Be142 Genset Controller Manual
Be142 Genset Controller Manual
Be142 Genset Controller Manual
e-mail: bernini@bernini-design.com
mobile #1: +39 335 70 77 148 mobile #2: 0040 721 241 361
Warranty
Bernini Design SRL (hereinafter "BD") warrants that Be142 shall be free from defect in material or workmanship
for a period of 3 years from the BD delivery date. BD shall, at its discretion, repair or replace the product without
charge. BD shall return the Be142 to the buyer with the Default parameters at no extra charge. The buyer shall
provide sufficient information on any alleged defects in the product, so as to enable BD to determine their cause
and existence. If the Be142 is not defective, or the product is defective for reasons other than covered by this
warranty, the buyer will be charged accordingly. This warranty shall not apply if the Be142 has not been used in
accordance with the User Manual and other operating instruction, particularly if any defects are caused by
misuse, improper repair attempts, and negligence in use or handling.
This purchase is non-refundable.
WARNING!! High voltage is present inside the Be142. To avoid electric-shock hazard, operating
personnel must not remove the protective cover. Do not disconnect the Earth connection. The Be142
can start the engine at anytime. Do not work on equipment, which is controlled by the Be142. When
servicing the engine, disconnect the battery and battery charger. We recommend that warning signs be
placed on equipment indicating the above.
1
Be142 OEM's Manual V3.X.XX - January - 2015 page 2
Alphabetic index
3
Be142 OEM's Manual V3.X.XX - January - 2015 page 4
The Be142 integrates a 3-Phase Automatic Mains Failure controller and a Generating Set controller. The Be142
provides visual indication by means of LEDs and Displays for Engine & Electrical parameters, Alarms and Status
of the contactors. It features 7 modes of operation and provides a RS485 (MODBUS-RTU) interface for remote
control & monitoring. Figure 1 presents the panel layout. Be242 is cost effective controller without RS485.
Alarm
Alarm Display control
acknowledge
messages & indicators
pushbutton
F10
F8 F9
F1 F2 F3 F4 F5 F6 F7
When you apply the DC supply, the display indicates for a second, the version of the software (example 1.0.01)
and the date of production (example 22.12, that means week 22 of year 2012). The modes of operation are
selected by pushbuttons and indicated by means of green LEDs (indicators) as shown below:
MAN OFF
OFF TEST
TEST AUTO
AUTO
Note: default programming for input #36 is ‘normally closed ‘. To inhibit the alarm [Er.08]
you are required to connect terminal #36 to ground (Emergency input).
Every time the power supply is switched on, if the BE142 was in TEST or AUTO prior to power down, the Be142
returns to the “AUTO” mode. In the other cases, the Be142 will enter the OFF mode. The following table
indicates the modes of operation.
4
Be142 OEM's Manual V3.X.XX - January - 2015 page 5
Push the button [OFF] to enter the OFF mode. The OFF mode clears the fault alarms and allows you to read or
program parameters (section 6.0). The Display and LEDs are turned off and a dot on the display will blink slowly.
Push one of the pushbuttons on the front panel to energise the display.
Note: default programming for input #36 is ‘normally closed ‘. To inhibit the alarm [Er.08]
you are required to connect terminal #36 to ground (Emergency input).
The MANUAL mode allows manual control of the Engine and Contactors.
Instructions
Manual Engine Control
Push the [MAN] pushbutton to select the MANUAL mode. Push
Engine Running
green LED
the [START] pushbutton until engine starts; the display indicates
the message [. . . .] during the starting attempts (and [! ! ! !] during
START STOP the preheat).
Pushbutton Pushbutton When the engine is running, the green LED turns on. To stop the
engine, push the [STOP] pushbutton until the [StOP] message
appears on the display. If the engine has already stopped, it is
possible to reset the STOP sequence by pressing the [STOP]
pushbutton.
2.21 Contactors: Manual control To control the contactors follow the instructions:
5
Be142 OEM's Manual V3.X.XX - January - 2015 page 6
Note: default programming for input #36 is ‘normally closed ‘. To inhibit the alarm [Er.08]
you are required to connect terminal #36 to ground (Emergency input).
Push the [AUTO] pushbutton until the green LED illuminates. The engine starts when the Be142 detects a
Mains failure (see table 7.01A). The Contactor of the MAINS (KM) opens after the BREAKER timing. After
the warm-up time, if the Voltage and Frequency are within the settings, the contactor of the Generator (KG)
will close. If the Mains restores, the KG will open. The KM will close following a programmed changeover
timing. The Engine will stop after a cooling down time (see tables 7.02 and 7.03). If the engine shuts down,
the KM closes independently of the Mains status if the [P.48] is [ON] (NFPA-110 mode), otherwise the KM
will close only if the Mains is within programmed settings. In AUTO mode, the Be142 will periodically test
the engine if the parameters [P.41] and [P.42] have been programmed. During this test, the green LED of
the AUTO mode will continue to blink. In AUTO mode, the Be142 can start and stop the engine according to
programmed inputs (see Tables 7.06 and 7.07 options [10] & [11] for example).
