RCPT Test Table
RCPT Test Table
RCPT Test Table
No. Location Casting Date Testing Date No. of Test Cubes Charged Passed (Columbs) Adjusted Charge Passed (Coloumbs) Average (Coloumbs) Company Chloride Ion Penetrability
182 -
1 P4 (1st cast) 21-10-19 17-12-19 3 94 - 169 BSEN Very Low
231 - Coloumbs passed Chloride Ion Penetrability
256 - >4000 High
2 P4 (2nd cast) 26-10-19 21-12-19 3 25 - 157 BSEN Very Low 2000 - 4000 Moderate
190 - 1000 - 2000 Low
192 174 100 - 1000 Very Low
3 P1 (1st cast) 08-11-19 03-01-20 3 224 203 205 USM Very Low <100 Negligible
262 238 *ASTM C1202
229 208
4 P1 (2nd cast) 14-11-19 09-01-20 3 217 197 209.67 USM Very Low
247 224
294 267
5 Abutment A 19-11-19 16-01-20 2 258.5 USM Very Low
276 250
231 210
6 P3 (1st cast) 23-11-19 21-01-20 3 185 168 180.67 USM Very Low
181 164
246 223
7 P3 (2nd cast) 28-11-19 24-01-20 3 330 299 244.67 USM Very Low
234 212
8 P3 Column (LHS) 07-12-19 03-02-20 1 323 293 293 USM Very Low
260 236
8 P2 (1st cast) 10-12-19 05-02-20 3 243 220 225.33 USM Very Low
242 220
250 227
9 P2 (2nd cast) 14-12-19 11-02-20 3 194 176 193 USM Very Low
194 176
312 283
10 P3 Column (RHS) 19-12-19 13-02-20 2 280 USM Very Low
305 277
14 P2 (E7) 3
15 P2 (M7) 3
16 P3 (M6) 3
17 P3 (E6) 3
18 P4 (M7) 3
19 P4 (E7) 3