Netys RT

from 1100 to 11000 VA


Complete professional solutions for the protection
and availability of IT infrastructures

Switch to Green Power energy


NeTYS RT from 1100 to 11000 VA
Complete professional solutions for the
protection and availability of IT infrastructures
Infrastructures such as data centres, The way in which maintenance is performed those offered by blade technologies), in terms
networking systems and modern data on power supply devices is crucial in IT of space consumption and heat output.
networks play a leading role in value environments: the possibility of unintrusive A detailed knowledge of the operating
production on the information market. servicing (performed without switching parameters of power supply equipment is
Power supply problems can result in data off the load), reduced maintenance time equally important. This enables breakdowns
loss and undermine the productivity of IT and load protection are all fundamental to be prevented by maintaining the profitability
infrastructures. That is why IT loads require an considerations. of the infrastructure's operations.
extremely high-quality power supply, without Such infrastructures are increasingly required
disturbances or interruptions: business to manage the high-density processing power
continuity is the name of the game. of modern servers and devices (including

RANGES 110 A

Your >Switching
protection >Storage
for
>Servers and networking devices
>VoIP communication systems
>Structured cabling systems
>Control systems
>Video surveillance systems

2
Equipment for professionals
NeTYS RT has been designed to meet the
Converts from Tower to Rack mounted
demands of professional applications.
NeTYS RT is the most effective high power
density solution on the market: 4.4W/cm3
(11 kVA/8 kW UPS module).
The space and time-saving tower/rack
conversion option means that it can be
installed easily either in tower mode or inside
standard 19“ rack cabinets. The system
also offers practical connectivity options by
means of IEC320 sockets or terminals.

APPLI 057 - 058 - 059 - 060 - 061 - 062 - 063 - 064 A


Protection
Online double conversion technology
guarantees matchless power quality. This
ensures a perfectly stable sinusoidal waveform
at the output of the NeTYS RT, regardless of
the quality of the mains supply.
It includes built-in backfeed protection, in
compliance with the latest UPS system
regulations. This feature protects against
reverse current flow without the need for
additional external devices.
providing a tailor-made solution. Additionally Standard features for communication with
Availability in the case of parallel installations, the same external devices, such as Ethernet or USB,
battery pack can be used for both power enable all NeTYS RT models to communicate
The optional external manual bypass module modules, guaranteeing full back-up time and integrate easily in the infrastructure
also assures the continuity of power supplied availability even if one of the two modules is via the most widespread protocols on the
to loads during routine or non-routine undergoing maintenance. market.
maintenance of the system, resulting in
NeTYS RT can be installed easily in rack or
reduced mean time to repair (MTTR).
Comprehensive range tower mode, or converted from one mode
With the special manual parallel/bypass to another at any time, using the standard
module, 1+1 redundant architectures are The wide range of NeTYS RT modules offers
accessories included with the product.
easy to construct using NeTYS RT. This type an effective power solution architecture to
of architecture guarantees maximum power match the high-quality power demands of
availability in any situation, even following any medium or small load.
the breakdown of an electronic module, This vast range of solutions is accompanied
and is therefore essential for mission-critical by a series of standard and optional features
applications. that fulfil all of the protection, quality and
The possibility of adding extra battery communication needs of the installation
modules (BEM) means that back-up time environment.
in battery mode is flexible. This enables the The multilingual LCD display provides
system to meet the need for different back-up detailed information about the status and
times depending on the load supplied, thus alarms of the applications.

tech info
High Power Density
High power density devices are increasingly The adoption of high-density servers calls for
common in server rooms. suitable environments, infrastructures and
For example, the introduction of blade devices that are flexible enough to manage
technology has led to the production of the complexities of machines and cabling
increasingly compact and dense servers arranged in rack-mounted systems.
which take up less space than conventional NeTYS RT is perfectly suited for use in
servers with the same processing power. this high-density environment owing to its
This means that increased processing compact footprint, high energy efficiency
power per cubic centimetre is accompanied and connectivity options.
by increased heat output per cubic
centimetre.

