Table 8.7.2.2.1: TABLE 8.7.2.2.1 Protection Areas and Maximum Spacing (Standard Sidewall Spray
Table 8.7.2.2.1: TABLE 8.7.2.2.1 Protection Areas and Maximum Spacing (Standard Sidewall Spray
Table 8.7.2.2.1: TABLE 8.7.2.2.1 Protection Areas and Maximum Spacing (Standard Sidewall Spray
TABLE 8.7.2.2.1 Protection Areas and Maximum Spacing (Standard Sidewall Spray
Sprinkler)
Maximum distance 14 ft 14 ft 10 ft 10 ft
along the wall (S)
Maximum room 12 ft 14 ft 10 ft 10 ft
width (L)
Maximum protection 120 ft2 196 ft2 80 ft2 100 ft2
area
8.7.2.2.2 In any case, the maximum area of coverage of a sprinkler shall not exceed 196 ft2
(18.2 m2).
Protection areas for sidewall sprinklers differ from those of standard spray upright and pen- 䊴 FAQ
dent sprinklers. Because of the characteristic horizontal or sideways travel of the sprinkler Why are standard sidewall
discharge, the water spray pattern of sidewall sprinklers has a greater tendency of being ob- spray sprinklers limited to a
maximum of 196 ft2 (18.2 m2)?
structed or otherwise impacted by furniture and other objects near the floor. The discharge of
standard spray sprinklers is not normally as adversely affected by furniture and other objects
on the floor. In addition, the discharge patterns of sidewall spray sprinklers are less uniform
than those of standard spray sprinklers.
Table 8.7.2.2.1 indicates the maximum allowable protection areas. Table 8.7.2.2.1 also
indicates sprinkler protection areas that are not affected by the building construction above
the ceiling. The sprinkler system is intended to control the fire below the ceiling if properly
designed and installed. The 2010 edition of NFPA 13 revised the column headings to clarify
that only the combustibility of the exposed surfaces is considered when determining the max-
imum allowable distance between sprinklers and the maximum sprinkler protection area.
Paragraph 8.15.1.2 identifies the concealed spaces above ceilings that are not required to be
protected with sprinklers.
8.7.3.1.4 Sidewall spray sprinklers shall not be installed back-to-back without being sepa-
rated by a continuous lintel or soffit.
FAQ 䊳 The use of a lintel or soffit is necessary to ensure that the sprinkler closest to the fire operates
Why are lintels or soffits and to minimize the possibility of sprinklers on both sides of the lintel operating unnecessar-
required for back-to-back ily. The baffle also serves to prevent the discharge pattern of the operating sprinkler from im-
installations?
pinging on the operating element of an adjacent sprinkler. The baffle is an important feature,
because sidewall sprinklers are actually designed to discharge a portion of their spray pattern
behind the sprinkler.
8.7.3.1.5 Where sidewall spray sprinklers are installed on two opposite walls or sides of bays,
the maximum width of the room or bay shall be permitted to be up to 24 ft (7.32 m) for light
hazard occupancy or 20 ft (6.1 m) for ordinary hazard occupancy, with spacing as required by
Table 8.7.2.2.1.
Due to the spacing limitations of sidewall sprinklers, only certain size rooms can be effec-
tively protected. Paragraph 8.7.3.1.5 permits sidewall sprinklers to be used in larger rooms
under certain conditions, including a maximum room width dimension and the use of two
lines of sprinklers on opposite walls. The maximum room width allowed for light hazard oc-
cupancies when standard sidewall sprinklers are located on opposite walls was reduced from
30 ft (9.1 m) to 24 ft (7.32 m) beginning with the 1996 edition of NFPA 13. Extended cover-
age sidewall sprinklers provide better coverage for wide rooms and should be used for rooms
over 24 ft (7.32 m) wide.
8.7.3.1.6 Sidewall spray sprinklers shall be permitted to be installed on opposing or adjacent
walls, provided no sprinkler is located within the maximum protection area of another sprin-
kler.
Testing has determined the minimum required distance to prevent cold soldering from an ad-
jacent sidewall sprinkler when both sprinklers are located along the same wall. However, no
testing has been done to determine the minimum distance when sprinklers are located on op-
posite or adjacent walls (see 8.7.3.1.6). Placing sidewall sprinklers outside the protection area
of the adjacent sprinklers is probably conservative but eliminates the potential for the dis-
charge from one sprinkler wetting the thermal element of another.
8.7.3.1.7 Where sidewall standard spray sprinklers are installed to protect areas below over-
head doors within ordinary hazard occupancy spaces or rooms, protection area and maximum
sprinkler spacing for light hazard as specified in Table 8.7.2.2.1 shall be permitted under the
overhead doors.
Sprinkler protection is required under overhead doors so that protection is provided when the
doors are open and the ceiling sprinklers are obstructed. In ordinary hazard areas, this provi-
sion permits larger doors to be protected by a single sidewall sprinkler, reducing the installa-
tion costs while not significantly impacting the protection of the space.
8.7.3.2 Maximum Distance from Walls. The distance from sprinklers to the end walls shall
not exceed one-half of the allowable distance permitted between sprinklers as indicated in
Table 8.7.2.2.1.
8.7.3.3 Minimum Distance from Walls.
8.7.3.3.1 Sprinklers shall be located a minimum of 4 in. (102 mm) from an end wall.
8.7.3.3.2 The distance from the wall to the sprinkler shall be measured perpendicular to the
wall.
