the relay.
Trip. This red LED is illuminated when a trip condition occurs and remains on until the trip condition, with its post-
trip display, is cancelled by pressing the red “accept” button on the keypad. If multiple trip conditions were
present at the time of trip, each condition must be sequentially accepted before the red LED will go off.
The value of the Ith>:xt can be set to “Alarm”. This is only used to signal the alarm condition
via one of the output relays. It is not linked to the yellow LED.
23
LCD Display
This 2 line x 16 character alpha-numeric display provides most of the information feedback to the operator. It has
a backlight which extinguishes after 1 minute of keypad inactivity. Pressing any button after this will light the
display once more. The function of that button is ignored for this purpose.
It supplies the following information:
o During normal relay operation – the display of various measured and calculated parameters, together
with the low-set thresholds associated with these parameters.
o After a relay trip condition – annunciation of the entire fault conditions, including the value of the fault
currents and voltages at the instant of trip, the information in which phase the max. / min. value occurred
and the relay trip time after commencement of the fault condition.
o During relay configuration – interactive configuration of the protection relay.
o During testing of the protection relay – interactive self-testing of the protection relay.
o In the event of the RLC04-B Relay failure – annunciation of any protection relay hardware, software or
memory failures detected during self-testing of the RLC04-B Relay, by displaying certain error codes.
These are for use by the manufacturer.
24
Installation and Commissioning
The RLC04-B incorporates static sensitive devices. However, the electronic circuits
are well protected by the fixed metal case. Therefore do not withdraw the draw-out
unit unnecessarily
If it is necessary to withdraw the RLC04-B module from its housing, the following precautions should be taken:
o Before removing the draw-out module, ensure that you are at the same electrostatic potential as the
equipment, by touching the fixed metal case.
o Handle the draw-out module by the metal fascia plate, frame or edges of the printed circuit boards. Avoid
touching the electronic components, printed circuit board tracks or connectors.
o If the equipment is to be passed to another person, first ensure you are both at the same electrostatic
potential, by touching.
o Place the draw-out module on an anti-static surface, or on a conducting surface, which is at the same
potential as you.
o Store or transport the draw-out module in an anti-static bag.
Further information on safe working procedures for electronic equipment can be found in the relevant national
and international standards.
In order to insert the draw-out chassis into the fixed case carefully
align the guide rails on the draw-out chassis with the corners of the
fixed case. Then firmly and slowly push the handle on the front
fascia plate to insert the draw-out chassis into the fixed case. When
the chassis is almost fully inserted, an extra resistance will be felt
as the moving contacts on the draw-out chassis mate with the
25
contacts of the fixed case. At this point, press the handle very firmly to fully insert the draw-out chassis. Then
place the front cover by hooking the top catch over the clip on the fixed case. Align the front cover and refasten
the bottom catch by a quarter turn.
Then, referring to figure above, identify the relay N/O and N/C selection links, on the Analogue / Power supply
printed circuit board. Move the link to the desired position for each relay, to select the appropriate contact form.
Mounting
The RLC04-B can be mounted anywhere that meets the environmental specifications as detailed in Appendix 2,
and in particular it should be mounted indoors, in a clean, dry atmosphere, out of direct sunlight, and free from
excessive dust and vibration.
Refer to Figure 1 in Appendix 3 for details of outline dimensions, cut-out details and mounting holes.
Heat producing devices must be located at sufficient distances away to ensure that
the maximum operating temperature of the RLC04-B relay is not exceeded.
The RLC04-B is normally used as a flush mounted or 19 inch rack mounted instrument, for fitting on or within
switchgear or relay panels. The relay should be mounted at a convenient height above floor level to facilitate
optimum visibility and operator interaction.
The mounting holes of the fixed metal casing of the RLC04-B are accessible without removing the front cover
and/or the draw-out module. Therefore it is strongly recommended that the draw-out module should remain
protected by the fixed metal case during mounting and assembly of a RLC04-B into a panel or 19 inch rack.
26
Wiring
All current transformer, auxiliary voltage, output relay, digital input, and rear data port wiring connects to the
terminal block with 28 recessed terminals on the rear of the fixed casing. The terminals are clearly labelled.
Check carefully before energizing, that the auxiliary voltage falls within the range
indicated on the RLC04-B. Ensure that the auxiliary supply to the RLC04-B is
adequately protected by means of fuses or miniature circuit breakers to suit the fault
level and wire size used as well as the inrush current. High rupturing capacity fuses
(2A) are recommended.
Ensure that the power supply to the relay is capable of handling the necessary inrush current. This can be
estimated using the following equations:
DC supply: I = VDC / 10
AC supply: I = VAC / 20
One side of each CT circuit should be earthed, and multiple earth connections and
earth loops should be avoided.
Check carefully, before applying current transformer inputs, that the current transformer rated currents are
correct and correspond with the nominal rated currents of the relevant measuring elements
Refer to Table 5 in Appendix 1 for the acceptable current range, the short-time Over-current, and the VA burden
of the measuring elements.
Check carefully before applying voltage to the output relay contacts that the loads and
voltages to be applied are within the ratings of the relay contacts. Refer to Appendix 1
for the continuous thermal rating, the short time current rating, the making/breaking
capacity, the maximum switching voltage and the maximum switching current of the
output relays.
27
Ensure that the voltages applied to the output relay contacts are adequately protected
by means of fuses or miniature circuit breakers to suit the fault-level, wire size and
contact rating.
Digital Input
If applicable, connect the digital input circuits to terminal numbers 9 and 11.
The digital input terminals can accept ac or dc input voltages and are not polarity sensitive.
Check carefully before applying voltage to the digital input terminals that the voltage
applied is correct and falls within the range detailed in Appendix 1.
Ensure that the voltage applied to the digital input is adequately protected by means of fuses or miniature circuit breakers to
suit the fault level and wire size used. High rupturing capacity fuses (2A) are recommended.
Earth Connection
It is recommended that a 4mm² earth conductor be installed from the RLC04-B earth terminal to the panel earth
bar. In addition, ensure that the panel is properly earthed in accordance with local regulations.
For personnel safety as well as not to adversely affect the RLC04-B by surges, transients
and other electrical and electro-magnetic disturbances, it is essential that the relay is
properly earthed as detailed above.
Noise Isolation
When properly connected and earthed, RLC04-Bs are highly tolerant of electrical and electro-magnetic noise.
Refer to Table 4 in Appendix 1 for the withstand ability. However, as with other microprocessor based
measurement and protection equipment, the RLC04-B must be installed, wired and located with some degree of
concern for electrical and electro-magnetic noise which could cause erratic operation. The relay should be wired,
mounted and isolated from sources of potential noise and disturbances in excess of those prescribed in Appendix
1.
