Catalogo LanPro
Catalogo LanPro
Catalogo LanPro
LP Series
Uninterruptible Power Supplies
3 - 30 kVA
LP Series
Uninterruptible Power Supplies
3 - 30 kVA
● Multi-language LCD, easy to use ● SNMP plug in card for integration into networks
● Excellent overload behaviour, withstands ● Potential free alarm contacts
toughest conditions ● Matching battery packs for extended back up times
● Cold start funtion ● Redundant Parallel Architecture™
(start-up without mains present)
● Manual bypass integrated in UPS
● Equipped with RS232 serial port
● Fits well in office environment
● Frequency converter
RPA™
Redundant Parallel ArchitectureTM
GE provides a unique technology called Redundant Parallel Architecture (RPA) that can parallel Uninterruptible
Power Supply (UPS) modules with true redundancy. With RPA, there is no need for external electronics or swit-
ches to control the UPS modules in the parallel system. One of the UPS modules in the system arbitrarily takes
a leadership role, while the other UPS modules have access to all control parameters. If one UPS fails to opera-
te, the load is automatically redistributed among the others. If the lead UPS fails to operate then a different
UPS automatically takes on the leadership role. The RPA systems are designed to have no single points of failure,
ensuring the highest level of power protection for critical loads.
MAINS
LOAD
Many other so-called redundant UPS offerings have one critical shortfall, in that they have critical components
that are not redundant. RPA technology provides complete redundancy of all critical components and there are
no single points of failure. RPA technology allows UPS system expansion not only to increase capacity but also
to improve the reliability of the power provided to critical loads. For mission critical applications, RPA technology
provides true redundancy for the highest reliability.
● RPA Configuration provides complete redundancy of all ● Easy to install and maintain.
critical components and allows paralleling of up to four
units for increased load capacity. It ensures excellent ● Scaleable design allows for efficient use of capital.
dynamic behaviour based on output voltage load sharing.
This provides the highest reliability and availability for ● Peer-to-Peer architecture where any UPS can be the
mission-critical applications. “logic leader” ensuring no single points of failure.
PROTECTION SOFTWARE
MANAGEMENT SOFTWARE
Rating (kVA / kW) 3/2.4 5/4 6/4.8 8/6.4 10/8 8/6.4 10/8 15/12 20/16 10/10 20/20 30/30
Battery (V/Ah) 144/7 240/7 240/7 240/12 240/12 2x240/7 2x240/7 2x240/14 2x240/14 2x240/7 2x240/14 2x240/21
Typical backup time
50 / 100% load (min) 25/10 25/10 20/8 29/11 22/8 35/14 25/10 30/13 25/10 26/10 26/10 26/10
Enclosure A A/B* A/B* C/D* C/D* E E E E F F G
Net weight incl. batt. (kg) 85 110/180* 115/185* 165/270* 170/275* 240 240 345 350 247 372 520
Input voltage (Vac) 172-285 172-285/ 172-285/ 172-285/ 172-285/ 300-470 300-470 300-470 300-470 324-478 324-478 324-478
340-470* 340-470* 340-470* 340-470*
Input power factor .99 .99 .99 .99 .99 .95 .95 .95 .95 .98 .98 .98
Input frequency (Hz) 40-70 40-70 40-70 40-70 40-70 45-65 45-65 45-65 45-65 45-65 45-65 45-65
Output voltage (Vac) 220/230/240 (user selectable) 380/400/415 (user selectable)
Output voltage regulation +/-1%
Output frequency (Hz) 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Environment IP20 (IEC60529)
Humidity 95% non-condensing
Ambient operating temperature 0º – +40ºC (32º–104ºF)
Audible noise 40-55 dB(A) load and temperature dependent
Standards safety EN 50091-1; EN 60950; IEC 950
Protection degree IP20
Standards EMC EN 50091-2/IEC 62040-2
ECO mode ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
SBM† ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Boost charging ✓ ✓ ✓ ✓ ✓
Potential free contacts optional optional optional optional optional ✓ ✓ ✓ ✓ ✓ ✓ ✓
RS 232 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
RPA (optional) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Plug-in SNMP Card ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Battery Extension (optional) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Backfeed protection optional optional/✓* optional/✓* - /✓* - /✓* ✓ ✓ ✓ ✓ ✓ ✓ ✓
Separate bypass input ✓ ✓ ✓ ✓ optional optional optional
PowerJUMP DataShield™ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
PowerJUMP Manager™ (optional) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
IRIS (optional) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
* = LP-11/LP-31T respectively A: 537 x 313 x 590 mm D: 995 x 313 x 720 mm G : 1310 x 660 x 780 mm
† = Superior Battery Management B: 855 x 313 x 590 mm E: 1190 x 410 x 890 mm
C: 680 x 313 x 720 mm F: 1310 x 500 x 780 mm
LPX-11 = Single phase in/single phase out
LPX-31 = Three phase in/single phase out
LPX-33 = Three phase in/three phase out
X = kVA rating
T = Transformer
Via Cantonale 50
6595 Riazzino (Locarno)
Switzerland
+ 41 (0) 91 850 51 51
Digital EnergyTM, RPATM, PowerJUMP ManagerTM and PowerJUMPinTM are all trademarks of the General Electric Company
GEA D1016 CE © General Electric Company, USA All Rights Reserved (01/04) Reproduction only upon written consent by GE