The dead-air space described in the commentary following 8.6.3.3 can also have a detrimen-
tal effect on sidewall sprinklers. Exhibit 8.27 shows the correct placement of a sidewall sprin-
kler adjacent to an end wall.
Sidewall
sprinkler
Wall
Plan View
8.7.3.4 Minimum Distance Between Sprinklers. Sprinklers shall be spaced not less than
6 ft (1.8 m) on center unless required by 8.7.4.1.3.1.
The reference to 8.7.4.1.3.1 clarifies that the minimum distance rule does not apply to pen-
dent sprinklers installed immediately adjacent to sidewall sprinklers under soffits deeper than
8 in. (203 mm).
8.7.4 Deflector Position from Ceilings and Walls (Standard Sidewall Spray
Sprinklers).
8.7.4.1 Distance Below Ceilings and from Walls.
8.7.4.1.1 Ceilings.
8.7.4.1.1.1 Unless the requirements of 8.7.4.1.1.2 are met, sidewall sprinkler deflectors shall
be located not more than 6 in. (152 mm) or less than 4 in. (102 mm) from ceilings.
8.7.4.1.1.2 Horizontal sidewall sprinklers shall be permitted to be located in a zone 6 in. to
12 in. (152 mm to 305 mm) or 12 in. to 18 in. (305 mm to 457 mm) below noncombustible
and limited-combustible ceilings where listed for such use.
Sidewall sprinklers should not be located in the dead-air space at the junction of the ceiling
and the wall (see 8.7.4.1.1.2). The desirable sprinkler location is 4 in. to 6 in. (102 mm to 152
mm) from the ceiling to optimize performance. As the sprinkler is lowered to more than 6 in.
(152 mm) from the ceiling, it is likely to take longer to operate. In addition, the ceiling has
an impact on the discharge of a sidewall sprinkler, causing the spray pattern to change as the
sprinkler is lowered. The sprinkler may be lowered as much as 18 in. (457 mm) when specif-
ically tested and listed for such use.
8.7.4.1.2 Walls.
8.7.4.1.2.1 Vertical sidewall sprinkler deflectors shall be located not more than 6 in. (152
mm) or less than 4 in. (102 mm) from the wall from which they are projecting.
8.7.4.1.2.2 Horizontal sidewall sprinkler deflectors shall be located no more than 6 in. (152
mm), and are permitted to be located with their deflectors less than 4 in. (102 mm), from the
wall on which they are mounted.
The requirement in 8.7.4.1.2.2 permits horizontal sidewall sprinklers to be installed less than
4 in. (102 mm) from the wall to which they are mounted. This requirement is similar to the
requirement in 8.6.4.1.1.2 for flush and concealed pendent sprinklers with respect to the po-
sition relative to the ceiling and allows the sprinkler to be mounted on the surface of a wall
or soffit.
For SI units, 1 in. = 25.4 mm; 1 ft = 0.3048 m. FIGURE 8.7.5.1.3 Positioning of Sprinklers to Avoid
Note: For A and B, refer to Figure 8.7.5.1.3. Obstructions (Standard Sidewall Spray Sprinklers).
A.8.7.5.2.2.1 Testing has shown that privacy curtains supported from the ceiling by mesh
fabric do not obstruct the distribution pattern in a negative way as long as the mesh is 70 per-
cent or more open and extends from the ceiling a minimum of 22 in. (559 mm).
A report of tests conducted by NIST in July 2004, “The Effect of Privacy Curtains on Sprin- 䊴 FAQ
kler Spray,” confirmed that privacy curtains supported by mesh that is at least 70 percent open How were the privacy curtain
and that extends down at least 22 in. (559 mm) allows as much water to reach the opposite requirements established?
side of the curtain as arrangements that meet the requirements of 8.7.5.2.2. This finding is rec-
ognized in 8.7.5.2.2.1.
8.7.5.3* Obstructions That Prevent Sprinkler Discharge from Reaching the Hazard.
A.8.7.5.3 See A.8.5.5.3.
8.7.5.3.1 Continuous or noncontinuous obstructions that interrupt the water discharge in a
horizontal plane more than 18 in. (457 mm) below the sprinkler deflector in a manner to limit
the distribution from reaching the protected hazard shall comply with this section.
8.7.5.3.2 Sprinklers shall be installed under fixed obstructions over 4 ft (1.2 m) wide such as
ducts, decks, open grate flooring, cutting tables, and overhead doors.
8.7.5.3.3 Sprinklers shall not be required under obstructions that are not fixed in place such
as conference tables.
8.8.1 General. All requirements of Section 8.5 shall apply to extended coverage upright
and pendent sprinklers except as modified in Section 8.8.
8.8.2 Protection Areas per Sprinkler (Extended Coverage Upright and Pen-
dent Spray Sprinklers).
8.8.2.1* Determination of the Protection Area of Coverage.
A.8.8.2.1 The protection area for extended coverage upright and pendent sprinklers is de-
fined in the listing of the sprinkler as a maximum square area. Listing information is pre-
sented in even 2 ft (0.6 m) increments up to 20 ft (6.1 m). When a sprinkler is selected for an
application, its area of coverage must be equal to or greater than both the length and width of
the hazard area. For example, if the hazard to be protected is a room 131/2 ft (4.1 m) wide and
171/2 ft (5.3 m) long as indicated in Figure A.8.8.2.1, a sprinkler that is listed to protect an area
of 18 ft ⫻ 18 ft (5.5 m ⫻ 5.5 m) must be selected. The flow used in the calculations is then
selected as the flow required by the listing for the selected coverage.