In extreme cases this may require that filters or surge suppressors be applied to electro-magnetic devices
operating in close proximity to the RLC04-B.
To avoid possible problems from electrical and electro-magnetic noise and disturbances, or if specific problems
are experienced in this regard, obtain specialist advice regarding counter measures and solutions.
Performing any changes to element variable or other settings, changes to output relay
configurations, or running the diagnostic test sequence to test the output relays, may
cause the associated circuit breaker to trip. This could cause serious system disruption.
Therefore the greatest care should be exercised when performing these functions on-
line, and the user should have a thorough knowledge of this entire manual as well as the
particular application and system.
28
Fully commissioning the relay involves programming it to the required configuration. It is necessary to read and
fully understand the following two sections with regard to this. Thereafter the complete step by step installation
and commissioning table in Appendix 1 can be referred to as a quick guide.
29
Navigating the RLC04-B Menu
When in menu mode, whether merely viewing information, or changing parameters, the
protection remains in operation and is not compromised in any way. The previous
parameters remain in force, until the “Save” action is activated, whereupon the changed
parameters come into force.
To enter the menu press both horizontal scroll buttons W and X simultaneously for five seconds.
If a unique password has not been defined, no password will be requested and the display will switch straight to
the Access PARAMETER SETUP menu screen in the main menu list.
If a password has been set, you will be requested to enter it. This is a 6
digit numeric code. For each digit scroll to the correct number using the S
or T buttons.
Move to the previous and next digits by using the W and X buttons
respectively.
The digit being addressed will be indicated by a cursor - a line beneath the
digit.
Once you have set all 6 digits correctly, press the red button to enter.
30
There are nine main menus available which can be scrolled through using W and X.
When shipped, the default password is 000000, which allows unrestricted access to all
menu functions. By setting a new password the valid password must be entered to
access to any interactive menu. This provides a measure of security against
inadvertent or unauthorized alterations to the relay settings. Unrestricted access is still
provided to the status and test functions, by pressing instead of entering the
password.
Some of these are used for programming the RLC04-B, and some for normal operation such as extraction of
information, and for testing:
st nd
When viewing one of these 9 main 1 level menus, access the 2 level beneath it by pressing T. In the case of
nd
the Parameter Set-up option, the 2 level consists of a further series of menus. For the other options it will be a
series of parameter adjustment, information, or test screens depending upon the option.
When arriving at a parameter adjustment screen after pressing T from a menu above
it, take care not to keep T pushed in for too long or a parameter may be inadvertently
adjusted.
31
Some Exceptions
Some sub-menus do not follow the general rules described above.
Trip History Scroll vertically to select a particular trip.
Scroll horizontally for information on a particular trip
Password Set-up Scroll through screens using .
Scrolling
As described above, displays and parameters can be scrolled in either direction and values can be incremented
or decremented, by using the appropriate buttons. Generally X scrolls in the forward direction and W in the
reverse direction; S increments and T decrements a value or toggles an option. Holding a scroll button down
scrolls continuously. All scrollable sub-menus and parameters are of the “wraparound” type i.e. last wraps around
to first. When held down, the scroll speed gradually increases the longer the button is held.
Usually, once a parameter has been set to a value, or choice, the operator simply scrolls to the next item. All
items on a submenu are saved together in one operation. This occurs when exiting the sub-menu.
When programming the RLC04-B, it is important that any function that is not required
must be disabled, to prevent confusion and possible spurious operation. Disable is an
available option when scrolling a value, or selecting from possible choices.
Exit the menu without making any changes since the last save
Press to have your choice accepted and conclude the exit process.
When “Save” is selected, there will be a short delay while the new parameters are
saved into the non-volatile memory.
To revert to the running displays from the 1st level menus, press both W and X simultaneously.
If the relay is inadvertently left in menu mode, it will automatically perform a “cancel”
operation and exit to the running displays after 10 minutes.
In the three sections of this manual that follow, the symbols W, X, S, T, or appearing at the beginning of a
line of text indicate that the relevant button should be pressed to change to the display to that which will be
described.
32
Programming the RLC04-B
Enter menu mode as described in the preceding section. Of the 9 first level menus the following 6 are used to
set-up the relay operating parameters. They all fall under the protection of the optional password. The first 4 set-
up menus are common to both Normal and H-Bridge Modes:
Hardware Password
Serial Ports Real-time Clock
The last two set-up menus offer different options which are mode dependent:
Setting a password is optional - Refer also to the Password Protection under Other
Facilities in Section 3 - Functional Description, and also Section 6 – Navigating the RLC04-B
Menu.
Keep the password in a secure place. Losing the password will mean that access to
the protected functions will be denied, causing substantial inconvenience.
33
Serial Port Options
This function only needs to be set if either of the serial ports are to be used.
Choose the baud rate for the front port using S and T. Choose from the seven
rates between 2400 and 115200 using S and T. For a short distance connection
to a laptop computer the highest setting of 115200 is normally used.
X Scrolling to the right allows the setting of the parity to EVEN, ODD, or NONE,
using S or T.
X Scroll right to set the type of serial connection for the rear port. Choose
between RS232 and RS485 using S or T.
In some applications e.g. with some modems, in high electrical noise environments, or
long transmission distances, a lower rate may be required to achieve error-free
communication. Data transfers will naturally take longer at the lower rates, although
because the data is quite compact, this may not be noticeable.
X The next two displays allow the setting of the baudrate and parity for the rear port in the same way as for the
front port described above.
X Scrolling further to the right displays the applicable settings for the Modbus
communications protocol. Firstly is the address of the particular relay. Choose from
the values1 to 255 using S and T.
X Next is the Modbus response time. Choose from the range 0.01 to 10.00 seconds
using S and T.
X Set the Modbus dead time from the range 0.01 to 10.00s using S and T.
X Finally set the Modbus Force Relay Time from the range 0.1 to 60 seconds using
S and T.
Note that an understanding of the operation and requirements of Modbus RTU, as well
as the specific application, is required to decide on appropriate settings for these
parameters. If it is not intended to use Modbus in the applications, these settings can
be ignored.
34
Setting the Real-time clock
Adjust each of the three values of hours, minutes, and seconds using
S or T, and scroll between them using W and X.
X Scroll right to change to date. Adjust each of the four values of day of
the week, day, month, and year using S or T, and scroll between them
using W and X.
Use W and X to scroll through the following 2nd level menus, before using T to access the 3rd level screens:
Set the Icr/In (capacitor rated current–to-CT nominal current) ratio to a value within the
range 0.25 to 1.50 using W and X.
X Further scrolling to the right allows the setting of the other parameters for Elements 1 to 3 in the same way:
35
Set Element 4 Variables
In the same fashion as for Elements 1 to 3, the following Element 4 variables can be set:
36
Compensate for Star Unbalance
Compensation of the natural unbalance current can only be done after the relevant capacitor bank or filter circuit
is in service.
