Electrical & Automation

Wärtsilä
JOVYFLEX
PRODUCT LE AFLET

The new modular UPS series Wärtsilä JOVYFLEX offers an extremely flexible solution for
power supplies from 20 kVA up to 210 kVA. The UPS systems are based on 20 or 30 kVA
power modules as well as a static switch 120/180 or 210 kVA / kW. The UPS modules
impress with efficient power control, dynamic transitions without switchover times and a
high efficiency of 95%. The modular UPS systems Wärtsilä JOVYFLEX are the first choice
especially for use in data centers.

ONLINE UPS networks. The three-phase UPS systems protect the


As an online system (double converter, continuous conver- connected loads safely and reliably against operational
ter), Wärtsilä JOVYFLEX UPS systems reliably and econo- failures or damage caused by poor network quality.
mically protect against mains failures or disturbances of Without static switches, the UPS systems can also be
any kind. used as frequency converters. Depending on the number
of modules, a corresponding power increase or redundan-
HIGH EFFICIENCY AND FLEXIBILITY BY MODULAR cy can be built up.
DESIGN
The three cabinet types JOVYFLEX 120, JOVYFLEX 180 100% AVAIL ABILIT Y BY HOT-SWAP
and JOVYFLEX 210 are available for the realization of a The modules of the Wärtsilä JOVYFLEX UPS systems
wide variety of power supply solutions. Each one is equip- can be exchanged under operating conditions without
ped with the appropriate static switch and can accommo- observing special procedures (hot-swap). Thus, service
date a different number of modules of 20 kVA / kW or 30 enhancements or service inserts can be implemented in a
kVA / kW. time-saving and efficient manner during ongoing operation
of the system.
SAFE PROTECTION AT UNSECURE AND INSTAB - The Wärtsilä series JOVYFLEX is a cost-effective alterna-
LE NET WORKS tive to our modular UPS series Wärtsilä JOVYCUBE, which
The large AC input voltage range makes the Wärtsilä JO- has been specially developed for shipbuilding and use
VYFLEX UPS system particularly suitable for unstable under extreme environmental conditions.

Autonomy times in dependency to 20 30 40 60 80 90 100 120 150 180 210


the power of the UPS System kVA kVA kVA kVA kVA kVA kVA kVA kVA kVA kVA
Article number Termination Autonomy times [min]
1.159.020 1B10ES072009 11 - - - - - - - - - -
1.159.021 1B10ES108009 19 11 8 - - - - - - - -
1.159.022 1B10ES072012 15 - - - - - - - - - -
1.159.023 1B11ES080018 29 18 - - - - - - - - -
1.159.024 2B11ES072026 43 25 16 - - - - - - - -
1.159.025 2B11ES072044 107 65 45 24 15 13 - - - - -
1.159.026 3B11ES108026 76 43 28 16 - - - - - - -
1.159.027 3B11ES108044 150 93 58 30 21 17 14 - - - -
1.159.028 2B13E064070 - - - - - - - 11 8 6 -
1.159.029 2B13E064100 246 148 107 61 43 37 32 26 18 13 9

08/2017
WÄRTSILÄ JOV YFLEX

TECHNICAL DATA

JOVYFLEX JOVYFLEX JOVYFLEX


120 (80) 180 (120) 210 (140)
MODUL AR ONLINE UPS
Power 20 - 120 kVA 20-180 kVA 20-210 kVA SYSTEM
Leistung 20 kVA / 20 kW 20 kVA / 20 kW 20 kVA / 20 kW VFI / double conver ter
Power per module 30 kVA / 30 kW 30 kVA / 30 kW 30 kVA / 30 kW Ma ximum safety for
connected consumersr
Power Static Switch 120 kVA 180 kVA 210 kVA

Number of possible 1-4 1-6 1-7 HIGH EFFICIENCY


modules SAVES ENERGY COSTS
Highest output power
Dimensions cabinet 600x1475x1100 600x1475x1100 600x2010x1100
(K VA = K W )
W x H x D [mm]
Dimensions module 483x170x692 483x170x692 483x170x692
W x H x D [mm] EFFICIENT PERFORMANCE
CONTROL
Weight UPS cabinet by intelligent, integrated con-
without modules 100 kg 208 kg 307 kg
trol
with 20 kVA modules 188 kg 237 kg 457 kg
with 30 kVA modules 335 kg 415 kg 549 kg

Weight modules 21,5 kg (20 kVA) 21,5 kg (20 kVA) 21,5 kg (20 kVA) HIGHEST FLEXIBILITY
34,5 kg (30 kVA) 34,5 kg (30 kVA) 34,5 kg (30 kVA) by 20 kVA or 30 kVA modules

INPUT
PREVIEW OF THE BATTERY
Nominal voltage 3x380 V/220 V, 3x400 V/230 V, 3x415 V/240 V CAPACITY AND RESERVE
(TN-C mains is pre-adjustabler)
TIME
Tolerance of the input 3 x 305/176 VAC - 3 x 478/276 VAC at >70% load
voltage 3 x 208/120 VAC - 3 x 478/276 VAC at <70% load
HOT-SWAPPABLE
Frequency 40 up to 70 Hz Exchange of modules during
operation
Power factor ≥0,99 (50% up to 100% load)

OUTPUT STARTABLE WITHOUT NET-


Nominal voltage 3x380 V/220 V, 3x400 V/230 V, 3x415 V/240 V WORK
(TN-C mains is pre-adjustabler) Cold start is possible without
problems
Tolerance range <2% at static load, <4% at dynamic load
(10% - 100% - 10%)

Overload behaviour 105% - 110% for 60 minutes


111% - 125% for 10 minutes
126% - 150% for 1 minute
>150% for 200 ms
Frequency 50 or 60 Hz (automatical or adjustable)

DC INTERMEDIATE CIRCUIT
Number of battery cells 192 (minimal)
216 (nominal)
240 (maximum
Temperature kompen- 5mV per °C each cell
sation (option)
Battery charging 6A per module
current

COMMUNICATION
Optional available: Communication via SNMP, MODBUS, Relaycard

www.wartsila.com www.jovyatlas.com/UPS Systems