EC sprinklers are not allowed under combustible obstructed construction. Testing has
shown that extending the sprinkler spacing under this type of construction allows the fire to
ignite the ceiling, increasing the fire challenge and the potential for system failure.
8.8.2.1.3 Determination of the protection area of coverage and sprinkler spacing for sprin-
klers listed for extended coverage extra hazard or high-piled storage shall be permitted to be
spaced in accordance with the requirements of 8.5.2 and 8.5.3 and shall not exceed 14 ft
(4.3 m) maximum spacing and 196 ft2 (18.2 m2) maximum area per sprinkler or 15 ft (4.6 m)
maximum spacing and 144 ft2 (13.4 m2) maximum area per sprinkler.
Due to the fact that EC sprinklers used in extra hazard and storage occupancies are limited by 䊴 FAQ
8.8.2.1.3 to a maximum of 14 ft (4.3 m) between sprinklers [a minimal increase considering Why are EC sprinklers listed for
extra hazard or high-piled
the 12 ft (3.7 m) permitted for upright and pendent sprinklers], and the fact that pressure is
storage permitted to be used by
not as much of a factor in obtaining the extended spacing, the protection area for these sprin- the requirements of 8.5.2 and
klers is not required to be a square pattern. The maximum distance between these sprinklers 8.5.3?
can be extended to 15 ft (4.6 m) if the protection area is limited to 144 ft2 (13.4 m2). The pro-
tection area for these sprinklers is calculated in the same manner as standard upright and pen-
dent sprinklers.
8.8.2.2 Maximum Protection Area of Coverage.
8.8.2.2.1* The maximum allowable area of coverage for a sprinkler (As) shall be in accor-
dance with the value indicated in Table 8.8.2.1.2.
A.8.8.2.2.1 Testing has shown that privacy curtains supported from the ceiling by mesh fab-
ric do not obstruct the distribution pattern in a negative way as long as the mesh is 70 percent
or more open and extends from the ceiling a minimum of 22 in. (559 mm).
8.8.2.2.2 In any case, the maximum area of coverage of a sprinkler shall not exceed 400 ft2
(37.2 m2).
The maximum area of coverage for an EC sprinkler limits the area that would be unprotected
if a sprinkler were to be severely obstructed or fail to operate. The limit of 196 ft2 (18.2 m2)
for extra hazard and high-piled storage considers that fires in these occupancies develop much
more rapidly than fires in light and ordinary hazard occupancies and can overtax adjacent
sprinklers if one sprinkler fails to operate as anticipated.
8.12.2.2.3* Deviations from the maximum sprinkler spacing shall be permitted to eliminate
obstructions created by structural elements (such as trusses, bar joists, and wind bracing) by
moving a sprinkler along the branch line a maximum of 1 ft (0.31 m) from its allowable spac-
ing, provided coverage for that sprinkler does not exceed 110 ft2 (10.2 m2) per sprinkler where
all of the following conditions are met:
(1) The average actual floor area protected by the moved sprinkler and the adjacent sprin-
klers shall not exceed 100 ft2 (9.3 m2).
(2) Adjacent branch lines shall maintain the same pattern.
(3) In no case shall the distance between sprinklers exceed 12 ft (3.7 m).
A.8.12.2.2.3 See Figure A.8.12.2.2.3.
ESFR sprinklers must be located a minimum distance from the nearest edge of any bottom
chord of a bar joist or truss. If the spacing of sprinklers is not an even multiple of the chord
spacing, the standard sprinkler spacing will not meet this requirement. Paragraphs 8.12.2.2.3
and 8.12.2.2.4 permit sprinklers to be moved 1 ft (0.31 m) to eliminate the obstruction caused
by the bottom chord, as long as the pattern is repeated and the protection area restrictions out-
lined in 8.12.2.2.3 are met.
8.12.2.2.4 Deviations from the maximum sprinkler spacing shall be permitted to eliminate
obstructions created by structural elements (such as trusses, bar joists, and wind bracing) by
moving a single branch line a maximum of 1 ft (0.31 m) from its allowable spacing, provided
coverage for the sprinklers on that branch line and the sprinklers on the branch line it is mov-
ing away from does not exceed 110 ft2 (10.2 m2) per sprinkler where all of the following con-
ditions are met:
(1) The average actual floor area protected by the sprinklers on the moved branch line and
the sprinklers on the adjacent branch lines shall not exceed 100 ft2 (9.3 m2) per sprinkler.
(2) In no case shall the distance between sprinklers exceed 12 ft (3.7 m).
(3) It shall not be permitted to move a branch line where there are moved sprinklers on a
branch line that exceed the maximum sprinkler spacing.
Similar to the requirements of 8.12.2.2.3, 8.12.2.2.4 permits an entire branch line to be moved
a maximum of 1 ft (0.31 m), provided the requirements of 8.12.2.2.4 are met.
8.12.2.3 Minimum Protection Area of Coverage. The minimum allowable protection area
of coverage for a sprinkler (As) shall not be less than 64 ft2 (6 m2).
The protection area for ESFR sprinklers is limited to not less than 64 ft2 (6 m2) by 8.12.2.3 to
prevent the possibility of skipping (see commentary following 8.11.2.3 for explanation of the
term skipping). Limiting the minimum distance between sprinklers, as required by 8.12.3.4,
also minimizes the potential for skipping.
(1) Where the storage height is less than or equal to 25 ft (7.6 m) and the ceiling height is
less than or equal to 30 ft (9.1 m), the distance between sprinklers shall be limited to not
more than 12 ft (3.7 m) between sprinklers as shown in Table 8.12.2.2.1.
