C12 Application Reference Data
C12 Application Reference Data
C12 Application Reference Data
Section 12
Application and technical reference data
Page
12
12 - 1
Innovators in Protection Technology
12 Notes: 1
) Minimum fuse size is based on grading under overload of one MCB with one
set of fuses. Where a single set of fuses protects more than one MCB, the
minimum fuse size shall be increased to allow for load biasing effects.
2
) Maximum fuse size based on testing to AS/NZS 3439.1 clause 8.2.3.
3
) For specific kA ratings applicable to MCBs, refer page 1 - 21 ratings chart.
Tables based on the following maximum pre-arcing I2t for both BS 88 and DIN fuses:
125 A - 0.4 x 105, 160 A - 0.62 x 105, 200 A - 1.2 x 105, 250 A - 2.1 x 105.
Suitable fuses include NHP, GEC, Siemens and Bovara-Crady.
Fuses with higher current ratings may be used provided I2t values are equal to, or less than, the levels above.
Semi-conductor fuses have very low I2t values and may suit some applications.
Attention is also drawn to AS/NZS 3000 clause 7.10.4.4, regarding the use of fault current limiters in
installations containing fire and smoke control equipment, evacuation equipment and lifts.
12 - 2
Innovators in Protection Technology
Application data
Selectivity and Cascading applications
12
breakers should be in accordance with the selection tables
located in this section.
The figures stated in NHP tables are for nominated Terasaki
devices only and should not be used as a guide to using
alternative brands of circuit breakers.
12 - 3
Innovators in Protection Technology
Application data
Selectivity and Cascade – Miniature circuit breakers
Upstream C curve
C Curve
Din-T 10 6 0.07 0.10 0.15 0.18 0.23 0.27 0.35 0.45 1.5 1.6 1.7
10 – – 0.15 0.18 0.23 0.27 0.35 0.45 1 1.1 1.2
16 – – – – 0.23 0.27 0.35 0.45 1 1.1 1.2
20 – – – – 0.23 0.27 0.35 0.45 1 1.1 1.2
25 – – – – – 0.27 0.35 0.45 0.9 1.1 1.1
32 – – – – – 0.27 0.35 0.45 0.9 1 1
40 – – – – – – – – – 0.9 0.9
50 – – – – – – – – – – –
63 – – – – – – – – – – –
Upstream C curve
C Curve
Din-T 6 6 0.07 0.10 0.15 0.18 0.23 0.27 0.35 0.45 1 1.1 1.2
Din-T 10 10 – – 0.15 0.18 0.23 0.27 0.35 0.45 1 1.1 1.2
Din-T 15 16 – – – – – 0.27 0.35 0.45 1 1.1 1.2
20 – – – – – 0.27 0.35 0.45 1 1.1 1.1
25 – – – – – 0.27 0.35 0.45 0.9 1 1.1
32 – – – – – – 0.35 0.45 0.9 0.9 1
40 – – – – – – – 0.45 – – 0.9
50 – – – – – – – – – – –
63 – – – – – – – – – – –
12
12 - 4
Innovators in Protection Technology
Application data
Selectivity and Cascade – Miniature circuit breakers
12 - 5
Innovators in Protection Technology
Application data
Selectivity and Cascade tables @ 400 / 415 V
MCCBs and MCBs
Guide
XX / YY
Selectivity Cascade
Upstream MCCBs
25 kA 36 kA 65 kA 125 kA 36 kA 25 kA
Downstream
E125NJ S125NJ S125GJ-ZS125GJ H125NJ S160NJ E125NJ
MCB
Current kA
Cat. No. Range (A) (RMS) 63 80 100 125 63 80 100 125 63 80 100 125 63 80 100 125 160 63 80 100 125 160
≤20 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 35/35 35/35 35/35 35/35 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
25 & 32 20/25 20/25 20/25 20/25 20/25 20/25 20/25 20/25 20/25 20/25 20/25 20/25 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30
6
DTCB6 40 - /25 20/25 20/25 20/25 -/25 20/25 20/25 20/25 -/25 20/25 20/25 20/25 -/30 30/30 30/30 30/30 30/30 -/30 30/30 30/30 30/30 30/30
50 & 63 - /25 -/25 20/25 20/25 -/25 -/25 20/25 20/25 -/25 -/25 20/25 20/25 -/30 -/30 30/30 30/30 30/30 -/30 -/30 30/30 30/30 30/30
≤32 25/25 25/25 25/25 25/25 30/36 30/36 30/36 30/36 30/50 30/50 30/50 30/50 36/36 36/36 36/36 36/36 36/36 40/36 40/36 4/36 40/36 40/36
DINT10H,
DSRCBH 40 10 - /25 20/25 20/25 20/25 -/25 20/25 20/25 20/25 -/25 20/25 25/25 25/25 -/30 30/30 30/30 30/30 30/30 - /30 30/30 30/30 30 /30 30/30
& DSRCB
50 & 63 - /25 -/25 20/25 20/25 -/25 -/25 20/25 20/25 -/25 -/25 25/25 25/25 -/30 -/30 30/30 30/30 30/30 - /30 - /30 30/30 30 /30 30/30
80 4/25 4/25 4/25 4/25 4/25 4/25 15/15 15/15 15/15 15/15 15/15 15/15
≤32 25/25 25/25 25/25 25/25 30/36 30/36 30/36 30/36 30 /50 30/50 30/50 30/50 30/36 30/36 30/36 30/36 30/36 40/65 40/65 40/65 40/65 40/65
DIN-T15 40 15 -/25 20/25 20/25 20/25 -/25 20/25 20/25 20/25 -/25 20/25 25/25 25/25 -/30 30/30 30/30 30/30 30/30 - /30 30/30 30/30 30/30 30/30
50 & 63 -/25 -/25 20/25 20/25 -/25 -/25 20/25 20/25 -/25 - /25 25/25 25/25 -/30 - /30 30/30 30/30 30/30 - /30 - /30 30/30 30/30 30/30
SAFE-T & ≤63 6 -/10 3/10 3/10 3 /10 -/10 3/10 3/10 3/10 -/10 3/10 3/10 3/10
SRCB
Upstream MCCBs
25 kA 36 kA 65 kA 70 kA
Downstream S250PE
E250NJ S250NJ S250GJ - ZS250GJ
MCB
Current kA
Cat. No. Range (A) (RMS) 63 80 100 160 200 250 160 200 250 160 200 250 63 80
≤20 25/25 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36
25 & 32 25/25 25/25 25/25 25/25 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30
6
DTCB6 40 -/25 20/25 25/25 25/25 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 -/30 30/30
50 & 63 -/25 -/25 25/25 25/25 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 -/30 -/30
≤32 25/25 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 40/65 40/65 40/65 40/65 40/65
DINT10H,
DSRCBH 40 10 -/25 20/25 25/25 25/25 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 -/30 30/30
12
& DSRCB
50 & 63 -/25 -/25 25/25 25/25 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 -/30 -/30
80 15/25 15/25 15/25 15/25 15/25 15/25 15/25 15/25 15/25 15/25
DIN-T10H 100 10 15/25 15/25 15/25 15/25 15/25 15/25 15/25 15/25 15/25
125 -/25 15/25 15/25 - /25 15/25 15/25 - /25 15/25 15/25
≤32 25/25 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 40/65 40/65 40/65 40/65 40/65
DIN-T15 40 15 -/25 25/25 25/25 25/25 25/25 25/25 20/25 20/25 -/25 30/30 30/30 30/30 -/30 30/30
50 & 63 -/25 -/25 25/25 25/25 25/25 25/25 30/30 30/30 30/30 -/65 -/65 30/30 -/30 -/30
12 - 6
Innovators in Protection Technology
Application data
Selectivity and Cascade tables @ 400 / 415 V
MCCBs and MCBs
Cascade
The resultant cascade level with the S250GJ (250 A, 65 kA MCCB) and DTCB10 (32 A, 10 kA MCB) is 65 kA.
This means that the S250GJ will back-up the DTCB10 MCB to 65 kA, which is beyond the normal breaking
capacity of 10 kA.
Selectivity
From the tables, the selectivity level between the same two breakers, S250GJ and DTCB10 connected in
series will be 40 kA. This means that for fault levels up to and including 40 kA, the DTCB10 will trip before
the S250GJ.
Conclusion
For short circuit currents up to and including 40 kA, the DTCB10 will trip before the S250GJ, therefore
ensuring selectivity. For fault levels above 40 kA, both breakers will trip, however the S250GJ will back up
the DTCB10 to 65 kA.