Push the [TEST] pushbutton until the green LED illuminates. The Be142 starts the engine and transfers the load
to the Generator if [P.17] is [on]. To stop the engine, select the AUTO mode (if Mains is present) or select the
OFF mode. If you push the [STOP] pushbutton when the Be142 is in AUTO or TEST, the [Er.09] will energise.
To clear the alarm, select the OFF mode (section 8.0).
The PROGRAM mode allows parameter programming and modifications of settings. A password can be set to
protect the panel from unauthorised access (see 6.0).
The CALIBRATION mode allows calibration of all analogue measurements (see 12.0).
4Digit Display
Use [←F8] and [F9→] to select a menu. Use [ACK-F10] (see the layout in section 1.0) to display the name of the
parameter. The OFF mode shuts down the display and turns on the dot on the right side of it. Push a button to
turn on the panel. The following table lists the functions of the display.
6
Be142 OEM's Manual V3.X.XX - January - 2015 page 7
Display Function Display indications (*) Pushbutton(s) Menu & Led indicator
Current of the Generator [AXXX] Ampere L1 A ac Yellow
(0 up to 1000A) [-XXX] Ampere L2 [←F8] or [F9→] menu
[_XXX] Ampere L3
[A -G] [ACK-F10]
Voltage of the Generator [GXXX] Volt L1-L2 V ac Yellow
(60V up to 998V) [-XXX] Volt L2-L3 [←F8] or [F9→] menu
[_XXX] Volt L1-L3
[U -G] [ACK-F10]
[batt] [ACK-F10]
[ bar ] [ACK]
[ °C ] [ACK]
[FUEL] [ACK-F10]
Hours-count :0 up to [XXXX] h [←F8] or [F9→] Yellow
50,000 h. Over 9999 a dot
on the right will appear [Hour] [ACK-F10] h/Prog
indicating X10. menu
(*)NOTE: X indicates a numerical digit, if the measurement is out of range, the display will indicate [- - - -]
7
Be142 OEM's Manual V3.X.XX - January - 2015 page 8
Display Display
Description of the Alarm Description of the Alarm
Message Message
[Er.01] Over Frequency Shutdown (see [P.12]) [Er. 14] Low Oil Pressure Shutdown
(Pressure switch connected to input #35)
[Er.02] Engine Belt Break Shutdown (see [P.26]) [Er. 15] Temperature Switch Shutdown
(Temperature switch connected to Input #34)
[Er.03] Remote LOCK Shutdown (see 7.07 option [Hi-C] Over Current Shutdown or Warning (see
[13]) [P.13]).
[Er.04] Alternator Failure Shutdown [Hi-U] Over Voltage Shutdown (see [P.10])
[Er.05] Overload Warning (see 7.07 option [20]) [Lo-U] Under Voltage Shutdown (see [P.09])
[Er.05] Overload Shutdown (see 7.07 option [21]) [InP.1] Input 1 Shutdown / Warning (see 7.07)
[Er.06] Under Frequency Shutdown (see [P.11]) [InP.2] Input 2 Shutdown / Warning (see 7.07)
[Er.07] Fail To STOP Shutdown (see parameter [InP.3] Input 3 Shutdown / Warning (see 7.07)
P.34, section 7, table 7.04)
[Er.08] Emergency Shutdown (see parameter [InP.4] Input 4 Shutdown / Warning (see 7.07)
P.35, section 7, table 7.04)
[Er.09] Emergency Shutdown triggered by Front [-oIL] Oil pressure warning or sensor failure. Push
Panel (Stop or [0] pushbutton) [←F8] to display the value (see P29).
[Er.10] Maintenance SERVICE warning [ -°C] Water temperature warning or sensor failure.
(see parameters P44,P45 and P46) Push [←F8] to display the value (see P30).
[Er.11] Fail To START Shutdown [FUEL] Fuel level warning (High or Low) or sensor
failure. Push [←F8] to display the value.
[Er.12] Low Fuel Shutdown (If Low Fuel input, [rEnt] The rental contract is going to expire (48
terminal #33, is activated for longer than hours remaining). Push [←F8] to display the
the P.36 time. See Table 7.04A) value.
