Outside Screw and Yoke (OS&Y) Gate Valve

OF300F

Control Valves
Technical Features
• Sizes available (Nominal) : 21/2”/DN65, 3”/DN80,
4”/DN100, 5”/DN125, 6”/DN150, 8”/DN200, 10”/DN250
and 12”/DN300.
• Pressure data :
Working pressure : 300 psi (21 bar)
• Seat type : Resilient wedge.
• Finish : Fusion bonded epoxy coated inside and outside.
• Connections : Flange diameter and thickness according to
ANSI B16.1 Class 125. Flange drilling varies by Reference
number. See Physical Data table below.
• Specifications : Design and dimensions conform to AWWA
C509.
• Features : Pre-notched, stainless steel stem for easy
attachment of supervisory switch.

Outside Screw and Yoke (OS&Y) Gate Valve - OF300F Physical Data
Nominal Pipe
Dimensions (mm / inch) Reference* Weight
Size
(lbs / kgs)
inch Metric L H (open) H (Closed) D ANSI PN10 PN16 Table E
2½” DN65 190.5 / 7.50 415 / 16.33 350 / 13.75 184 / 7.250 OF300F-0250 OF300F-0250PN OF300F-0250E 56 / 25
3” DN80 203 / 8 480 / 18.90 400 / 15.75 254 / 10 OF300F-0300 OF300F-0300PN OF300F-0300E 68 / 31
4” DN100 229 / 9 550 / 21.66 450 / 17.75 254 / 10 OF300F-0400 OF300F-0400PN 106 / 48
5” DN125 254 / 10 655 / 25.80 530 / 20.90 305 / 12 OF300F-0500 OF300F-0500PN 99 / 45
6” DN150 268 / 10.50 740 / 29.10 590 / 23.25 305 / 12 OF300F-0600 OF300F-0600E 168 / 76
8” DN200 292 / 11.50 930 / 36.60 730 / 28.75 356 / 14 OF300F-0800 OF300F-0800PN10 OF300F-0800PN16 OF300F-0800E 254 / 115
10” DN250 330 / 13 1130 / 44.50 880 / 34.75 445 / 17.50 OF300F-1000 OF300F-1000PN10 OF300F-1000PN16 OF300F-1000E 432 / 196
12” DN300 356 / 14 1320 / 52.0 1020 / 40.16 445 / 17.50 OF300F-1200 OF300F-1200PN10 OF300F-1200PN16 OF300F-1200E 683 / 310
* Valve flange drilling (size and location of bolt holes and pitch circle diameter) allows mating with the following flange types :
ANSI = ANSI B16.1 Class 125 PN10 = DIN 2501, BS 4504, EN 1092 - PN10 PN16 = DIN 2501, BS 4504, EN 1092 - PN16 Table E = BS10-1962 Table E

OF300F Materials List


Description Material
Body Ductile Iron A536 65-45-12
Wedge Ductile Iron EPDM encapsulated
Disc Nut Stainless Steel AISI 304
Stem Stainless Steel AISI 420
Bonnet Ductile Iron A536 65-45-12
New Datasheet Created

Gasket EPDM Commercial


Packing Graphite Commercial
Gland Ductile Iron A536 65-45-12
Yoke Nut Bronze ASTM B62
Handwheel Ductile Iron A536 65-45-12
Nut on Handwheel Ductile Iron A536 65-45-12
NPT Plug Brass B16, C36000
2011-04-20

Bolt & Nut on Gland Stainless Steel AISI 316


Bolt on Bonnet Flange Carbon Steel A307 B

Worldwide Fire Protection www.vikinggroupinc.com

FireKing™ is a trademark of The Viking Corporation. Refer to Manufacturer’s datasheet. Specifications subject to change without notice.
Outside Screw and Yoke (OS&Y) Gate Valve
OF300F

Control Valves
Installation Inspection and Maintenance
1. Piping systems and valves should be 1. Valves should be inspected periodically
thoroughly cleaned and free from ingress of and should be cycled to prevent buildup of
foreign materials. foreign materials in the piping system and
2. Visually inspect the valve seating and valve body.
ports for cleanliness immediately prior to 2. In the event of a packing leak adjust the
installation. packing nuts to increase pressure on the stem
3. All valves should be independently packing. Packing nuts should be tightening
supported against movement and stress evenly approximately a quarter turn in a
from the connected piping system. clockwise direction.
4. Ensure that the valve pressure rating is 3. Always shut down the system before
compatible with service conditions repacking the valve. Valves are designed with
5. Operate the valve at least once from the backseats for repacking under pressure but
open to closed position. this is not recommended.
6. Verify that packing nuts are tight before
pressurizing the system 1

7. Check valves must be oriented properly


for flow and gravity and must be installed
sufficiently distant from pumps or other
devices producing turbulence.
8. 8 Gate valves are not suitable for throttling
plications.
9. Gate valves should be installed in the
vertical position on horizontal pipework
and in the horizontal position on vertical
pipework.

Operation
Gate valves are manually operated multi-turn
valves and are opened by a handwheel or
other operating device, generally in a clockwise
direction and then closed counterclockwise. Gate
valves with counterclockwise opening should be
clearly identified to ensure safe operation.