NP7 - 010

ISSUE 5

AVR CONVERSION INSTRUCTIONS


FITTING KIT 45-0053
FOR USE WITH MX341 AVR Part No. E000-23410
PERMANENT MAGNET GENERATORS ONLY
Fitting kit 45-0053 comprises the following:- The MX341 AVR is fully interchangeable with the following:-

1 - Adjustment & Identity Label E00-13418 Series 3 4 Pole 450-11700


Series 3 3 Phase Sensing 450-11800**
1 - MX341 Instruction Sheet NP7-006:5513
Series 3 VAr, AVR E000-23010
Series 3 VAr, AVR (3 Phase Sensing) E000-23015**
Series 3 Special Slope AVR E000-23000
Series 3 LA32 E000-23020
Series 3 LA33 E000-23030

** For 3 phase sensing unit see final section on 3 phase sensing unit.
Figure 1 : New MX341 AVR - E000-23410 Figure 2 : Old Series 3 - 450-11700
5
1

2
3

DO NOT CONNECT AS SHOWN FOR 3


PHASE SENSING UNLESS THE GENERATOR
IS ALREADY FITTED WITH A 3 PHASE
Warning ! SENSING UNIT.

INSTRUCTIONS
Refer to figure 1 and 2 (above) the following instructions refer to items 1-5 respectively on above diagrams.
Refer to figure 3 and 4 (overleaf) for instruction 6 and AVR and auxiliary terminal position.

1. Connect AVR wires to terminals with identical markings. Cut off and insulate lead P1 if fitted.
2. Select correct frequency tapping 50Hz or 60Hz, 4 and 6 pole machines.
3. Select correct link on C, B, A, for size of generator.
4. Links will be connected as shown on AVR, DO NOT MOVE THESE LINKS unless your old AVR (figure 2) is type 450-11800
with separate 3 phase sensing unit. See section overleaf on 3 phase sensing unit.
5. DO NOT REMOVE LINK MARKED K1-K2 on AVR terminals, unless a protection trip was fitted across K1-K2 on previous AVR.
Refer to figure 3,4,5 and 6 overleaf.
6. Remove generator terminal box lid, link together auxiliary terminals marked 1 and 2 or short wires 1 and 2 together on the
same terminal.
Generator Types - AVR and Auxiliary Terminal Position
Auxiliary Terminals
AVR Position Auxiliary Terminals
6
6
PMG
AVR Position
Assembly

Figure 4 : SC and HC Range Generator with AVR


Figure 3 : C Range Generator with AVR Mounted on Frame Mounted on the Terminal Box

AUXILIARY TERMINALS SETTING UP INSTRUCTIONS


If a remote voltage trimmer is not required, short circuit auxiliary Refer to MX341 instruction sheet (Publication No.
terminal 1 and 2, as shown in figures 5 and 6. NP7-006:5513), for adjustment of voltage and stability controls.
MACHINES MANUFACTURED AFTER FEB 87 If the generator is NOT required for parallel operation or for
For machines manufactured after February 1987 a new Push- use with VAr/PF controller, adjust AVR controls marked
on auxiliary terminal arrangement is within the terminal box "DROOP" AND "TRIM" fully ANTICLOCKWISE.
(See figure 5 below). Pull-off wire marked 1 and push-on to
auxiliary terminal marked 2. For parallel operation the MX341 AVR is fully compatible with
existing droop equipment in the generator.
Remove cable marked 1
to terminal marked 2
REMOTE HAND TRIMMER : 1K W Part No. 071-01649

If a remote hand trimmer is required, it is connected to the


auxiliary terminal block at terminals 1 and 2 in the generator
terminal box. If a 4.7K W trimmer (Part No. 071-01037) is
already fitted, then the effective control will be "all at one
end". If this is unsatisfactory for fine voltage adjustment
then the new 1K W hand trimmer should be fitted.

Figure 5 : Auxiliary Terminals after February 1987 3 PHASE SENSING UNIT


The MX341 will operate in conjunction with the existing 3
MACHINES MANUFACTURED BEFORE FEB 87 phase sensing unit (Part No. 450-11000). The correct
connection links must be made on the AVR for 3 phase
For machines manufactured before February 1987 a Stud
sensing. Refer to the MX341 instruction sheet (Publication
arrangement is within the terminal box (See figure 6 below).
No. NP7-006:5513).
Unscrew stud holding wire marked 1 remove all washers and
place onto auxiliary terminal marked 2.
Should the 3 phase sensing unit be faulty, a direct replace-
ment is available from our Parts Department.
Remove cable marked 1
to terminal marked 2
IMPORTANT ! SEE ITEM 4 OVERLEAF.
DO NOT CONNECT AVR IN THE 3 PHASE SENSING MODE
UNLESS A SEPERATE 3 PHASE SENSING UNIT IS ALREADY
FITTED OR HAS BEEN PURCHASED FOR FITTING WITH THE
MX341 AVR.

Figure 6 : Auxiliary Terminals before February 1987

NEWAGE INTERNATIONAL LIMITED


Registered Office and Address:
PO Box 17, Barnack Road, Stamford, Lincolnshire PE9 2NB England.
Telephone: 44 (0) 1780 484000 Fax: 44 (0) 1780 484100 Website: newagestamford.com Registered in England No. 441273

PRINTED IN ENGLAND