[Er. 13] Battery Voltage Warning. Push [←F8] to [FAIL] There is an internal failure or memory error in
display the value. the BE142 controller (see 12.3)
[rESt] The Be142 is counting the rest time between [ProG] The Be142 is in program mode
the starting attempts
[n-on] MAINS simulated by an input programmed with [-CAL] The Be142 is in calibration mode
option [15] (see table 7.07). [. . . .] The Be142 is cranking the engine
[''''] The Be142 is performing the pre-glow (P22) [tEst] The Be142 is in Test mode
[StoP] The Be142 is stopping the engine (P25) [----] Measurement out of range or disabled
[U-uP] Warm up time of the engine before closing the The engine is running off load for
contactor of the generator (P23). [CooL] cooling.
[ dEL] Delay time before cranking (P.19,table 7.03A)
8
Be142 OEM's Manual V3.X.XX - January - 2015 page 9
Note: to cancel the LOG EVENTS push [←F8] and [F9→] simultaneously until the display blinks (approx. 10
seconds).
To test the LEDs and DISPLAY push the [OFF] pushbutton; the display turns off (OFF mode). Push and hold the
[←F8] and [F9→] pushbuttons simultaneously. The LEDs and DISPLAYs remain energised as long as the
pushbuttons are pressed and held together.
1) - Provide a voltage from a battery supply of over 11.5 V. Push the [OFF-F7] pushbutton to enter the OFF
mode; the LEDs and display turn OFF (the dot on the right side of the display will start to blink)
2) - Push and hold the [F9→] and [ACK-F10] pushbuttons simultaneously for about 5 seconds, until the yellow
Led [h/Prog.] starts to blink. When the display indicates [ProG], release the buttons.
3) - If the Be142 is password protected (*), the messages [PASS] and [42.42] will appear in sequence; you are
required to follow the instructions of Table 6.11. If the Be142 is not password protected, the programmable
parameter [P.0] will be displayed and the Be142 is ready for programming (section 6.12, step-2).
(*) Note: the password consists of 2 groups of digits ranging from 0 to 99. Example: [12.34]; 12 is the 2-digit code
on the left, and 34 is the 2-digit code on the right.
1) - Push [TEST] or [AUTO] in order to choose the proper code (between 00 and 99, except 42).
2) - Push [F9→] to select the 2 digits on the right side.
3) - Push [TEST] or [AUTO] in order to choose the proper code (between 00 and 99, except 42).
4) - Push [ACK-F10] to confirm the password; if the password is ok, the Be142 will indicate [P.0] and the unit is ready
for programming. If the password is wrong, the display will indicate [4242] and you are required to insert the correct
password.
If you lose the password, the unit must be returned for service.
9
Be142 OEM's Manual V3.X.XX - January - 2015 page 10
6.12 Programming
6.13 Saving
Press and hold the [ACK-F10] and [F9→] pushbuttons simultaneously until the [SaVE] message appears
(approximately 5 seconds); the Be142 saves the settings and will enter the OFF mode. You can select the mode
of operation as indicated in section 2.0.
Note: if the memory fails, the message [FAIL] will appear. Try again to save or remove the power supply. If the
message persists, the Be142 is damaged and should be returned to Bernini Design for repair.
Press the [OFF] pushbutton to enter the OFF mode without saving the parameters. You can select a mode of
operation as indicated in section 2.0.
The parameters of the Be142 are programmed in factory with default settings (section 7.0). To restore them,
enter the Programming Mode (section 6.10). When the message [P.0] appears, follow the instructions:
1) - Press and hold the [←F8] and [F9→] pushbuttons simultaneously until the display blinks twice. Select option
2A or 2B according to your needs.
2A) - Press the [OFF] pushbutton to exit the procedure without saving the parameters.
2B) - Press and hold the [ACK-F10] and [F9→] pushbuttons simultaneously until the [SAVE] message appears
(approximately 5 seconds); the Be142 saves the settings and the display will indicate [P0]. Push the [OFF]
pushbutton in order to enter the OFF mode.
10
Be142 OEM's Manual V3.X.XX - January - 2015 page 11
1) - Enter the programming as indicated in section 6.10 and table 6.11. When the display indicates the
parameter [P.0], push and hold the [ACK-F10] pushbutton for about 10 seconds until the messages [PP.PP] and
[4242] appear. The two digits on the right side of the display will blink.
2) - Push [TEST] or [AUTO] in order to choose a code.
3) - Push [←F8] to select the 2 digits on the left side. Repeat step 3) in order to choose a code
4) - Press the [OFF] pushbutton if you want to exit the procedure without activating the password.