The display initially shows the magnitude and angle of the compensation vector. The
examples here show instances where the system is firstly uncompensated, and secondly a
typical screen for a compensated system.
X Scrolling right shows the calculated unbalance current, either in absolute terms if
uncompensated, or in relative terms, ΔIub, if compensated. To compensate the system
toggle the display to Yes with S or T and press .
After compensation, the compensation vector has the same magnitude as the initial measured fundamental
frequency unbalance current at the instant of compensation, but has the opposite polarity (i.e. is 180° out of
phase).
Immediately after compensation, ΔIub will always be the null vector.
However, after compensation any subsequent change in capacitance will cause. ΔIub to assume a non-zero
magnitude and some phase angle ranging from 0° to 360°. The magnitude of ΔIub is a measure of the change in
capacitance in any leg of the double star capacitor bank arrangement. The phase angle of ΔIub indicates the leg
in which the change in capacitance has occurred. Refer to figure 8 and 9 in Appendix 3 for further details on this.
X The next screen allows the user to clear the existing compensation from the system by
toggling the display to Yes with S or T and pressing . The display then reverts to the
previous screen.
The first screen allows the user to allocate any combination of the 5 output relays to a
vc>alarm signal. The relay being addressed is denoted by the cursor. Use S or T to
toggle between 0 (de-allocated) and 1 (allocated). Scroll between relays and subsequent
screens using W and X
By scrolling to the right the output relays can be allocated to the following signals in the same way:
37
Io>trip Io>>trip Ilub>start Ilub>trip Ilub>>trip B fail 1
B fail 2 B era Event_trip
X The next screen allows the user to select for each relay whether it is normally
energised (1) or de-energised (0) in the healthy state.
X Select for each relay whether it latches upon a trip, and would subsequently need to
be reset, or whether it resets automatically after the fault causing the trip has cleared.
X The next 5 screens show the internally generated checksums for each relay.
Performing a manual calculation of these checksums and comparing the two, provides
a double check that the relays have been allocated correctly. See Appendix 2 for more
details on this.
Use W and X to scroll through the following 2nd level menus, before using T to access the 3rd level screens:
Set the alarm threshold within the allowed range using S and T
X Next adjust the time-out value associated with the alarm threshold.
Further scrolling right will allow the user to adjust the low-set and high-set thresholds with their associated timers
for aIub, as well as all of the similar settings for bIub and cIub.
Revert to the 2nd level menus by pressing .
38
Set Other Functions
Using S or T, select between Remote Reset, Event Trip, or Disabled for the Digital input
function.
X Toggle between active high or low for the digital input using S or T.
X Select the Event:xt time-out value S and T. This is only relevant if the digital input
function has been set to Event.
X Using S or T, select between Only trip STARTS, Only ALARMS, STARTS and
ALARMS, or always off.
The display initially shows the magnitude and angle of the compensation vector. The
examples here show instances where the system is firstly uncompensated, and secondly a
typical screen for a compensated system.
X Scrolling right shows the calculated unbalance current, either in absolute terms if
uncompensated, or in relative terms, ΔIub, if compensated. To compensate the system
toggle the display to Yes with S or T and press .
After compensation, the compensation vector has the same magnitude as the initial measured fundamental
frequency unbalance current at the instant of compensation, but has the opposite polarity (i.e. is 180° out of
phase).
Immediately after compensation, the compensated current, ΔaIub, will always be the null vector.
However, after compensation any subsequent change in capacitance will cause .Iub to assume a non-zero
magnitude and some phase angle ranging from 0° to 360°. The magnitude of ΔaIub is a measure of the change
in capacitance in any leg of the double star capacitor bank arrangement. The phase angle of ΔaIub indicates the
leg in which the change in capacitance has occurred.
X The next screen allows the user to clear the existing compensation from the system by
toggling the display to Yes with S or T and pressing . The display then reverts to the
previous screen.
39
Output Relay Set-up - H-Bridge Mode
The first screen allows the user to allocate any combination of the 5 output relays to an
aIub alarm signal. The relay being addressed is denoted by the cursor. Use S or T to
toggle between 0 (de-allocated) and 1 (allocated). Scroll between relays and subsequent
screens using W and X
By scrolling to the right the output relays can be allocated to the following signals in the same way:
X The next screen allows the user to select for each relay whether it is normally
energised (1) or de-energised (0) in the healthy state.
X Select for each relay whether it latches upon a trip, and would subsequently need to
be reset, or whether it resets automatically after the fault causing the trip has cleared.
X The next 5 screens show the internally generated checksums for each relay.
Comparing these to manually calculated ones provides a double check that the relays
have been allocated correctly. See Appendix 2 for more details on this.
40
Operating the RLC04-B
The operation of the RLC04-B falls into three categories, Healthy condition, Fault (trip or alarm) condition, and
Information retrieval
Healthy Condition
The associated screens are shown alongside each other in the full listings of available screens below.
So for example, if the Time & Date screen has been scrolled to using S or T, pressing W or X will bring up the
Digital Input detail screen. Further use of W or X will display the other screens in the extended set.
Most of the screens show values measured or calculated by the relay and are fairly self-explanatory.
<
The displays show small indicators for each of the protective function thresholds (alarm: al ; undercurrent: ; low-
>
set: ; high-set: >>) where they have been set.
This not only allows the user to see which protective functions are set, but furthermore if the function is active the
associated indicator starts to blink.
If the relay is not measuring a signal or if the signal is below the suppression level the display will only show --%.
In both Normal and H-Bridge modes the Reference phase screen shows the fundamental component of Element
1.
If the Reference phase current falls below 10% of the nominal current In, then this has an impact on the way the
star point and H-bridge unbalance protection functions operate – see Section 3 – Functional Description for
details.
Again applicable for both modes, the last screen in the extended set (adjacent to the Date and Time) shows the
state of the digital input. The text reflects the function of the input as follows:
41
Normal Mode Displays
The available displays in Normal Mode are shown in the table below. The three values shown in each of the first
four standard set screens are the instantaneous values for the Elements 1, 2 and 3. In the extended set, the
maximum value of the three parameters is shown, along with the low set threshold.
Standard (S / T) Extended (W / X)
H-Bridge Displays
The available displays in H-Bridge Mode are shown in the table here:
Standard (S / T) Extended (W / X)
A typical display for a compensated system (indicated by the Δ) will look as follows:
The screen shows that the alarm, as well as the low set and high set trip thresholds have
been set, and that the actual unbalance current in the a-phase is 1%.