125 kA 36 kA 50 kA 70 kA
100 125 160 200 250 100 200 250 400 100 200 250 400 100 200 250 400
36/36 36/36 36/36 36/36 36/36
40/65 40/65 40/65 40/65 40/65 36/36 36/36 36/36 36/36 40/50 40/50 40/50 40/50 40/65 40/65 40/65 40/65
30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30
30/30
15/15
30/30
15/15
15/15
30/30
15/15
15/15
30/30
15/15
15/15
30/30
15/15
15/15
30/30
10/10
10/10
30/30
10/10
10/10
30/30
10/10
10/10
30/30
10/10
10/10
30/30
10/10
10/10
30/30
10/10
10/10
30/30
10/10
10/10
30/30
10/10
10/10
30/30
10/10
10/10
30/30
10/10
10/10
30/30
10/10
10/10
30/30
10/10
10/10
12
-/10 10/10 10/10 10 /10 -/10 10/10 10/10 10/10 -/10 10/10 10/10 10/10
40/65 40/65 40/65 40/65 40/65 36/36 36/36 36/36 36/36 40/50 40/50 40/50 40/50 40/65 40/65 40/65 40/65
40/65 40/65 40/65 40/65 40/65 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30
40/65 40/65 40/65 40/65 40/65 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30
12 - 7
Innovators in Protection Technology
Application data
Selectivity and Cascade tables @ 400 / 415 V MCCBs
Electronic MCCBs upstream
XX / YY
Selectivity / Cascade
H250NE
H400NE
L400NE
Upstream
S400NE
E630NE
S400GE
S250PE
S400PE
S630CE
MCCBs
Downstream kA
MCCBs (RMS) 70 125 50 70 85 125 200 36 50
E125NJ 25 25 /50 25 65 25 /36 25 /50 25 /50 25 /65 25 /85 25 /36 25 /36
S125NJ 36 36 /65 36 85 36 /50 36 /65 36 /65 36 /85 36 /125 36 /36 36 /50
S125GJ 65 65 /70 65 125 50 /50 65 /70 65 /85 65 /125 65 /150 36 /36 50 /50
ZS125GJ
H125NJ 125 70 /70 125 125 50 /50 70 /70 85 /85 125 /125 125 /200 36 /36 50 /50
S160NJ 36 - /65 - 85 36 /50 36 /65 36 /65 36 /85 36 /125 36 /36 36 /50
S160GJ 65 - /70 - 125 50 /50 65 /70 65 /85 65 /125 65 /150 36 /36 50 /50
H160NJ 125 - /70 - 125 - /50 - /70 - /85 125 /125 125 /200 36 /36 50 /50
E250NJ 25 - /50 - 85 25 /36 25 /50 25 /50 25 /65 25 /85 25 /36 25 /36
S250NJ 36 - /65 - 85 36 /50 36 /65 36 /65 36 /85 36 /125 36 /36 36 /50
S250GJ 65 - /70 - 125 50 /50 65 /70 65 /85 65 /125 65 /150 36 /36 50 /50
ZS250GJ
S250PE 70 - 125 - /50 - /70 - /85 70 /125 70 /150 36 /36 50 /50
H250NJ 125 - /50 - /70 - /85 125 /125 125 /200 36 /36 50 /50
H250NE 125 - /50 - /70 - /85 125 /125 125 /200 36 /36 50 /50
E400NJ 25 - /36 - /50 - /50 - /65 - /85 10 /36 10 /36
S400CJ 36 - /50 - /65 - /65 - /70 - /100 10 /36 10 /50
S400NE 50 - /50 - /70 - /50 - /50 10 /36 10 /50
S400NJ 50 - /70 - /70 - /85 - /125 10 /36 10 /50
S400GJ 70 - /85 - /125 - /150 10 /36 10 /50
H400NJ 125 - /85 - /125 - /150 10 /36 10 /50
H400NE 125 - /85 10 /36 10 /50
E630NE 36
E630CE 50
S630GE 70
XS630CJ 45
XS630NJ 65
XS630PJ 85
XS630SE 50
XH630SE 65
12 XH630PE
XS800NJ
65
65
XS800SE 50
XJ800PJ 85
XH800SE 65
XH800PE 65
XS1250SE 65
XS1600SE 85
12 - 8
Innovators in Protection Technology
Application data
Selectivity and Cascade tables @ 400 / 415 V MCCBs
XX / YY
Selectivity / Cascade
XS2000NE
XS2500NE
XS3200NE
TL1250NE
XS1250SE
XS1600SE
XH630SE
XH800SE
TL630NE
TL800NE
XS630SE
XS800SE
Upstream
S630GE
MCCBs
Downstream kA
MCCBs (RMS) 50 65 70 125 50 65 125 85 125 100 85
E125NJ 25 25 /36 25 /50 25 /50 25 /25 25 /36 25 /36 25 /36 25 /25 25 /25 25 /25 25 /25
S125NJ 36 36 /50 36 /65 36 /65 36 /36 36 /50 36 /36 36 /36 36 /36 36 /36 36 /36 36 /36
S125GJ 65 50 /50 65 /65 65 /70 65 /65 50 /50 65 /65 65 /65 65 /65 65 /65 65 /65 65 /65
ZS125GJ
H125NJ 125 50 /50 50 /65 70 /70 70 /125 50 /50 65 /65 65 /125 85 /85 85 /125 100 /100 85 /85
S160NJ 36 36 /50 36 /50 36 /50 36 /36 36 /50 36 /65 36 /36 36 /36 36 /36 36 /36 36 /36
S160GJ 65 50 /50 50 /65 65 /70 65 /65 50 /50 50 /65 50 /65 65 /65 65 /65 65 /65 65 /65
H160NJ 125 50 /50 50 /65 70 /70 70 /125 50 /50 50 /65 50 /125 85 /85 85 /125 100 /100 85 /85
E250NJ 25 25 /36 25 /50 25 /50 25 /25 25 /36 25 /50 25 /50 25 /25 25 /25 25 /25 25 /25
S250NJ 36 36 /50 36 /65 36 /65 36 /36 36 /50 36 /65 36 /65 36 /36 36 /36 36 /36 36 36
S250GJ 65 50 /50 50 /65 65 /70 65 /65 50 /50 50 /65 50 /65 65 /65 65 /65 65 /65 65 65
S250PE 70 50 /50 50 /65 70 /70 70 /70 50 /50 65 /65 50 /70 70 /70 70 /70 70 /70 70 70
H250NJ 125 50 /50 50 /65 70 /70 70 /125 50 /50 50 /65 50 /125 85 /85 85 /125 100 /100 85 85
H250NE 125 50 /50 50 /65 70 /70 70 /125 50 /50 65 /65 50 /125 85 /85 85 /125 100 /100 85 85
E400NJ 25 10 /36 10 /50 10 /50 10 /36 25 /36 25 /50 25 /36 25 /36 25 /36 25 /36 25 25
S400CJ 36 10 /50 10 /65 10 /65 10 /50 25 /50 25 /65 25 /50 36 /50 36 /50 36 /50 36 36
S400NE 50 10 /50 10 /50 10 /50 10 /50 25 /50 25 /50 25 /50 50 /50 50 /50 50 /50 50 50
S400NJ 50 10 /50 10 /65 10 /70 10 /65 25 /50 25 /65 25 /65 50 /65 50 /65 50 /65 50 50
S400GJ 70 10 /50 10 /65 10 /70 10 /70 25 /50 25 /65 25 /70 70 /70 70 /70 70 /85 70 70
H400NJ 125 10 /50 10 /65 10 /70 10 /85 25 /50 25 /65 25 /85 70 /85 85 /85 85 /85 85 85
H400NE 125 10 /50 10 /65 10 /70 10 /125 25 /50 25 /65 25 /125 85 /85 85 /125 85 /100 85 85
E630NE 36 25 /36 25 /36 25 /36 36 /36 36 /36 36 /36 36 36
E630CE 50 25 /50 25 /50 25 /50 50 /50 50 /50 50 /50 50 50
S630GE 70 70 /70 70 /70 70 /70 70 70
XS630CJ 45 30 /42 30 /42 30 /42 35 42
XS630NJ 65 30 /65 30 /65 30 /65 35 65
XS630PJ 85 30 /85 30 /85 30 /85 35 85
XS630SE 50 30 /65 30 /65 30 /85 30 85
12
XH630SE 65 30 /65 30 /65 30 /85 30 85
XH630PE 65 30 /65 30 /65 30 /85 30 85
XS800NJ 65 15 /65 15 /65 20 /65 35 65
XS800SE 50 15 /50 15 /50 20 /50 35 50
XJ800PJ 85 15 /85 15 /85 20 /85 35 85
XH800SE 65 15 /65 15 /65 20 /65 35 65
XH800PE 65 15 /65 15 /65 20 /65 35 65
XS1250SE 65 20 /65 35 65
XS1600SE 85 35 85
12 - 9
Innovators in Protection Technology
Application data
Cascade / back-up application tables @ 380 - 415 V AC
Upstream-Downstream MCCBs (Thermal magnetic upstream)
Upstream MCCBs
H125NJ
H160NJ
L125NJ
L160NJ
E125NJ
S125NJ
S160NJ
S125GJ
S160GJ
Cascade
@ 380 – 415 V AC 1)
Downstream kA
MCCBs (RMS) 25 36 65 125 200 36 65 125 200
E125NJ 25 25 36 50 65 85 36 50 65 85
S160NJ 36 – – 65 36 36 36 65 85 125
E250NJ 25 – – – – – – 25 25 25
S250NJ 36 – – – – – – 65 36 36
S250GJ 65 – – – – – – – – –
S250PE 70 – – – – – – – – –
H250NJ 125 – – – – – – – – –
E400NJ 25 – – – – – – – – –
S400CJ 36 – – – – – – – – –
S400NJ 50 – – – – – – – – –
S400GJ 70 – – – – – – – – –
H400NJ 125 – – – – – – – – –
12
1
Note: ) Ratings have not been verified where a dash “–” is shown.