5) - Press and hold the [ACK-F10] and [F9→] pushbuttons simultaneously until the [SAVE] message appears
(approximately 5 seconds); the Be142 saves the password and remains in PROGRAM mode. To exit, push the
OFF pushbutton.
1) - Enter the programming mode as indicated in section 6.10 part 3 (you are required to use the old password).
2) - When the display indicates the parameter [P.0], push and hold the [ACK-F10] pushbutton, for about 10
seconds until the display indicates in sequence [PPPP] and [4242]. The two digits on the right side will start to
blink. The code [4242] disables the use of the password. Follow step 3 of 4 according to your needs.
3) - Press the [OFF] pushbutton if you no longer want to remove the password (exits the procedure).
4) - Press and hold the [ACK-F10] and [F9→] pushbuttons simultaneously until the [SAVE] message appears
(approximately 5 seconds); the Be142 saves the code [4242] that disables the password. The Be142 remains in
PROGRAM mode. To exit, push the OFF pushbutton.
11
Be142 OEM's Manual V3.X.XX - January - 2015 page 12
Table 7.01A - Mains Failure Control Note: [ xx " ] = seconds, [ xx ' ] = minutes, [xxh ] = hours
P.0 Mains Contactor control (KM). If the Mains Failure persists for more than [P.0] [ 5’’] 0 59 mins
(seconds or minutes), the Mains contactor will open and the [P.1] timer will start to
count. The Mains contactor will close only after the [P.2] timing.
P.1 Mains Failure time. After the [P.0] timing (see above), the engine will start if the [ 5’’] 0 23 h
Mains Failure persists for the [P.1] time.
P.2 Mains Restore time. The Be142 transfers the Load to the Mains once the MAINS [ 5’’] 0 23 h
is stable for at least [P.2] (seconds, minutes or hours). During [P.2], the engine will
continue to run ON-LOAD. After [P.2], the [P.24] timer will take place to run the engine
OFF-LOAD (the contactor of the generator will open).
Table 7.01B - Mains Failure Control Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
P.3 Contactors changeover. This timing introduces a delay [ 2’’] 0.1secs 15.0secs -
between the switching of the contactors.
P.4 Under voltage limit. If the Phase-to-Phase voltage falls [320] 60V 998V
under this limit, the [P.0] timer will energise. [oFF]
P.5 Over voltage limit. If the Phase-to-Phase voltage rises [500] 60V 998V [oFF]
above the limit, the [P.0] timer will energise.
P.6 Under Hz limit. If the Phase-to-Phase frequency falls [47.0] 20.0Hz 70.0Hz
under the limit, the [P.0] timer will energise. [oFF]
P.7 Over Hz limit. If the Phase-to-Phase frequency rises [53.0] 20.0Hz 70.0Hz
above the limit, the [P.0] timer will energise. [oFF]
12
Be142 OEM's Manual V3.X.XX - January - 2015 page 13
Table 7.02A - GENERATOR PARAMETERS Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
Parameter Code & Description Mode (°) Default Min Max Options
P.9 Under voltage (AUTO & TEST mode) 1 [320] 60 V 998 V [oFF]
P.11 Under Hz (AUTO & TEST mode) 1 [47.0] 20.0 Hz 70.0 Hz [oFF]
(°) Mode1: The engine shuts down after a cooling down time ([P.24]). (°) Mode2: The engine shuts down without a cooling down time.
(°) Mode3: The Be142 provides a warning if the parameters rise above the setting for the specified timing.
(*) The setting is allowed in step of 5 Amps by using the pushbutton on Be142 or in step of 1Amp by using programming by Computer.
P.15 Alternator failure options. The alarm [E04] energises if the [oFF] - - [on]
voltage (or the frequency) is lower than the setting of P.9 (or [oFF]
P11) for more than 150 seconds.
P.16 Alternator number of Poles. Options [2] or [4] allow you to [4] 2 4 -
display the engine speed.
P.17 Generator Contactor Control. The option [off] inhibits Load [oFF] - - [on]
transfer to the generator in TEST mode (or remote TEST) [oFF]
when MAINS is present.