If the value would exceed the alarm threshold for the time set, the alarm indicator will start to blink. If the
unbalance current exceeds the low set threshold (10%), the low set trip indicator (>) would also start to blink,
while if the value would exceed the high set threshold, all three indicators (al and > and >>) would blink.
42
Default Display
Upon power up, or when in normal operation no scroll key has been pressed for one minute, the relay will revert
to the default display. Upon delivery, the default display for the relay in Normal Mode is the Element 1,2 and 3
repetitive peak capacitor voltage, vc screen, while for the H-Configuration mode the summary screen showing
the a-, b- and c-phase unbalance currents is the default display.
Any other of the standard or extended screens can be set as the default simply by pressing while that desired
screen is displayed. The relay will show a short message “New DEFAULT DISPLAY saved”.
Fault Condition
The Start LED lights on STARTS which will cause a subsequent trip; ALARMS are
Only trip STARTS
ignored
Only ALARMS The Start LED will flash on ALARMS; STARTS are ignored
The Start LED will flash for ALARMS and light up constantly on STARTS which will
STARTS + ALARMS
cause a subsequent trip
Always off The Start LED will never light.
Red LED: This indicates that a trip condition has occurred that has not yet been acknowledged. Only when all the
post trip fault annunciation screen displays have been acknowledged will this LED extinguish.
The magnitude of parameter causing the corresponding software trip signal at the instant of generation is
recorded, as well as the time taken from the moment the relevant trip threshold was exceeded, until the software
signal was generated. In case of protective functions which operate with values from Element 1, 2 and 3, the
post-trip display also shows the Element number in which the maximum or minimum of the parameter occurred
as well as the element(s) which have been above the threshold at the instant of trip.
In the case of the star-point and H-Bridge unbalance trip signals, the relevant phase angle of the unbalance
current is also recorded, to indicate in which leg of the capacitor bank, capacitor failure has occurred (Refer to
Figures 6 to 9 in Appendix 3).
43
Under normal circumstances, after a trip condition, an operator would assess and note the relevant information
from the post-trip annunciation screen, and then acknowledge (i.e. reset) the trip by pressing .
At this point, any other trip conditions that may have occurred after the first trip condition, will be displayed. Again
the user can acknowledge this indication, by pressing .
After all of the post-trip annunciation screens have been acknowledged, the display reverts to the normal default
operating screen.
After investigating and rectifying the fault condition, the operator would normally only then re-energize the tripped
circuit breaker. If, however, the tripped circuit breaker is re-energized before the post-trip screens have been
acknowledged, then the post-trip annunciation screens will continue to be displayed until they are acknowledged,
as previously detailed, after which the normal operation screen, will be displayed.
If a further fault condition were to occur, causing the circuit breaker to trip again, before the previous post-trip
screens have been acknowledged, then the previous fault trip data is replaced with the latest data.
It is only possible to acknowledge a trip once the fault has been cleared – the yellow
LED must be OFF, otherwise you will only be able to scroll through the post trip data.
M3-12 means that Element 3 attained the maximum amplitude at the instant of trip, while elements 1 and 2 were
also above the threshold setting.
Information Retrieval
44
This is an example of the first screen which indicates how many trips are in memory.
W and X toggle between the first screen and this screen which shows
exactly the when the trip history list was last cleared.
When either of the two screens above are being displayed, it is possible to clear the complete trip history by
pressing . The following is displayed:
Use the S or T to toggle the “No” to “Yes”. Then press to clear the Trip History list.
This is only possible if the correct password has been entered when accessing Menu Mode, or if no password
has been set. Alternatively the trip history can be cleared from within the Parameter Setup menu.
T Scrolling down from the Trip History screen, the display shows trip number screen.
This indicates the time and date of the 1st (N01) trip of the first trip session (G01).
X Scrolling right will reveal the details of the trip over three screens. The
first shows the cause of the trip and its magnitude, which elements were
affected, and the time it took to trip.
The second screen shows the relevant values for all three elements.
The third screen shows which relays were tripped.
X Scrolling right once more will return to the trip number screen
TScrolling down further will reveal all of the trip number screens in succession, from which the details can be
discovered using W and X.
When all of the desired TRIP HISTORY list data has been viewed, press to revert to the main menu.
Status Information
(Optional Password Protection – partially)
This menu allows the user to obtain certain information from the relay such as:
45
The first screen displays a moving message of maximum length 100 characters, which can
be downloaded from a PC running the dedicated communication software.
X This screen enables the user to check that the digital input is functional. When a voltage
is applied to the digital input terminals, the above display should change from Low to High.
X This screen enables the user to check if any of the output relays are energized.
X These two screens (Front / Rear) enable the user to check if the serial data ports are
functional. When data is received or transmitted, the respective part of the communication
display should change from OFF to ON.
X This screen allows user to check how many times the set-up has been saved on this
unit.
Additionally by pressing S or T the date of the last save of set-up
information can be accessed.
The screens which follow are operating mode dependant. They show the trip counters for the individual trip functions
together with the time stamp information when the counter has been last cleared.
X The next 20 screens will show the user similar information about the following trip functions:
X This indicates that the aIub alarm signal has been generated 12 times since the last
clearance of the counter.
S or T toggle between the above screen and this which shows the date of
the last clearance of the counter.
X The next 9 screens will show the user similar information about the following trip functions:
46
In order to reset the individual counters perform the following steps:
Select the desired counter using W orX. Press the to select the counter.
Use S or T to toggle between No and Yes, then press to clear the counter. The time
stamp information will be updated accordingly. If No is selected the relay will revert to the
Access STATUS INFORMATION menu.
47
Testing and Troubleshooting
Automatic Self-testing
On application of the auxiliary supply voltage, and at regular intervals in the background during normal operation,
the RLC04-B automatically performs a number of diagnostic checks of the:
o EEPROM
o Calibration factors
o EPROM
o RAM
o Processors
Any errors detected will cause the relay to suspend all protective functions, de-energize the self-supervision relay
and display an error message as detailed below:
48
Performing the following diagnostic test on the output relays, while the associated circuit
breaker is energized may cause the circuit breaker to trip, with consequent system
disruption. Therefore the greatest care should be exercised when performing this function
under live conditions.
X To perform the output relay tests, press S or T to toggle the “No” to “Yes”, then press
.
To skip this test press X to go to the next screen.
If Yes had been selected a screen as shown below will be displayed:
Press W or X to select the desired relay to test, then press S or T to toggle
the “No” to “Yes”, followed by . The selected output relay will then energize
for 1 second. Repeat for each relay.
Press W or X until this screen is displayed. Press S or T to toggle the “No”
to “Yes”, followed by . The first screen in the DIAGNOSTIC TEST MENU is
now displayed again.
If “No” is selected at the “Test Relays?” screen, pressing X displays:
X The next two screens supply hardware information which may be necessary in future to
ensure compatibility with firmware upgrades.
