DS Catalogue UPS English
DS Catalogue UPS English
DS Catalogue UPS English
UPS
Uninterruptible Power Supplies
GE imagination at work
UPS
For more than a century, GE has led the way with innovative technologies and groundbreaking quality initiatives literally helping to power the world. Along the way, through the development and delivery of state-of-the-art products and uncompromising service, GE has also built a legacy as a leading supplier of critical power solutions. To bridge the gap between the traditional utility grid and the needs of todays business, GE offers a complete portfolio of critical power products and services, from desktop Uninterruptible Power Supply (UPS) units to engineered power systems, and from basic UPS and battery maintenance to comprehensive service contracts covering every aspect of your power quality and delivery system. At GE, our goal is simple to never let power quality stand in the way of our customers success. Thats why GE is committed to continue developing and delivering UPS technology for the digital world
UPS topologies RPA Redundant Parallel Architecture IEM Intelligent Energy Management Service for mission-critical power Overview UPS families
A.1
UPS
UPS topologies - a brief overview
Passive Standby
The passive standby system channels the incoming mains power, via a lter, directly to the load. As soon as the incoming power is outside tolerance, the UPS switches to battery operation. GEs solution: none
mains
lter
Introduction
battery
Line-Interactive
A B X
The line-interactive system channels the incoming mains power, via an AVR - Automatic Voltage Regulator, directly to the load. Compared to off-line, the system can handle much larger voltage variations before switching to battery operation. GEs solutions: ML Series, Match
mains
lter
AVR
battery
Double Conversion
Input and output are completely separated: the output converter (DC to AC, or = to ~) continuously supplies the critical load with a completely new, regulated and clean sine wave output. No switching takes place when the incoming mains power gets outside tolerances. A bypass switch automatically transfers the load to the mains when the output converter is unable to supply the load (e.g. due to overload or overtemperature). GEs solutions: NetPro, LP Series, SitePro, SG Series
static switch
battery
A.2
UPS
RPA - Redundant Parallel Architecture
The principle GE provides a unique technology called Redundant Parallel Architecture (RPA) that can parallel Uninterruptible Power Supply (UPS) modules with true redundancy. With RPA, there is no need for external electronics or switches to control the UPS modules in the parallel system. One of the UPS modules in the system arbitrarily takes a leadership role, while the other UPS modules have access to all control parameters. If one UPS fails to operate, the load is automatically redistributed among the others. If the lead UPS fails to operate then a different UPS automatically takes on the leadership role. The RPA systems are designed to have no single points of failure, ensuring the highest level of power protection for critical loads.
UPS 1
mains UPS 2
load
RPA
A unique concept Many other so-called redundant UPS offerings have one critical shortfall, in that they have critical components that are not redundant. RPA technology provides complete redundancy of all critical components and there are no single points of failure. RPA technology allows UPS system expansion not only to increase capacity but also to improve the reliability of the power provided to critical loads. For mission critical applications, RPA technology provides true redundancy for the highest reliability.
A B X
Characteristics RPA Conguration provides complete redundancy of all critical components and allows paralleling of up to four units for increased load capacity. It ensures excellent dynamic behaviour based on output voltage load sharing. This provides the highest reliability and availability for mission-critical applications. Modular design allows for system upgrades to meet future power needs without any interruption to the critical load or transfer to bypass. Easy to install and maintain. Scaleable design allows for efcient use of capital. Peer-to-Peer architecture where any UPS can be the logic leader ensuring no single points of failure.
A.3
UPS
RPA - a comparative overview
Multiple UPS are congured in a system to support an increase in load capacity and/or to improve reliability. There are several congurations that include multiple UPS. These congurations all share a common shortfall: they all have critical components that are not redundant.
Parallel system with automatic transfer switch The parallel system with an Automatic Transfer Switch (ATS) consists of one or more UPS modules with outputs connected by a switch that senses a loss in voltage and transfers the load to a different module or modules.
utility
UPS #1
communication link
UPS #2
Introduction
Characteristics If one of the UPS modules fails, another unit is available to provide power to the load. No load sharing. Additional cost of the ATS.
A B X
Parallel system with paralleling cabinet The parallel cabinet conguration uses an external set of centralised electronics to distribute the load between the systems UPS modules.
The ATS is a single point of failure: if it fails, the load will be interrupted even if utility power is available.
utility
Characteristics If one of the UPS modules fails, another unit is available to provide power to the load. Motor-operated breakers replace the function of the ATS. While less expensive than an ATS, they operate much more slowly. Failure or malfunction of the shared control electronics will result in a load interruption, which is possible even if the power is present. The shared electronics package is a single point of failure. Non-redundant communications links. System price is increased because of the additional cost of the shared control electronics and motor-operated breakers.
A.4
UPS
RPA - a comparative overview
Hot standby The cascade system or isolated redundant system uses the bypass static switch of the primary UPS to tie the output of a secondary (stand-by) UPS to the load.
critical load output
secondary UPS
primary UPS
Characteristics
RPA
Inexpensive, since no additional components are added to the system. There are many single points of failure. No sharing of the load. If the primary unit fails, the secondary unit must be able to accept a 100% load increase in 10 milliseconds. Overload capacity is limited to the rating of the static switch of the primary module. System MTBF* is typically lower than the MTBF of a single module. * Mean Time Between Failures.
A B X
Parallel system with centralized logic The parallel system with centralized logic is basically designed the same as the paralleling cabinet conguration. The difference is that they utilize the control electronics of one lead UPS module to control the distribution of the load between the systems other modules.
lead UPS #1
UPS #2
UPS #3
UPS #4
UPS #5
UPS #6
critical load
Characteristics No ATS required. If the lead UPS module fails, the remaining units are uncontrolled. The system may go to bypass on all units, or may stop operation completely. If the communication link between the lead and other units fails, the load may be interrupted even without a utility power failure.
As stated before, these congurations all share a common shortfall: they all have critical components that are not redundant. GEs RPA technology provides complete redundancy of all critical components and there are no single points of failure. RPA technology allows UPS system expansion not only to increase capacity but also to improve the reliability of the power provided to critical loads. For mission critical applications, RPA technology provides true redundancy for the highest reliability.
A.5
UPS
IEM - Intelligent Energy Management
GE offers the award-winning Intelligent Energy Management (IEM) capability to optimise energy costs while maintaining the highest possible reliability for parallel redundant UPS systems.
10% 15%
38%
37%
purchasing direct operating cost indirect operating cost maintenance
Introduction
The life cycle cost of a UPS system is built up from different components. In general, approximately half of the total cost is operating cost as a result of energy losses - both direct heat losses in the UPS and indirect energy losses of the air conditioning system. UPS systems are engineered into applications taking into account the maximum load that needs to be supplied by the system. In practice the UPS will only supply a part of that load for most of the time. Many applications are shut down outside business hours. In addition very often a safety margin is included (over-dimensioning) for future expansion. As a result the system is not used at its nominal rating most of the time during operation. This reduces the efciency of the system and increases the energy costs. For parallel UPS installations, secured with RPA, IEM saves energy by dynamically utilising the UPS modules as required to supply the load without compromising on the power reliability.
A B X
load
80%
The set-up of IEM is exible, giving the end user the freedom of choice to select redundancy degrees in different time periods. IEM also rotates amongst the units that are switched off to get operating hours equally distributed over all units. Use of IEM resulted in incremental energy savings of up to $33,000 annually for a system of four 100kVA units secured by RPA operating at full load for 50 hours per week and partial load (10%) for the remaining time.
20%
20%
time In a typical application the actual load supplied is generally smaller than the nominal rating of the system
Benets Reduced energy consumption Maintaining of power quality and reliability to the critical load Mains power quality monitoring User-denable protection levels Scheduled activation Automatic switch on of additional units in critical situations, increasing reliability Equal operating hours for each UPS in a parallel system
A.6
UPS
IEM - compared to legacy parallel system
load UPS 1 100 kVA UPS 2 100 kVA UPS 3 100 kVA UPS 4 100 kVA
75%
Legacy Parallel System Full-Load Condition In full load condition the efciency of a UPS is optimal. However, this condition only occurs typically 10 hours / day.
75%
75%
efciency 4 UPS
75%
load %
load UPS 1 100 kVA UPS 2 100 kVA UPS 3 100 kVA UPS 4 100 kVA
15%
IEM
15%
load 60 kVA
15%
18:00
In partial load condition (most of the time) the efciency of the UPS is lower causing higher energy costs.
efciency 4 UPS
A B
15%
load %
X
load UPS 1 100 kVA load = 20% UPS 2 100 kVA UPS 3 100 kVA UPS 4 100 kVA
30%
time
07:00
IEM Intelligent Energy Management Partial Critical Load Condition (UPS Redundancy) With IEM installed 2 units will be switched off automatically. In this way the efciency is improved, still maintaining a n+1 redundant system.
load 60 kVA
18:00
efciency 2 UPS
30%
load %
load UPS 1 100 kVA load = 20% UPS 2 100 kVA UPS 3 100 kVA UPS 4 100 kVA
60%
time
07:00
IEM Intelligent Energy Management Partial non-Critical Load Condition (Utility Redundancy)
load 60 kVA
18:00
efciency 1 UPS
load %
With IEM installed 3 units can be switched off. In this way the efciency is improved even more. The bypass is still available and will supply the load in case of a failure.
A.7
UPS
Service for mission-critical power
Service coverage GE has local ofces in a number of countries around the globe and also a network of selected business partners, whose salespeople and service engineers combine expertise in our solutions with an in-depth knowledge of local market conditions. GEs business partners, located in more than 80 countries around the world, use all that expertise and knowledge to adapt GEs products and services precisely to their customers needs.
