Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Diversity Factor

The diversity factor has an important place in the design of an installation and its final costing. IEE
regulation 311-01 deals with the subject. Diversity factor is a factor which is applied to sub main and
main cables and their associated gears/ circuit breakers to reduce:
a) the cross sectional area of the cable conductor, and
b) the capacity of the switch gears/ circuit breakers.
The factor is based on the assumption that the whole of the connected load will not be turned on at
the same time. For example, the total lighting load in a dwelling house is rarely switched on at a time.
Thus, it can be taken that if the total lighting load is 1000W during the life of the installation, only 66%
of the load (660W) will be switched on at any one time. The factor in this instance is 0.66. A factor for
diversity shall not be allowed for calculating the size of circuit conductor and switchgears of final sub
circuits, other than specified circuits such as cooker circuits. It is noted that the provision of an allowance
for diversity is a matter of calling for a special knowledge and experience. Indeed, the application of the
diversity should be decided by the engineer responsible for designing each particular installation. The
amount by which they are increased or decreased for each installation is a matter for the installation
engineer to decide.
There are ten types of final circuit fed from wiring to which diversity applies: lighting, heating,
cooking appliances which are permanently connected, motors (other than lifting motors), instantaneous-
type water heater, thermostatically controlled water heater, floor-warming installation, thermal-storage
space-heating installation, 13A fused socket outlets and appliance fed there from, and other socket
outlets such as 15A sockets. Three general groups of installation premises are also recognized:
1) Individual domestic installation, including individual flats of a block.
2) Hotels, boarding houses, lodging houses etc.
3) Shops, stores, offices and business premises
In the case of lighting for each type of installation, it will be noticed that the more the total lighting
load is likely to switched on over definite periods, the smaller is the allowance made for diversity. In a
domestic installation, it is estimated that some two-thirds (0.66) of the lighting load will be on at any one
time. In a hotel, the figure is 75%(0.75), and in a shop, where virtually all the lights are on for most of
the time when the shop is open, the figure is 90% (0.90). It should be noted that no diversity is allowable
in the relevant wiring supplying certain types of load.

Example: An apartment having 15 individual rooms each 9mX4m (see figure


below) is to be installed with the following loads: Ventilator (500W), Fridge
(1kW), Stove (2kW), six 60W lamps, and five socket outlets.
a) Locate the approximate area of location of each lamps and socket outlets.
b) Calculate the sub-feeder cable size for this room if the average ambient temperature of
the local area is taken as 38oC and five groups of circuits are running together in a Fig 1 Floor Plan for the above example
conduit with it. The length of run is 15m and protection is by MCB.
c) Choose the rating of the MCB and the branch circuits breakers.

By Sintayehu Challa

You might also like