3
NeTYS RT from 1100 to 3000 VA
The high-performance, versatile and
comprehensive UPS system
Simple to install Meets practical needs Standard electrical equipment
• IEC input and output connections compatible • Online double conversion technology with • Built-in backfeed protection;
with most IT equipment; sinusoidal waveform, to completely filter out • Protection against atmospheric phenomena
• Compact footprint (2U/89 mm) for installation all disturbances from/to the mains power (NTP) for telephone/ADSL modems;
in rack cabinets; supply and to ensure maximum protection • RJ11 connection for Emergency Power Off
• Attractive design for visible installation in of the utility; (EPO);
offices; • Optional battery extension modules (BEM) • Connection for battery extension modules.
• USB port and HID protocol as standard for to meet all back-up time requirements, even
direct interfacing with Windows systems®, after installation;
Communication options
without the need for additional specialist • Clear and uncluttered LED interface, with
software. buzzers that immediately indicate the • Programmable dry-contact interface;
operating status of the UPS, even for less • WEB / SNMP manager interface for
specialist users. connection to LAN network. This accessory
Easy to use
can be integrated in the UPS by means of
• No configuration necessary on first startup; the slot located on the back panel.
Standard communication
• Wide range of communication protocols
equipment
(including TCP/IP and SNMP) for integration Electrical options
into LAN networks or building management • USB connection;
systems (BMS). • Battery extension modules.
• RS232 connection for JBUS protocol;
• HID protocol for interfacing with Windows
systems®.

netys 065 A

4
Connections

1
8

9
4
5
6 9
7

10
netys 066 a

11

1 100 VA

1 8

3 11

4 9
5
6
7 9
APPLI 377 a
netys 067 a

10

1 700 VA - 2200 VA - 3 000 VA


Control panel
1. Mains input socket (IEC 320)
2. Fan 1. Yellow LED lit. Operation in bypass mode.
3. Output socket (full power) 1 4 2. Green LED lit. Mains healthy.
4. Telephone / modem line protection 3. OFF button.
5. EPO (Emergency Power Off) input 4. Green LED lit. Normal operation (inverter in-line)
6. RS232 interface (JBUS protocol) 2 5. ON/TEST and buzzer override button.
7. USB port 6.  ED bar. Depending on the situation, this indi-
L
netys 052 a

8. Input protection cates either the charge level or the capacity of


9. Output sockets (IEC 320 - 10 A) the battery
3 5
10. Battery extension connector
11. Slot for optional communication boards

Battery expansion
UPS EBM Back up time (minutes)
10 20 30 40 50 60 70 80 90 100 110 120 130 140
NRT-U1100 Internal
NRT-U1100 1 x NRT-B1100
NRT-U1100 2 x NRT-B1100
NRT-U1700 Internal
NRT-U1700 1 x NRT-B2200
NRT-U1700 2 x NRT-B2200
NRT-U2200 Internal

UPS UPS + 1 EBM UPS + 2 EBM NRT-U2200 1 x NRT-B2200


NRT-U2200 2 x NRT-B2200
NRT-U3000 Internal
NRT-U3000 1 x NRT-B3000
NRT-U3000 2 x NRT-B3000
50% of nominal load 75% of nominal load 100% of nominal load

UPS + 1 EBM UPS + 2 EBM UPS + 3 EBM


(standard)
55
NeTYS RT from 5000 to 11000 VA
The professional UPS system for high power
density, high availability and complete integration
Simple to install Meets practical needs Standard electrical equipment
•T  erminal input and output connections •O  nline double conversion technology with •B  uilt-in backfeed protection;
with built-in input protection by means of sinusoidal waveform, to completely filter out • RJ11 connection for Emergency Power
magnetothermal switch; all disturbances from/to the mains power Off (EPO);
• Compact footprint: 4U (178 mm) for 5-7 supply and to ensure maximum protection • Connection for battery extension modules.
kVA and 6U (267 mm) for 9-11 kVA, for of the utility;
• Port for parallel operation.
installation in rack cabinets; • Modular battery extension (BEM) to meet
• Optional manual bypass enables routine all back-up time requirements, even after
Communication options:
maintenace to be performed without installation;
disconnecting the powered appliance; • Possibility of 1+1 parallel redundant • Programmable dry-contact interface;
• Built-in LAN interface for remote monitoring configuration to maximise the availability
via Web browser or SNMP protocol of critical utilities, even in the event of a
module breakdown.
Easy to use
Standard communication
•L CD display with menu available in
6 languages features
• Extensive range of communication •1  0/100 LAN Ethernet connection;
protocols (including TCP/IP and SNMP) for • WEB/SNMP manager interface for connecting
integration in building management system the UPS system to the Ethernet network;
(BMS) networks. • RS 232 serial connection with JBUS
protocol.