(2) Unless the requirements of 8.12.3.1(3) or 8.12.3.1(4) are met, where the storage height
exceeds 25 ft (7.6 m) and ceiling height exceeds 30 ft (9.1 m), the distance between sprin-
klers shall be limited to not more than 10 ft (3 m) between sprinklers.
(3)* Regardless of the storage or ceiling height arrangement, deviations from the maximum
sprinkler spacing shall be permitted to eliminate obstructions created by trusses and bar
joists by moving a sprinkler along the branch line a maximum of 1 ft (0.31 m) from its
allowable spacing, provided coverage for that sprinkler does not exceed 110 ft2 (10.2 m2)
where all of the following conditions are met:
(a) The average actual floor area protected by the moved sprinkler and the adjacent
sprinklers shall not exceed 100 ft2 (9.3 m2).
(b) Adjacent branch lines shall maintain the same pattern.
(c) In no case shall the distance between sprinklers exceed 12 ft (3.7 m).
(4) Where branch lines are parallel to trusses and bar joists, deviations from the maximum
sprinkler spacing shall be permitted to eliminate obstructions created by trusses and bar
joists by moving a single branch line a maximum of 1 ft (0.31 m) from its allowable spac-
ing, provided coverage for the sprinklers on that branch line and the sprinklers on the
branch line it is moving away from does not exceed 110 ft2 (10.2 m2) per sprinkler where
all of the following conditions are met:
(a) The average actual floor area protected by the sprinklers on the moved branch line
and the sprinklers on the adjacent branch lines shall not exceed 100 ft2 (9.3 m2) per
sprinkler.
(b) In no case shall the distance between sprinklers exceed 12 ft (3.7 m).
(c) It shall not be permitted to move a branch line where there are moved sprinklers on
a branch line that exceed the maximum sprinkler spacing.
For SI units, 1 in. = 25.4 mm; 1 ft = 0.3048 m. FIGURE 8.12.5.1.1 Positioning of Sprinklers to Avoid
Note: For A and B, refer to Figure 8.12.5.1.1. Obstructions to Discharge (ESFR Sprinkler).
represent potential obstructions for ESFR sprinklers and should be positioned in accordance
with the provisions of 8.12.5.2 with regard to both the fan motor unit and the blades.
8.12.5.3 Continuous Obstructions Below the Sprinklers.
8.12.5.3.1 General Continuous Obstructions. Sprinklers shall be arranged with respect to
obstructions in accordance with one of the following:
(1) Sprinklers shall be installed below continuous obstructions, or they shall be arranged to
comply with Table 8.12.5.1.1 for horizontal obstructions entirely below the elevation of
sprinklers that restrict sprinkler discharge pattern for two or more adjacent sprinklers
such as ducts, lights, pipes, and conveyors.
(2) Additional sprinklers shall not be required where the obstruction is 2 in. (51 mm) or less
in width and is located a minimum of 2 ft (0.6 m) below the elevation of the sprinkler de-
flector or is positioned a minimum of 1 ft (0.3 m) horizontally from the sprinkler.
(3) Additional sprinklers shall not be required where the obstruction is 1 ft (0.3 m) or less in
width and located a minimum of 1 ft (0.3 m) horizontally from the sprinkler.
(4) Additional sprinklers shall not be required where the obstruction is 2 ft (0.6 m) or less in
width and located a minimum of 2 ft (0.6 m) horizontally from the sprinkler.
(5) Ceiling sprinklers shall not be required to comply with Table 8.12.5.1.1 where a row of
sprinklers is installed under the obstruction.
8.12.5.3.2 Bottom Chords of Bar Joists or Open Trusses. ESFR sprinklers shall be posi-
tioned a minimum of 1 ft (0.3 m) horizontally from the nearest edge to any bottom chord of
a bar joist or open truss.
8.12.5.3.3 Open Gratings. Sprinklers installed under open gratings shall be of the interme-
diate level/rack storage type or otherwise shielded from the discharge of overhead sprinklers.
8.12.5.3.4 Overhead Doors. Quick-response spray sprinklers shall be permitted to be uti-
lized under overhead doors.
8.12.5.3.5 Special Obstruction Allowance. Sprinklers with a special obstruction allowance
shall be installed according to their listing.
8.13.1 System Size. The area protected by a single system of sprinklers in racks shall not
exceed 40,000 ft2 (3716 m2) of floor area occupied by the racks, including aisles, regardless
of the number of levels of in-rack sprinklers.
8.15.3 Stairways.
8.15.3.1 Combustible Construction. Sprinklers shall be installed beneath all stairways of
combustible construction.
8.15.3.2 Noncombustible Construction.
Why are sprinklers required in
8.15.3.2.1 In noncombustible stair shafts having noncombustible stairs with noncombustible noncombustible stair shafts at
or limited-combustible finishes, sprinklers shall be installed at the top of the shaft and under the top of the shaft and under
the first accessible landing above the bottom of the shaft. the first landing above the
bottom of the shaft?
The storage of materials in stairwells obstructs the egress route and is prohibited by NFPA 䊴 FAQ
101. However, if there is an open space under the first landing or a large landing at the top of
the stairs it is often an irresistible location for transient storage. As a result, 8.15.3.2.1 requires
sprinklers at these locations.
8.15.3.2.2 Where noncombustible stair shafts are divided by walls or doors, sprinklers shall
be provided on each side of the separation.