Service
Whether you are a large corporation with multiple sites or a small business owner with a single location, GE will enable you to have a constant supply of clean and reliable power to keep your business up and running. We are at home in all industries, specialized in solutions and services for your electrical infrastructure, including: Critical power systems UPS systems stationary battery systems static transfer switches (STS) Low voltage equipment maintenance & service contracts extended warranty remote monitoring & diagnostics Industrial controls variable speed drives soft starters PLC
Service portfolio GE offers a comprehensive portfolio of power quality services including: On site & emergency services 24*7 emergency hotline installation, commissioning, start-up and upgrades repair, upgrade, retrots assessment, inspection, testing on-line assistance Contractual services maintenance & service contracts extended warranty remote monitoring & diagnostics guaranteed intervention times preventive, planned maintenance resident technical services upgrade management Parts and repairs spare parts supply repair services replacement / return web based parts supply equipment rental Training training for operators training for maintenance staff product training web based training
A B X
24*7
A.8
UPS
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.9
A B X
UPS
UPS families - overview
Line-interactive
UPS - overview
1-1 phase
0.5-3 kVA
0.6-4 kVA
LP 11 LP 31T
8-20 kVA
A B X
3-1 phase
5-10 kVA
LP 31 LP 33 10-30
40-120 kVA
Hard-wired
10-30 kVA
3-3 phase
10-500 kVA
80-200 kVA
SG Series
A.10
Numerical Index
B.1
UPS
ML Series - line-interactive UPS Applications
The line-interactive Digital Energy ML Series UPS is used in a wide range of IT, networking and telecommunications applications. It will protect servers, hubs, switches and routers, and may also be installed to protect PCs, workstations, cash registers, fax machines, modems and ISDN adaptors.
Order codes
Characteristics
The line-interactive ML Series UPS normally supplies the load through a bypass circuit. Filtering capabilities guard against surges, spikes and high frequency interferences. The utility also keeps the battery fully charged. The input voltage window is extremely wide: as long as the input voltage is within 140-300 Vac (ML 350-700 VA) or between 160-265 Vac (ML 1000 VA) the Automatic Voltage Regulation (AVR) guarantees an output voltage that is between 198-265 Vac and acceptable for every modern ICT device. In case of a mains failure the UPS switches to battery operation with a transfer time of 4 milliseconds, sufciently short for computers which therefore will continue to operate without interruption.
Function
A B X
Standards / Marking
Safety: EN 50091-1-1; EN 60950; EMC: EN 50091-2
B.2
UPS
ML Series - line-interactive UPS
ML Series
Rating (VA / W)
TM
Ref. No.
ML - line-interactive
Option
Manual service bypass 53x130x204 0.8 912349
A B X
B.3
UPS
Match Series - line-interactive UPS Applications
The line-interactive Digital Energy Match Series UPS is used in a wide range of IT, networking and telecommunications applications. It will protect servers, hubs, switches and routers, and may also be installed to protect PCs, workstations, cash registers, fax machines, modems and ISDN adaptors.
Order codes
Characteristics
The line-interactive Match Series UPS normally supplies the load through a bypass circuit. Filtering capabilities guard against surges, spikes and high frequency interferences. The utility also keeps the battery fully charged. The input voltage window is extremely wide: as long as the input voltage is within 165-275 Vac (Match 500-1500 VA) or even between 140-305 Vac (Match 2200-3000 VA) the Automatic Voltage Regulation (AVR) guarantees an output voltage that is between 190-254 Vac and acceptable for every modern ICT device. In case of a mains failure the UPS switches to battery operation with a transfer time of 4 milliseconds, sufciently short for computers which therefore will continue to operate without interruption.
Function
A B X
Standards / Marking
Safety: EN 50091-1-1; EN 60950; IEC 60950 EMC: EN 50091-2
(1) Max. power factor Match 500-1500: 0.6; Match 2200/3000: 0.7
B.4
UPS
Match Series - line-interactive UPS
Match
1000-3000 VA Rating (VA / W) 500/300 700/420 1000/600 1500/900 2200/1540* battery pack 3000/2100* battery pack Runtime (minutes) at 100% load 4 8 8 10 5 5 Dimensions (hxwxd, mm) 144x155x350 144x155x350 225x180x360 225x180x360 225x187x485 225x187x485 225x187x485 225x187x485 Net weight (kg) 7.2 10.0 16.5 20.8 18.0 21.3 20.1 26.5 Battery (V/Ah) 12/7 24/7 36/7 36/12 36/14 48/14 No. of outlets IEC 320 3 3 4 4 7 7 Ref. No.
500-700 VA
Match - line-interactive
* UPS enclosure without batteries, order separate battery pack more battery packs can be connected for longer runtimes
Match L
built-in longer runtime 700/420 1000/600 30 20 225x180x360 225x180x360 20.8 20.8 36/12 36/12 4 4 912323 912325
Match 19 inch
700/420 1000/600 1500/900 2200/1540 3000/2100 2200-3000 VA: 6HU 8 8 10 5 5 3HUx19x440mm 3HUx19x440mm 3HUx19x440mm 6HUx19x440mm 6HUx19x440mm 19.0 22.0 26.0 50.0 57.0 12/7 24/7 36/7 36/12 48/14 3 3 4 4 7 912439 912440 912441 915571 915572
A B X
15 15
3HUx19x440mm 3HUx19x440mm
26.0 30.0
36/14 48/14
912453 912454
to increase runtime
Options
Manual service bypass Manual service bypass box, hxwxd = 53x130x204mm DC cable (1.5m) for 3rd party external battery Match 2200 DC cable (1.5m) for 3rd party external battery Match 3000 912349 914850 914851
B.5
UPS
NetPro Series - double conversion UPS Applications
The on-line NetPro UPS is designed for mission-critical applications. It is used in a wide range of IT networking and telecommunications applications: missioncritical servers, telecommunication equipment and local area networks.
Characteristics
Order codes
The NetPro UPS is a true VFI (Voltage & Frequency Independent) on-line double conversion UPS. This technology allows the NetPro to eliminate any power reliability problem. The incoming AC mains power is continuously converted by the input converter to DC, which is used to charge the batteries and to supply the output converter. This output converter synthesizes a completely new AC sine wave output for the connected load. Any mains disturbance is blocked at the input. The 2000-4000 VA models are equipped with a LCD information panel with status and alarm settings. The 3000-4000 VA models have a programmable outlet that can be switched off for less critical loads, thus maximizing up-time of critical devices.
Standards / Marking
A B X
Safety: EN 50091-1-1; EN 60950; IEC 60950 EMC: EN 50091-2; EN 50081-1 + EN 50082-1; IEC 61000-4-5
Function
Providing exceptionally reliable protection for electrical equipment
B.6
UPS
NetPro Series - double conversion UPS
NetPro Series
2000-4000 VA Rating (VA / W) 600/360 1000/600 1500/900 2000/1200 3000/1800 4000/2400 Runtime (minutes) at 100% load 9 8 7 9 9 7 Dimensions (hxwxd, mm) 225x185x430 225x185x430 225x185x430 293x220x557 293x220x557 293x220x557 Net weight (kg) 13.0 15.5 18.0 29.0 38.0 42.0 Battery (V/Ah) 24/7 36/7 48/7 72/7 108/7 120/7 No. of outlets DC connector (batt. ext.) IEC 320 2 2 2 2 2+1 (1) 2+1 (1) no yes no yes yes no Ref. No.
9 mm 6 mm
600-1500 VA
NetPro ISO
2000/1200 3000/1800 9 9 293x220x557 293x220x557 40.0 50.0 72/7 108/7 2 2+1 (1)
(1) programme output
yes yes
912336 912338
galvanic isolation
for NP 1000 for NP 1000 for NP 2000 for NP 2000 for NP 2000 for NP 2000 for NP 3000 for NP 3000 for NP 3000
35 22 36 52 22 37 -
A B X
to increase runtime
NetPro 19 inch
600/360 1000/600 1500/900 2000/1200 3000/1800 9 8 7 9 9 3HUx19x440mm 3HUx19x440mm 3HUx19x440mm 3HUx19x440mm 6HUx19x440mm 19.0 22.0 24.0 29.0 52.0 24/7 36/7 48/7 72/7 108/7 4 4 4 4 4 no no yes yes yes 912444 912445 912446 912447 915573
35 70 36 22
to increase runtime
Options
Manual service bypass Manual service bypass box, hxwxd = 53x130x204mm DC cable (1.5m) for 3rd party external battery NetPro 1000 DC cable (1.5m) for 3rd party external battery NetPro 2000 DC cable (1.5m) for 3rd party external battery NetPro 3000 912349 910042 910043 910044
B.7
UPS
LP 11 Series - double conversion UPS Applications
The on-line LP UPS Series is designed for a range of mission-critical applications. The LP UPS is easy to install and service, optimised for the ofce environment. The robust design allows for more traditional industrial applications.
Order codes
Characteristics
The LP 11 UPS is a 1-phase in / 1-phase out, true VFI (Voltage & Frequency Independent) on-line double conversion, intelligent and heavy duty UPS. The VFI design concept enables the highest level of protection even under the toughest conditions.
Standards / Marking
A B X
The system power and reliability can be easily expanded by adding units, creating a redundant system with no single points of failure, utilizing GEs unique Redundant Parallel Architecture (RPA) technology.
Safety: EN 50091-1-1; EN 60950; IEC 60950 EMC: EN 50091-2; IEC 62040-2 Surge capability: IEC 61000-4-5 (6kV 1.2/50s, 3kA 8/20s)
Function
Providing exceptionally reliable protection for electrical equipment
B.8
UPS
LP 11 Series - double conversion UPS
LP 11 with batteries
Rating (kVA) 3 5 6 8 10
Ref. No.
