Avr Conversion Instructions
Avr Conversion Instructions
Avr Conversion Instructions
ISSUE 5
** For 3 phase sensing unit see final section on 3 phase sensing unit.
Figure 1 : New MX341 AVR - E000-23410 Figure 2 : Old Series 3 - 450-11700
5
1
2
3
INSTRUCTIONS
Refer to figure 1 and 2 (above) the following instructions refer to items 1-5 respectively on above diagrams.
Refer to figure 3 and 4 (overleaf) for instruction 6 and AVR and auxiliary terminal position.
1. Connect AVR wires to terminals with identical markings. Cut off and insulate lead P1 if fitted.
2. Select correct frequency tapping 50Hz or 60Hz, 4 and 6 pole machines.
3. Select correct link on C, B, A, for size of generator.
4. Links will be connected as shown on AVR, DO NOT MOVE THESE LINKS unless your old AVR (figure 2) is type 450-11800
with separate 3 phase sensing unit. See section overleaf on 3 phase sensing unit.
5. DO NOT REMOVE LINK MARKED K1-K2 on AVR terminals, unless a protection trip was fitted across K1-K2 on previous AVR.
Refer to figure 3,4,5 and 6 overleaf.
6. Remove generator terminal box lid, link together auxiliary terminals marked 1 and 2 or short wires 1 and 2 together on the
same terminal.
Generator Types - AVR and Auxiliary Terminal Position
Auxiliary Terminals
AVR Position Auxiliary Terminals
6
6
PMG
AVR Position
Assembly