Gen set control unit NEW

 Three-phases AMF
automatic genset
controller
 True RMS readings
on generator and
GC310
AMF generator set controller
mains voltages and
currents A new range of automatic generator set controller is introduced by SICES starting
 Additional current from the GC310 model.
measurement for
This basic model has all required features for the most common generator
neutral or
applications (Single Prime Mover and Single Stand-by).
differential
protection
 Active, Reactive and
apparent power
measurement
 Frequency and
power measurement
on Mains input
 Graphic display
 8+3 fully
programmable
digital input
 Up to 8 digital output
(6 programmable)
 RS232 interface port
with MODBUS RTU
protocol
 J1939 and MTU
MDEC CAN interface
 Real Time Clock
 Events and data
logging
 Engine speed It is designed for the current generation of engines that have CAN interface (mostly
J1939 protocol) but, nevertheless, it can be used with standard engines since
measurement by
engine measurements can be carried out by the embedded analogue interfaces.
pick-up or W
 GSM and PSTN The graphic display allows to implement an optimize human interface showing a
modem great number of measures and data.
management
As all SICES controls, an huge set of parameters allows to easily adapt the
 SMS communication controller to specific and not standard applications. The Parameters are easily
 ETHERNET interface managed by a free software tool (BoardPrg) but they can be manually
programmed from the front panel as well.

GC310 is able to measure the MAINS frequency and compute power and energy
even when the load is connected to the MAINS.

Via Molinello 8/B 21040 Jerago (VA) Events and DTC logs can be accessed from the front panel and read on the display.
Italy
Tel +39 0331 212941 GC310 is projected to connect different devices for local or remote control, i.e.
Fax +39 0331 216102 Modem GSM, Gateway module for Ethernet interface, Analogic modem, ….
www.sices.eu Moreover, thanks to its support of standard protocol, it can be easily interfaced to
E-mail: info@sices.eu
any proprietary supervision system.
Rev. 1
Technical characteristics
Measures Inputs, outputs and aux. functions
Mains Voltages 8 Programmable digital inputs
L1-L2, L2-L3, L3-L1 3 Analogue inputs, if not used, can be used as not insulated digital
Lx-N max. voltage < 300Vac cat. IV inputs
Generator Voltages: 1 Relay (3A) fuel solenoid
L1-L2, L2-L3, L3-L1, True RMS measure. 8 Digital outputs (6 programmable)
Lx-N max. voltage < 300Vac cat. IV 2 SPDT (10A) relays for power changeover management
Generator Currents:
L1, L2, L3, N True RMS measure. Embedded functions
Nominal max. current: 5Aac
Engine diagnostic code
Overload measurable current: 4x 5Aac (sinusoidal, max. 3 s)
Periodical test.
Generator and Mains Frequency meter:
Real Time Clock
Resolution = 0.1 Hz.
Fuel pump management.
Accuracy = ± 50ppm, ±35ppm/°C (typical)
Pre-glow and coolant heater management
Battery Voltmeter:
Remote start and stop
Resolution = 0.1V
Maintenance working
Oil Pressure Gauge:
Embedded alarm horn.
VDO 0-10 Bar, VDO 0-5 Bar, Veglia 0-8 Bar
Engine speed measurement by pick-up or W
Coolant Temperature sensors:
VDO, Veglia, BERU
Communication:
Fuel Level:
Serial port RS232 Modbus RTU
VDO, Veglia, Generic max. 380 ohm
Ethernet network by means additional electronic module
Engine revolution counter:
“Gateway Modbus TCP/RTU”
By W. Programmable frequency/revolution ratio.
GSM and PSTN modem management
Same input can be used for pick-up signal.
SMS communication with Modem GSM
Supervision software for remote control available
Other measures available by J1939 bus

Computed Measures Other Technical data


Active power meter Supply voltage: 7…32 Vdc
Reactive power meter Power consumption: typical less than 2W (AUTO mode, STAND-
Apparent power meter BY, AMF active, LCD Lamp Saving active).
Power factor: Total and phase by phase Operating frequency 50Hz or 60Hz
Active and reactive energy counter LCD: transflective with LED backlight.
Hour counter Operating temperature: -25 °C to 70 °C
Hour counter for maint./rental Protection degree: IP55
Start Counter
Weight: 830g
Overall dimension: 247x187mm (LxH)
Engine Protections Panel cutout: 218x159 (LxH)
Overspeed Graphic display dimensions: 70 x 38mm - 128 x 64 pixel
Coolant temperature by ON/OFF and by analogue (warning and
block) Specific function for French market EJP / EJP-T
Oil pressure by ON/OFF and by analogue (warning and block) EMC: conform to EN61326-1.
Fuel level ON/OFF by ON/OFF and by analogue (warning and Safety: built in conformity to EN61010-1
block)
Belt break
Maximum deliverable power SAMPLE CONNECTION DIAGRAM
Overcrank and start failure.

Generator Protections
Underfrequency (81U)
Overfrequency (81O)
Undervoltage (27)
Overvoltage (59)
Power direction (32)
Time dependent overcurrent (51)
Instantaneous overcurrent (50)
Phase sequence
Current and Voltage unbalance
Rated conditions failure
Differential protection (51N)

EAAD030000EN - REV. 1