13
Be142 OEM's Manual V3.X.XX - January - 2015 page 14
Table 7.03A - ENGINE PARAMETERS Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
P.20 Crank time (maximum cranking time if the [ 5" ] 1 sec 15 secs -
engine fails to start during the attempt)
P.21 Rest time (pause of time between starting [ 5" ] 3 secs 15 secs -
attempts)
P.22 Pre-glow time (see ‘Modes’ for the mode of [ oFF ] 1 sec 59 mins [ oFF ]
operation
P.26 Crank termination setting (Charger Alternator) [ 8.0 ] 3.0 V 30.0 V [oFF]
Table 7.03B - ENGINE PARAMETERS Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
P.29 Low Oil pressure warning [oFF] 0.1 Bar 20.0 Bar [oFF]
P.32 Purge timing (for Gas fuelled engine) [ 1" ] 1 sec 15 secs -
14
Be142 OEM's Manual V3.X.XX - January - 2015 page 15
Table 7.04 - ALARM OPTIONS Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
P.33 Alarm bypass (for Oil, Temperature, Auxiliary1- [ 5" ] 2 secs 90 secs -
2-3-4 alarms)
P.34 Fail to stop alarm control (oFF = inhibited, [oFF] - - [oFF]/ [on]
on = enabled)
P.36 No fuel bypass timeout (it starts to count when [ 5' ] 15 secs 99 mins
you activate the Low Fuel Input, terminal #33. It
shuts down the engine after timeout) [oFF]
P.39 Engine Temperature Switch type (input # 34) [n.o.] - - [n.o. / n.c.]
Table 7.05 - MISCELLANEOUS Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
P.41 Periodic Test interval (see 16.10) [oFF] 2 hours 9999 h [oFF]
P.50 Horn timeout (see section 8.0) [ 5" ] 5secs 15 mins [oFF]
15
Be142 OEM's Manual V3.X.XX - January - 2015 page 16
_
Table 7.07 - Input Options List
Option Option
[0] Off: disables the input [ 14 ] Generator simulation ON
[1] Immediate Stop [ 15 ] Mains Simulated ON
[2] Bypass and Stop [ 16 ] Front panel LEDs test
[3] Cooling and Stop [ 17 ] Horn silence
[4] Bypass+Cooling and Stop [ 18 ] Display Right Pushbutton
[5] Warning only (^) [ 19 ] Display Left Pushbutton
[6] Bypass and Warning [ 20 ] Overload Input Warning
[7] Remote Manual Mode (^^) [ 21 ] Overload Input Shutdown
[8] Remote Auto Mode (^^) [ 22 ] KG Forced closed
[9] Remote Off Mode (^^) [ 23 ] KM Forced closed
[ 10 ] Remote Engine Test [ 24 ] KG LED Feedback
[ 11 ] Remote Generator Test [ 25 ] KM LED Feedback
[ 12 ] Ejp function [ 26 ] Idle Engine
[ 13 ] Remote LOCK [ 27 ] Manual START pushbutton
[ 28 ] Manual STOP pushbutton
16
Be142 OEM's Manual V3.X.XX - January - 2015 page 17
(^^^) If an input is configured with option [20] or [21] (see table 7.07)
17
Be142 OEM's Manual V3.X.XX - January - 2015 page 18
18
Be142 OEM's Manual V3.X.XX - January - 2015 page 19
If you use the Be142 to control a PUMP SET, we recommend the use of the following settings:
The Be142 inhibits the starter motor when the engine starts running. When the engine is not running, voltage in
terminal D+/WL of the charger alternator (input #22) is 0 V. As soon as the Be142 starts the engine, a voltage
appears in the D+/WL terminal (0.8 to 2.5 V). When the engine starts running, the voltage of the D+/WL terminal
increases by up to 3 V - 6 V. When the engine runs, the voltage reaches 14 V (28 V) needed to charge the
battery. The safest point to disconnect the starter motor is between 6 V to 10 V. The default parameter of [P.26]
is 8.0 V. This value is recommended for engines using 12 V batteries. For 24 V batteries, we recommend that
you set the threshold to 16 V.
For safe calibration, be sure that the green ‘ENGINE RUNNING’ LED on the front panel is off during all of the
starting attempts. The Charger Alternator voltage can be displayed in the 'Engine menu' as indicated in the
section 3.0. For Flywheel chargers, the reading is not accurate. The [P.26] setting, in this case, expresses only a
proportional factor.
The Be142 also uses the output of the Generator in order to disconnect the crank motor. Parameters [P.27] and
[P.28] set the crank termination. These parameters do not affect the status of the green ‘ENGINE RUNNING’
LED. The insertion of switches or breakers in series to terminals #13 and #14 is not recommended.
NOTE: THE ‘ENGINE RUNNING’ LED MUST BE LIT WHEN THE ENGINE RUNS. USING THE ENGINE
WITHOUT THIS SIGNAL MAY BE DANGEROUS.
Normally, using a diesel engine, we recommend enabling the BELT BREAK protection. This is accomplished by
programming a voltage setting in the [P.26] sub-menu. To test the efficiency of this protection, disconnect
terminal D+ from the charger alternator and connect to ground the #22 terminal. This protection is delayed by 15
seconds.