All pick-up and time delay settings are to be set at a maximum for upstream MCCBs
Refer to section 13 for TemBreak 1 selectivity and cascade values.
12 - 10
Innovators in Protection Technology
Application data
Selectivity tables @ 400/ 415 V AC
ACB/MCCB
Upstream ACB
Frame (A) 800 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A 6300 A
AR325H
AR212H
AR212H
AR216H
AR332H
AR220H
AR440S
AR212S
AR212S
AR220S
AR325S
AR332S
AR216S
AH50C
AH60C
Model
125 A E125NJ 25 kA 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
S125NJ 36 kA 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S125GJ 65 kA 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65
H125NJ 125 kA 65 80 65 80 65 80 65 80 85 100 85 100 100 100 120
L125NJ 200 kA 65 80 65 80 65 80 65 80 85 100 85 100 100 100 120
160 A/ S160NJ 36 kA 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
250 A S160GJ 65 kA 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65
E250NJ 25 kA 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
S250NJ 36 kA 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
Downstream MCCB
S250GJ 65 kA 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65
S250PE 70 kA 65 70 65 70 65 70 65 70 70 70 70 70 70 70 70
H250NJ 125 kA 65 80 65 80 65 80 65 80 85 100 85 100 100 100 120
L250NJ 200 kA 65 80 65 80 65 80 65 80 85 100 85 100 100 100 120
400 A/ E400NJ 25 kA 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
630 A S400CJ 36 kA 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S400NJ 50 kA 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S400NE 50 kA 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S400GJ 70 kA 65 70 65 70 65 70 65 70 70 70 70 70 70 70 70
S400GE 70 kA 65 70 65 70 65 70 65 70 70 70 70 70 70 70 70
S400PE 85 KA 65 80 65 80 65 80 65 80 85 85 85 85 85 85 85
H400NJ 125 kA 65 80 65 80 65 80 65 80 85 100 85 100 100 100 120
H400NE 125 kA 65 80 65 80 65 80 65 80 85 100 85 100 100 100 120
E630NE 36 kA 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S630CE 50 kA 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S630GE 70 kA 65 70 65 70 65 70 65 70 70 70 70 70 70 70 70
800 A XS800NJ 65 kA 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65
XH800SE 65 kA 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65
XH800PJ 100 kA 65 80 65 80 65 80 65 80 85 100 85 100 100 100 100
XS800SE 50 kA 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
1250 A/ XS1250SE 65 kA 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65
1600 A XS1600SE 85 kA - - - - 65 80 65 80 85 85 85 85 85 85 85
12
12 - 11
Innovators in Protection Technology
Tembreak 2 MCCB
Socomec
Load-break
switch MCCB (kA) MCCB (kA) MCCB (kA) MCCB (kA)
SLB63 E125NJ 6.5 S125NJ 6.5 S125GJ 6.5 H125NJ 7.5
SLB125 E125NJ 22 S125NJ 22 S125GJ 22 H125NJ 30
- - S160NJ 15 S160GJ 15 H160NJ 27
E250NJ 15 S250NJ 15 S250GJ 15 H250NJ 26
SLB200 E125NJ 25 S125NJ 36 S125GJ 65 H125NJ 80
- - S160NJ 30 S160GJ 30 H160NJ 80
E250NJ 25 S250NJ 30 S250GJ 30 H250NJ 80
SLB250 E250NJ 25 S250NJ 30 S250GJ 30 H250NJ 50
E400NJ 25 S400NJ 25 S400GJ 25 H400NJ 35
SLB315 E250NJ 25 S250NJ 36 S250GJ 65 H250NJ 100
E400NJ 25 S400NJ 50 S400GJ 65 H400NJ 100
SLB400 E400NJ 25 S400NJ 50 S400GJ 65 H400NJ 100
Tembreak MCCB
Socomec
Load-break
switch MCCB (kA) MCCB (kA) MCCB (kA)
SLB630 E630NE 35 S630CE 35 TL630NE 24
SLB800 XS800NJ 40 XH800PJ 40 TL800NE 28
SLB1000 XS1250SE 45 XS1600SE 45 TL1250NE 45
SLB1250 XS1250SE 65 XS1600SE 75 TL1250NE 70
SLB1600 XS1600SE 75 XS2000NE 60 - -
SLB2000 XS2000NE 60 XS2500NE 60 - -
SLB2500 XS2500NE 60 - - - -
12
MCCBs can be changed to electronic types.
ZS ELCBs can be used.
Upstream MCCB
12 - 12
Innovators in Protection Technology
Application data
Motor starting – introduction
Generally, an item of switchgear is selected on the basis of one When clearing a fault, every SCPD has a finite opening time,
or more performance criteria, be it current/power carrying or which will result in an amount of fault current and energy being
interrupting capabilities. “let-through” to the downstream system and other devices. At
Additional consideration is often necessary when several the same time a control device, such as a contactor, can only
different pieces of switchgear are connected in series, none withstand a finite level of fault current and energy, otherwise
moreso than in motor starting applications. As motors play a internal damage could occur.
significant part in most modern-day electrical systems, it is Even at relatively low fault levels the electromagnetic forces
important to ensure that the components of switchgear created by the fault current can cause the contacts of a
controlling and protecting the motor will interact with each contactor to lift. This can cause heating or even mild arcing
other, in other words, they are “co-ordinated”. which in turn can damage or weld the contacts of the contactor.
In order to protect and operate a motor, several components Furthermore, the let-through current of the SCPD can distort the
may be used, each with a different function. A typical set-up is bi-metal strip in the overload relay. This can prevent the
as follows: restoration of the bi-metal strip to its original configuration on
cooling, altering the relay’s protection characteristics, thus
The main purpose of the Short Circuit Protective
Device (SCPD) is to give protection against short resulting in under or over protection of the motor.
Short circuit circuits.
protective device Commonly used devices are circuit breakers or What solutions are available?
(S.C.P.D.) fuses. Each offer particular benefits and both
configurations are commonly used. Good component design, in association with correct component
co-ordination, is the only way to ensure reliable protection and
The function of the contactor is for circuit operation under abnormal conditions.
control, i.e. for the on-off operations of the
Contactor motor. Terasaki circuit breakers and Sprecher + Schuh starter
As contactors are capable of thousands or even
millions of operations, they are the most combinations are tested to provide full and safe
commonly used control devices. co-ordination for most motor starting applications.
A thermal overload relay will give ideal protection
against overloads on the motor, as well as phase-
Thermal loss protection. Although the SCPD will give
overload overload protection, the thermal overload is more
relay closely related to the characteristics of the motor.
If a fault is detected the thermal overload relay
will open the contactor or control device, thereby
isolating supply to the motor.
12 - 13
Innovators in Protection Technology
Application data
Motor starting and protection
TemBreak
A new generation of MCCBs offering a choice of 3 series
(economical, standard and high fault) and two types, ie,
adjustable thermal magnetic or microprocessor based solid state
OCR are available from Terasaki. Both types have common
construction features and interchangeable plug-in accessories.
TemBreak thermal-magnetic MCCBs offer a wide adjustment
12
range, with 63 % to 100 % of rated current. Each MCCB is
individually calibrated to ensure precision tripping on
overcurrent.