8.15.3.2.3 Sprinklers shall be installed beneath landings or stairways where the area beneath
is used for storage.
8.15.3.2.4 Sprinklers shall be permitted to be omitted from exterior stair towers when the ex-
terior walls of the stair tower are at least 50 percent open and when the stair tower is entirely
of noncombustible construction.
Exhibit 8.31 shows a set of exterior stairs complying with 8.15.3.2.4. Exterior stairs are nor-
mally accessible for manual fire fighting. If the stairs are more than 50 percent open and of
noncombustible construction, a sprinkler can be eliminated from these stairs.
8.15.3.3* Stairs Serving Two or More Fire Divisions. Sprinklers shall be installed in the
stair shaft at each floor landing where two or more doors open from that landing into sepa-
rate fire divisions.
A.8.15.3.3 See Figure A.8.15.3.3(a) and Figure A.8.15.3.3(b). Sprinklers would be required
in the case shown in Figure A.8.15.3.3(a) but not in the case shown in Figure A.8.15.3.3(b).
Sprinklers are required at each floor landing where a noncombustible stair shaft serves two
fire-separated buildings or two fire sections of one building, as shown in Figure A.8.15.3.3(a),
or where the stair landing serves as a horizontal exit. If the stair serves only one fire section,
sprinklers are required only at the roof and under the lowest landing. [See Figure
A.8.15.3.3(a) and Figure A.8.15.3.3(b).]
spaces creates a level of safety from the accumulation of the products of combustion. Because
of this characteristic of the space, there is no additional benefit to install draft stops and
closely spaced sprinklers in these spaces.
Smaller vertical openings may be referred to in the local building code or NFPA 101 as
communicating spaces or convenience openings. These spaces are not required to have a bar-
rier around the opening perimeter. (See Section 8.6, Vertical Openings, in NFPA 101 for more
details.) An example of a communicating space is shown in Exhibit 8.32. Because this space
is permitted to be unenclosed by NFPA 5000®, Building Construction and Safety Code®, or
NFPA 101, 8.15.4.1 does not require draft stops and closely spaced sprinklers.
Escalator openings in department stores (see Exhibit 8.33) are examples of vertical open-
ings that would not be considered a convenience opening or a communicating space, and as
a result, they would be required by NFPA 5000 or NFPA 101 to be enclosed to protect against
vertical fire spread. However, enclosed escalators would not be very convenient for the occu-
pants of the department store, so an alternative to the enclosure is necessary. That alternative
is established in 8.15.4.2 and 8.15.4.3 by means of draft stops and closely spaced sprinklers
as shown in Exhibit 8.33.
8.15.4.2 Draft Stops. Draft stops shall meet all of the following criteria:
(1) The draft stops shall be located immediately adjacent to the opening.
(2) The draft stops shall be at least 18 in. (457 mm) deep.
(3) The draft stops shall be of noncombustible or limited-combustible material that will stay
in place before and during sprinkler operation.
Sprinklers
EXHIBIT 8.32 Communicating Space Not Requiring Draft EXHIBIT 8.33 Example of Closely Spaced Sprinklers and
Stops and Closely Spaced Sprinklers. Draft Stops.
8.15.4.3 Sprinklers.
8.15.4.3.1 Sprinklers shall be spaced not more than 6 ft (1.8 m) apart and placed 6 in. to 12
in. (152 mm to 305 mm) from the draft stop on the side away from the opening.
8.15.4.3.2 Where sprinklers are closer than 6 ft (1.8 m), cross baffles shall be provided in ac-
cordance with 8.6.3.4.2.
When the features of the opening warrant sprinklers that are spaced at intervals of less than 6
ft (1.8 m), as described in 8.15.4.3.2, the installation of baffles between adjacent sprinklers
prevents the occurrence of the cold solder effect. The use of such devices is discussed in the
commentary to 8.6.3.4 for standard spray sprinklers.
Sprinklers used to achieve the protection outlined in 8.15.4 can be of the open or au-
tomatic type. Privately conducted tests using closed sprinklers have indicated their effec-
tiveness. The use of deluge-type water curtains has become quite rare since the early
1960s. Accidental discharge of deluge-type water curtains results in considerable water
damage, as well as potential injury to persons on escalators, when such false actuation
occurs.
8.15.4.4 Large Openings. Closely spaced sprinklers and draft stops are not required around
large openings such as those found in shopping malls, atrium buildings, and similar structures
where all adjoining levels and spaces are protected by automatic sprinklers in accordance
with this standard and where the openings have all horizontal dimensions between opposite
edges of 20 ft (6 m) or greater and an area of 1000 ft2 (93 m2) or greater.
8.15.5.1* Sidewall spray sprinklers shall be installed at the bottom of each elevator hoistway
not more than 2 ft (0.61 m) above the floor of the pit.
A.8.15.5.1 The sprinklers in the pit are intended to protect against fires caused by debris,
which can accumulate over time. Ideally, the sprinklers should be located near the side of the
pit below the elevator doors, where most debris accumulates. However, care should be taken
that the sprinkler location does not interfere with the elevator toe guard, which extends below
the face of the door opening.
ASME A17.1, Safety Code for Elevators and Escalators, allows the sprinklers within 2
ft (0.65 m) of the bottom of the pit to be exempted from the special arrangements of inhibit-
ing waterflow until elevator recall has occurred.
Refuse and residual hydraulic fluids tend to collect at the bottom of shafts. A properly located
sprinkler, as required by 8.15.5.1, can control a fire of such material. Conventional require-
ments regarding the placement of the deflector and clear space below the sprinkler cannot al-
ways be adhered to in this area. These issues are not critical, however, because the sprinkler
would be physically close to any point where a fire could originate, still allowing the sprin-
kler to control the fire.