1) - Make sure the Battery voltage is over 12.0 Vdc and select the MAN mode. Start the engine if you need to
calibrate a parameter of the generator or,
2) - Push and hold the [F9→] and [ACK-F10] pushbuttons simultaneously, for about 5 seconds, until the yellow
LED [h/Prog.] starts to blink and display indicates [-CAL]; release the buttons.
3) - If the Be142 programming is password protected, the message [42.42] will appear; follow the instructions in
table 6.11. If the Be142 is not password protected, the parameter [n1.n2] will appear on the display and you can
proceed as indicated in section 12.2.
19
Be142 OEM's Manual V3.X.XX - January - 2015 page 20
12.2 - Calibrating a measurement (Note: to exit the procedure push the [OFF] pushbutton at anytime)
1) - Press the [←F8] or [F9→] pushbutton to select a 'Parameter name' (see Table 12.2).
2) - Press the [ACK-F10] pushbutton to display the reading of the measurement (example 395 V).
3) - Press the [TEST ↑] (or [AUTO ↓]) to adjust the reading according to an external reference (example 400 V).
4) - When finished, push the [ACK-F10] again to display the 'Parameter name'. Select another 'Parameter
name' to calibrate by pushing the [←F8] or [F9→] pushbutton. When finished, you have 3 options: 5A, 5B or 5C.
5 A ) - Exit the procedure without saving by pushing the [OFF] pushbutton.
5 B ) - Restore the factory default calibration: press and hold the [←F8] and [F9→] pushbuttons simultaneously
until the display blinks twice. You are required to save the setting as indicated in step 5C).
5 C ) - Save the calibration: push and hold the [ACK] and [F9→] pushbuttons simultaneously until the [SAVE]
message appears (approximately 5 seconds); the Be142 saves the calibrations and remains in Manual mode.
(°)Note: in order to obtain a reading on display you are required to set a value in P29, P30 and P38
- Remove the supply. Push and hold the [I-F3] & [I-F5] pushbuttons simultaneously and apply the Vdc supply.
- As soon as the message AUTO-TEST appears, release the pushbuttons; the display will indicate [ F1].
- Push [F1] and then push, one by one, all pushbuttons indicated by the message on display.
- After pushing the last pushbutton ([AUTO]), the message [-EPP] will appear; wait a few seconds.
- The memory, now, is erased. The Be142 will use the factory-programmed parameters (defaults).
- Remove the supply and re-program the controller according to your need. We always recommend that you
program a password in order to limit the access (see section 6.40).
The Basic Troubleshooting Guide is intended to provide you with a guide to problems that you may experience
with the Be142. We recommend that you disconnect the unit from the panel and set up the troubleshooting
application circuit as indicated in section 13.1. This procedure should only be carried out by qualified personnel.
20
Be142 OEM's Manual V3.X.XX - January - 2015 page 21
1A-FUSE
3 x Resistor 1%
Switches (100-1000Ohm) 12-24V
(normally-open)
Not connected
40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21
TERMINATION
GROUND SENSING
CONFIGURABLE 2
CONFIGURABLE 4
CONFIGURABLE 3
CONFIGURABLE 1
EMERGENCY STOP
SIGNAL-B
SIGNAL-A
OIL PRESSURE
TEMPERATURE
GROUND
OIL-PRESSURE
TEMPERATURE
LOW FUEL
RUNNING
RUNNING
BATTERY
BATTERY
FUEL-LEVEL
MODBUS
OUTPUTS
GENERATOR CONT.
MAINS CONTACTOR
CONFIGURABLE 4
CONFIGURABLE 3
CONFIGURABLE 2
CONFIGURABLE 1
FUEL SOLENOID
STOP SOLENOID
CHARGER ALT.
START PILOT
1 2 3 4 5 6 7 8 9 10
3W - LAMP
NOTE - At this stage of the TEST, if the display indicates one of the codes contained in Table13.1 or 13.2,
the Be142 is damaged and should be returned to Bernini Design.
A) - Push the pushbuttons on the front panel one by one. The display will show a message according to Table
13.1. As soon as you release all buttons, the message [- - - -] will be displayed.
21
Be142 OEM's Manual V3.X.XX - January - 2015 page 22
Push and hold the [ACK-F10] button until the message [-in-] appears. Connect, one by one, inputs #29 to #36 to
the battery minus. For each input, a code will be displayed according to Table 13.2. If more than one input is
connected together (or some of them in short circuit), the display indicates the messages in sequence.
