Liebert NXR Series: 30kva To 200kva
Liebert NXR Series: 30kva To 200kva
Liebert NXR Series: 30kva To 200kva
Scalability alone can’t get you there. You need an infrastructure that takes it
one step further. An infrastructure that can adapt to your needs.
Efficient and Adaptive Power For Your Only a double-conversion topology provides
100% protection with complete input to
Critical Applications output isolation and totally regenerated
The Liebert NXr from Emerson Network Power presents an efficient, space saving and power. A double-conversion UPS delivers
flexible solution for your network. With an above industry standard efficiency rate 100% power conditioning, zero transfer
time to battery, great stability of output
of up to 96% in a compact, low footprint UPS, Liebert NXr keeps your network
voltage and frequency and better transient
protected while saving on cost and data center space. suppression than line-interactive units.
With best in class true online double conversion technology, redundancy options
and flexible battery configurations, trust the Liebert NXr to provide the same level of Double-conversion systems also offer a
reliability you have come to expect from the Liebert NX UPS series. wider input voltage window that allows the
UPS to absorb deeper sags without having to
Features and Benefits transfer to battery.
High efficiency rating of up to 96% on true online double conversion mode DSP Control
Full digital control technology provides
High Power density with 200kVA load in <0.5m2 footprint
a highly accurate and drift-proof control
Advanced digital signal processor (DSP) and digital control technology to ensure higher compared to traditional analog electronics.
system reliability These features enable the UPS to provide
accurate and reliable power protection
Parallel technology allowing four (4) parallel units, without the need for centralized bypass under a wide range of conditions.
cabinet and additional external modules
Digital current sharing technology for externely small circulating current and high parallel
reliability
Wide input voltage and frequency range against harsh utility environment
Power output overload and short circuit capacity enhancing system stability and system
safety under extreme conditions
Intelligent battery management for automatic battery maintenance and prolonged
battery life
6-Inch LCD display available in 12 different languages
Layered Independent sealed duct and redundant fan design, circult board painting
Extended Load Ranges
protection and dust filter, offering outstanding protection from harsh environment
Modern Data Centers, Blade Servers, and IT
Advanced monitoring and communication capabilities for improved visibility and control applications in general, need more active
power. Moreover; In some instances, new
Lower mean time to repair (MMTR) with front access for maintenance
Data Centers have capacitive or leading
Flexible UPS system configuration that works in different modes of operation features while traditional systems had
inductive power factors, also known as
Efficiency Savings lagging.
Commercial Tariff : Cost Based on Rs. 7 per kWH* Leading Power Factor
Annual This exists when capacitive circuits prevail
Traditional UPS Liebert NXr / Total Annual
Rating ( ή =@92%) APM ( ή =@96%)
Energy Cost Annual Air
Saving
Saving @ 10 over inductive circuits. In this case, current
Saving Con. Saving Years is said to be “leading”, because its curve
(kVA) Energy Charges Energy Charges (in INR)
(in INR) (in INR) (D) (In INR)
(in INR) (A) (in INR) (B) (C=A-B)
E =(C+D) on a 2D chart is phase-shifted ahead of the
30 1,999,565 1,916,250 83,315 35,706 119,022 1,190,220 voltage curve. A UPS must be able to work
60 3,999,130 3,832,500 166,630 71,413 238,043 2,380,430 according to real load requirements. While in
90 5,998,696 5,748,750 249,946 107,120 357,065 3,570,650 the past, 0.7-0.8 Power Factor was common
120 7,998,261 7,665,000 333,261 142,826 476,087 4,760,870 for IT applications, today’s computers PF is
150 9,997,826 9,581,250 416,576 178,533 595,109 5,951,090 getting closer to 1.
Model NXr
Power (kVA) 30 kVA 60 kVA 90 kVA 120 kVA 150 kVA 100 kVA* 160 kVA* 200 kVA*
Power (KW) 30 KW 60 KW 90 KW 120 KW 150 KW 90 KW* 144 KW* 180 KW*
System efficiency
AC - AC online double conversion
75 - 100% Load Upto 96%
45 - 75% Load Upto 96%
25 - 45% Load Upto 95%
Input Parameters
Rated input voltage 380/400/415 VAC, three-phase four-wire
Rated operating frequency 50/60Hz
Input voltage range 305V - 477V at full load, -25% to -40% with linear load de-rating
Input frequency range 40Hz - 70Hz
Input power factor >0.99
Input THDi <3%
Input walk-in function Available, 5 - 30s (settable)
DC Parameter
Battery Type SMF / Wet Acid / Ni-Cd
Battery Compensation Yes
Charger output voltage regulation accuracy 1%
DC ripple low voltage ≤1%
Output Parameter
Inverter output voltage 380/400/415 VAC, three-phase four-wire
Inverter output frequency 50/60Hz
Output frequency stability 50Hz/60Hz±0.02%
Load power factor handling compatibility (without capacity derating) 0.9 leading - 0.9 lagging
Voltage stability
Steady state <±1%, typical
Transient state +/-5%, typical
Transient state response time <20ms
Inverter overload capacity 1 hour for 110%, 10 mins for 125%, 1 min for 150%, 200ms for >150%
Phase Shift
With 100% balanced load <1°
With 100% unbalanced load <1.5°
THDv
100% linear load <1%
100% non-linear load <1.5%
Bypass Parameter
Bypass input voltage 380/400/415 VAC, three-phase four-wire
Bypass voltage range settable through software Default: -20% to +15%, other values, such as -40%, -30%, -10% to +10%, +15%
Bypass overload capacity 135% long term, 170% for 1 hour, 1000% for 100ms
Environmental Conditions
Operating temperature range 0 - 40 °C*
Storage temperature -25 to 70 °C
Maximum Operating altitude ≤1000m, when operating at 1000>2000M, derated by 1% for every 100m increase of altitude
Relative Humidity ≤95%
Noise (1m) 55 - 62dB, adjusted according to load rate
IP Class IP20
Safety: IEC60950-1; IEC62040-1-1/AS62040-1-1,
Standards EMC: IEC62040-2/AS62040-2/EN50091-2 Class A,
Design and test: IEC62040-3/AS62040-3
Physical Parameters
Dimension, Width (mm) 600
Height (mm) 1400 1400 1400 1400 1400 1400 1400 1600
Depth (mm) 794
Weight (kg) 155 190 225 255 295 225 295 350