12 - 14
Innovators in Protection Technology
Application data
Starting motors - starting methods
Selection of the starting method and sometimes further reduce the minimum pick-up current by
the design of the motor depend on the load torque selecting a specific starting method. In all cases,
and on the line power. The load torque often varies starting with reduced voltages and pick-up currents
with the speed of rotation. During the starting will result in a longer motor run-up time.
phase, the motor torque must be greater than the In industrial plants, the supply network usually has
load torque at all rotational speeds, the difference sufficient capacity to support direct-on-line
results in the accelerating torque. starting. Even if several large motors are present,
When a motor is started, substantial current surges they can usually be started directly as a control
will occur in the power network. This may lead to system prevents them from running up
undesired voltage sags. To prevent other active simultaneously.
components connected to the mains network from If a drive system is to be started with a high load
being affected, utility companies define limit torque on a weak supply network, a slip-ring motor
values for motor run-up currents as a factor of their with an insulated rotor winding should be used. by
rated operational currents. The permissible values appropriate selection of the three-phase starting
vary and depend on the capacity of the networks. resistance and the number of starting steps, pick-
Direct on-line starting is the simplest and most up currents and torque values can be adapted to
economical method to start a squirrel-cage motor. the circumstances. However, the costs of this
The motor develops a high accelerating torque, and approach are high: the motor is more expensive,
the run-up time is usually very short. The main and an external starting resistor as well as devices
disadvantage lies in the high pick-up current. for its step-by-step shorting will be required.
All other starting methods for squirrel-cage motors No additional external switching devices are
are associated with a reduced voltage and thus a required for slip-ring motors with centrifugal stator.
reduced run-up current. The starting torque and the In this case, the starting resistors rotate and are
momentum during run-up are almost proportional switched off by speed-controlled centrifugal
to the applied power E.I. As a result, a reduction of contacts. Combined motors also require switching
voltage and pick-up current will also reduce the only in the stator circuit, since their rotors are
motor torque. Conversely, if load torque and motor equipped with a shorted cage winding and an
type are determined, it will not be possible to insulated winding with a centrifugal switch.
12
pick-up
current (A) 4…8 1.5…2.4 1.5…2.4 1.3…5 2…4 2…4 4…8 4…8 2.2…3.5 1.1…2.8
Pick-up
torque[Nm] 1.5…3 0.4…0.8 0.4…0.8 1…2.4 0.4…0.8 0.4…0.8 0.1…1 1.5…3 0.7…1.1 0.5…2
Normal
run-up 0.2…5 s Y2…16 s Y2…16 s 4…60 s 2…20 s 2…20 s 4…30 s 0.2…5 s Y2…10 s 4…60 s
time(s) ∆ 0.2…4 s ∆ 0.2…4 s ∆ 0.2…3 s
Heavy duty
run-up time 5…30 s 20…60 s 20…60 s 60…180 s – – – 5…30 s 10…30 s 60…180 s
Note: Electronic soft starters and variable speed drives (VSDs) are alternate methods of
starting not covered by the above.
For details contact NHP.
12 - 15
Innovators in Protection Technology
Application data
Rated outputs and standard values for rated operational
currents of standard squirrel-cage motors.
0.18 0.3 1.2 0.6 0.6 0.4 0.3 0.24 0.37 0.5 4
0.37 0.5 1.95 1.1 1.0 0.6 0.4 0.4 0.55 0.75 5
0.55 0.75 2.7 1.5 1.3 0.9 0.6 0.56 0.75 1 6.3
0.75 1 3.2 1.8 1.7 1.2 1.0 0.7 1.1 1.5 9
1.1 1.5 4.6 2.6 2.3 1.6 1.1 0.92 1.5 2 12
1.5 2 6.3 3.4 3.1 2.1 1.5 1.3 1.8 2.5 15
2.2 3 9 4.8 4.4 2.9 2 1.85 2.2 3 18
3 4 12 6.5 6 4 2.7 2.5 3 4 23
4 5.5 15.5 8.2 7.7 5 3.4 3.2 4 5 28
4.5 6 17 9 8 5.7 4.4 3.5 5.5 7.5 41
5.5 7.5 20 11 10 6.6 6 4.3 6 8 42
7.5 10 27 14 13 9 7 5.6 7.5 10 52
10 13.5 36 19 17 12 7.6 7.5
11 15 39 21 19 13 9 8
15 20 52 28 26 17 12.1 10.5
18.5 25 63 34 32 22 15 13
22 30 75 40 38 25 18 15.5
25 35 83 46 43 28 22 18
30 40 100 55 52 35 23 21
37 50 122 65 63 40 27 25
45 60 147 80 77 49 34 30
55 75 180 100 97 59 42 37
75 100 240 130 128 79 54 50
90 125 290 155 150 95 66 60 Notes:
1
110 150 ) Standard values for standard squirrel-cage
350 200 185 114 80 73
motors: Rated operational currents for
132 180 410 225 221 135 90 85 motors with n = 1500/min (4 pole),
160 220 500 270 270 160 117 105 possible deviation +_ 10 % depending on
185 250 570 325 310 185 135 120 type and manufacturer, +_ 50 % for small
200 270 625 361 340 200 150 130 motors.
220 300 675 380 353 220 160 142 Deviation of rated operational currents for
250 340 775 430 410 250 200 160 motors with other speeds (greater
deviations for smaller motors):
280 380 830 480 460 280 225 180
300 410 920 505 495 300 235 195 With n = 3000 rpm (2 pole): –2 %…–10 %
315 430 980 535 515 315 240 200 With n = 1000 rpm (6 pole): +2 %…+10 %
With n = 750 rpm (8 pole): +5 %…+20 %
375 500 1150 650 610 375 270 240
400 545 1225 665 645 400 290 255 2
) The power factor is usually around 0.8, but
475 645 1450 780 750 465 335 300 this varies with the size and speed
500 680 - 820 790 495 360 320 of the motor. Efficiency ranges from 85%
560 750 - 920 810 570 390 350 in small motors to 90 % and over for
600 800 - 1000 960 610 420 390 large motors.
670 900 - 1100 1080 680 470 430
750 1000 - 1250 1220 770 530 490
12 - 16
Innovators in Protection Technology
Technical data
Motor circuit application table for DOL starting
Technical data
General motor circuit application table – Reduced Voltage starting
Breaker type and current rating, star-delta, auto-transformer, resistor or reactance starting
E630
Motor Approx. Din-T S/H/L160 S630 XS800NJ
rating FLC C&D E/S/H/L 125 E/S/H/L250 E/S/H/L400 XH630 XH800SE XS1250-
(kW) (Amps) curve Safe-T XS/XH125 E250 XS/XH250NJ XS/XH400 XS630 XS800SE SE/1000
0.37 1.1 4 6
0.55 1.5 4 6 20
0.75 1.8 4 6 20
1.1 2.6 6 6 20
1.5 3.4 10 6 20
2.2 4.8 10 10 20
3.0 6.5 16 16 20
4 8.2 20 16 20
4.5 9 20 16 20
5.5 11 25 20 20
7.5 14 32 25 20
10 19 40 40 32
11 21 50 40 32
15 28 50 50 50
18.5 34 63 63 50
22 40 80 ) 1 63 63
25 46 100 ) 1 80 100
30 55 125 1) 100 100 160
37 66 125 1) 100 125 160
45 80 125 125 160 250
55 100 150 160 250
75 135 175 250 250
90 160 225 250 250
110 200 250 250 400
132 230 400 400
160 270 400 400
185 320 400 400 800 2)
200 361 400 2) 630 800 2)
220 380 630 800
250 430 630 800
280 480 630 800
300 510 630 800
12
375 650 800 2)
450 750 1000
These motor circuit application tables are to be used as a selection guide for average 3 phase, 4 pole 400/415 V motors
for standard applications only. Non-standard applications refer NHP.
Notes: 1) 80, 100 and 125 amp refers to Din-T10H type.
2
) Electronic TemBreak MCCB only.
If co-ordination to IEC 60947-4-1 is required refer to Type ‘1’ and ‘2’ co-ordination tables, contact NHP.
Reduced voltage table is based on holding 120 % FLC continuously and 350 % FLC for 20 seconds.
Din-T MCBs are calibrated to IEC 60898 Curve ‘C’ & ‘D’. Selected sizes of ‘D’ Curve are available from stock
refer NHP.
Circuit breaker sizings are primarily to provide short circuit protection. Mild overcurrent protection is provided
by the starter circuit overload relay.
12 - 18
Innovators in Protection Technology
Technical data
Motor circuit application table – DOL FIRE PUMP starting duty
12 - 19
Innovators in Protection Technology
Full Load
Motor Size Current Voltage
(kW) Amperes (A) MCCB (V)
V
1000 0.37–10 0.4–7.5 TL100EM/15K 1000
2
type ion 11.0 9.0 TL100EM/20K 1000
t
rdi a
n
co-o vailable 15–18.5 12–14.5 TL100EM/30K 1000
a
chart
22–33 17–23 TL100EM/40K 1000
37–50 28–38 TL100EM/50K 1000
55–80 40–57 TL100EM/75K 1000
90–110 65–78 TL100EM/100K 1000
150 102 XV400NE/160K 1000
185–220 138–160 XV400NE/250K 1000
220–500 160–350 XV400NE/400K 1000
12
Sprecher + Schuh
1000 V CA 6 Contactor
(Refer Part A for more information)
Notes: This table should be used as a selection guide for standard applications only.