FAQ 䊳 Because the sprinkler at the bottom of the shaft cannot discharge onto the elevator or
Where sprinklers are installed at other operating components of the elevator, ASME A17.1 no longer requires that the sprin-
the bottom of the elevator shaft,
kler discharge at the bottom of the shaft be delayed until power shutdown has occurred. The
is water discharge required to
be delayed until power sprinkler at the bottom of the shaft, where installed, is permitted to be part of the normal
shutdown has occurred? building sprinkler system and is not required to be part of the special system used to protect
the rest of the elevator equipment.
8.15.5.2 The sprinkler required at the bottom of the elevator hoistway by 8.15.5.1 shall not
be required for enclosed, noncombustible elevator shafts that do not contain combustible hy-
draulic fluids.
8.15.5.3* Automatic sprinklers in elevator machine rooms or at the tops of hoistways shall
be of ordinary- or intermediate-temperature rating.
A.8.15.5.3 ASME A17.1, Safety Code for Elevators and Escalators, requires the shutdown
of power to the elevator upon or prior to the application of water in elevator machine rooms
or hoistways. This shutdown can be accomplished by a detection system with sufficient sen-
sitivity that operates prior to the activation of the sprinklers (see also NFPA 72, National Fire
Alarm and Signaling Code). As an alternative, the system can be arranged using devices or
sprinklers capable of effecting power shutdown immediately upon sprinkler activation, such
as a waterflow switch without a time delay. This alternative arrangement is intended to inter-
rupt power before significant sprinkler discharge.
8.15.5.4* Upright, pendent, or sidewall spray sprinklers shall be installed at the top of eleva-
tor hoistways.
Historically, upright or pendent sprinklers were required at the top of the elevator shaft. In
many instances, however, upright/pendent sprinklers cannot be centered above the hoistway
because cables and so forth are present. Sidewall sprinklers, which can be installed clear of
elevating equipment and may be easier to install and replace, are now permitted as an alter-
native.
A.8.15.5.4 Passenger elevator cars that have been constructed in accordance with ASME
A17.1, Safety Code for Elevators and Escalators, Rule 204.2a (under A17.1a-1985 and later
editions of the code) have limited combustibility. Materials exposed to the interior of the car
and the hoistway, in their end-use composition, are limited to a flame spread index of 0 to 75
and a smoke developed index of 0 to 450, when tested in accordance with ASTM E 84, Stan-
dard Test Method of Surface Burning Characteristics of Building Materials.
8.15.16 Stages.
8.15.16.1 Sprinklers shall be installed under the roof at the ceiling, in spaces under the stage
either containing combustible materials or constructed of combustible materials, and in all ad-
jacent spaces and dressing rooms, storerooms, and workshops.
8.15.16.2 Where proscenium opening protection is required, a deluge system shall be pro-
vided with open sprinklers located not more than 3 ft (0.9 m) away from the stage side of the
proscenium arch and spaced up to a maximum of 6 ft (1.8 m) on center. (See Chapter 11 for
design criteria.)
The sprinkler requirements for proscenium opening protection are addressed in 8.15.16.2.
Building codes and NFPA 101 describe a series of protection schemes to properly protect
these openings. One method of protecting these openings is with a deluge-type system.
The primary purpose of the sprinklers is to protect the audience from a fire on the stage.
When a curtain is provided, the sprinklers should be on the stage side of the curtain between Ceiling
the curtain and the fire, so that they wet the curtain when they operate.
8.15.17 Stair Towers. Stair towers, or other construction with incomplete floors, if piped
on independent risers, shall be treated as one area with reference to pipe sizes.
A fire in a stair or tower, which is addressed in 8.15.17, can open a large percentage of sprin-
klers in the area. An independent riser supplying a stair or tower must be sized to supply all
the sprinklers.
In-rack
sprinklers
Control
valve for
ceiling
system
Control valve
Fire for in-rack system
department
connection
8.16.1.6.1 Unless the requirements of 8.16.1.6.2 or 8.16.1.6.3 are met, where sprinklers are
installed in racks, separate indicating control valves and drains shall be provided and arranged
so that ceiling and in-rack sprinklers can be controlled independently.
8.16.1.6.2 Installation of 20 or fewer in-rack sprinklers supplied by any one ceiling sprinkler
system shall not require a separate indicating control valve.
Paragraph 8.16.1.6.2 permits an in-rack sprinkler system consisting of up to 20 sprinklers to
be supplied from the overhead system without a separate control valve (see Exhibit 8.44).
System
In-rack
check valve
sprinklers
Fire
department No more than 20 sprinklers
connection System on in-rack portion
control
valve System riser
connection to the system should be located off the top of horizontal piping at a high point in
the system; however, the vent connection can also be effectively located off the side of a riser
or rise nipple at a high point in the system.
Manual air venting valves should be readily accessible. The manual air venting valve
should be located at an accessible point and preferably not over 7 ft (2 m) above the floor. Au-
tomatic air valves are not required to comply with the accessibility requirement of manual air
venting valves; however, it is recommended the designer locate automatic air vents over areas
without ceilings, above a lay-in ceiling, or above an access panel.
Each wet pipe sprinkler system should be vented every time the system is filled.
8.16.4.2.3 Where corrosive conditions exist or piping is exposed to the weather, corrosion-
resistant types of pipe, fittings, and hangers or protective corrosion-resistant coatings shall be
used.