LP 11 - double conversion
* * * * *
3 5 6 8 10
8 9 7 10 7
* * * * *
LP 11 without batteries
3 5 6 8 10
53 58 63 93 98
* * * * *
A B
3 5 6 8 10
53 58 63 93 98
* * * * *
for LP 5-11 for LP 5-11 for LP 6-11 for LP 6-11 for LP 8-11 for LP 8-11 for LP 10-11 for LP 10-11
24 40 19 32 20 29 15 23
* * * * * * * *
for LP 5/6/8/10-11
537x313x590
20
Options for LP 11
RPA Redundant Parallel Architecture kit (1 per unit) Backfeed relay for LP 3/5/6-11 Connector and cable for 3rd party external battery
* * *
(1) For longer runtimes choose LP 5-11 * For ordering please contact customer service.
B.9
UPS
LP 31T Series - double conversion UPS Applications
The on-line LP UPS Series is designed for a range of mission-critical applications. The LP UPS is easy to install and service, optimised for the ofce environment. The robust design allows for more traditional industrial applications.
Characteristics
Order codes
The LP 31T UPS is a 3-phase in / 1-phase out, true VFI (Voltage & Frequency Independent) on-line double conversion, intelligent and heavy duty UPS. The VFI design concept enables the highest level of protection even under the toughest conditions. The system power and reliability can be easily expanded by adding units, creating a redundant system with no single points of failure, utilizing GEs unique Redundant Parallel Architecture (RPA) technology. The LP 31T is a LP 11 UPS equipped with a 3-1 phase conversion input transformer, galvanically separating the UPS from the incoming 3-phase mains.
Standards / Marking
A B X
Safety: EN 50091-1-1; EN 60950; IEC 60950 EMC: EN 50091-2; IEC 62040-2 Surge capability: IEC 61000-4-5 (6kV 1.2/50s, 3kA 8/20s)
Function
Providing exceptionally reliable protection for electrical equipment
B.10
UPS
LP 31T Series - double conversion UPS
LP 31T with batteries
Rating (kVA) 5 6 8 10
Ref. No.
* * * *
5 6 8 10
9 7 10 7
* * * *
5 6 8 10
* * * *
A B
5 6 8 10
* * * *
for LP 5-31T for LP 5-31T for LP 6-31T for LP 6-31T for LP 8-31T for LP 8-31T for LP 10-31T for LP 10-31T
24 40 19 32 20 29 15 23
* * * * * * * *
537x313x590
20
RPA Redundant Parallel Architecture kit (1 per unit) Connector and cable for 3rd party external battery
* *
B.11
UPS
LP 31 Series - double conversion UPS Applications
The on-line LP UPS Series is designed for a range of mission-critical applications. The LP UPS is easy to install and service, optimised for the ofce environment. The robust design allows for more traditional industrial applications.
Order codes
Characteristics
The LP 31 UPS is a 3-phase in / 1-phase out, true VFI (Voltage & Frequency Independent) on-line double conversion, intelligent and heavy duty UPS. The VFI design concept enables the highest level of protection even under the toughest conditions.
Function
A B X
The transformerless design provides a high efciency. In the ECO Mode the efciency can be even further increased. The batteries are easy to replace by acces via the front. Superior Battery Management optimizes the lifespan of the batteries and keeps you from surprises.
Standards / Marking
Safety: EN 50091-1-1; EN 60950; IEC 60950 EMC: EN 50091-2; IEC 62040-2
13 75 56 28 24 13 10
B.12
UPS
LP 31 Series - double conversion UPS
LP 8-31
Battery capacity (V/Ah) LP 8-31 UPS 8 kVA without battery LP 8-31 UPS with 7Ah battery in UPS cabinet LP 8-31 UPS with 14Ah battery in UPS cabinet 240/7 240/12 Runtime (minutes) at 100% load 14 36 Dimensions (hxwxd, mm) 1190x410x890 1190x410x890 1190x410x890 Net weight (kg) 135 250 355 Ref. No.
LP 31 - double conversion
* * *
LP 10-31
LP 10-31 UPS 10 kVA without battery LP 10-31 UPS with 7Ah battery in UPS cabinet LP 10-31 UPS with 14Ah battery in UPS cabinet 240/7 240/14 10 25 1190x410x890 1190x410x890 1190x410x890 135 250 355 * * *
LP 15-31
LP 15-31 UPS 15 kVA without battery LP 15-31 UPS with 14Ah battery in UPS cabinet 240/14 13 1190x410x890 1190x410x890 150 365 * *
A
LP 20-31
LP 20-31 UPS 20 kVA without battery LP 20-31 UPS with 14Ah battery in UPS cabinet 240/14 10 1190x410x890 1190x410x890 150 365 * *
B X
Battery cabinet without batteries Battery cabinet with batteries 2x240V/14Ah Battery charger 4.2A, necessary for battery capacity over 14Ah on LP 8-31 and LP 10-31 with capacity > 14Ah
925x410x890 925x410x890 -
85 300 -
* * *
Options special
Wooden crate (per cabinet) mandatory for sea and air freights
Runtimes (minutes) at full load, power factor 0.8 LP 8-31 58 80 101 125 LP 10-31 40 58 78 96 LP 15-31 33 55 LP 20-31 25 41
B.13
UPS
LP 33 10-30 Series - double conversion UPS Applications
The on-line LP UPS Series is designed for a range of mission-critical applications. The LP UPS is easy to install and service, optimised for the ofce environment. The robust design allows for more traditional industrial applications.
Order codes
Characteristics
The LP 33 UPS is a 3-phase in / 3-phase out, true VFI (Voltage & Frequency Independent) on-line double conversion, intelligent and heavy duty UPS. The VFI design concept enables the highest level of protection even under the toughest conditions.
Function
A B X
The system power and reliability can be easily expanded by adding units, creating a redundant system with no single points of failure, utilizing GEs unique Redundant Parallel Architecture (RPA) technology.
Standards / Marking
Safety: EN 50091; IEC 62040 Protection: IEC60529 EMC: EN 50091-2 (Class A)
10-33 15 48 27 14 10 7Ah
20-33 15 90 57 35 27 15 10 14Ah
30-33 15 130 80 53 42 28 21 10
21Ah
B.14
UPS
LP 33 10-30 Series - double conversion UPS
LP 10-33
Battery capacity (V/Ah) LP 10-33 UPS 10 kVA with 7 Ah battery, single input LP 10-33 UPS 10 kVA with 14 Ah battery, single input LP 10-33 UPS 10 kVA with 7 Ah battery, single input + RPA LP 10-33 UPS 10 kVA with 14 Ah battery, single input + RPA LP 10-33 UPS 10 kVA with 7 Ah battery, dual input LP 10-33 UPS 10 kVA with 14 Ah battery, dual input LP 10-33 UPS 10 kVA with 7 Ah battery, dual input + RPA LP 10-33 UPS 10 kVA with 14 Ah battery, dual input + RPA LP 10-33 UPS 10 kVA without battery, single input LP 10-33 UPS 10 kVA without battery, single input + RPA LP 10-33 UPS 10 kVA without battery, dual input LP 10-33 UPS 10 kVA without battery, dual input, + RPA LP 20-33 UPS 20 kVA with 14 Ah battery, single input LP 20-33 UPS 20 kVA with 14 Ah battery, single input + RPA LP 20-33 UPS 20 kVA with 14 Ah battery, dual input LP 20-33 UPS 20 kVA with 14 Ah battery, dual input + RPA LP 20-33 UPS 20 kVA without battery, single input LP 20-33 UPS 20 kVA without battery, single input + RPA LP 20-33 UPS 20 kVA without battery, dual input LP 20-33 UPS 20 kVA without battery, dual input, + RPA LP 30-33 UPS 30 kVA with 21 Ah battery, single input LP 30-33 UPS 30 kVA with 21 Ah battery, single input + RPA LP 30-33 UPS 30 kVA with 21 Ah battery, dual input LP 30-33 UPS 30 kVA with 21 Ah battery, dual input + RPA LP 30-33 UPS 30 kVA without battery, single input LP 30-33 UPS 30 kVA without battery, single input + RPA LP 30-33 UPS 30 kVA without battery, dual input LP 30-33 UPS 30 kVA without battery, dual input, + RPA 240/7 240/14 240/7 240/14 240/7 240/14 240/7 240/14 240/14 240/14 240/14 240/14 240/21 240/21 240/21 240/21 Runtime (minutes) at 100% load 10 25 10 25 10 25 10 25 10 10 10 10 10 10 10 10 Dimensions (hxwxd, mm) 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x500x780 1310x660x780 1310x660x780 1310x660x780 1310x660x780 1310x660x780 1310x660x780 1310x660x780 1310x660x780 Net weight (kg) 247 345 247 345 247 345 247 345 113 113 113 113 372 372 372 372 140 140 140 140 520 520 520 520 140 140 140 140 Ref. No.
LP 20-33
* * * * * * * * * * * * * * * * * * * * * * * * * * * *
LP 30-33
A B X
Battery cabinet with 21 Ah batt, including cables (5m) and battery temperature sensor Battery cabinet with 28 Ah batt, including cables (5m) and battery temperature sensor Battery cabinet with 35 Ah batt, including cables (5m) and battery temperature sensor Battery cabinet with 42 Ah batt, including cables (5m) and battery temperature sensor Battery cabinet without batteries, including cables (5m) and battery temperature sensor Mounting set for 7 Ah battery in UPS cabinet (40 blocks) without battery Mounting set for 2x7 Ah battery in UPS cabinet (80 blocks) without battery Mounting set for 3x7 Ah battery in UPS cabinet (120 blocks) without battery Mounting set for each 7 Ah battery in battery cabinet (40 blocks) without battery, incl. fuses Battery fuse box (with fuses) for LP 10-33 Battery fuse box (with fuses) for LP 20-33 Battery fuse box (with fuses) for LP 30-33 Additional battery charger 4.2 A (can be installed in UPS) Note: UPS and battery cabinets without batteries are also without battery mounting sets. To mount locally purchased batteries, order the mounting set.