netys 050 B

6
APPLI 378 a

Connections Electrical options


10 10 •1  +1 parallel module;
9 9 • Manual bypass without interruption;
8 8 • Battery extension modules.
11
2 11 1
1 7
2
2
6

netys 051 a
3
7
3 2
4 4 UPS with bypass
6
5
netys 076 a

netys 077 a

Control panel
5 000 VA - 7 000 VA+ battery 9 000 VA - 11 000 VA + battery

1. EPO (Emergency Power Off) input 7. RJ45 LAN ethernet connector


2. Fan 8. Parallel port connector 4
7
3. Battery extension connector 9. RS232 interface (JBUS protocol)
4. Output terminals 10. Slot for optional communication boards 1
5. Input terminals 11. Battery extension connector
6. Input switch
2
Battery expansion 5
UPS EBM Back up time (minutes)
10 20 30 40 50 60 70
netys 070 a

UPS UPS + 1 EBM UPS + 2 EBM


NRT-5000K Standard
NRT-5000K 2 x NRT-B7000 3 6
NRT-5000K 3 x NRT-B7000
NRT-7000K Standard 1. Yellow LED lit. Operation in bypass mode.
2. Green LED lit. Mains healthy.
NRT-7000K 2 x NRT-B7000
3. OFF button.
NRT-7000K 2 x NRT-B7000 4. Green LED lit. Normal operation (inverter in-line)
UPS + 1 EBM UPS + 2 EBM UPS + 3 EBM
(standard)
NRT-9000K Standard 5. ON/Enter and buzzer override button.
NRT-9000K 2 x NRT-B11000 6.  avigator buttons.
N
7.  lphanumeric LCD display.
A
NRT-9000K 3 x NRT-B11000
NRT-11000K Standard
NRT-11000K 2 x NRT-B11000
NRT-11000K 3 x NRT-B11000
50% of nominal load 75% of nominal load
100% of nominal load

7
Communication

To ensure optimal system availability while Remote multi-server shutdown


increasing resource efficiency and overall client option
system functionality, management of the
physical layer is key to monitoring and JNC shutdown client software, installed
controlling the power devices that support on the servers to be protected, prevents
your IT infrastructure. possible data loss by performing automatic
operating system shutdown in the event
of an extended power outage or other
Embedded UPS remote
potentially critical situation:
management • JAVA technology, uses standard TCP/IP and
All NeTYS RT models above 3 kVA integrate protocol and minimises CPU resources

NETYS 0 72 A
network management functionality, to enable • Possibility of customising the parameters
supervision of the UPS by connecting it and shutdown scripts for each individual
directly to the LAN network. Dry-contact card
client
The UPS has its own IP address with local • Constant checking of communication/
intelligence providing both an SNMP agent connection with UPS
and an HTTP/Web server via 10/100 Mb • Network Shutdown for Virtual Server
Ethernet connection: architecture
• Browser-accessible user interface for quick
access from anywhere on the network Modbus/JBus interface
• Display of UPS & BATTERY status,
measurements, settings and alarms The serial interface RS232 is available in all
NeTYS RT models allowing:
• Display of history log and statistical
measurements • P oint-to-point communication with
UNIVISION & UNIVISION PRO SW suite
• Pop-up warning messages in the event of
an alarm • The ability to fully integrate the UPS with a
building management system

NETYS 0 73 A
• Notification of alarms via e-mail (SMTP)
• SNMP protocol compliance: SNMPv1,
SNMPv3 USM HID
• E nterprise management system Some operating systems, such as Windows®,
SNMP interface (1.1-3 kVA)
compatibility with NMS systems such as have built-in power management service
Openview (via SNMP protocol) by means functions.
of MIB tables compliant with RFC1628 NeTYS RT models equipped with USB UPS Dry-Contact Management
• Communication with shutdown client port are HID protocol compatible, making
software installed on the remote to be the UPS system easy to manage when it Relay I/O Slot Card enables monitoring of
protected. is connected to computers using a USB UPS status through a simple dry-contact
cable; the operating system detects the interface
• Password Security to prevent unauthorised
access and to allow shared access without UPS automatically, enabling the UPS power • Customisable Input Contact
the risk of unauthorised configuration management function • 6 Customisable Output Relays
changes
• Security login by MD5
• Security authentication and encryption
features to ensure effective access control
and integrity for SSL browser and SSH NeTYS RT
NETYS 0 71 A GB

sessions.
Network Management features provide NMS System.
Remote control
a complete solution for the UPS power via SNMP
administration over the network, allowing
for orderly remote server shutdown to be Ethernet
network
performed via communication with JNC client. Remote
monitoring with
Web browser