Injection Testing
The RLC04-B Relay is a complex device with many sophisticated protective functions. It is beyond the scope of
this manual to fully detail how too comprehensively injection test the RLC04-B. However the following points
should be noted.
Ideally, a 3 phase secondary injection test set, with the ability to inject not only mains frequency currents but also
complex 3 phase waveforms (including harmonic currents) is required to properly test the RLC04-B.
In this way one can properly test and confirm the peak repetitive overvoltage protective functions, the rms
thermal overcurrent protective functions, and the mains frequency current protective functions including the star
unbalance, line unbalance, earth fault, fundamental frequency over- and under-current, breaker fail and breaker
enable timer.
Such a test set is available from Strike Technologies.
It is possible to perform tests on the relay with only a single phase current injection test set. In this case the user
should preferably test each element separately, one protective function at a time, with all other protective
functions disabled.
If testing several protective functions and/or elements simultaneously, the following must be kept in mind:
The earth fault current Io is derived mathematically as the vector summation of the phase currents of elements 1,
2 and 3. Therefore the earth fault protective function should be tested by injecting 1/3 of the desired earth fault
current into elements 1, 2 and 3 connected in series. This will generally avoid the other protective functions,
including the line unbalance current protective function, from operating before the earth fault protective function.
In order to test the line unbalance current function, inject a low magnitude single phase current into elements 1
and 2 (or elements 2 and 3) connected in series but with opposite polarities. This will avoid the earth fault
protective function from operating.
In order to test the overcurrent, undercurrent and thermal current, protective functions of elements 1, 2 and 3,
disable the earth fault protective function and inject a single phase current into elements 1, 2 and 3 connected in
series. This will avoid both the earth fault and the line unbalance current protective functions from operating.
Alternatively disable both the earth fault and the line unbalance current protection functions. This will enable
elements 1, 2 and 3 to be tested individually, without all 3 elements connected in series.
49
Without the ability to inject harmonic currents superimposed onto the fundamental current, the repetitive peak
overvoltage protective function of element 1, 2 and 3 can be easily tested by disabling all other protective
functions, and injecting a sinusoidal current into element 1, 2 or 3. It is suggested that Icr/In = 1 and vc>/vcr = 1,1
should be set. In this case, when a sinusoidal current equal to In is injected (1A or 5A rms) then the calculated
peak repetitive voltage vc/vcr should be 1p.u. The vc>starter should operate for injected currents above 1,1In.
Trip times for currents above the threshold (1,1In) may be checked against the inverse time curve of Figure 3 in
Appendix 3.
Trouble Shooting
Before attempting to trouble-shoot the equipment, the user should thoroughly understand this entire manual, and
should have a prior knowledge of power system protection, power system measurements, and power system
safety procedures. The user should study carefully the applicable sections of this manual, taking particular note
of WARNINGS, CAUTIONS and NOTES included for personnel and equipment protection.
A three or single phase primary or secondary injection test set to enable injection of the CT nominal rated
secondary currents into the RLC04-B Relay measuring elements.
Due to the nature of the RLC04-B Relay, it is not recommended that the user should attempt repairs other than
the removal and replacement of the draw-out unit which houses all electrical and electronic parts.
If erroneous, inconsistent or nonsensical data is displayed on the RLC04-B, or if erratic faulty operation is
experienced by the user, check the various parameters set in the relay and verify that the relay is set up
correctly.
If the user has performed all the above checks, and is satisfied that no external or setting-up problems exist
which are causing the malfunctions experienced, then the relay should be returned to Strike Technologies
together with a fault report, documenting the details of the problem experienced, the configuration & set-up, as
well as installation details.
The user may elect to send only the draw-out unit without the fixed case. If so then special attention should be
paid to the handling requirements, as detailed in the Installation and Commissioning section.
50
Appendix 1
52
Iub_al:xt Alarm time-out setting for Iub
Iub_alarm Software signal indicating that Iub has exceeded Iub_al for the time Iub_al:xt set
Iub> Iub low-set overcurrent threshold
Iub>:xt Low-set time-out setting for the Iub timer
Iub>start Software signal indicating that (Δ)Iub has exceeded Iub> and the Iub timer is running
Iub>trip Software signal indicating that (Δ)Iub has exceeded Iub> for the time Iub>:xt set
Iub>> Iub high-set overcurrent threshold
Iub>>:xt High-set time-out setting for the Iub timer
Iub>>trip Software signal indicating that (Δ)Iub has exceeded Iub>> for the time Iub>>:xt set
Ilub Calculated fundamental frequency line unbalance current
Ilub> Ilub low-set overcurrent threshold
Ilub>:xt Low-set time-out setting for the Ilub timer
Ilub>start Software signal indicating that Ilub has exceeded Ilub>, and that the Ilub timer is running
Ilub>trip Software signal indicating that Ilub has exceeded Ilub> for the time Ilub>:xt set
Ilub>> Ilub high-set overcurrent threshold
Ilub>>:xt High-set time-out setting for the Ilub timer
Ilub>>trip Software signal indicating that Ilub has exceeded Ilub>> for the time Ilub>>:xt set
Io Calculated fundamental frequency earth fault current
Io> Io low-set overcurrent threshold
Io>:xt Low-set time-out setting for the Io timer
Io>start Software signal indicating that Io has exceeded Io>, and that the Io timer is running
Io>trip Software signal indicating that Io has exceeded Io> for the time Io>:xt set
Io>> Io high-set overcurrent threshold
Io>>:xt High-set time-out setting for the Io timer
Io>>trip Software signal indicating that Io has exceeded Io>> for the time Io>>:xt set
Bon Input signal indicating that the circuit breaker of the capacitor bank / harmonic filter circuit is on
Signal indicating that when a trip occurred, the Bfail1 release function had not been fulfilled within the Bfail1:xt
Bfail1
time, indicating a failure of the circuit breaker to open
Bfail1 The function which stops the Bfail1 timer, selectable from: Ifund<10%In; Dig-Input (logic “1“ to “0“); Ifund AND
release Input; Ifund OR Input
Bfail1:xt Time-out setting associated with Bfail1 logic
Software signal indicating that the fundamental frequency current remained above the undercurrent threshold for
Bfail2 the Bfail2:xt time, while the digital input (Breaker-Bon) signalled a switching off (logic “1“ to “0“) - indicating the
failure of the circuit breaker to interrupt the capacitor bank / harmonic filter circuit current.
Bfail2:xt Time-out setting associated with Bfail2 logic
Software signal that can be used to inhibit the re-energizing of the banks’ circuit breaker for a definite time after
the Bena trigger signal has become active. Bena output signal (Breaker inhibit) is normally at logic “0“ (low) and
Bena
goes to logic “1“ (high) when the bank is switched off, and reverts to logic “0“ (low) the definite time Bena:xt
thereafter.