8.16.4.2.4 Where steel pipe is used underground, the pipe shall be protected against corro-
sion.
8.16.4.3 Protection of Piping in Hazardous Areas.
8.16.4.3.1 Private service main aboveground piping shall not pass through hazardous areas
and shall be located so that it is protected from mechanical and fire damage.
8.16.4.3.2 Private service main aboveground piping shall be permitted to be located in haz-
ardous areas protected by an automatic sprinkler system.
Private fire service main piping addressed in 8.16.4.3.2 should be located outside of buildings
and buried. In some cases, running piping within the building may be necessary. The piping
must not be exposed to hazardous areas, because it would be subject to damage and would be
unable to provide water to other areas that might need protection. If automatic sprinkler pro-
tection designed for the hazard involved is provided, the potential for main damage is mini-
mized.
8.17.1.5.1 For all types of sprinkler systems employing water motor-operated alarms, a listed
3
/4 in. (20 mm) strainer shall be installed at the alarm outlet of the waterflow detecting device.
8.17.1.5.2 Where a retarding chamber is used in connection with an alarm valve, the strainer
shall be located at the outlet of the retarding chamber unless the retarding chamber is pro-
vided with an approved integral strainer in its outlet.
See the commentary following 6.9.3.4 and Exhibit 8.50. The strainer and the pipe of corrosion-
resistant material are required to protect against obstruction of the small orifice through which
water enters the water motor.
8.17.1.6* Alarm Attachments — High-Rise Buildings. When a fire must be fought inter-
nally due to the height of a building, the following additional alarm apparatus shall be pro-
vided:
(1) Where each sprinkler system on each floor is equipped with a separate waterflow device,
it shall be connected to an alarm system in such a manner that operation of one sprinkler
will actuate the alarm system, and the location of the operated flow device shall be indi-
cated on an annunciator and/or register. The annunciator or register shall be located at
grade level at the normal point of fire department access, at a constantly attended build-
ing security control center, or at both locations.
(2) Where the location within the protected buildings where supervisory or alarm signals are
received is not under constant supervision by qualified personnel in the employ of the
owner, a connection shall be provided to transmit a signal to a remote central station.
(3) A distinct trouble signal shall be provided to indicate a condition that will impair the sat-
isfactory operation of the sprinkler system.
A.8.17.1.6 Monitoring should include but not be limited to control valves, building temper-
atures, fire pump power supplies and running conditions, and water tank levels and tempera-
tures. Pressure supervision should also be provided on pressure tanks.
Check valves can be required to prevent false waterflow signals on floors where sprin-
klers have not activated — for example, floor systems interconnected to two supply risers.
To improve the reliability of an automatic sprinkler system in a high-rise building, supervi-
sion of any portion of the system that could impair its operation is required. A sprinkler wa-
terflow alarm annunciated by floor is not required, because some systems can take on
configurations that would not lend themselves to this type of zoning. On the other hand,
where sprinkler waterflow alarms are provided on each floor, they are intended to be annun-
ciated at a point to allow rapid identification of the fire location by the fire department on ar-
rival.
The overall reliability of the system is further improved by requiring remote monitoring
of supervisory signals in the numerous cases where 24-hour surveillance of on-site supervi-
sory equipment is not provided.
8.17.1.7 Sprinkler Waterflow Alarm for In-Rack Sprinklers. See Section C.4.
▼
C.4 [8.17.1.7]
The time of operation of the first sprinkler varied from 52 seconds to 3 minutes and
55 seconds, with most tests under 3 minutes, except in Test 64 (Class III), where the
first sprinkler operated in 7 minutes and 44 seconds. Fire detection more sensitive
than waterflow is, therefore, considered necessary only in exceptional cases.
Typical fire department connections are shown in Figure A.8.17.2(a) and Figure
A.8.17.2(b). See NFPA 13E, Recommended Practice for Fire Department Operations in
Properties Protected by Sprinkler and Standpipe Systems.
Fire
department
connection
Check
Header valve
in valve
room
Automatic drip
8.17.2.1* Unless the requirements of 8.17.2.2 are met, a fire department connection shall be
provided as described in 8.17.2 in accordance with Figure 8.17.2.1.
A.8.17.2.1 Fire department connections should be located and arranged so that hose lines can
be readily and conveniently attached without interference from nearby objects, including
buildings, fences, posts, or other fire department connections. Where a hydrant is not avail-
able, other water supply sources such as a natural body of water, a tank, or a reservoir should
be utilized. The water authority should be consulted when a nonpotable water supply is pro-
posed as a suction source for the fire department. EXHIBIT 8.50 Example of
8.17.2.2 The following systems shall not require a fire department connection: Typical Fire Department
Connection.
(1) Buildings located in remote areas that are inaccessible for fire department support
(2) Large-capacity deluge systems exceeding the pumping capacity of the fire department
(3) Single-story buildings not exceeding 2000 ft2 (186 m2) in area
Paragraphs 8.17.2.2(1), (2), and (3) are examples of situations in which a fire department 䊴 FAQ
connection is not practical. Paragraphs 8.17.2.2(1) and (2) are conditions in which the Why are some systems not
required to have a fire depart-
connection would be of little or no benefit; thus, the decision not to provide the connec- ment connection?
tion is an economical one. Paragraph 8.17.2.2(3) addresses a situation in which fire de-
partment access is readily available to all sides and areas of the structure; thus, the
connection is likely to provide only minimal benefit. See Exhibit 8.50 for a typical fire de-
partment connection.