Remote shutdown
workstation/server with JNC
E-mail
warning message

Remote monitoring and


control with Web browser

8
APPLI 379 A
Parallel / redundant function

Parallel redundant operation In a redundant configuration, overall system


for business continuity availability is much higher than a conventional
UPS system using similar technology.
To achieve the highest level of availability and 1+1 redundant configuration does not
to power critical utilities, NeTYS RT UPS require additional circuits and can therefore
modules above 3 kVA can be configured for be set up at a later date, simply by using
1:1 redundancy. two UPS modules and a collector/manual
Redundant operation (1+1) means: the bypass module which simplifies cabling and
system incorporates one more UPS module maintenance of the UPS installation.
than is needed to protect the load; in To further streamline the solution, it is also
the event of a breakdown, it guarantees possible to select between operation with
sufficient power supply capacity to the load separate battery or shared battery, which is
by maintaining online protection. extremely useful in the case of applications
NETYS 0 74 A GB

Parallel technology is based on the principle requiring high levels of autonomy.


of load sharing, whereby both units are
Load Load
always kept active.

9
Specifications
NeTYS RT 1100 NeTYS RT 1700 NeTYS RT 2200 NeTYS RT 3000 NeTYS RT 5000 NeTYS RT 7000 NeTYS RT 9000 NeTYS RT 11000
MODELS NRT-U1100 NRT-U1700 NRT-U2200 NRT-U3000 NRT-5000K NRT-7000K NRT-9000K NRT-11000K
POWER 1100 VA / 800 W 1700 VA/1200 W 2200 VA/1600 W 3000 VA/2100 W 5000 VA/3500 W 7000 VA/4900 W 9000 VA/6400 W 11000 VA/8000 W
Architecture online double conversion VFI with input PFC and automatic bypass
Parallel redundant function - - - - 1+1 1+1 1+1 1+1
INPUT
Voltage 230 V (1ph) 160~275 Vac; up to 130 Vac @70% load 230 V (1ph) 156~280 Vac up to 130 Vac @70% load
Frequency 50/60 Hz +/-10% (Auto-Selectable)
Power factor / THDi >0.98 / <6% >0.99 / <5%
OUTPUT
Waveform pure sinewave
Voltage 230 V (1ph) selectable 200/208/220/240V
Voltage THDv < 2%
Frequency 50 Hz or 60 Hz +/- 2% (+/- 0.05 Hz in battery mode)
Efficiency up to 91% online mode up to 92% online mode
Overload capability up to 105% continuously; 125% x 3 min; 150% x 30 sec up to 105% continuously; 125% x 5 min; 150% x 30 sec
Crest factor 3:1
Output connections 6 x IEC 320-C13 (10 A) 6 x IEC 320-C13 (10 A) + 1 x IEC 320-C20 (16 A) terminals
BATTERY
Standard autonomy* 7 7 7 8 10 7 10 7
+1EMB / +2EMB / +3EMB 30/60/80 40/80/120 30/60/80 38/70/100 27/47/60 18/29/48 25/45/60 18/32/43
Sealed lead acid maintenance free 2 pcs*12 V*9 Ah 4 pcs*12 V*7 Ah 4 pcs*12 V*9 Ah 6 pcs*12 V*9 Ah 16 pcs*12 V*5 Ah 16 pcs*12 V*5 Ah 20 pcs*12 V*7 Ah 20 pcs*12 V*9 Ah
Voltage 24 Vdc 48 Vdc 48 Vdc 72 Vdc 192 Vdc 192 Vdc 240 Vdc 240 Vdc
Recharge time < 6h to recover 90% capacity < 4h to recover 90% capacity
COMMUNICATION
Mimic panel LED LCD 6 languages
RS232 (DB9 port) Jbus protocol • • • • • • • •
USB HID protocol • • • • - - - -
WEB/SNMP (Ethernet RJ45 port) option option option option • • • •
COMM slot • • • • • • • •
Dry contacts card option option option option option option option option
EPO input (RJ11 port) • • • • • • • •
Modem/ADSL surge protection • • • • - - - -
Parallel port - - - - • • • •
OPTIONS
Manual bypass 2U - - - - option option option option
Parallel bypass 3U - - - - option option option option
Isolation transformer - - 2U 2U 3U 3U 3U 3U
Extra charger - 8A 8A 8A 4A 4A 4A 4A
STANDARDS
Performance & topology IEC 62040-3 (VFI-SS-111)
Safety /EMC IEC 62040-1-1 (TÜV-GS certified) IEC 62040-2
Product certifications CE, TÜV-GS, C-Tick
ENVIRONMENT
Operating ambient temperature from 0 °C to +40 °C (from 15 °C to 25 °C for best battery life)
Storage temperature range from -15 °C to +50 °C (from 15 °C to 25 °C for best battery life)
Relative Humidity 0-90% non-condensing
Maximum altitude 1000 m without derating (maximum 3000 m)
Noise level (ISO 3746) < 45 dB < 55 dB
Thermal dissipation (BTU/h) * 190 280 370 490 810 1140 1480 1851
ACCESSORIES included
Tower stand • • • • • • • •
Rack ear brackets • • • • • • • •
Cable glands - - - - • • • •
RS232 cable • • • • • • • •
Input mains cable • • • • - - - -
Load supply cable 2 IEC type 2 IEC type 2 IEC type 2 IEC type - - - -
DIMENSIONS & WEIGHT
UPS size std BUT (W x D x H mm) 440 x 332 x 88.7 440 x 430 x 88.7 440 x 430 x 88.7 440 x 608 x 88.7 440 x 670 x (177.4) 440 x 670 x (177.4) 440 x 623 x (261.2) 440 x 623 x (261.2)
UPS size RACK U 2U 2U 2U 2U 2U+2U 2U+2U 3U+3U 3U+3U
UPS weight std BUT (kg) 13 21 22 31 15.5+40 16+40 19.5+66 20+66
EBM module size (W x D x H mm) 440 x 332 x 88.7 440 x 430 x 88.7 440 x 430 x 88.7 440 x 608 x 88.7 440 x 608 x 88.7 440 x 608 x 88.7 440 x 623 x 130.6 440 x 623 x 130.6
EBM module RACK U 2U 2U 2U 2U 2U 2U 3U 3U
EBM module weight (kg) 16 29 29 43 40 40 66 66
MBP module size (WxDxH mm) - - - - 440 x 135 x 88.5
MBP module RACK U - - - - 2U
MBP module weight (kg) - - - - 3.5
MBP for parallel module size (WxDxH mm) - - - - 440 x 195 x 130.6
MBP for parallel module RACK U - - - - 3U
MBP for parallel module weight (kg) - - - - 5.0
* @ 75% of nominal load. EBM codes on page 5 (1.1-3 kVA range) and page 7 (5-11 kVA range).