Bena:xt Timer setting associated with the Bena logic
A trip session starts from the first active trip condition until the last trip condition has been cleared. The visible
observation of this session is defined by the time when the trip LED lights up to the time when the alarm LED
Trip session goes off. During this time S or T may be used to scroll between the different trip messages. may be used to
acknowledge trips for which the cause of the trip has fallen below the trip threshold. In case of an Ith trip, the trip
can be acknowledged as soon as the Irms has fallen below the Ith trip threshold, however the trip output function
will only be reset once Ith has fallen below the Ith trip threshold
53
Table 3: Nomenclature & Definitions for H-Bridge Mode
Symbol Definition
1/2/3/4 Element 1/2/3/4
In Current transformer nominal primary current.
a/b/cIub Calculated uncompensated fundamental frequency a/b/c-phase unbalance current
a/b/cIub_al/In a/b/cIub alarm threshold per unit of In
a/b/cIub_al:xt Alarm time-out setting for the a/b/cIub timer
a/b/cIub_alarm Software signal indicating that a/b/cIub has exceeded a/b/cIub_al for the time a/b/cIub_al:xt set
a/b/cIub>/In a/b/cIub low-set threshold per unit of In
a/b/cIub>:xt Low-set time-out setting for the a/b/cIub timer
a/b/cIub>start Software signal indicating that ( ∆)a/b/cIub has exceeded a/b/cIub>, and that the a/b/cIub timer is running
a/b/cIub>trip Software signal indicating that ( ∆)a/b/cIub has exceeded a/b/cIub> for the time a/b/cIub>:xt set
a/b/cIub>>/In a/b/cIub high-set threshold per unit of In
a/b/cIub>>:xt High-set time-out setting for the a/b/cIub timer
a/b/cIub>>trip Software signal indicating that ( ∆)a/b/cIub has exceeded a/b/cIub>> for the time a/b/cIub>>:xt set
∆a/b/cIub Compensated fundamental frequency rms a/b/c -phase unbalance current, i.e. the change in fundamental
frequency rms current from that at the instant of compensation
54
Table 4: General Characteristics
Applicable standard IEC 60255
Operating temperature -10 to +55 °C to IEC 60068-2-2
Storage temperature range -20 to +70 °C to IEC 60068-2-2
Humidity 4 days, 95% RH, with temperature cycled between +25°C and + 45°C, to IEC 60068-2-3
Enclosure degree of protection IP50 to IEC 600529
Shock: 15g, 3 pulses per direction, per axis. (total 18 times).
Shock and bump Bump: 10g, 1000 pulses per direction, per axis (total 6000 times).
To IEC 60255-21-2
Vibration 9, 8ms-² (1g) constant frequency from 10 to 500 Hz per axis. To IEC 60255-21-1
2 kV rms 50 Hz for 1 minute, from all terminals to case (earth), and between terminals of
independent circuits.
Power frequency voltage withstand
1.5 kV rms across open contacts of output relays.
To IEC 60255-5
5 kV peak, 1.2/50 µs waveshape, 0.5 J energy content, 10 shots in each polarity, between all
Impulse voltage withstand terminals and case (earth), and between terminals of independent circuits.
To IEC 60255-5
Insulation resistance 50 MΩ minimum at 500 V dc, to IEC 60255-5
2.5 kV peak between independent circuits, and to case (earth).
Immunity to high frequency disturbances
1 kV peak across terminals of the same circuit.
(1MHz burst disturbance test)
To IEC 60255-22-1
8 kV discharge in air with cover in place.
Immunity to electrostatic discharges
4 kV point contact discharge with cover removed.
(Electrostatic discharge test)
To IEC 60255-22-2 and EN 50082-2
Immunity to fast transient bursts (Fast
Class 4 (4 kV). To IEC 60255-22-4 and EN 50082-2
transient burst test)
10 V / m from 27 to 500MHz, to IEC 60255-22-3
Immunity to high frequency electromagnetic
10 V, 80% AM, from 150 to 80 MHz as well as
fields
10 V / m, 80% AM, from 80 to 1000 MHz, to EN 50082-2
Conducted disturbances induced by radio-
To EN 50081
frequency fields immunity test
Immunity to high frequency electromagnetic
field (Pulse modulated, simulation of the To ENV 50204
effect of cell phones)
Conducted emissions To EN 50081-2, from 150 kHz to 30 MHz.
Radiated emissions To EN 50081-2, from 30 kHz to 1000 MHz.
Nett Mass 3 kg
Overall dimensions 103(w) x 177(h) x 248(d)
The power supply inputs of the RLC04-B are protected by MOV´s. Therefore it is not
possible to perform the power frequency and the impulse voltage withstand test on
these terminals on the commercial unit without causing damage!
