LV Cable Commissioning Test Report

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

LV CABLE COMMISSIONING TEST REPORT

CABLE NUMBER/S LOCATION: REPORT:

FEEDER:

Preliminary Details: Main backbone identified as section 1, Each tee-off or spur identified as separate section
Section From To Conductor Type and Size:
1
2
3
4

Core Continuity Instrument Number:


Readings in Section A-N B-N C-N A-B B-C C-A
Ohms 1
2
3
4

Insulation Resistance Instrument Number:


Readings in Megohms.
All cable sections together A - B+C+N+E B - A+C+N+E C - A+B+N+E N - A+B+C+E Acceptance Levels
Test Voltage: 1.0kV @ 1Min New 100M, aged 1 M

Sheath Integrity Applicable to metallic Instrument Number:


screen cables only
Readings in All cable sections together Msh- E Msh- E Msh- E Msh- E Acceptance Levels
Megohms. Test Voltage: 1.0kV @ 1Min Greater then 10 M
MEN Resistance Instrument Number:
Readings in Location Ohms Location Ohms
Ohms

Voltage Measurements Instrument Number:


Location Voltage
A-N B-N C-N A-B B-C C-A

LV Phase Out
From: To: Instrument Number:
Voltage Measurement
A1-A2 A1-B2 A1-C2 B1-A2 B1-B2 B1-C2 C1-A2 C1-B2 C1-C2

Phasing marked: Yes / No Cable number marked: Yes / No / NA


MENs replaced: Yes / No Pillars/switchgear labelled: Yes / No
Neutrals replaced: Yes / No Terminations tightened: Yes / No
Fuses replaced: Yes / No Pillars/switchgear correct alignment/depth: Yes / No
Polarity okay: Yes / No Pillars/switchgear closed/locked: Yes / No
REMARKS:…………………………………………………………………………………………………………
……………………..…………………………………………………………………………………………………
TEST OFFICER: DATE: SUPERVISOR:

Page 1 of 1 Form SP0405C01 Ver 4