10
SOCOMEC Group:
a manufacturer at your service

body 223 C
An established manufacturer The company’s standard turnover, operating Renowned expertise
profit and net profit are all showing steady
Incorporated in 1922, SOCOMEC is an Having already received the Award for
growth.
industrial group with a workforce of 2,200 Customer Service Excellence from Frost &
people. These figures allow the company to make Sullivan, the Best Practices Group, SOCOMEC
prudent yet ambitious plans for the future: UPS recently won a further prize, the 2006
Our independence allows us to have
plans which guarantee profitability and which Innovation Award.
long-term vision and complete control of
also aim to capture new market share, namely
any decisions affecting our development. This prestigious accolade was presented in
by setting up new subsidiaries worldwide.
The company is organised into two recognition of the company’s ability to propose
­independent divisions: SOCOMEC SCP, innovative solutions and, among other things,
experts in switching components and for the integration of its dynamic energy storage
­protection solutions, and SOCOMEC UPS, system VSS+ DC, which replaces batteries in
specialists in critical system power supply. DELPHYS UPS systems.
ranges 046 B
ranges 008 N

SOCOMEC UPS SOCOMEC SCP


UPS from 400 VA to 4800 kVA Switching and Protection Systems

An organisation focused
on customer satisfaction
Our equipment is designed and produced to
meet ISO 9001:2000 standards. SOCOMEC
UPS systems provide you with a fully protected
electrical power supply and first-rate service.