55
Table 5: Technical Specifications
56
Table 6: Settable Parameters and Ranges – Normal Mode
Parameter Setting Range Resolution Preset Value
Icr/In 0,25 to 1,50 0,01 1.00
vc>al/vcr 0,80 to 1,50 // N/A 0,01 N/A
vc>al:xt 0,1 to 3600 s 0,1 s 0,1 s
vc>/vcr 0,80 to 1,50 // N/A 0,01 N/A
vc>>/vcr 0,80 to 10,0 // N/A 0,01 N/A
vc>>:xt 0,03 to 10,0 s 0,01 s 0,03 s
vc>reset:xt 1 s to 3600 s 1s 1s
Ith>/In 0,25 to 1,50 // N/A 0,01 N/A
Ith>:xt 0 to 600 s // Alarm 0,01s 0,0 s
Ith>>/In 0,25 to 1,50 // N/A 0,01 N/A
Ith>>:xt 0 to 60 s 0,01 s 0,0 s
τ 0,5 to 7200 s 0,1 s 0,5 s
I1>/In 0,25 to 1,50 // N/A 0,01 N/A
I1>:xt 0,1 to 1200 s 0,1 s 0,1 s
I1>>/In 0,2 to 10,0 // N/A 0,1 N/A
I1>>:xt 0,05 to 10,0 s 0,01 s 0,05 s
I1</In 0,05 to 1,00 // N/A 0,01 N/A
I1<:xt 0,1 to 10,0 s 0,1 s 0,1 s
Irms>/In 0,25 to 1,50 // N/A 0,01 N/A
Irms>:xt 0,1 to 1200 s 0,1 s 0,1 s
Irms>>/In 0,2 to 10,0 // N/A 0,1 N/A
Irms>>:xt 0,03 to 10,0 s 0,01s 0,03 s
Iub_al/In 0,01 to 2,00 // N/A 0,01 N/A
Iub_al:xt 0,1 to 600 s 0,1s 0,1 s
Iub>/In 0,01 to 2,00 // N/A 0,01 N/A
Iub>:xt 0,1 s to 14400 s 0,1 s 0,1 s
Iub>>/In 0,01 to 2,00 // N/A 0,01 N/A
Iub>>:xt 0,05 to 60 s 0,01 s 0,05 s
Io>/In 0,05 to 1,00 // N/A 0,01 N/A
Io>:xt 0,1 to 60 s 0,01 s 0,1 s
Io>>/In 0,05 to 10,0 // N/A 0,01 N/A
Io>>:xt 0,05 to 10,0 s 0,01 s 0,05 s
Ilub>/In 0,01 to 1,00 // N/A 0,01 N/A
Ilub>:xt 0,1 to 60 s 0,1 s 0,1 s
Ilub>>/In 0,01 to 1,00 // N/A 0,01 N/A
Ilub>>:xt 0,05 to 10,0 s 0,01 s 0,05 s
Function of Digital Breaker-Bon // Remote Reset // Event Trip // Disabled Disabled
Input
Event:xt 0,03 to 600 s 0,01 s 0,03 s
Bfail1:xt 0,01 to 2,0 s // N/A 0,01 s N/A
Bfail1 released: Ifund<10%In // Dig-Input // Ifund AND Input // Ifund OR Ifund<10%In
Input
Bfail2:xt 0,01 to 2,0 s // N/A 0,01 s N/A
Bena:xt 1 to 1200 s // N/A 1s N/A
Bena trigger by: Ifund<10%In // Dig-Input // Ifund AND Input // Ifund OR Ifund<10%In
Input
Start LED shows: Only trip STARTS // Only ALARMS // STARTS + STARTS +
ALARMS // Always off ALARMS
57
Table 7 – Settable Parameters and Ranges – H-Bridge Mode
Parameter Setting Range Resolution Preset Values
aIub_al/In 0,01 to 2,00 // N/A 0,01 N/A
aIub_al:xt 0,1 to 600 s 0,1 s 0,1 s
aIub>/In 0,01 to 2,00 // N/A 0,01 N/A
aIub>:xt 1 s to 240 min 1s 1s
aIub>>/In 0,05 to 2,00 // N/A 0,01 N/A
aIub>>:xt 0,0 to 60 s 0,1 s 0,1 s
bIub_al/In 0,01 to 2,00 // N/A 0,01 0,01
bIub_al:xt 0,1 to 600 s 0,1 s 0,1 s
bIub>/In 0,01 to 2,00 // N/A 0,01 0,01
bIub>:xt 1 s to 240 min 1s 1s
bIub>>/In 0,05 to 2,00 // N/A 0,01 0,01
bIub>>:xt 0,0 to 60 s 0,1 s 0,1 s
cIub_al/In 0,01 to 2,00 // N/A 0,01 N/A
cIub_al:xt 0,1 to 600 s 0,1 s 0,1 s
cIub>/In 0,01 to 2,00 // N/A 0,01 N/A
cIub>:xt 1 s to 240 min 1s 1s
cIub>>/In 0,05 to 2,00 // N/A 0,01 N/A
cIub>>:xt 0,0 to 60 s 0,1 s 0,1 s
Function of Digital Remote Reset // Event Trip // Disabled Disabled
Input
Event:xt 0,03 to 600 s 0,01 s 0,03 s
Start LED shows: Only trip STARTS // Only ALARMS // STARTS +
STARTS + ALARMS // Always off ALARMS
58
Appendix 2
2 2 D 4 A 0 1 3 Checksum
MSB LS B
1 0 0 0 1 0 1 1 1 0 0 1 0 0 1 0 1 0 0 0 0 0 0 0 0 1 0 0 1 1
Bfail1
Bfail2
Bena
Latch
vc>alarm
vc>start
vc>trip
vc>>trip
I1>start
I1>trip
I1>>trip
Irms>start
Irms>trip
Irms>>trip
Ith>start
Ith>trip
Ith>>trip
I1<trip
Iub_alarm
Iub>start
Iub>trip
Iub>>trip
Io>start
Io>trip
Io>>trip
Ilub>start
Ilub>trip
Ilub>>trip
Event_trip
Energize
MSB LSB
1 1 0 0 0 1 0 0 0 1 0 0 0 1 1
Latch
aIub_alarm
aIub>start
aIub>trip
aIub>>trip
bIub_alarm
bIub>start
bIub>trip
bIub>>trip
cIub_alarm
cIub>start
cIub>trip
cIub>>trip
Event_trip
Energize
59
Example 2: RLC04-B Setting Calculations
I1 385A I5 30 A
I2 30A I7 20 A
Rated Currents 20.6m H
I3 90A I11 10 A
I4 25A I13 5A 400Ars s
13
Irms
∑ ( In )
n =1
2
= 400A
37.19 MVAr
a t 45kV
60
Settings
Element 1, 2, 3 variables Bena:xt = 600 s (18)
Icr/In = 477/500=0,95 (1) Function selected for Breaker-Bon (19)
vc>/vcr = 1,1 (2) digital input:
vc>>/vcr = 3,0 (3) Bena triggered by Dig Input (20)
vc>>:xt = 0s (4) Element 4 variables
vc>reset:xt = 30 s (5) Iub_al/In = 4/20=0,2 (21)
Ith>/In = 395/500=0,79 (6) Iub_al:xt = 3 (22)
Ith>:xt = N/A (7) Iub>/In = 8/20=0,4 (23)
Ith>>/In = 410/500 = 0,82 (8) Iub>:xt = 10 min (24)
Ith>>:xt = 0s (9) Iub>>/In = 12/20=0,6 (25)
t = 1200 s (10) Iub>>:xt = 1s (26)
I1>/In = 1,075·350/500=0,81 (11) Element 5 variables
I1>:xt = 600 s (12) Io>/In = 0,2·350/500=0,14 (27)
I1>>/In = 1,5·350/500=1,05 (13) Io>:xt = 0,1 s (28)
I1>>:xt = 0s (14) Io>>/In = N/A (29)
I1</In = 0,2·350/500=0,14 (15) Io>>:xt = 0s (30)
I1<:xt = 0,2 s (16) Ilub>/In = 0,05·350/500=0,04 (31)
Other variables Ilub>:xt = 2s (32)
Bfail1:xt = 0,2 s (17) Ilub>>/In = 0,1·350/500=0,07 (33)
Bfail2:xt = 0,1 s (17) Ilub>>:xt = 0,2 s (34)
Notes on Settings
1. Capacitor rated current in p.u. of line CT primary current.
2. Capacitors made to IEC can withstand 110% of rated voltage for extended periods of time.
3. With reference to Figure 3 in Appendix 3, it can be seen that for vc/vcr greater than 3,0 the peak repetitive
overvoltage withstand curve is undefined and therefore for capacitor overvoltages above this value it is
considered necessary to trip with a definite time delay.