8.17.4.4.2 The connection used to control the level of priming water shall be considered ad-
equate to test the operation of the alarms monitoring the supervisory air pressure.
8.17.4.4.3 For double interlock preaction systems, a trip test connection or manifold not less
than 1 in. (25 mm) in diameter, terminating in a smooth bore corrosion-resistant orifice to pro-
vide a flow equivalent to one sprinkler of a type installed on the particular system, shall be
installed.
8.17.4.4.4 For double interlock preaction systems, the trip test connection or manifold shall
be located on the end of the most distant sprinkler pipe in the upper story and shall be
equipped with a readily accessible shutoff valve and a plug not less than 1 in. (25 mm), of
which at least one shall be brass.
8.17.4.4.5 When flow is from four sprinklers, the trip test manifold shall be arranged to sim-
ulate two sprinklers on each of two sprinkler branch lines.
8.17.4.5 Deluge Systems. A test connection shall not be required on a deluge system.
8.17.4.6* Backflow Devices.
A.8.17.4.6 Where backflow prevention devices are installed, they should be in an accessible
location to provide for service and maintenance.
8.17.4.6.1* Backflow Prevention Valves. Means shall be provided downstream of all back-
flow prevention valves for flow tests at system demand.
A.8.17.4.6.1 The full flow test of the backflow prevention valve can be performed with a test
header or other connection downstream of the valve. A bypass around the check valve in the
fire department connector line with a control valve in the normally closed position can be an
acceptable arrangement. When flow to a visible drain cannot be accomplished, closed loop
flow can be acceptable if a flowmeter or site glass is incorporated into the system to ensure
flow. When a backflow prevention device is retroactively installed on a pipe schedule system,
the revised hydraulic calculation still follows the pipe schedule method of 11.2.2 with the in-
clusion of friction loss for the device.
8.17.4.6.2 Retroactive Installation. When backflow prevention devices are to be retroac-
tively installed on existing systems, a thorough hydraulic analysis, including revised hy-
draulic calculations, new fire flow data, and all necessary system modifications to
accommodate the additional friction loss, shall be completed as a part of the installation.
A hydraulic analysis is required by 8.17.4.6.2 to determine and properly account for the im-
pact of a retroactively installed backflow prevention device on the performance of an existing
sprinkler system. Existing pipe schedule systems are not required to be recalculated in accor-
dance with the hydraulic calculation methods of Chapter 11 when a backflow prevention de-
vice is retroactively installed. However, pipe schedule systems are required to meet certain
pressure and flow requirements in accordance with Chapter 11. As in the case of a hydrauli-
cally calculated sprinkler system, it must be verified that the water supply still meets the de-
mand of the pipe schedule system after the installation of a backflow prevention device. A
backflow prevention device is shown in Exhibit 8.55.
C.5 [8.17.5.1]
In most tests conducted, it was necessary to use small hose for mop-up operations.
Small hose was not used in the high-expansion foam test.
Test 97 was conducted to evaluate the effect of dry pipe sprinkler operation. Test
results were approximately the same as the base test with a wet pipe system. A study
of NFPA records, however, indicates an increase in area of operation of 30 percent
to be in order for dry pipe systems as compared with wet pipe systems.
8.17.5.1.1* Where required, small [11/2 in. (38 mm)] hose connections shall be installed.
Valves shall be available to reach all portions of the area with 100 ft (30.5 m) of hose plus 30
ft (9.1 m) of hose stream distance.
Storage fires normally require the use of hose lines for complete extinguishment of fires
within boxes or other areas that can be shielded from the sprinklers at the ceiling. Fire de-
partments normally use their own hose. When specifically required, the hose connections can
be supplied from separate or adjacent systems or outside hydrants, so that the ceiling sprin-
klers can be shut off during the clean-up operation. These hose connections are not intended
to serve as standpipes in accordance with NFPA 14, Standard for the Installation of Stand-
pipe and Hose Systems. Exhibit 8.56 shows an example of a small hose station. Exhibit 8.57
shows a hose connection equipped with a hose line in a storage facility.
A.8.17.5.1.1 One and one-half inch (40 mm) fire hose packs are not required unless desig-
nated by the AHJ, as it is not likely that such hoses will be adequately maintained for safe use
by first responders. Civilian workers who are not properly trained in fire-fighting techniques
are expected to evacuate the building in the event of a fire.
Hose connections of 11/2 in. (40 mm) are restricted to wet pipe systems (see A.8.17.5.1.1). The
maintenance problems due to loss of air pressure through the hose valves in other types of
systems would outweigh their value. These types of connections are convenience connections
for first-aid fire-fighting conditions. These connections are not standpipe connections. Thus,
the flows noted in Chapters 11 and 12 through 20 are all that need to be accounted for in this
type of connection.
EXHIBIT 8.56 Example of Hose connections of 11/2 in. (40 mm) supplied from sprinkler systems have been suc-
Small Hose Station. cessful in fire extinguishment and fire control for many years. The requirements for Class II
Pressure Pressure
Indicating-type floor control gauge gauge
valve with supervisory switch Check Indicating-type floor control Check
Waterflow To valve with supervisory switch To
valve switch valve Waterflow
sprinkler switch sprinkler
system system
Drain Drain
riser Inspector’s riser Inspector’s
test and drain test and drain
Fire hose valve
connection 2¹⁄₂ in. Fire hose valve connection
(65 mm)
min.
Combination sprinkler/
standpipe riser Combination sprinkler/
standpipe riser