Table 13.2
Terminal number Display Terminal number Display
(function) Code (function) Code
#29 (Input 4) [ inP 4] #33 (Low fuel) [ FUEL]
#30 (Input 3) [ inP 3] #34 (Temperature) [ tEMP]
#31 (Input 2) [ inP 2] #35 (Oil pressure) [ oiL]
#32 (Input 1) [ inP 1] #36 (Emergency) [ EMEr]
22
Be142 OEM's Manual V3.X.XX - January - 2015 page 23
13.4 Testing the senders and analog inputs
A) - Push the [ACK-F10] pushbutton, for about 10 seconds, until the message [SEnS] appears. If the display
indicates the message [Gnd] you are requested to connect the ground compensation input terminal #25.
B) - Apply 3 resistors of known value (+/- 1%) in a range 100 Ohm up to 1000 Ohm as indicated in section 13.1.
C) - Push the pushbuttons according to the Table 13.4. You should read the value in OHM on the display. The
display indicates the reading as long as you push and hold the button. If the value indicated by the display is
more than 3% (or less than 3%), the Be142 is damaged and should be returned for service.
Dimensions: 224 mm X 105 mm X 68 mm, Panel Cut-out: 190 mm X 93 mm, indoor operation
Operating Temperature range: -30 deg C up to +70 deg C. Humidity Range: 5% up to 95% non-condensing.
Weight: 500 gr., Vibration: 40 mm/sec
General Design: 89/336 EEC, 89/392 EEC, 73/23 EEC, 93/68 EEC, IEC 68-2-6 Certification: CE
Mains and Generator Voltage Inputs: Nominal Voltage: 80 Vac up to 600 Vac (permanent & continously Ph-Ph)
Over voltage: 4 KVac for one second. Measurement precision: +/- 2% [**]. Input impedance: 2 Mega Ohm
Mains and Generator Frequency Measurements: 30-99Hz, Resolution 0,1Hz, Precision/Accuracy 0,2% /0.2%.
Current Transformer Inputs (3-Phases): 10 / 5 Aac up to 1000 / 5 Aac. Maximum Over Current: 8 Aac for 30 seconds.
Measurement precision: +/- 2% [**]. Internal resistance: 0.05 Ohm
Digital /Analog Inputs: Open circuit voltage: 10 /22 Vdc (12 V /24V supply). - Closed circuit current: 15 mAdc max.
Sensors (Analog Inputs): 0-2000 OHM precision +/-2% .(BAR/FUEL%TEMPERATURE reading precision 2%)
Charger Alternator Monitoring: Operating 3-36 Vdc. Vdc reading accuracy +/- 2%. Excitation Power: max 3 W
Hour Run Counter & Timers: internal Quartz Crystal oscillator 4.91Mhz. Resolution 1 second; precision 0,25%
[*] NOTE: the sum of the total output current (# 1- # 10) may not exceed 2 A at 70°C
[**] NOTE: errors can be reduced by using the calibration mode (section 12.0)
[***] NOTE: operations with memory (storing parameters, hours, etc) are allowed only if the Vdc is over 11.5V.
23
Be142 OEM's Manual V3.X.XX - January - 2015 page 24
Section 16.0 Application Notes
16.10 - Programming of the Automatic Periodic Test (example: 20 minutes every 7 days)
A) - Enter the 'Program Mode' and set [P.41] to [168] hours (168 hours=7days).
B) - Set [P.42] to [ 20'] and save the programming
C) - Select the AUTO mode
D) - Disconnect the battery and wait for the desired start time (using an external clock reference).
E) - Connect the battery and select the 'AUTO' mode.
The Be142 will start the engine after the programmed hours. The engine will run OFF-LOAD for 20 minutes. If
the Mains fails during the automatic periodic test, the Be142 will transfer the load to the generator.
The Be142 does not use an internal real time clock for the programmed hours ([P.41] setting, table 7.05). The
user could experiment with shifting the periodic tests (about some minutes a month). To avoid error
accumulation, we recommend the following procedures (D) and (E) as indicated in section 16.10.
IMPORTANT NOTICE If the Vdc voltage supply is removed, the Be142 loses count of the days. When the
supply restores, the Be142 starts to count the A.P.T. from zero. To synchronize the periodic start follow the
above instructions (D) & (E).
To use the Be142 as an A.T.S. controller, follow the wiring diagram of the section 17.0. If the engine running
output from the AUTOSTART is not available, program the [P.26] to [oFF]. We recommend that you program the
[P.31] to [15] (number of attempts) in order to provide proper time for AUTOSTART to start the engine.