12 - 20
Innovators in Protection Technology
Application data
Motor starting Type ‘1’ and ‘2’ co-ordination
What is co-ordination?
The motor starter consists of a combination of contactor, AS 3947.2 requires that during the tests the equipment installed
overload relay and Short Circuit Protective Device (SCPD) being in the switchboard performs in accordance to its own standard.
either fuses or circuit breakers. A selection by the customer of the performance required needs
During motor starting and at normal loading, the overload relay to be made, as AS 3947.4.1 allows for Type ‘1’ and Type ‘2’
protects both the motor and cables by tripping the contactor in performance.
a time inversely proportional to the current. However, under Type ‘1’
short circuit conditions, the response time would be too long Under short circuit conditions the starter shall not cause danger
and the fuses or circuit breakers must take over to interrupt the to persons or the installation. The starter itself may need repair.
fault current therefore limiting energy passed through the
starter components. When this is successfully achieved, the Type ‘2’
combination is said to be co-ordinated. After a short circuit the starter is suitable for further service. A
It is a requirement of the Australian Standard AS 3947.4.1 that contact weld is permitted, but it must be easily separated - for
combination motor starters are capable of withstanding the example, by a screwdriver, without significant deformation.
effects of loadside short circuits. Some damage to the Type ‘2’ co-ordination does not mean the starter is suitable for
combination is permitted, but this must be confined and not normal operation without inspection/repair of the contacts. So,
present a risk to the operator or damage equipment adjacent to in both cases it is important that the condition of the starter is
the starter. checked, to ensure that the SCPD has operated and that no
Contactors and thermal overload relays only have limited ability damage has taken place.
to withstand the high current associated with a fault such as an
internal motor short. Their design is optimised for performance Notes: IEC Standards are the basis of many Australian Standards.
AS 3947.4.1 is equivalent to IEC 60947.4.1 and AS 3947.2 is
at much lower currents. To ‘design in’ the ability to control or equivalent to IEC 60947.2.
withstand high fault levels would add to costs and possibly Both Australian Standards list some amendments to the IEC
reduce performance at normal levels. versions.
12 - 21
Innovators in Protection Technology
12 250
320
425
538
S630GE/630A
S630GE/630A
CA6-860-EI
CA6-860-EI
CEP 7 EEMH
CEP 7 EEMH
120 - 600
120 - 600
400 700 XH800SE/800A CA6-860-EI CEP 7 EENH 160 - 800
Note: • Recommended circuit breaker sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the maximum instant trip setting of the MCCB.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
• Refer to NHP for other component combinations.
• MCCBs rated 65kA may be replaced by 50kA types where the kA rating does not need to be 65kA.
12 - 22
Innovators in Protection Technology
Note: • Recommended circuit breaker sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the maximum instant trip setting of the MCCB.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
• Refer to NHP for other component combinations.
• MCCBs rated 65kA may be replaced by 50kA types where the kA rating does not need to be 65kA.
12 - 23
Innovators in Protection Technology
12 250
320
250
320
S630GE / 630A
S630GE / 630A
CA6-860-EI
CA6-860-EI
CEP 7 EEMH
CEP 7 EEMH
120 – 600
120 – 600
400 400 XH800SE / 800A CA6-860-EI CEP 7 EENH 160 – 800
Note: • Recommended circuit breaker sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the maximum instant trip setting of the MCCB.
• CEP7 overload add-on modules are available for Profibus, DeviceNet, EtherNet, Ground Fault, remote reset, Jam protection, and a
thermistor protection relay. Only one option can be used at any one time on a CEP7 overload.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
• MCCBs rated 65kA may be replaced by 50kA types where the kA rating does not need to be 65kA.
12 - 24
Innovators in Protection Technology
12
220 383 S400GJ / 400A CA6-630-EI CEP7 C3 860 630 125 – 630
250 425 S630GE / 630A CA6-860-EI CEP7 C3 860 630 125 – 630
320 538 S630GE / 630A CA6-860-EI CEP7 C3 860 630 125 – 630
400 700 XH800SE / 800A CA6-860-EI CEP7 C3 860 860 172 – 860
Note: • Recommended circuit breaker sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the maximum instant trip setting of the MCCB.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
• CEP7 C3 overloads include DeviceNet communications, an earth fault relay, and a thermistor relay.
• MCCBs rated 65kA may be replaced by 50kA types where the kA rating does not need to be 65kA.
12 - 25
Innovators in Protection Technology
12
200 361 H400NE / 400A CA6-420-EI CEP 7 EELG 100 – 500
220 383 H400NE / 400A CA6-630-EI CEP 7 EEMH 120 – 600
250 425 XH630PJ / 630A CA6-860-EI CEP 7 EEMH 120 – 600
320 538 XH630PJ / 630A CA6-860-EI CEP 7 EEMH 120 – 600
400 700 XH800PJ / 800A CA6-860-EI CEP 7 EENH 160 – 800
Note: • Recommended circuit breaker sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the maximum instant trip setting of the MCCB.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
12 - 26
Innovators in Protection Technology
12
220 383 H400NE / 400A CA6-630-EI CEP 7 EEMH 120 – 600
250 425 TL630NE / 630A CA6-860-EI CEP 7 EEMH 120 – 600
320 538 TL630NE / 630A CA6-860-EI CEP 7 EEMH 120 – 600
400 700 TL800NE / 800A CA6-860-EI CEP 7 EENH 160 – 800
Note: • Recommended circuit breaker sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the maximum instant trip setting of the MCCB.
• CEP7 overload add-on modules are available for Profibus, DeviceNet, EtherNet, Ground Fault, remote reset, Jam protection, and a
thermistor protection relay. Only one option can be used at any one time on a CEP7 overload.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
12 - 27
Innovators in Protection Technology
12
250 425 S630GE_AG / 630A Ig = 0.2 x In min. CA6-860 CEP 7 EEMH 120 – 600
320 538 S630GE_AG / 630A Ig = 0.2 x In min. CA6-860 CEP 7 EEMH -120 – 600
400 700 XH800SE 800_ LSIG Ig = 0.2 x In min. CA6-860 CEP 7 EENH 160 – 800
Note: • Recommended circuit breaker sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the maximum instant trip setting of the MCCB.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
• CEP7 overload add-on modules are available for Profibus, DeviceNet, EtherNet, Ground Fault, remote reset, Jam protection, and a
thermistor protection relay. Only one option can be used at any one time on a CEP7 overload.
• MCCBs 400 to 800A have a Ground Fault option fitted. This will not sense small earth leakage (residual currents).
• MCCBs 400 to 800A need an external 4th CT when 3 pole MCCBs are used, only if a neutral is present. 4 pole GF MCCBs have internal 4th CT.
12 - 28
Innovators in Protection Technology
Note: • Recommended circuit breaker sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the maximum instant trip setting of the MCCB.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
• CEP7 C3 overloads include DeviceNet communications, an earth fault relay, and a thermistor relay.
• MCCBs 400 to 800A have a Ground Fault option fitted. This will not sense small earth leakage (residual currents).
• MCCBs 400 to 800A need an external 4th CT when 3 pole MCCBs are used, only if a neutral is present. 4 pole GF MCCBs have internal 4th CT.
12 - 29
Innovators in Protection Technology
12
250 425 630 SSFBS 630 CA6-630 CEP 7 EEMH 120 – 600
320 538 710 SSFBS 800 CA6-860 CEP 7 EEMH 120 – 600
380 650 800 SSFBS 800 CA6-860 CEP 7 EENH 160 – 800
Note: • Recommended fuse link sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the fault interruption point of the fuse link.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
• BS, DIN or cylindrical gG fuse links are an option. The appropriate fuse holder or fuse switch must be used to suit the fuse link.
12 - 30
Innovators in Protection Technology
Note: • Recommended fuse link sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the fault interruption point of the fuse link.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
• CEP7 overload add-on modules are available for Profibus, DeviceNet, EtherNet, Ground Fault, remote reset, Jam protection, and a
thermistor protection relay. Only one option can be used at any one time on a CEP7 overload.
• Type gG: BS, DIN or cylindrical fuse links are an option. The appropriate fuse holder / fuse switch must be used to suit the fuse link.
12 - 31
Innovators in Protection Technology
12
Note: • Recommended circuit breaker sizes are based on the following starting conditions, using standard efficiency motors:
< 3 kW starting current maximum of 6 x motor rated current, starting time maximum of 5 seconds
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the maximum circuit breaker instant trip point.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
• TL100NJ MCCBs are to be magnetic only. Refer NHP.