A worldwide presence
With a strong international presence in over
70 countries and subsidiaries in 17 countries,
SOCOMEC is a major player in the global
electrical equipment market.
maps 021 A

11
Socomec UPS
worldwide
IN EUROPE IN ASIA

COUV 156 A / QUAT UPS 3


BELGIUM PORTUGAL CHINA
Schaatsstraat, 30 rue du Patinage Universal Business Park
Rua Moinho do Cuco
B - 1190 Bruxelles B33, 3rd Fl, 10 Jiuxianqiao Rd.,
Bloco A
Tel. +32 (0)2 340 02 34 Chaoyang, Beijing 100016 P.R., China
Lj. Dta. - Paz
Fax +32 (0)2 346 16 69 Tel. +86 10 59756108
2640-566 MAFRA
be.ups.sales@socomec.com Fax. +86 10 59756109
Tel. +351 261 812 599
socomec@socomec.com.cn
FRANCE Fax +351 261 812 570
95, rue Pierre Grange portugal@socomec.com INDIA
F - 94132 Fontenay-sous-Bois Cedex B1, IInd Floor, Thiru-Vi-Ka-Industrial Estate
RUSSIA
Tel. +33 (0)1 45 14 63 90 Guindy
Kutuzovsky pr. 13, 44-45
Fax +33 (0)1 48 77 31 12 Chennai – 600 032
121248 - Moscow
ups.paris.dcm@socomec.com Tel. +91 44 3921 5400
Tel. +7 495 775 19 85
Fax +91 44 3921 5450 — 51
GERMANY Fax +7 495 775 19 85
sales@socomec-ups.co.in
Heppenheimerstraße 57 ups.russia@socomec.com
D - 68309 Mannheim
SLOVENIA MALAYSIA
Tel. +49 (0) 621 71 68 40 31 Jalan SS 25/41- Mayang Industrial Park
Savlje 89
Fax +49 (0) 621 71 68 44 4 47301 Petaling Jaya.- Selangor, Malaysia
SI - 1000 Ljubljana
de.ups.all@socomec.com Tel. +603 7804 1153
Tel. +386 1 5807 860
Fax +603 7803 8901
ITALY Fax +386 1 5611 173
sales@cspm.com.my
Via Leone Tolstoi, 73 - Zivido si.ups.info@socomec.com
20098 San Giuliano Milanese (MI)
SPAIN SINGAPORE
Tel. +39 02 98 242 942 31 Ubi Road 1, Aztech Building
C/Nord, 22 Pol. Ind. Buvisa
Fax +39 02 98 240 723 # 01-00 (Annex) - SG - Singapore 408694
E - 08329 Teià (Barcelona)
siconmi@socomec.com Tel. +65 6745 7555
Tel. +34 935 407 575
Fax +65 6458 7377
NETHERLANDS Fax +34 935 407 576
sg.ups.sales@socomec.com
Bergveste 2F info@socomec-aron.com
NL - 3992De Houten
UNITED KINGDOM THAILAND
Tel. +31 (0)30 63 71 504 No.9 Soi Vibhavadirangsit 42
Units 7-9 Lakeside Business Park
Fax +31 (0)30 63 72 166 Vibhavadirangsit Rd, Ladyao
Broadway Lane - South Cerney
info@socomec.nl Chatujak Bangkok 10900
Cirencester - GL7 5XL
Tel. +66 2 941-1644-7
POLAND Tel. +44 (0)1285 863300
Fax. +66 2 941-1650
Nowowiejska St 21/25 Fax +44 (0)1285 862304
info@socomec-th.com
00-665 Warszawa uk.ups.sales@socomec.com
Tel. +48 (0)22 2345 223
Fax +48 (0)22 2345 223
ups.poland@socomec.com

Réf. DOC 96023 - 01/09 - Photo : Alberto Carolo - Réalisation : SOCOMEC Service Communication
HEAD OFFICE S ales , M ar k eting and
SOCOMEC GROUP S ervice M anagement
S.A. SOCOMEC capital 11 302 300 E - R.C.S. Strasbourg B 548 500 149 SOCOMEC UPS paris
B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex 95, rue Pierre Grange
SOCOMEC UPS Strasbourg F-94132 Fontenay-sous-Bois Cedex - FRANCE
11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12
Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90 ups.paris.dcm@socomec.com
ups.benfeld.admin@socomec.com
SOCOMEC UPS Isola Vicentina
Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY
Tel. +39 0444 598611 - Fax +39 0444 598622
info.it.ups@socomec.com

www.socomec.com
Non contractual document. © 2009, Socomec SA. All rights reserved.