Program the parameter [P.8] with the proper option as indicated in section 7.01B. Connect the Mains to
terminals ‘R’ (Phase) and ‘S’ (Neutral). Connect the Generator to terminals ‘L1’ (Phase) and ‘L2’ (Neutral).
Connect the current transformer to terminals ‘COM’ and ‘CT1’. Do not forget to set P4, P5, P9 and P10
(Over/Under Voltage settings) according to your needs.
------------------------------------------------------------------------------------------------------------
24
Be142 OEM's Manual V3.X.XX - January - 2015 page 25
Section 17.0 - Automatic Transfer Switch (A.T.S.) controller wiring diagram
RS-485-LINK
EMERGENCY
K-ALARM
(Switch)
Be142 Rear View
40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21
TERMINATION
GROUND SENSING
CONFIGURABLE 2
CONFIGURABLE 3
CONFIGURABLE 4
CONFIGURABLE 1
EMERGENCY STOP
SIGNAL-B
SIGNAL-A
OIL PRESSURE
TEMPERATURE
GROUND
OIL-PRESSURE
TEMPERATURE
LOW FUEL
RUNNING
RUNNING
BATTERY
BATTERY
FUEL-LEVEL
MODBUS
36Vdc 60Vdc
DIGITAL INPUTS SENSOR INPUTS Max. Max.
SUPPLY
INPUT
MAINS CONTACTOR
CONFIGURABLE 4
CONFIGURABLE 3
CONFIGURABLE 2
CONFIGURABLE 1
FUEL SOLENOID
STOP SOLENOID
CHARGER ALT.
START PILOT
Max.
600Vac 600Vac
Max. Max.
COM.
C.T. 1
C.T. 2
C.T. 3
1 2 3 4 5 6 7 8 9 10 L L L T S R
3 2 1
KGC
(**)
KMC
KFS
K-ALARM Mechanical
N interlock N
MAINS
S
T
KG KM
N
A B C L1 L2 L3
(*)
KM-AUX KG-AUX
N KGC KG KM KMC
A B C L1 L2 L3
Autostart Terminal Block Power ac Terminal Block
(**) Relays connected to the Be142 must be
GENERATING SET suppressed using flywell diodes
(*) Shielding required over 25 meters
25
Be142 OEM's Manual V3.X.XX - January - 2015 page 26
Vac
40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21
TERMINATION
GROUND SENSING
CONFIGURABLE 2
CONFIGURABLE 3
CONFIGURABLE 4
CONFIGURABLE 1
EMERGENCY STOP
SIGNAL-B
SIGNAL-A
OIL PRESSURE
TEMPERATURE
GROUND
OIL-PRESSURE
TEMPERATURE
LOW FUEL
RUNNING
RUNNING
BATTERY
BATTERY
FUEL-LEVEL
MODBUS
36Vdc 60Vdc
DIGITAL INPUTS SENSOR INPUTS Max. Max.
SUPPLY
300mA
Max. CURRENT GENERATOR MAINS INPUT
OUTPUTS
INPUTs INPUT
GENERATOR CONT.
MAINS CONTACTOR
CONFIGURABLE 4
CONFIGURABLE 3
CONFIGURABLE 2
CONFIGURABLE 1
FUEL SOLENOID
STOP SOLENOID
CHARGER ALT.
START PILOT
Max.
600Vac 600Vac
Max. Max.
COM.
CT 1
CT 3
CT 2
1 2 3 4 5 6 7 8 9 10
L L L T S R
3 2 1
KGC
(°°)
KMC
Mechanical
N interlock N
L1 R
KC1 MAINS
L2 S
(°°) L3 T
KFS
KG KM
KSS
Charger KG KM
2A Fuse Alternator 30A Fuse
B+
D+
KFS 20A 20A 20A
KSP 40A KSS KC1
Rated Rated Rated
Rated
12-24V Starter
Pilot
Battery negative Starter Motor Fuel Solenoid Horn
must be grounded Valve
(°°) Relays connected to the Be142 must be suppressed using flywheel diodes
26
Be142 OEM's Manual V3.X.XX - January - 2015 page 27
Be142 Be142
Fuses
NOTE
Battery charger the separation of the battery Battery charger
(see NOTE)
charger wires is a mandatory
requirements in case of
switching or SCR chargers
Fuel sensor
Temperature sensor
Ground reference
Oil sensor
Be142
Miscellaneous
A V Hz / R.P.M. Engine h / Prog. Shipping Dimensions: 130x250x60mm
TEST
224 mm 14 45 mm
204 mm mm
105 mm
84 mm
91 mm
27
Be142 OEM's Manual V3.X.XX - January - 2015 page 28
Section 21.0: Connections description
28