* * * * * * * * * * * * *
Options special
Wooden crate (per cabinet) mandatory for sea and air freights, 10-20 kVA Wooden crate (per cabinet) mandatory for sea and air freights, 30 kVA Wooden crate (per cabinet) mandatory for sea and air freights, battery cabinets
* * *
Runtimes (minutes) at full load, power factor 0.8 LP 10-33 45 60 80 100 LP 20-33 20 28 37 45 LP 30-33 15 22 28
B.15
UPS
LP 33 40-120 Series - double conversion UPS Applications
The GE Digital Energy LP 33 Series is a highly reliable and cost effective three phase UPS system providing critical power protection for a wide range of applications. The GE Digital Energy LP 33 40-120 was developed using GEs Design for Six Sigma methodology to ensure that the product fully meets customer requirements and expectations.
Order codes
Characteristics
The LP 33 UPS is a 3-phase in / 3-phase out, true VFI (Voltage & Frequency Independent) on-line double conversion, intelligent and heavy duty UPS. The VFI design concept enables the highest level of protection even under the toughest conditions. The LP 33 40-120 UPS offers reliability at its best. The unit is equipped with a redundant power supply ensuring the load being transferred in an instant to the static bypass in the event of a breakdown of the power electronics. To further increase system reliability, 2 or more units can be connected in parallel. In this way a redundant fault tolerant system is created with maximum availability and reliability. The decentralized bypass offers maximum exibility to the end-user for future expansion of the system.
Function
A B X
Standards / Marking
Safety: EN 62040-1; EN 60950; IEC 60950 Protection: IEC 60529 EMC: EN 62040-2 (Class A)
8 12 -
9 12 19
10 12
10
B.16
UPS
LP 33 40-120 Series - double conversion UPS
LP 40-33
Battery capacity (V/Ah) LP 40-33 UPS 40 kVA without battery, THDi < 10% LP 40-33 UPS 40 kVA without battery, THDi < 5% LP 60-33 UPS 60 kVA without battery, THDi < 10% LP 60-33 UPS 60 kVA without battery, THDi < 5% LP 80-33 UPS 80 kVA without battery, THDi < 10% LP 80-33 UPS 80 kVA without battery, THDi < 5% LP 100-33 UPS 100 kVA without battery, THDi < 10% LP 100-33 UPS 100 kVA without battery, THDi < 5% LP 120-33 UPS 120 kVA without battery, THDi < 10% LP 120-33 UPS 120 kVA without battery, THDi < 5% (1) preliminary Runtime (min) at load 100% Dimensions (hxwxd, mm) 1400x600x725 1400x600x725 1800x600x725 1800x600x725 1800x600x725 1800x600x725 1800x725x725 1800x725x725 1800x725x725 1800x725x725 Net weight (kg) 220 220 280 280 290 290 400 (1) 400 (1) 450 (1) 450 (1) Ref. No.
* * * * * * * * * *
Battery cabinets with batteries Battery cabinet with 480 V / 22 Ah battery for LP 40-33 with fuses
Battery cabinet with 480 V / 33 Ah battery for LP 40-33 with fuses Battery cabinet with 480 V / 33 Ah battery for LP 60/80-33 without fuses Battery cabinet with 480 V / 50 Ah battery for LP 60/80-33 without fuses Battery cabinet with 480 V / 2x33 Ah battery for LP 60/80-33 without fuses Battery cabinet with 480 V / 2x33 Ah battery for LP 100/120-33 without fuses
* * * * * *
A B X
Battery cabinets without batteries Battery cabinet without battery for LP 40-33 with fuses
Battery cabinet without battery for LP 60/80-33 without fuses Battery cabinet without battery for LP 60/80-33 without fuses Battery cabinet without battery for LP 100/120-33 without fuses Battery fuse box for LP 40-33 with fuses Battery fuse box for LP 60/80-33 without fuses Battery fuse box for LP 100/120-33 without fuses Battery fuse kit for LP 60-33 Battery fuse kit for LP 80-33 Battery fuse kit for LP 100-33 Battery fuse kit for LP 120-33
* * * * * * * * * * *
RPA Redundant Parallel Architecture Separate bypass input for LP 40-33 Separate bypass input for LP 60-33 Separate bypass input for LP 80-33 Separate bypass input for LP 100/120-33
* * * * *
RPA Redundant Parallel Architecture (eld installed) Extended customer interface card (6 relay contacts) Bottom Grid for cabinet 430x725 mm Bottom Grid for cabinet 600x725 mm Bottom Grid for cabinet 725x725 mm Bottom Grid for cabinet 780x725 mm
* * * * * *
Options special
Seaworthy packing (also for air freights), LP 40-33 Seaworthy packing (also for air freights), LP 60/80/100/120-33
* *
Runtimes (minutes) at full load, power factor 0.8 LP 40-33 8 12 LP 60-33 9 12 18 LP 80-33 9 12 LP 100-33 10 LP 120-33 9
Battery cabinet with 22 Ah battery for LP 40-33 Battery cabinet with 33 Ah battery for LP 40-33 Battery cabinet with 33 Ah battery for LP 60/80-33 Battery cabinet with 50 Ah battery for LP 60/80-33 Battery cabinet with 2x33 Ah battery for LP 60/80-33 Battery cabinet with 2x33 Ah battery for LP 100/120-33 * For ordering please contact customer service.
B.17
UPS
SitePro Series - double conversion UPS Applications
The on-line SitePro UPS is an extremely reliable UPS providing critical power protection for a wide range of demanding mission-critical applications such as computer and data centers, medical facilities, broadcasting and satellite transmission systems, manufacturing and process control units, security systems, nancial institutions, transportation infrastructure etc. etc.
Order codes
Characteristics
The SitePro family of 3-phase in / 3-phase out high-performance UPS systems operates in a double conversion mode (providing true on-line operation), thus providing the highest levels of power reliability. Each UPS is fully compliant with international standards regarding Voltage and Frequency Independent (VFI) operation. True VFI makes the GE SitePro an extremely reliable UPS for data security and other demanding critical applications, even under the toughest conditions. The SitePro UPS is available in models from 10 kVA up to 500 kVA. For highpower redundant applications, the GE SitePro can be installed with up to eight units in parallel achieving power protection up to 4 MVA. The systems are controlled in a true peer-to-peer conguration with redundancy in all critical elements and functions, utilizing GEs unique Redundant Parallel Architecture (RPA) technology. This advanced technology provides the highest possible system reliability for mission critical applications with no single points of failure.
Function
A B X
Standards / Marking
Safety: EN 50091; 62040-1-2 EMC: EN 50091-2; EN 62040-2
B.18
UPS
Technical specications Technical specications (model dependent)
Output power rating Output power factor Output power rating Dimensions Weight (without batteries) Noise level (DIN 45630) Dimensions (hxwxd, mm): A = 1450x680x800 B = 1450x750x800 C = 1800x1100x800 D = 1800x1550x800 E = 1800x2600x800 (kVA) 10 1 10 A 240 48 15 1 15 A 290 50 20 1 20 A 290 50 30 1 30 A 320 55 40 1 40 A 350 60 60 0.9 54 B 475 60 150 0.9 135 C 930 65 200 250 300 400 500
(kW) kg dB(A)
0.9 0.9 0.9 0.9 0.9 180 225 270 360 450 C D D E E 1000 1450 1550 2725 2950 65 68 68 70 70
A B X
8 15 30 43 50 100 120
10 15 24 30 60 70
6 10 16 20 40 50
6 10 12 25 30
6 7 17 20
10 12
(1) For the full SitePro range (10-500 kVA) runtimes are possible from 5 minutes up to 4 hours. Contact your dealer for customised battery solutions not mentioned in this catalogue.
B.19
UPS
SitePro Series - double conversion UPS
SitePro 10
Battery capacity (V/Ah) SitePro 10 kVA without battery, with 6 pulse rectier RPA kit installed in factory 10 Ah battery in UPS cabinet 17 Ah battery in UPS cabinet 24 Ah battery in UPS cabinet 33 Ah battery in UPS cabinet 10 Ah battery mounted in separate cabinet 17 Ah battery mounted in separate cabinet 24 Ah battery mounted in separate cabinet 38 Ah battery mounted in separate cabinet 65 Ah battery mounted in separate cabinet 2x38 Ah battery mounted in separate cabinet Battery fuses for cabinet Battery fuse box (with fuses) Battery contactor mounted in UPS cabinet Input isolation transformer mounted in UPS cabinet batt. cavity Input lter for 5th harmonic with power factor correction, mounted inside the batt. cavity for 50Hz Output cabinet 4x 360/10 360/17 360/24 360/33 360/10 360/17 360/24 360/38 360/65 360/76 Runtime (min) at 100% load 8 15 30 43 8 15 30 50 100 120 Dimensions (hxwxd, mm) 1450x680x800 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x750x800 1450x1100x800 300x200x150 1450x500x800 Net weight (kg) 240 140 230 290 400 230 290 370 530 790 1030 Ref. No.