4. The time delay should be set as low as possible, preferably with no intentional delay.
5. Refer to the figure under Programmable vc>reset Timer in the Functional Description section to see the
effect of vc>reset:xt.
6. The low set thermal trip threshold is set in this case slightly below the continuous current rating, as it is
assumed that the total current includes some safety margins.
7. The associated timer is set to N/A (disabled) which means that only the Ith>start signal will be generated in
case of an overload and no subsequent trip signal Ith>trip is output.
8. The high set thermal overcurrent threshold is set slightly above the max. continuous rms current rating of the
reactor. If this is exceeded the bank must be disconnected.
61
10. Refer to Example 3 in Appendix 2 for some guidance of the heating/cooling time constant of air-core filter
reactors. The time constant is the time taken for the reactors to reach 63% of their final temperature, for a
step change in current from 0 to 100%.
11. For a system having a maximum system voltage of 105% of nominal, a low set fundamental frequency
overvoltage/overcurrent limit of 107,5% is considered appropriate. Above this value the associated definite
timer will start timing out.
12. A value of 600s for this definite timer is considered appropriate to allow any automatic tap-changers to
operate in the case of extended fundamental frequency system overvoltages (which in time causes
fundamental frequency overcurrents in the capacitor/filter circuit).
13. A fundamental frequency overcurrent above 150% of nominal would indicate a catastrophic failure of some
kind requiring immediate tripping.
14. Therefore the associated definite time delay is set to 0 (no intentional delay).
16. The undercurrent definite timer is set as 0,2s or any appropriate low value to avoid spurious trip outs.
17. The breaker fail timer is set as 0,2s for Bfail1 and 0,1s for Bfail2 or any appropriate low value to avoid
spurious breaker fail signal output.
18. The breaker enable timer is set to enable breaker re-energization 600s (10min) after de-energization to allow
the capacitor to discharge before switching on again.
19. Setting the digital input to Breaker-Bon allows the breaker enable re-switching timer and the undercurrent
protection function to be used.
20. This parameter is set to Dig In so that the Bena function is triggered by the digital input.
21. The star point unbalance alarm level is to be provided by the capacitor unit and bank designer / manufacturer
as it is determined by the specific capacitor unit and capacitor bank design.
22. The definite timer associated with the above should be set to a reasonable value to avoid spurious alarms
due to inrush or other short time operating conditions.
23. The star point unbalance low set trip current is to be provided by the capacitor unit and bank
designer/manufacturer.
24. The definite timer associated with the above is set as 10 min as informed by the capacitor unit / bank
manufacturer.
25. The star point unbalance high set trip current is to be provided by the capacitor unit and bank designer /
manufacturer.
26. The definite timer associated with the above is set as 1 s as informed by the capacitor unit / bank
manufacturer. In addition, this timer should not be set less than 1s due to the response time of the calculation
62
of the phase angle of the unbalance current, if the phase angle of this unbalance current is of interest to the
user after a trip out.
27. The fundamental frequency earth fault threshold is set to any suitably low value below the expected earth
fault current (as limited by the system and earth fault zero sequence impedance.
28. The definite time delay is set to 0,1 (no intentional delay).
29. Because the low set earth fault threshold definite time delay is set to 0,1 the high-set threshold is disabled.
30. Because the high-set threshold is disabled, the timer setting is irrelevant.
31. The low-set line unbalance current threshold should be set as low as possible whilst avoiding spurious trip
outs due to normal system line voltage unbalance. A line unbalance current of 5% of nominal capacitor
current is considered suitable.
32. The definite timer associated with the above is set at 2s to avoid trip out on short term unbalance
disturbances.
33. The high-set line unbalance current threshold is set as 10% of nominal capacitor current.
34. The definite time associated with the above is set as 0,2s
63
Example 3: Calculation of the Reactor Heating and Cooling Time Constant (τ)
The correct heating and cooling time constant of a damping or filter reactor should normally be obtained from the
reactor manufacturer.
τ = C1 * m / A
Where:
C1 Constant of convection and radiation and heat capacity
C1=100 for single layer coils
C1 = 76 for multi layer coils
m Mass of winding (Aluminium and insulation) [kg]
A Surface for convection and radiation [m²]
⎛ D1 + D 2 ⎞
For double – layer coil : A = ⎜ ⎟ * Π * Hw * 2,5
⎝ 2 ⎠ Hw
⎛ D1 + D 2 ⎞
For n – layer coil : A = ⎜ ⎟ * Π * Hw * n D2
⎝ 2 ⎠
64
Appendix 3
83,9
78,5
176,8
78,5
83,9
10 29 208
150,9
Side view
65
Figure 2: Schematic Diagram and Terminal Numbering
66
3
2 .5
vc/v cr (p u )
V C > /V C R = 1 .5
1 .5
Figure 3: Repetitive Peak Overvoltage vs. Trip Time Curves
V C > /V C R = 1 .2 5
V C > /V C R = 1 .1
V C > /V C R = 1 .0
1
V C > /V C R =0 .9
V C > /V C R = 0 .8
-1 0 1 2 3
10 10 10 10 10
Tim e (s )
.
67
Figure 4: Thermal Trip Time Curves
For various prior thermal loading conditions
2.5
(seconds)
Trip times for t =1
1.5
1
Prior
Thermal
Loading:
0,0 . Ith>
0.5
0,70 . Ith>
0,85 . Ith>
0,80 . Ith>
0,90 . Ith>
0 0,95 . Ith>
1 1.5 2 2.5 3 3.5
Overload current : I / Ith> (pu)
68
Figure 5: Typical Application Examples
Normal Mode
Legend:
L1 = Filter or Damping Reactor C1 = Capacitor Bank R1 = Damping Resistor
69
Figure 6: Typical Wiring Diagram For A Double Star Capacitor / Filter Bank
70
Figure 7: Element Failure in a Double Star Connected Capacitor Bank
71
Figure 8: Typical Wiring Diagram for an H-Bridge Capacitor / Filter Bank
72
Figure 9: Element Failure in an H-Bridge Connected Capacitor Bank
a2 b1 b2 c1 c2
a1
a4 b3 b4 c3 c4
a3 c b
73
Figure 10: Output Relay 1 to 5 Configuration
74
Strike Technologies
Co. Reg No: 1979/00174407 VAT No: 4200116657
Gauteng Office
P O Box 1810
Halfway House
1685
19 Mansell Road
Killarney Gardens
Killarney
7440
Durban Branch
4 Walter Place
Mayville
4091
P O Box 30167
Mayville
4058
www.strike.co.za
75