Experiment No.7 Name-Siddharth Bansal Roll No. - 193073 Branch-Mechanical Engineering
Experiment No.7 Name-Siddharth Bansal Roll No. - 193073 Branch-Mechanical Engineering
Experiment No.7 Name-Siddharth Bansal Roll No. - 193073 Branch-Mechanical Engineering
Branch-Mechanical Engineering
Aim – To study the hermetically sealed compressor and different types of cut-
out/safety devices used in Vapor Compression Refrigeration system
Theory-
In hermetically sealed compressor, the compressor and the motor are enclosed in the
welded steel casing and the two are connected by a common shaft. This makes the
whole compressor and the motor a single compact and portable unit that can be
handled easily. The hermetically sealed compressor is very different from the
traditional open type of compressors in which the compressor and the motor are
different entities and the compressor is connected to the motor by coupling or belt.
One of the most popular types of the hermetically sealed compressors are the
reciprocating compressors. They were the first to be used as the hermetically sealed
compressors are still being used widely. These days the vane type of rotary
compressor has become more popular. It is considered that the rotary type of
hermetically sealed compressor consumes less electricity, makes lesser noise,
requires lesser maintenance, and is cheaper than the reciprocating type of
hermetically sealed compressor. This is because the rotary compressors has less
frictional parts and have only a rotor. The centrifugal types of hermetically sealed
compressor are used for the large units.
The hermetically sealed reciprocating compressor is widely used for the refrigeration
and air conditioning applications. In all the household refrigerators, deep freezers,
window air conditioners, split air conditioners, most of the packaged air conditioners,
the hermetically sealed reciprocating compressor is used. The hermetically sealed
reciprocating compressor is very easy to handle, and requires low maintenance. They
are used with motor power requirements from 1/20 to 71/2 hp.
All these parts of the hermetically sealed compressor are assembled and enclosed in a
strong and rigid casing made up of welded steel shell. The steel shell comprises of two
half rounded steel bodies that are welded together to form the casing for the
hermetically sealed compressor. In some cases the two halves of the shell can be
bolted together instead of welding, which permits easy opening of the casing in case
of compressor burnout.
The hermetically sealed compressors have inbuilt lubrication system for the
lubrication of the piston and cylinder and crankshaft. The lubricant also acts the
coolant for the piston and cylinder. Additionally, the cool suction refrigerant also
offers cooling effect.
Externally, the casing has refrigerant suction and discharge connections that are
connected to the evaporator and condenser respectively. There is also socket for the
electrical connection.
Advantages of the Hermetically Sealed Compressors
The hermetically sealed compressors are used widely in the refrigeration and air
conditioning applications because of several advantages, here are some of them:
The hermetically compressors can be moved easily from one place to the
other place, they are highly portable. One does not have to disassemble the
compressor from the motor and no coupling, belt and pulley arrangement is
involved.
The whole condenser unit of the refrigeration or the air conditioning unit
comprising of the condenser and the compressor can be moved easily from
one place to the other. Its location can be changed easily.
Since no coupling, belt or pulley is involved, the maintenance is lesser.
The lubrication system of the hermetically sealed compressor is inherent and
no external lubrication is required, unless the fresh gas charging is done.
The installation of the hermetically sealed compressor is very easy. The
suction and discharge connections and the electrical connections are available
externally.
Hermetically sealed compressors have very long life, the companies offer
warranty period of up to seven years for these compressors.
Apart from the many advantages the hermetically sealed compressor has some
disadvantages, as mentioned below:
When the motor winding of the hermetically sealed compressor burns, the
whole compressor has to be replaced. In such cases though the company gives
some compensation for the old damaged compressor, still it’s a costly affair to
replace the whole compressor of your household refrigerator or air
conditioner. Not only you will have to replace the compressor, but fresh gas
charging has to be done. In open type of compressor, if the motor winding
burns, merely the winding has to be changed.
If any parts of the compressor like the cylinder, piston etc, gets damaged,
again the whole hermetically sealed compressor has to be replaced and then
one has to do fresh gas charging. In open type of compressor one can easily
replace various parts of the compressor.
Cut-out safety devices used in vapor Compression Refrigeration System
Low Pressure or LP cut off: This is a compressor safety which cut off the
compressor in the event of pressure drop in the suction line. The pressure of
the suction line is continuously sensed by the control unit and when it goes
below the set value, which means the room is properly cooled, the LP cut out
will auto trip the compressor. When the pressure rises, indicating there is flow
of refrigerant in the line due to increase in room temperature, the LP switch
will start the compressor.
High pressure or HP cut out: As the name suggests, the high pressure cut out
activates and trips the compressor when the discharge side pressure increases
above the limit value. The HP cut out is not auto reset and has to be done
manually. The reason behind it is to manually attend the fault which is leading
to rise in pressure, else this situation can lead to overloading of compressor
parts and may damage the same
Oil differential cut out: This safety is again for compressor as it is the only
machinery in the circuit having rotational parts which requires continuous
lubrication. In the event of low supply or no supply of lube oil to the bearing,
the differential pressure will increase and activates a trip signal to safeguard
the bearing and crankshaft.
Relief valves: Relief valves are fitted in discharge side of compressor and will
lift and safeguard the compressor in the event of over pressure. One relief
valve is also fitted in the condenser refrigerant line to avoid damage to the
condenser if there is high pressure in the discharge line.
Solenoid valves: Master solenoid valve is fitted in the common or main line
after the condenser discharge. It closes when compressor stops or trips to
avoid over flow of refrigerant in to evaporator. All holds or rooms are fitted
with individual solenoid valve which control the flow of refrigerant to that
room.
Oil heater: Oil heater is provided for the compressor crank case oil and
prevents compressor from getting excessively cold which may effect the
lubrication of the parts.