Order codes
* * * * * * * * * * * * * * * * * *
SitePro 15
A B X
SitePro 15 kVA without battery, with 6 pulse rectier RPA kit installed in factory 17 Ah battery in UPS cabinet 24 Ah battery in UPS cabinet 33 Ah battery in UPS cabinet 17 Ah battery mounted in separate cabinet 24 Ah battery mounted in separate cabinet 38 Ah battery mounted in separate cabinet 65 Ah battery mounted in separate cabinet 2x38 Ah battery mounted in separate cabinet Battery fuses for cabinet Battery fuse box (with fuses) Battery contactor mounted in UPS cabinet Input isolation transformer mounted in UPS cabinet batt. cavity Input lter for 5th harmonic with power factor correction, mounted inside the batt. cavity for 50Hz Output cabinet 4x
10 15 24 10 15 30 60 70 -
* * * * * * * * * * * * * * * *
SitePro 20
SitePro 20 kVA without battery, with 6 pulse rectier RPA kit installed in factory 17 Ah battery in UPS cabinet 24 Ah battery in UPS cabinet 33 Ah battery in UPS cabinet 17 Ah battery mounted in separate cabinet 24 Ah battery mounted in separate cabinet 38 Ah battery mounted in separate cabinet 65 Ah battery mounted in separate cabinet 2x38 Ah battery mounted in separate cabinet Battery fuses for cabinet Battery fuse box (with fuses) Battery contactor mounted in UPS cabinet Input isolation transformer mounted in UPS cabinet batt. cavity Input lter for 5th harmonic with power factor correction, mounted inside the batt. cavity for 50Hz Output cabinet 4x 360/17 360/24 360/33 360/17 360/24 360/38 360/65 360/76 6 10 16 6 10 20 40 50 1450x680x800 1450x500x800 1450x500x800 1450x500x800 1450x750x800 1450x1100x800 300x200x150 1450x500x800 290 230 290 400 290 370 530 790 1030 * * * * * * * * * * * * * * * *
B.20
UPS
SitePro Series - double conversion UPS
SitePro 30
Battery capacity (V/Ah) SitePro 30 kVA without battery, with 6 pulse rectier RPA kit installed in factory 24 Ah battery in UPS cabinet 33 Ah battery in UPS cabinet 24 Ah battery mounted in separate cabinet 38 Ah battery mounted in separate cabinet 65 Ah battery mounted in separate cabinet 2x38 Ah battery mounted in separate cabinet Battery fuses for cabinet Battery fuse box (with fuses) Battery contactor mounted in UPS cabinet Input isolation transformer mounted in UPS cabinet batt. cavity Input lter for 5th harmonic with power factor correction, mounted inside the batt. cavity for 50Hz Output cabinet 4x 360/24 360/33 360/24 360/38 360/65 360/76 Runtime (min) at 100% load 6 10 6 12 25 30 Dimensions (hxwxd, mm) 1450x680x800 1450x500x800 1450x500x800 1450x750x800 1450x1100x800 300x200x150 1450x500x800 Net weight (kg) 320 290 400 370 530 790 1030 Ref. No.
* * * * * * * * * * * * * *
SitePro 40
SitePro 40kVA without battery, with 6 pulse rectier SitePro 40kVA without battery, prepared for 12 pulse rectier RPA kit installed in factory 33 Ah battery in UPS cabinet 38 Ah battery mounted in separate cabinet 65 Ah battery mounted in separate cabinet 2x38 Ah battery mounted in separate cabinet Battery fuses for cabinet Battery fuse box (with fuses) Battery contactor mounted in UPS cabinet Input isolation transformer mounted in UPS cabinet batt. cavity 12 pulse rectier without galv. separation in separate cabinet 12 pulse rectier with galv. separation in separate cabinet Input isolation transformer in separate cabinet Input lter for 5th harmonic with power factor correction, mounted inside the batt. cavity for 50Hz Output cabinet 4x 360/33 360/38 360/65 360/76 6 7 17 20 1450x680x800 1450x680x800 1450x500x800 1450x750x800 1450x1100x800 300x200x150 1450x500x800 1450x500x800 1450x500x800 1450x500x800 350 350 400 530 790 1030 * * * * * * * * * * * * * * * *
A B X
SitePro 60
SitePro 60kVA without battery, with 6 pulse rectier SitePro 60kVA without battery, prepared for 12 pulse rectier RPA kit installed in factory 65 Ah battery mounted in separate cabinet 2x38 Ah battery mounted in separate cabinet Battery fuses for cabinet Battery fuse box (with fuses) Input isolation transformer in separate cabinet 12 pulse rectier without galv. separation in separate cabinet 12 pulse rectier with galv. separation in separate cabinet Input lter for 5th harmonic with power factor correction, mounted inside the batt. cavity for 50Hz Output cabinet 4x 360/65 360/76 10 12 1450x750x800 1450x750x800 1450x750x800 1450x1100x800 400x300x200 1450x500x800 1450x500x800 1450x500x800 1450x500x800 1450x1100x800 475 475 790 1030 * * * * * * * * * * * *
B.21
UPS
SitePro Series - double conversion UPS
SitePro 150
Dimensions (hxwxd, mm) SitePro 150 kVA without battery, with 6 pulse rectier SitePro 150 kVA without battery, prepared for 12 pulse rectier with galv. separation SitePro 150 kVA without battery, prepared for 12 pulse rectier without galv. separation RPA kit installed in factory Input isolation transformer in separate cabinet 12 pulse rectier without galv. separation in separate cabinet 12 pulse rectier with galv. separation in separate cabinet Battery fuse box (with fuses) Input lter for 11th and 13th harmonic, in separate cabinet, for 50Hz, only with 12 pulse rectier Input lter for 5th harmonic with power factor correction, in separate cabinet, for 50Hz Input lter for 5th harmonic with power factor correction, in separate cabinet, for 60Hz Distortion Control Unit, lter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Cables for common mains (1) Output cabinet 2x Output cabinet 3x Output cabinet 4x 1800x1100x800 1800x1100x800 1800x1100x800 1800x680x800 1800x680x800 1800x680x800 600x400x200 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x1100x800 1800x1100x800 1800x1550x800 Net weight (kg) 925 925 925 Ref. No.
* * * * * * * * * * * * * * * *
Order codes
SitePro 200
A B X
SitePro 200 kVA without battery, with 6 pulse rectier SitePro 200 kVA without battery, prepared for 12 pulse rectier with galv. separation SitePro 200 kVA without battery, prepared for 12 pulse rectier without galv. separation RPA kit installed in factory Input isolation transformer in separate cabinet 12 pulse rectier without galv. separation in separate cabinet 12 pulse rectier with galv. separation in separate cabinet Battery fuse box (with fuses) Input lter for 11th and 13th harmonic, in separate cabinet, for 50Hz, only with 12 pulse rectier Input lter for 5th harmonic with power factor correction, in separate cabinet, for 50Hz Input lter for 5th harmonic with power factor correction, in separate cabinet, for 60Hz Distortion Control Unit, lter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Cables for common mains (1) Output cabinet 2x Output cabinet 3x Output cabinet 4x
1800x1100x800 1800x1100x800 1800x1100x800 1800x680x800 1800x680x800 1800x680x800 600x400x200 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x1100x800 1800x1100x800 1800x1550x800
* * * * * * * * * * * * * * * *
SitePro 250
SitePro 250 kVA without battery, with 6 pulse rectier SitePro 250 kVA without battery, prepared for 12 pulse rectier with galv. separation SitePro 250 kVA without battery, prepared for 12 pulse rectier without galv. separation RPA kit installed in factory 12 pulse rectier without galv. separation in separate cabinet 12 pulse rectier with galv. separation in separate cabinet Battery fuse box (with fuses) Input lter for 11th and 13th harmonic, in separate cabinet, for 50Hz, only with 12 pulse rectier without galv. separation Input lter for 11th and 13th harmonic, in separate cabinet, for 50Hz, only with 12 pulse rectier with galv. separation Input lter for 5th harmonic with power factor correction, in separate cabinet, for 50Hz Input lter for 5th harmonic with power factor correction, in separate cabinet, for 60Hz Distortion Control Unit, lter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Cables for common mains (1) Output cabinet 2x Output cabinet 3x Output cabinet 4x 1800x1550x800 1800x1550x800 1800x1550x800 1800x680x800 1800x1100x800 600x400x200 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x1100x800 1800x1550x800 1800x1780x800 1450 1450 1450 * * * * * * * * * * * * * * * *
(1) In case of common mains and DCU or lter (input to UPS and bypass) order also the cables
B.22
UPS
SitePro Series - double conversion UPS
SitePro 300
Dimensions (hxwxd, mm) SitePro 300 kVA without battery, with 6 pulse rectier SitePro 300 kVA without battery, prepared for 12 pulse rectier with galv. separation SitePro 300 kVA without battery, prepared for 12 pulse rectier without galv. separation RPA kit installed in factory 12 pulse rectier without galv. separation in separate cabinet 12 pulse rectier with galv. separation in separate cabinet Battery fuse box (with fuses) Input lter for 11th and 13th harmonic, in separate cabinet, for 50Hz, only with 12 pulse rectier without galv. separation Input lter for 11th and 13th harmonic, in separate cabinet, for 50Hz, only with 12 pulse rectier with galv. separation Input lter for 5th harmonic with power factor correction, in separate cabinet, for 50Hz Input lter for 5th harmonic with power factor correction, in separate cabinet, for 60Hz Distortion Control Unit, lter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Cables for common mains (1) Output cabinet 2x Output cabinet 3x Output cabinet 4x 1800x1550x800 1800x1550x800 1800x1550x800 1800x680x800 1800x1100x800 600x400x200 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x680x800 1800x1100x800 1800x1550x800 1800x1780x800 Net weight (kg) 1550 1550 1550 Ref. No.