• CEP7 overload add-on modules are available for Profibus, DeviceNet, EtherNet, Ground Fault, remote reset, Jam protection, and a
thermistor protection relay. Only one option can be used at any one time on a CEP7 overload.
• Refer to NHP for other component combinations.
12 - 32
Innovators in Protection Technology
12
Note: • Recommended circuit breaker sizes are based on the following starting conditions, using standard efficiency motors:
> 3 kW starting current maximum of 7 x motor rated current, starting time maximum of 5 seconds
The use of high inrush, high efficiency motors needs to be considered, along with the maximum circuit breaker instant trip point.
• Combinations are based on the overload tripping before the circuit breaker at overload currents up to the motor locked rotor current.
• CEP7 overload add-on modules are available for Profibus, DeviceNet, EtherNet, Ground Fault, remote reset, Jam protection, and a
thermistor protection relay. Only one option can be used at any one time on a CEP7 overload.
• CEF1 CT type overloads can replace CEP7 overloads if required.
• When using CEP7 C3 overloads, 1000 V rated CTs must be used. Refer Microelettrica CTs type “TO”
• Refer to NHP for other component combinations.
12 - 33
Innovators in Protection Technology
Application data
MCCBs for protection of Power Factor Correction (PFC) units
In circuits containing capacitor banks for power factor 2. Nuisance tripping due to in-rush current
correction (PFC), two conditions that the circuit breaker must When feeding a circuit containing a PFC unit the circuit breaker
overcome are as follows: and the PFC unit can be exposed to a large in-rush current,
1. Voltage surges during MCCB opening. equal to the instantaneous value of the power source. The end
2. Nuisance tripping due to in-rush current. result of this is a large in-rush current, which could cause the
1. Voltage surges during MCCB opening circuit breaker to operate instantaneously due to its short-circuit
At the instant where the MCCB has to open, the voltage protection. (The value of in-rush current will depend on the
developed across its contacts can be up to twice the supply source voltage, the inductance and reactance in the circuit).
voltage, which can have damaging consequences should the
Special care should be taken to ensure that the MCCB selected
breaker be slow to operate. If this worse case scenario actually
occurs a potential re-arcing can take place across the contacts of will not nuisance trip due to high in-rush currents.
the MCCB, until the breaker has fully opened and the distance The table below shows typical MCCB selections for varying
between the contacts is at a maximum. capacitor ratings, and the breaker selection is by a rule-of-
Re-arcing at each instant can be: thumb.
1st re-arcing – 3 x supply voltage Capacitor rated current = kVAr x 1000 (A)
2nd re-arcing – 5 x supply voltage √3 x V
3rd re-arcing – 7 x supply voltage
kVAr: Capacitor rating
Internal capacitor damage will occur if the voltage level is
V: Source voltage
greater than the capacitor’s Dielectric Strength. With modern-day
protection devices, (for example the Terasaki TemBreak MCCBs) MCCB Rating = Capacitor rated current x 1.5 (A)
this problem will not occur. Once the MCCB rating has been determined, the MCCB type
The numerous cases of re-arcing are mainly a result of older style should be selected according to the short circuit fault level of
“dependant manual closing” devices, which rely on the operator the system. (Please refer to Section 4 for MCCB breaking
speed for opening or closing. capacities).
All Terasaki MCCBs are of the “manually independent closing”
type, with high speed opening to prevent re-arcing between the
contacts.
12
150 209 S400CJ/400 S400NJ/400 S400NE/400 S400GE/400
200 278 S400CJ/400 S400NJ/400 S400NE/400 S400GE/400
300 417 S630CE/630 S630GE/630 S630GE/630 S630GE/630
400 556 XS800NJ/800 XS800SE/800 XH800SE/800
500 696 XS1250SE/1250
600 835 XS1250SE/1250
800 1113 XS1600SE/1600
1000 1391 XS2000NE/2000
1
Note: ) Select applicable short circuit rating required by system specifications.
2
) MCCBs can be changed to electronic types if required.
12 - 34
Innovators in Protection Technology
Application data
MCCB use in high frequency (400 Hz) applications
General higher Eddy currents. As a result, the thermal protection must be
Terasaki TemBreak MCCBs are designed to operate primarily in 50 derated to take the heating effect into account.
or 60 Hz systems. However, it is possible to use the same MCCBs In short-circuit (magnetic) regions, the demagnetising effects of
in high frequency (400 Hz) applications, provided consideration the Eddy currents mean that a larger fault will be required to trip
is given to the effects high frequencies will have on the breaker. the breaker. The rule of thumb generally used is that the
Magnetic/Instantaneous Trip setting will be approximately twice
A consequence of high frequencies is an increase in Eddy
that at normal 50/60 Hz operation.
currents in conductors, including those internal to the breaker.
This generally causes an increase in temperature, in and around Electronic MCCBs
the breaker. As such, some derating allowances must be made Electronic MCCBs offer better performance at higher frequencies,
when selecting a breaker in these 400 Hz systems. although some consideration must be given in regard to the heating
effects caused by the Eddy currents. The figures in the table give
Thermal magnetic MCCBs
the maximum overcurrent relay (OCR) rated current setting
In low overload (thermal) regions the current required to trip the
(I0 x I1) that should be used in high frequency applications.
MCCB is reduced as a result of the heat generated due to the
12
XS800NJ Thermal/Magnetic 800 2 x 240 600
S400NE/XV400 Electronic 250 120 238
S400GE/S400GE 400 240 360
XS630SE/S630CE/XV630 Electronic 630 2 x 185 600
XH630SE/PE/S630GE
XS800SE Electronic 800 2 x 240 640
XH800SE/PE/XV800
XS1250SE/XV1250 Electronic 1250 2 x (80 x 5t) 800
XS1600SE Electronic 1600 2 x (100 x 5t) 900
1
Note: ) When used at 400 Hz, the rated current setting of the OCR must not exceed the values shown in Column 4.
12 - 35
Innovators in Protection Technology
Application data
Circuit breaker selection for DC applications
The characteristics of an MCB or MCCB for DC applications are n The type of DC system used.
different from AC. The main differences are as follows: n Maximum short circuit current to determine the breaking
1. Maximum permissible voltage is reduced in value capacity.
(refer table below). As a general rule the Isc (short circuit current at the battery
2. Number of electrical operations is reduced (refer table). terminals) can be calculated as follows:
3. Magnetic trip current increases by 40 %. Isc = Vb
Ri
Selecting the circuit breaker Where Vb – maximum discharge battery voltage
When selecting the MCB most suitable for the protection of DC Where Ri – internal resistance (sum of all cell resistances)
circuits the following criteria must be considered:
Note: If Ri is not known an estimation of Isc can be
n Rated current.
determined using the formula Isc = kC where C
n Rated voltage which determines the number of poles
is the battery capacity (in Ah) and k a factor between
required to be involved in the interruption of the circuit.
10 and 20. (refer battery manufacturer)
Terasaki MCB use in DC systems 4) 110 V
Circuit Rated 48 V 1 Pole 250 V 500 V
Breaker Current 1 Pole in series 1 Pole 1 Pole
Type (A) Icu (kA) Icu (kA) Icu (kA) Icu (kA)
Din-T6 0.5...63 A 20 25 - -
Din-T10 0.5...63 A 25 30 - -
Din-T DC 0.5...63 A - - 6 6
Din-T15 6...25 A 25 30 - -
Din-T10H 80...125 A 10 10 - -
Safe-T 6...100 A - 5 - -
MCCB
type 1) 2) 24/48/60 V 125 V 250 V 350 V 500 V 600 V
S160NF 1 pole -15 15 -
ES125/NJ 25 25 25
Refer to section 4 for ‘ND’ DC MCCBs rated to
SHL125NJ/GJ 50 40 40 600 V DC at 20 A - 800 A
E250NJ 25 25 25 Refer NHP for MCCBs rated to 1000 V DC
2
SHL160/250 ) 50 40 40
E400NJ 25 25 25
SHL400NJ/GJ 3) 50 40 40
XS630NJ 50 40 40 30 20 20
XS800NJ 50 40 40 30 20 20
1
XS1000ND ) – 40 40 30 20 20
XS1250ND – 40 40 30 20 20
XS1600ND – 40 40 30 20 20
1
XS2000ND ) – 40 40 30 20 20
1
XS2500ND ) – 40 40 30 20 20
1
Notes: ) Magnetic trip, without overload protection. The following connection diagram should be applied to TemBreak circuit
Available on indent only. breakers when the voltage is greater than 250 V DC.
12
2
) Thermal magnetic types only can be used on DC.
2
) MCCBs not suitable for 12 V DC.