* * * * * * * * * * * * * * * *
SitePro 400
SitePro 400 kVA without battery, with 12 pulse rectier without galv. separation SitePro 400 kVA without battery, prepared for 12 pulse rectier with galv. separation RPA kit installed in factory 12 pulse rectier with galv. separation in separate cabinet Input lter for 11th and 13th harmonic, in separate cabinet, for 50Hz, only with 12 pulse rectier without galv. separation Input lter for 11th and 13th harmonic, in separate cabinet, for 50Hz, only with 12 pulse rectier with galv. separation Distortion Control Unit, lter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Battery fuse box (with fuses) Output cabinet 2x Output cabinet 3x Output cabinet 4x 1800x2600x800 1800x2600x800 1800x680x800 1800x680x800 1800x680x800 1800x1100x800 1000x600x260 1800x1550x800 1800x1780x800 1800x1780x800 2700 2700 * * * * * * * * * * *
A B X
SitePro 500
SitePro 500 kVA without battery, with 12 pulse rectier without galv. separation SitePro 500 kVA without battery, prepared for 12 pulse rectier with galv. separation RPA kit installed in factory 12 pulse rectier with galv. separation in separate cabinet Input lter for 11th and 13th harmonic, in separate cabinet, for 50Hz, only with 12 pulse rectier without galv. separation Input lter for 11th and 13th harmonic, in separate cabinet, for 50Hz, only with 12 pulse rectier with galv. separation Distortion Control Unit, lter for 5,7,11,13 harmonics, in separate cabinet, for 50Hz Battery fuse box (with fuses) Output cabinet 2x Output cabinet 3x Output cabinet 4x 1800x2600x800 1800x2600x800 1800x1100x800 1800x680x800 1800x680x800 1800x1100x800 1000x600x260 1800x1550x800 1800x2200x800 1800x2200x800 2900 2900 * * * * * * * * * * *
(1) In case of common mains and DCU or lter (input to UPS and bypass) order also the cables
B.23
UPS
SitePro Series - double conversion UPS
Options miscellaneous
Dimensions (hxwxd, mm) Kit to convert Single to RPA operation for SitePro S6 (in case of ISM please order kit version E below) RPA kit factory installed, version E, required in combination with ISM Kit to convert Single UPS to RPA operation, version E, required in combination with ISM ISM Intelligent Synchronization Module (compatible with RPA version E) Data cable for RPA system between unit 6 meters Data cable for RPA system between unit 12 meters Data cable for RPA system between unit 30 meters Data cable for RPA system between unit 85 meters Maxium distance between the rst and the last UPS in one system is 85 meters -
Ref. No.
* * * * * * * * * * * * * * * * *
Order codes
Additional Customer Interface card (10-500 kVA) Remote signalling panel (incl. 24 Vdc Power Supply) Remote monitoring system Kit to mount Chinese Display for SitePro S6 Auxiliary Power Supply 24VDC, factory mounted only Top cable entry box (10-60 kVA only) 2 bottom side grids + 1 x side panel for cabinet with factory installed batteries (10-60 kVA) Mounting set for battery 10/17/24 AH in 10-30 kVA UPS cabinet Mounting set for 33 Ah battery in 10-40 kVA UPS cabinet Note: UPS without batteries are also without battery mounting sets. To mount locally purchased batteries, order the mounting set.
A B X
Battery cabinet 500mm with 4 shelves (with 2 side panels and 2 bottom side grids) 10-40 kVA Battery cabinet 750mm with 4 shelves (with 2 side panels and 2 bottom side grids) 10-60 kVA Battery cabinet 1100mm with 4 shelves (with 2 side panels and 2 bottom side grids) 10-60 kVA Note: Battery cabinets are normally mounted next to the UPS. For remote placement, order bottom grids and side panel. Battery cabinet 680mm with 4 shelves (3 mobile) c/w 1 x sides (150-500 kVA) Battery cabinet 1100mm with 4 shelves (3 mobile) c/w 1 x sides (150-500 kVA) Battery cabinet 1550mm with 4 shelves (3 mobile) c/w 1 x sides (150-500 kVA) 2 bottom side grids + 1 x side panel for cabinet (150-500 kVA) Note: For all batteries installed on racks, it is recommended that a battery fuse box also be installed. Note: For battery cabinets that are placed more than 3 meters from the UPS, it is recommended that a battery fuse box (wall-mounted) or battery fuse+holder (inside battery cabinet) also be installed. Battery temperature sensor 5 meter Battery temperature sensor 15 meter Battery temperature sensor 20 meter Battery temperature sensor 30 meter (shielded) Empty cabinet 500mm c/w 2 x sides and 2 x bottom grills (10-60 kVA) Empty cabinet 750mm c/w 2 x sides and 2 x bottom grills (10-60 kVA) Empty cabinet 1100mm c/w 2 x sides and 2 x bottom grills (10-60 kVA) Empty cabinet 680mm c/w 2 x sides and 2 x bottom grills (150-500 kVA) Empty cabinet 1100mm c/w 2 x sides and 2 x bottom grills (150-500 kVA) Empty cabinet 1550mm c/w 2 x sides and 2 x bottom grills (150-500 kVA) Note: empty cabinets are battery cabinets without battery shelves
* * *
* * * *
* * * * * * * * * *
Active Filter 45A, 3-wire Active Filter 45A, 3-wire with EMI Filter IEC62040-2 Class A Active Filter 115A, 3-wire Active Filter 115A, 3-wire with EMI Filter IEC62040-2 Class A
* * * *
Options colour
Non standard colour (per cabinet) (10-40 kVA) Non standard colour (per cabinet) (60 kVA) Non standard colour (per cabinet) (150-500 kVA)
* * *
Wooden crate (per cabinet) mandatory for sea and air freights (10-60 kVA) Wooden crate (per cabinet) mandatory for sea and air freights (150-500 kVA) Reception test in our factory (per system per day) (10-40 kVA) Reception test in our factory (per system per day) (60-500 kVA)
* * * *
B.24
UPS
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.25
UPS
SG Series - double conversion UPS Applications
The on-line SG series UPS is an extremely reliable UPS providing critical power protection for a wide range of demanding mission-critical applications such as computer and data centers, medical facilities, broadcasting and satellite transmission systems, manufacturing and process control units, security systems, nancial institutions, transportation infrastructure etc. etc.
Order codes
Characteristics
The GE Digital Energy 3-phase in / 3-phase out high-performance SG Series is one of the best performing and most reliable three-phase UPS systems providing critical power protection for a wide range of applications. Every SG Series system operates in VFI mode (Voltage Frequency Independent) yielding the maximum levels of power reliability for all mission-critical processes. The Digital Energy SG Series was developed using GEs Design for Six Sigma methodology to ensure that the product fully meets customer requirements and expectations. With proven technology the SG Series UPS provides top class reliability and performance. With backfeed protection and compliance to EMC standards the SG Series complies to current and future standards. Reliability can be further increased by paralleling up to eight UPS units utilising GEs unique RPA technology (Redundant Parallel Architecture). With RPA every UPS is controlled in a true peer-to-peer conguration with redundancy in all critical elements and functions, eliminating all single points of failure. The decentralised bypass offers great exibility to up or down grade the system in case future needs might change.
Function
A B X
Standards / Marking
Safety: EN 62040-1-1; IEC 62040-1-1 EMC: EN 62040-2
B.26
UPS
Technical specications Technical specications (model dependent)
Output power rating (kVA) Output power rating (kW) Dimensions Weight (without batteries), kg Input current THD (optional) Dimensions, hxwxd (mm): A = 1820x800x800 B = 1820x1200x800 C = 1820x1650x800
80 72 A 605 < 6%
A B X
6 11 33
(2)
(2)
(2)
8
(2)
5
(2)
15
(2)
47 63
(2)
10 30
(2)
48 61
46
(1) For the full SG Series range (80-200 kVA) runtimes are possible from 5 minutes up to 3-4 hours. Contact your dealer for customised battery solutions not mentioned in this catalogue. (2) This combination of battery set / UPS model is not available.
B.27
UPS
SG Series - double conversion UPS
SG 80
Dimensions (hxwxd, mm) SG 80 kVA without battery, with 6 pulse rectier SG 80 kVA without battery, with 6 pulse rectier, with Class A EMI lter SG 80 kVA without battery, prepared for 12 pulse rectier SG 80 kVA without battery, prepared for 12 pulse rectier, with Class A EMI lter RPA kit installed in factory 5th harmonic lter in UPS cabinet for THDi < 8% 5th and 11th harmonic lter in UPS cabinet for THDi < 6% 12 pulse rectier without galv. separation in separate cabinet 12 pulse rectier with galv. separation in separate cabinet Input isolation transformer in separate cabinet Battery fuse box (without fuses) Battery fuses for SG 80 kVA Output cabinet 2x Output cabinet 3x Output cabinet 4x Battery solutions, 10 year lifetime, matching cabinets (1) Battery 1x75 Ah, runtime 6 minutes Battery 1x82 Ah, runtime 11 minutes Battery 2x92 Ah, runtime 33 minutes Battery 2x130 Ah, runtime 47 minutes Battery 3x110 Ah, runtime 63 minutes 1820x800x800 1820x800x800 1820x800x800 1820x800x800 1820x500x800 1820x500x800 1820x500x800 600x400x200 1820x800x800 1820x800x800 1820x800x800 1x 1820x1200x800 1x 1820x1200x800 2x 1820x1200x800 2x 1820x1650x800 3x 1820x1200x800 Net weight (kg) 605 605 605 605 990 1170 2460 3360 4230 Ref. No.
Order codes
* * * * * * * * * * * * * * * * * * * *
A B X
SG 100
SG 100 kVA without battery, with 6 pulse rectier SG 100 kVA without battery, with 6 pulse rectier, with Class A EMI lter SG 100 kVA without battery, prepared for 12 pulse rectier SG 100 kVA without battery, prepared for 12 pulse rectier, with Class A EMI lter RPA kit installed in factory 5th harmonic lter in UPS cabinet for THDi < 8% 5th and 11th harmonic lter in UPS cabinet for THDi < 6% 12 pulse rectier without galv. separation in separate cabinet 12 pulse rectier with galv. separation in separate cabinet Input isolation transformer in separate cabinet Battery fuse box (without fuses) Battery fuses for SG 100 kVA Output cabinet 2x Output cabinet 3x Output cabinet 4x Battery solutions, 10 year lifetime, matching cabinets (1) Battery 1x82 Ah, runtime 8 minutes Battery 1x130 Ah, runtime 15 minutes Battery 2x110 Ah, runtime 31 minutes Battery 3x110 Ah, runtime 48 minutes Battery 3x130 Ah, runtime 61 minutes 1820x1200x800 1820x1200x800 1820x1200x800 1820x1200x800 1820x500x800 1820x500x800 1820x500x800 600x400x200 1820x800x800 1820x800x800 1820x800x800 1x 1820x1200x800 1x 1820x1650x800 2x 1820x1200x800 3x 1820x1200x800 3x 1820x1650x800 830 830 830 830 1170 1680 2820 4230 5040 * * * * * * * * * * * * * * * * * * * *
SG 120
SG 120 kVA without battery, with 6 pulse rectier SG 120 kVA without battery, with 6 pulse rectier, with Class A EMI lter SG 120 kVA without battery, prepared for 12 pulse rectier SG 120 kVA without battery, prepared for 12 pulse rectier, with Class A EMI lter RPA kit installed in factory 5th harmonic lter in UPS cabinet for THDi < 8% 5th and 11th harmonic lter in UPS cabinet for THDi < 6% 12 pulse rectier without galv. separation in separate cabinet 12 pulse rectier with galv. separation in separate cabinet Input isolation transformer in separate cabinet Battery fuse box (without fuses) Battery fuses for SG 120 kVA Output cabinet 2x Output cabinet 3x Output cabinet 4x Battery solutions, 10 year lifetime, matching cabinets (1) Battery 1x82 Ah, runtime 5 minutes Battery 1x130 Ah, runtime 10 minutes Battery 2x130 Ah, runtime 30 minutes Battery 3x130 Ah, runtime 46 minutes Battery 4x130 Ah, runtime 66 minutes (1) All runtimes based on nominal load, PF 0.8 1820x1200x800 1820x1200x800 1820x1200x800 1820x1200x800 1820x500x800 1820x500x800 1820x500x800 600x400x200 1820x800x800 1820x800x800 1820x800x800 1x 1820x1200x800 1x 1820x1650x800 2x 1820x1650x800 3x 1820x1650x800 4x 1820x1650x800 830 830 830 830 1170 1680 3360 5040 6720 * * * * * * * * * * * * * * * * * * * *
B.28
UPS
SG Series - double conversion UPS
SG 160
Dimensions (hxwxd, mm) SG 160 kVA without battery, with 6 pulse rectier SG 160 kVA without battery, with 6 pulse rectier, with Class A EMI lter RPA kit installed in factory 5th harmonic lter in UPS cabinet for THDi < 8% 5th and 11th harmonic lter in UPS cabinet for THDi < 6% Input isolation transformer in separate cabinet Battery fuse box (without fuses) Battery fuses for SG 160 kVA Output cabinet 2x Output cabinet 3x Output cabinet 4x 1820x1650x800 1820x1650x800 1820x680x800 600x400x200 1820x800x800 1820x800x800 1820x800x800 Net weight (kg) 1100 1100 Ref. No. * * * * * * * * * * *
SG 200
SG 200 kVA without battery, with 6 pulse rectier SG 200 kVA without battery, with 6 pulse rectier, with Class A EMI lter RPA kit installed in factory 5th harmonic lter in UPS cabinet for THDi < 8% 5th and 11th harmonic lter in UPS cabinet for THDi < 6% Input isolation transformer in separate cabinet Battery fuse box (without fuses) Battery fuses for SG 200 kVA Output cabinet 2x Output cabinet 3x Output cabinet 4x 1820x1650x800 1820x1650x800 1820x680x800 600x400x200 1820x800x800 1820x800x800 1820x800x800 1300 1300 * * * * * * * * * * *
A B
Options miscellaneous
RPA kit factory installed, version E, required in combination with ISM Kit to convert Single UPS to RPA operation, version E, required in combination with ISM ISM Intelligent Synchronization Module (compatible with RPA version E) Data cable for RPA system between unit 6 meters Data cable for RPA system between unit 12 meters Data cable for RPA system between unit 30 meters Data cable for RPA system between unit 85 meters Maxium distance between the rst and the last UPS in one system is 85 meters Additional Customer Interface card Remote signalling panel (incl. 24 Vdc Power Supply) Remote monitoring system Auxiliary Power Supply 24VDC, factory mounted only
* * * * * * * * * * *
Empty battery cabinet 800mm Empty battery cabinet 1200mm Empty battery cabinet 1650mm Battery fuse holder and bracket (to be mounted in batt. cabinet in case of no batt, fuse box) Battery temperature sensor 5 meter Battery temperature sensor 15 meter Battery temperature sensor 20 meter Battery temperature sensor 30 meter (shielded) Battery temperature sensor 60 meter (shielded)
* * * * * * * * * *
Active Filter 45A, 3-wire Active Filter 45A, 3-wire with EMI Filter IEC62040-2 Class A Active Filter 115A, 3-wire Active Filter 115A, 3-wire with EMI Filter IEC62040-2 Class A
* * * *
Non standard colour 80-120 kVA (per cabinet) Non standard colour 160-200 kVA (per cabinet)
* *
Wooden crate (per cabinet) mandatory for sea and air freights 80-120 kVA Wooden crate (per cabinet) mandatory for sea and air freights 160-200 kVA Reception test in our factory (per system per day)
* * *
B.29
UPS
STS - Static Transfer Switch Applications
Order codes
Static Transfer Switches (STS) are designed to transfer the supply between two independent AC power sources. Unlike traditional automatic transfer switches (ATS), a static transfer switch provides a fast load transfer (typically 1/4 of a cycle), which ensures uninterrupted operation of sensitive electronic equipment. Load retransfer to the preferred input source is virtually instantaneous (typically 0.1 ms). The basic applications of STS are in automatic systems in the power industry, power supply systems for petrochemical industry, computer and telecommunication centres, automatic and security systems of intelligent buildings as well as other equipment which is sensitive to interruptions in the supply.
Characteristics Function
Providing exceptionally reliable protection for electrical equipment The excellent overload capability and transfer algorithm enables fast fuse clearance in the event of a short-circuit. As a consequence the voltage immediately returns to normal to supply the other loads. The built-in transient voltage surge suppression system for SCR switches provides additional protection against damage to the supplied equipment. The static transfer switch consists of two bidirectional thyristor switches for each phase equipped with a control and protection system. The 2 or 4 pole types have an additional neutral line switch. After failure of the preferred source, the STS checks the state of the alternate power source and transfers the load to whichever source provides power within selectable limits. This transfer can be triggered by disturbance in the preferred source voltage, overcurrent in the source or manual or remote change of the preferred source. With both sources in limits and synchronised (phase error within the acceptable range), manual or remote transfer is performed in less than 200 s. Transfers initiated by fault conditions in the preferred source depend on the status of the alternate source. For synchronised power sources with phase error within the limits, transfer to an alternate source is made within 6ms delay. Lack of synchronisation causes delay before transfer. It is possible to set the delay with dipswitches.
A B X
Standards / Marking
Safety: EN 60950 EMC: EN 50022 level B, EN 60555-2-3
B.30
UPS
STS - Static Transfer Switch
1-phase, 1-pole stand alone
Static Transfer Switch STS-230-25-1P Static Transfer Switch STS-230-40-1P Static Transfer Switch STS-230-63-1P Static Transfer Switch STS-230-100-1P Static Transfer Switch STS-230-150-1P Static Transfer Switch STS-230-250-1P Static Transfer Switch STS-230-400-1P
Dimensions (hxwxd, mm) 340x507x440 340x507x440 340x507x440 1100x800x400 1100x800x400 1900x800x500 1900x800x500
Ref. No.
* * * * * * *
Static Transfer Switch STS-230-25-1P-RM Static Transfer Switch STS-230-40-1P-RM Static Transfer Switch STS-230-63-1P-RM Manual Bypass for STS-230-25-1P-RM Manual Bypass for STS-230-40/63-1P-RM
25 40 63 25 63
* * * * *
Static Transfer Switch STS-230-25-2P Static Transfer Switch STS-230-40-2P Static Transfer Switch STS-230-63-2P Static Transfer Switch STS-230-100-2P Static Transfer Switch STS-230-150-2P Static Transfer Switch STS-230-250-2P Static Transfer Switch STS-230-400-2P
* * * * * * *
A B X
Static Transfer Switch STS-230-25-2P-RM Static Transfer Switch STS-230-40-2P-RM Static Transfer Switch STS-230-63-2P-RM Manual Bypass for STS-230-25-2P-RM Manual Bypass for STS-230-40/63-2P-RM
25 40 63 25 63
* * * * *
Static Transfer Switch STS-400-25-3P Static Transfer Switch STS-400-40-3P Static Transfer Switch STS-400-63-3P Static Transfer Switch STS-400-100-3P Static Transfer Switch STS-400-150-3P Static Transfer Switch STS-400-250-3P Static Transfer Switch STS-400-400-3P Static Transfer Switch STS-400-630-3P Static Transfer Switch STS-400-800-3P Static Transfer Switch STS-400-1000-3P
400 400 400 400 400 400 400 400 400 400
1100x800x400 1100x800x400 1100x800x400 1100x800x400 1900x800x500 1900x800x500 1900x1200x500 2100x1200x600 2300x1600x800 2300x1600x800
* * * * * * * * * *
Static Transfer Switch STS-400-25-3P-RM Static Transfer Switch STS-400-40-3P-RM Static Transfer Switch STS-400-63-3P-RM Static Transfer Switch STS-400-100-3P-RM
25 40 63 100
* * * *
Static Transfer Switch STS-400-25-4P Static Transfer Switch STS-400-40-4P Static Transfer Switch STS-400-63-4P Static Transfer Switch STS-400-100-4P Static Transfer Switch STS-400-150-4P Static Transfer Switch STS-400-250-4P Static Transfer Switch STS-400-400-4P Static Transfer Switch STS-400-630-4P Static Transfer Switch STS-400-800-4P Static Transfer Switch STS-400-1000-4P
400 400 400 400 400 400 400 400 400 400
1100x800x400 1100x800x400 1100x800x400 1900x800x500 1900x1200x500 1900x1200x500 2100x1200x600 2300x1200x600 2300x1600x800 2300x1600x800
* * * * * * * * * *
Static Transfer Switch STS-400-25-4P-RM Static Transfer Switch STS-400-40-4P-RM Static Transfer Switch STS-400-63-4P-RM
25 40 63
* * *
Options
MODBUS RS485 interface Seaworthy packing (also for air freights) 25-100A Seaworthy packing (also for air freights) 150-250A Seaworthy packing (also for air freights) 400-630A * For ordering please contact customer service. * * * *
B.31
UPS
Connectivity solutions Applications
In todays business environment, a power failure causes loss of crucial data, expensive down time and damaged computers or industrial equipment. With the use of appropriate monitoring and management software, the UPS becomes a comprehensive power quality solution. The software is an indispensable and fully integrated element, increasing system availability and process protection.