Notes for MCCB only: For voltage levels up to and including 250 V standard
breakers maybe be used, with 2 both poles connected in series.
For voltage levels greater than 250 V DC 3-pole breakers must be used, with
all three poles connected in series as shown.
The time constant (L/R) of the circuit should be:
less than 2ms at rated current.
less than 2.5ms for overload (2.5 x in).
less than 7ms for short circuit ≤ 10 kA.
less than 15ms for short circuit > 10 kA.
4
) Additional MCB DC applications information, refer section 3.
12 - 36
Innovators in Protection Technology
Application data
Circuit breaker selection for DC applications (cont’d)
+ +
R R
Ub Ub
– –
The poles required to interrupt the fault can be divided between the (+) and (-) polarities. The total number of poles connected in
series should be capable of breaking the short circuit current at a voltage level of Ub.
Sharing the circuit breaker interrupting poles between both polarities also ensures isolation as well as protection of the system.
+ +
R R
Ub Ub
– –
Full protection is assured if the total number of poles in series on the side not connected to earth are capable of breaking the short
circuit current at a voltage level of Ub. If full isolation is required then at least one interrupting pole is also required on the earthed
polarity side.
+
R
12
Ub
–
To ensure full protection the number of poles connected in series on each polarity must be capable of breaking the maximum short
circuit current, but at a reduced voltage level of Ub/2.
Having circuit breaker interrupting poles breaking both polarities ensures isolation as well as protection of the system.
Note: For specific DC applications (e.g. parallel pole connection) consult NHP.
12 - 37
Innovators in Protection Technology
Application data
Selection of MCCBs for use in welder circuits
2. MCCB selection
Time
a) Current rating MCCB
It can be seen from the diagrams below that the welder only characteristic curve
draws current intermittently. MCCB selection should be based on
the thermally equivalent continuous current, T
T > T1 is
i.e. the current which would produce the MCCB average
conditional
temperature shown in the diagram below. T1
It can further be seen that the MCCB temperature will not be
constant but will vary as the load varies.
Current
I
T1 T2
12 welders.
ii) Two times the primary ratings of the largest transformer arc
welders.
Welding with RCDs in the circuit
During welding a varing amount of earth leakage may occur. If
an earth leakage relay or EL MCCB is installed, the leakage
current setting should be set high enough (if possible) to
ensure unwanted tripping does not occur.
Application data
Selection of MCCBs for use in welder circuits (cont’d)
2. MCCB Selection (Cont’d) K = 1 to 1.5 for synchronous type with peak control.
K = 1.4 to 3 for synchronous type without peak control.
b) Instantaneous setting
K = 2 to 6 for non-synchronous soft start type.
The MCCBs instantaneous trip setting should be high enough to
If protection of the thyristor stack is also required, the
avoid nuisance tripping due to the welding transformers
instantaneous trip setting must be greater than Im, but less than
excitation inrush current. When voltage is supplied to the
the surge on-state current rating of the thyristor stack:
transformer primary side, the iron core is saturated. This results
in the flow of a large inrush current caused by a combination of
Im < I INST < Is
the DC component of the voltage at the instant of closing and
1.1
the residual magnetic flux of the transformer. The transformer
input current value when the welder secondary is completely where:
short-circuited is about 30% higher than the value calculated Is = surge on-state current rating of thyristor stack, in A
from the nominal maximum power input of the welder. So the
Im = maximum welder input current at start of welding, in A
maximum welder input current, Im, at the start of welding is
given by: I INST = MCCB Instantaneous trip setting, in A
Im = Pm x 1000 x 1.3 x K
V 1.1 = Factor to allow for + 10% tolerance on the
instantaneous setting
12
12 - 39
Innovators in Protection Technology
Application data
Primary LV/LV transformer protection
When selecting an MCCB to protect the primary of an LV/LV The excitation current is, in theory, at a maximum when the
transformer, the inrush current during initial energisation must voltage is at a minimum, and vice versa.
be taken into account. Usually the level does not exceed 30 times the normal operating
The magnitude of inrush current for any transformer is governed current.
by several variables: If the inrush current is not known then a rule of thumb is that it
1. The primary winding resistance. is approximately 15 x the Primary Current.
2. The supply impedance.
3. The excitation current.
1 phase 240V 3 phase 415V
Transformer MCCB MCCB BC (kA) MCCB MCCB BC (kA)
(kVA) Cat. No rating (A) at 240V Cat. No rating (A) at 415V
5 S125/160NF 50 25 S125NJ 20 36
7.5 S125/160NF 63 25 S125NJ 32 36
10 S125/160NF 100 25 S125NJ 32 36
15 E250NJ 125 25 S125NJ 50 36
S250GJ 160 65
S160GJ 160 65
20 S160GJ 160 65 S125NJ 63 36
S160GJ 160 65
30 S125NJ 100 36
50 S125NJ 125 36
75 E250NJ 225 25
S250NJ 250 36
100 S400NE 250 50
150 S400NE 250 50
200 S400NE 400 50
300 S630CE 630 50
The above breaker selections are based on inrush currents calculated using the table below
12 50
75
-
-
-
-
24
20
4-7
4-7
100 - - 18 6 - 10
150 - - 16 6 - 10
200 - - 14 6 - 10
300 - - 12 6 - 10
Notes: First peak multiplier is the first peak current as a multiple of the transformer rated current.
The above table/multipliers are in general larger than the practical current levels, as the current limiting by the circuit impedance is not
taken into account.
12 - 40
Innovators in Protection Technology
Application data
MCB selection for high pressure sodium lamps
Assumptions
2. Run-up time 10 minutes with the current decaying
1. The maximum inrush current which the circuit will pass
exponentially.
is a feature of the current limiting ballast and not the
3. Based on 415/240 V 3 phase or 240 V single phase
lamp.
systems.
Assuming these ballasts comply with the relevant IEC
specification, the circuit will pass currents not exceeding
twice the appropriate lamp nominal current.
Example
Given 42 lamps each 250 W installed on a 415 V 3 phase system.
Which MCB must be selected?
Number of tubes per phase = 42 = 14
3
Therefore from the table above a 32 A MCB should be selected.
A short circuit rating as appropriate must be selected.
12
Note: Observe the requirements of AS 3000 for No. of lighting points on a final sub-circuit.
12 - 41
Innovators in Protection Technology
Application data
MCB selection for fluorescent lighting loads
Assumptions
1. The power rating of the ballast is 25% of power of the tubes.
2. Power factor - 0.6 for non-compensated fittings 0.86 for compensated fittings.
3. MCBs are installed in an enclosure with external ambient of 25 °C.
4. Based on 415/240 V 3 phase or 240 V single phase systems.
5. MCB is used for circuit protection only, not switching.
For switching duties of Din-T MCBs refer NHP.
Note: Observe the requirements of AS/NZS 3000 for No. of lighting points on a final sub-circuit.
Assumptions Method
n Tungsten lamps have a theoretical inrush current of In order to cope with this inrush the following
14 times normal current, when switched from cold. formula should be used to calculate breaker size:
n The circuit impedance typically limits the inrush to Breaker rating = W x 10
10 times normal running current, the inrush current P x 240 x I inst
peaking at 0.0007 seconds falling exponentially to Where W = Total wattage
normal running current within 0.1 seconds. Where P = Number of phases
12
n Consider the worst case, if all lamps are switched on I inst = Minimum instantaneous tripping
simultaneously, then nuisance tripping of MCB may co-efficient.
result. C curve = 5
n Above is based on 415/240 V 3 phase and neutral or D curve = 10
240V single phase system and 240 V lamps.
n MCB is used for circuit protection only, not switching.
For switching duties of Din-T MCBs refer NHP.
12 - 42
Innovators in Protection Technology
Application data
12
12 - 43
Innovators in Protection Technology
Application data
Downstream short circuit current calculator
12
2 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 2 1.8 1.7 1.7 1.4 1.1 1.0 0.9 0.8 0.7 0.4
1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1 0.9 0.9 0.9 0.8 0.7 0.7 0.6 0.5 0.5 0.3
Notes: • Values shorter than 0.8 m or longer than 1 km are not considered
• All values are for voltage 400 V.
12 - 44
Innovators in Protection Technology
Application data
Transformers in parallel
Let-through energy
The standard IEC 60364 describes that the current limiting of the conductors (K2S2) shall be equal to
or greater than the let-through energy (I2t) quoted by the protective device.