Order codes
IRIS
Characteristics
During a power failure, the software takes a number of actions: users are alerted, processes are managed into dened statuses, open les and communication links are closed and unattended systems are shut down in a controlled way. When the mains power returns, the system is automatically started up and begins operating.
Function
A B X
Turning the UPS in to a comprehesive power quality solution, thus providing increased system availability and process protection.
Protection software
The main function of the GE protection software is data and operating system protection. JUMP DataShield diminishes the risk of lost data or system crashes. The software provides events handling and computer shutdown for all major operating systems, protecting the security of precious data. Multivendor and multi-platform environments as well as client-server structures are managed, using SNMP-based network communication protocols.
Management software
JUMP DataShield The GE UPS management software provides direct access to remote UPS and active management of each UPS in multi-unit congurations to ensure efcient and predictable power quality. A network manager or facilities engineer can use JUMP Manager to monitor and control the local or remote UPS, and the equipment and processes it protects. Typically, an SNMP connection, direct serial link or modem connection is used for this purpose. The UPS can also be monitored on the Internet using the GE IRIS system.
JUMP Manager
B.32
UPS
Connectivity solutions
Code reference table
Code cs cp i
UPS interface / functionality contact / power failure, battery low & shutdown contact / power failure, battery low & shutdown intelligent / features depend on UPS type
Connectivity Solutions
This free software (on CD-ROM) and an intelligent communication cable are shipped with each UPS (except SitePro/SG Series UPS) Additional copies of this software can be ordered, all software is without cabling.
Medium CD-ROM
Operating system Microsoft Windows (all) Novell Netware IBM OS/2 Linux AT&T Intel COMPAQ Tru64 Unix DEC UNIX AXP Alpha DEC Ultrix RISC DEC OpenVMS VAX/AXP HP-UX 700/800 IBM AIX RISC/60x UNIXWARE INTEL SCO INTEL Siemens SINIX RM SUN OS SPARC All OS supporting JAVA 1.2 + The CD-ROM contains UPS Protection and Management Program, incl. SNMP Agent and Client. For detailed information on compatibility for the various versions please refer to detailed specications.
Code cp,i cs,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i cp,i i
A B X
Service software
912473
JUMP manager
Product Free to use with max. 2 single UPS or 2 complete parallel congurations, no limitation of managed power JUMP Manager on CD-ROM License for more than 2 UPS systems and max. 100 kVA managed power License for more than 2 UPS systems and max. 1000 kVA managed power License for more than 2 UPS systems and unlimited managed power SSL security internet communication module
code
Ref. No.
Product Free to use with max. 1 single UPS. Compatible with Windows 9.x ARGUS Software Package 30 days full featured license License for 2 to 10 single UPSs License for more than 10 single UPSs License for more than 1 parallel UPS system License for unlimited number of single & parallel UPS system Intelligent Energy Management (IEM), only for parallel units (order also 911382) 911382 911003 915655 911004 915656 911005
B.33
UPS
Connectivity solutions
Code reference table
Code cs cp i
UPS interface / functionality contact / power failure, battery low & shutdown contact / power failure, battery low & shutdown intelligent / features depend on UPS type
IRIS software
Product Starter Kit (incl. 1st year fee and InterLinc box) IRIS starter kit, per system, incl. messaging and refresh After 1st year (excl. InterLinc box) IRIS yearly fee after 1st year, incl. messaging and refresh
code
Order codes
A B X
Contact UPS Relay-Box Contact UPS Splitter-Box 2-way Contact UPS Splitter-Box 4-way Contact UPS Alarm-Box Contact UPS Shutdown Adapter UPS Service Box (1) SNMP/Web Interface Card UTP for Match (19) (2), NetPro (19), LP-11/31T/31 Advanced SNMP/Web Interface card UTP/BNC for LP-33, SitePro Series 6 and SG Series SNMP/Web Interface Box Ethernet UTP/BNC (1) for Match (19), NetPro (19), LP-11/31(T); With Linc-box also valid for SitePro Series 5 Relay card for Match 700L-1500 (3) and Match 19 1000-1500 (3) Relay card for Match (19) 2200-3000, NetPro (19) and LP-11/31(T) Multi Serial Board (8 x RS232) (1) Analogue modem for IRIS (1) (Only valid for European market) Converter RS232-RS485 kit (1) (4) USB2Serial adaptor pack
c cs cs c cs cs,i i i cs,i
912466 912467 909226 912214 912460 912468 909224 911701 909223 912459 912458 901145 917641 911227 901240
i i i
These products are delivered including cable(s). Not for Match 500-700 and Match 19 700; alternative: SNMP Box, Art.no. 909223 Not for Match 500-700 and Match 19 700; alternative: Relay Box, Art.no. 912466 Not needed if ESI is installed. Only if distance is more than 15m
External Signal Interface (ESI) Linc Box: CP4 Protocol Converter* Modbus RTU Interface RS 232 * (Match-NetPro-LP-SitePro-SG Series) Modbus RTU Interface RS 485 * (Match-NetPro-LP-SitePro-SG Series) * These products are delivered including cable(s).
i i i
ML Series Connectivity Cable (1.5m) AC Cable 10A IEC320 male / female, 1.5 m IMV-I Cable Intelligent UPS (2m) for LP and SitePro VIC-23 Cable Intelligent UPS (2m) for Match and NetPro IMV-C Cable Kit Contact UPS (2m) VIC-32 Cable UPS to modem (2m) for Match and NetPro IMV-M Cable UPS to modem (2m) for LP and SitePro Series 6 Adapter 9p male -> 25p female subd IBM AS400 Cable Kit for built-in UPS driver (2m) Note: length of all cables is 2 meters
i i i cs i i c,cs,i c
B.34
X.1
UPS
Ref. No.
901145 901240 909223 909224 909225 909226 909227 909227 909230 909231 910042 910043 910044 911003 911004 911005 911162 911163 911164 911167 911176 911227 911249 911382 911483 911701
Page
B.34 B.34 B.34 B.34 B.34 B.34 B.33 B.33 B.34 B.34 B.7 B.7 B.7 B.33 B.33 B.33 B.33 B.33 B.33 B.34 B.34 B.34 B.34 B.33 B.34 B.34 B.34 B.33 B.5 B.5 B.5 B.5 B.5 B.5 B.5 B.5 B.5 B.5 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.3 B.5 B.7 B.5 B.5 B.5
Ref. No.
912444 912445 912446 912447 912449 912450 912451 912452 912453 912454 912458 912459 912460 912466 912467 912468 912469 912470 912471 912472 912473 914341 914850 914851 915170 915571 915572 915573 915655 915656 916181 916182 916183 916184 916275 916276 917641
Page
B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.7 B.5 B.5 B.34 B.34 B.34 B.34 B.34 B.34 B.34 B.34 B.34 B.34 B.33 B.34 B.5 B.5 B.34 B.5 B.5 B.7 B.33 B.33 B.3 B.3 B.3 B.3 B.34 B.34 B.34
A B X
912214 912316 912321 912322 912323 912324 912325 912326 912328 912329 912330 912331 912332 912333 912334 912335 912336 912337 912338 912339 912340 912341 912342 912343 912344 912345 912346 912347 912348 912349 912349 912349 912439 912440 912441
The policy of GE Consumer & Industrial is one of continuous improvement. The right is reserved to alter the design or any structural details of the products at any time without giving notice. September 2005 GE Consumer & Industrial
X.2
UPS
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X.3
A B X
UPS
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X.4
A B X
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Protection (formerly GE Power Controls), a division of GE Consumer & Industrial, is a rst class European supplier of low-voltage products including wiring devices, residential and industrial electrical distribution components, automation products, enclosures and switchboards. Demand for the companys products comes from wholesalers, installers, panel-board builders, contractors, OEMs and utilities worldwide www.gepowercontrols.com
GE POWER CONTROLS International Sales Nieuwevaart 51 B-9000 Gent - Belgium Tel. +32/9 265 21 11 Fax +32/9 265 28 90 E-mail: gepcbel@gepc.ge.com GE POWER CONTROLS Hornhouse Lane Knowsley Industrial Park Liverpool L33 7YQ United Kingdom Tel. 0800/587 1251 Fax 0800/587 1239 E-mail: gepcuk@gepc.ge.com
GE imagination at work
680863 Ref. I/3184/E/EX 5.0 Ed. 09/05 Copyright GE Consumer & Industrial 2005 All specications subject to change without prior notice
35777