The K coefficient depends on the conductor insulation. S is the cross section of the conductor. I2t ≤ K2S2
Copper conductor
Insulation PVC Rubber Polyethylene
ALPE
K= 115 135 146
Cross
section
mm2 Maximum admissible value K2S2 x 103
1.5 30 41 48
2.5 83 114 133
4 212 292 341
6 476 656 767
10 1323 1823 2132
16 3386 4666 5457
25 8266 11391 13323
35
50
16201
33063
22326
45563
26112
53290 12
70 64803 89303 104448
95 119356 164481 192377
120 190440 262440 306950
150 297563 410063 479610
185 452626 623751 729540
240 761760 1049760 1227802
12 - 45
Application data
Protection grades against contact and foreign bodies -
Ingress Protection (IP)
IP Tests IP Tests
O No protection. O No protection.
1 Protected against 1 Protected against
solid objects up to vertical falling
drops of water.
50 mm.
(eg. accidental touch
by hands). 2 Protected against direct
sprays of water up to
15 ° from the vertical.
2 Protected against
solid objects up to
3 Protected against spray of
12 mm (eg. fingers).
water up to 60 ° from the
vertical.
3 Protected against
solid objects over 4 Protected against
2.5 mm (tools + small water sprayed from
all directions - limited
wires). ingress permissable.
4 Protected against
5 Protected against low
pressure jets of water
solid objects over from all directions - limited
1 mm (tools + small ingress permissable.
wires).
6 Protected against strong
jets of water eg. for use on
5 Protected against dust
shipdecks - limited ingress
- limited ingress
permissable
permitted (no harmful
deposit). 7 Protected against the
12 affects of immersion
between 15 cm and 1 m.
6 Totally protected
against dust. 8 Protected against long
periods of immersion
under pressure.
12 - 46
Application data
Useful formulae and conversion factors.
kW x 1000
I=
E x PF
I=
746 x hp
E x PF x Eff 12
IxE
kVA =
1000
12 - 47
Application data
Derived units of the International system
Formula symbols for the quantities are printed in italics, unit symbols in regular type.
Formula Unit
Quantity symbol Name of unit symbol Definitions, Notes
Geometry
Length l metre m Basic SI unit
Area A square metre m2
Volume V cubic metre m3
Time
Time, duration t second s Basic SI unit
Frequency f hertz Hz 1 Hz = 1/s
Rotational frequency ω reciprocal second 1/s ω = 2πf
Revolutions n reciprocal second 1/s
Mechanics
Mass m kilogram kg Basic SI unit
Density kilogram per cubic metre kg/m3
Velocity v metres per second m/s
Acceleration a metres per second squared m/s2
Force F newton N 1 N = 1 kg m / s2
Impulse I newton-second Ns 1 Ns = 1 kg m / s
Pressure (mechanical) p pascal Pa 1 Pa = 1 N / m2 = 105 bar
Fluid pressure p bar bar 1 bar = 105 Pa
Stress σ newton per square metre N/m2 1 N / m2 = 1 Pa
Energy, work W joule J 1 J = 1 Nm = 1 Ws
Moment M newton-metre Nm 1 Nm = 1 kgm2 / s2
Torque T 1) newton-metre Nm 1 Nm = 1 kgm2 / s2
Power P watt W 1 W = 1 Nm / s = 1 J / s
Heat
Temperature T kelvin K Basic SI unit
ϑ degrees Celsius °C ϑ = T – To with To = 273.15 K
Temperature difference ΔT kelvin K preferred
Δϑ degrees Celsius °C 1°C - 1 K
Quantity of heat Q joule J 1 J = 1 Nm = 1 Ws
Heat flux Φ watt W 1 W = 1 Nm / s = 1 J / s
Electricity
Electric current I ampere A Basic SI unit
Electric voltage U volt V 1V=1W/A
Current density J ampere per square metre A/m2
Electric charge Q coulomb C 1 C = 1 As
Capacitance C farad F 1 F = 1 C / V = 1 As / V
Magnetomotive force Θ ampere A ampere-turns of a coil
Resistance R ohm Ω 1Ω=1V/A
Conductance G siemens S G = 1 / R, 1 S = 1 A / V = 1 / Ω
Conductivity χ siemens per metre S/m χ=1/
Resistivity ohm-metre Ωm 1 Ωm = 1 Vm / A
Magnetic flux Φ weber Wb 1 Wb = 1 Vs
Magn. field strength
12
H ampere per metre A/m
Magn. flux density B tesla T 1 T = 1 Wb / m2 = 1 Vs / m2
Inductance L henry H 1 H = 1 Wb / A = 1 Vs / A
Apparent power S volt-ampere VA
Active power P watt W 1W=1J/s
Reactive power Q volt-ampere reactive Var
Energy W joule J 1 J = 1 Nm = 1 Ws
Impedance Z ohm Ω
Reactance X ohm Ω
Phase displacement angle ϕ radian rad 1 rad = 1
1
Note: ) According to IEC 27-1.
According to DIN 1304 and 40121, the formula symbol M is used for torque.
12 - 48
Standards, codes and approvals
International and National testing institutes/authorities
AS/NZS Australia / Joint Australia and New Zealand Standard. Increasingly harmonised.
NewZealand
BS Great Britain British Standard of the British Standards Institution (BSI). Extensively
harmonised with IEC.
CEMA Canada Canadian Electrical Manufacturers Association. Old name of the EEMAC.
CENELEC EC and EFTA Comite Européen de Normalisation electrotechnique. Its European standards
countries (EN) are increasingly applied by governments and users. General
administration in Bruxelles. Old name CENELCOM.
CSA Canada Canadian Standards Association. Independent codes. Statutory approval and
labelling requirement for all electrical equipment.
DEMKO Denmark Danmarks Elektriske Materielkontrol. Codes, approval and labelling required
up to 63 A nominal or continuous current.
DNV Norway Det Norske Veritas, ship classification company, headquartered in Oslo.
EN EC and EFTA European standards (EN). The member countries are required to implement
countries these standards without modification and to give it the status of a national
standard.
FI Finland
Sähkötarkastuskeskus/Elinspektionscentralen. Testing laboratory with
independent specifications. Statutory approval and labelling required up
to 63 A.
12
Federal
GL Republic of Germanischer Lloyd. Ship classification company. Headquartered in Hamburg.
Germany
IEC International International Electrical Commission. Most countries use the IEC
recommendations as a base and implement these with or without
modifications, with supplements or in major areas as their own national codes.
Only components that have passed the tests in the corresponding country may be labelled with the approval symbol.
12 - 49
Standards, codes and approvals (Cont’d)
International and National testing institutes/authorities
KEMA Netherlands N.V. tot Keuring van Elektrotechnische Materialen. Netherlands testing
institute, also authorised to issue CSA approvals in Europe.
LRS United Kingdom Lloyd’s Register of shipping. Ship classification institute. Headquartered in
London.
NBN Belgium Normes Belges/Belgisch Norm, standards of the Belgian Standards Institute,
partially harmonised with IEC.
NEC USA National Electrical Code. Installation codes of the National Fire Protection
Association (NFPA) and the American National Standards Institute (ANSI).
NEMKO Norway Norges Elektriske Materiellkontroll. Codes, approval and labelling required
up to 32 A nominal or continuous current.
NZS New Zealand New Zealand Standards association. Extensively harmonised with IEC & AS.
ÖVE Austria Österreichischer Verband für Elektrotechnik. Approval and labelling required
for house installations and fuse devices.
SABS South Africa South African Bureau of Standards. Specifications partially harmonised with
IEC.
VDE Federal Republic Verband Deutscher elektrotechniker. Recent German standards (DIN)
of Germany coincide with the VDE rules. Extensively harmonised with IEC. Older rules
partially similar to CEE.
Only components that have passed the tests in the corresponding country may be labelled with the approval symbol.
12 - 50
Pt C 2010 Sec 12_Part C - 12 24/11/10 12:01 PM Page 51
12
45. Thermal simulation of switchgear
46. Cable considerations.
47. Output chokes for use with Variable Speed Drives.
48. VSD installation techniques
49. The modern SCADA system
50. NHP still delivering its promise
51. Electrical design considerations for commercial buildings
52. Terminal temperatures - how hot are they?
53. Taking care of business - prevention is better than cure
54. Control voltages for contactors
55. Electrical switchgear - Will it turn you off?
56. Electrical Arcs, Beauty and the Beast
12 - 51
Terasaki MCCB Old Vs New cross reference
2009/10
TemBreak 2 400 V
& TemBreak AC
TO/TG/ OCR Base TemBreak TemBreakPlus 1 combined ratings
Amps kA TTMCCB type current adj. Cat.No. Cat.No. range kA
12.5-125 18 TO100BA Adj. therm. fixed mag. 63-100 % XS125CJ – E125NJ 25
160-250 S250NJ
160-250 S250GJ
250-400
160-250 50 TG400B Adj. therm. adj. mag. 63-100 % XS400NJ 1) – S400NJ 50
250-400
200-400
200-400
400-630
TO1200B Electronic
TO2000 Electronic
12
12 - 52