Silent Check Valve (Flanged) : Technical Features
Silent Check Valve (Flanged) : Technical Features
Silent Check Valve (Flanged) : Technical Features
SCF
Check Valves
Technical Features
• Sizes available (Nominal) : DN50/2”, DN65/21/2”,
DN80/3”, DN100/4”, DN125/5”, DN150/6”, DN200/8”,
DN250/10” and DN300/12”.
• Pressure data :
Working pressure : 16 bar (235 psi).
Shell test pressure : 24 bar (348 psi). D
Seat test pressure : 17.6 bar (255 psi).
• Seat type : Stainless steel.
• Finish : Red oxide approved for water use.
• Connections : Flange diameter and thickness according to
BS4504 PN16. Flange drilling varies by Reference number.
See Physical Data table below.
FLOW
Updates the datasheet of 2004-07-19 (Added notes on Installation, Operation, Inspection and Removal Procedures)
Metric inch A D Kv Cv ANSI PN10 PN16 (kg / lbs)
DN50 2” 133 / 5.2 165 / 6.5 43 50 SCF-0200 SCF-0200PN SCF-0200PN 18 / 40
DN65 21/2” 140 / 5.5 185 / 7.3 120 140 SCF-0250 SCF-0250PN SCF-0250PN 24 / 53
DN80 3” 152 / 6.0 200 / 7.9 154 180 SCF-0300 SCF-0300PN SCF-0300PN 28 / 62
DN100 4” 185 / 7.3 220 / 8.7 282 330 SCF-0400 SCF-0400PN SCF-0400PN 43 / 95
DN125 5” 216 / 8.5 250 / 9.8 457 535 SCF-0500 SCF-0500PN SCF-0500PN 55 / 121
DN150 6” 248 / 9.8 285 / 11.2 637 745 SCF-0600 SCF-0600 SCF-0600 72 / 158
DN200 8” 318 / 12.5 340 / 13.4 1120 1310 SCF-0800 SCF-0800PN10 SCF-0800PN16 123 / 271
DN250 10” 393 / 15.5 405 / 15.9 1847 2160 SCF-1000 SCF-1000PN10 SCF-1000PN16 183 / 403
DN300 12” 362 / 14.3 460 / 18.1 2565 3000 SCF-1200 SCF-1200PN10 SCF-1200PN16 306 / 675
* Friction Loss : Kv = Cubic meters per hour of water at 1 bar pressure drop ; Cv = U.S. gallons per minute of water at 1 psi pressure drop.
** Valve flange drilling (size and location of bolt holes and pitch circle diameter) allows mating with the following flange types :
ANSI = ANSI B16.1 Class 125 PN10 = DIN 2501, BS 4504, EN 1092 - PN10 PN16 = DIN 2501, BS 4504, EN 1092 - PN16
5 1 4
2 3
Manufactured for Viking SupplyNet by Fivalco™ Inc. Refer to Manufacturer’s datasheet. Specifications subject to change without notice.
Silent Check Valve (Flanged)
SCF
Check Valves
Installation Inspection and removal procedures
1. Piping systems and valves should be Close the isolating valve on the discharge side.
thoroughly cleaned and free from ingress of Bleed system pressure from the discharge flange
foreign materials. Do not loosen the flange bolts on the inlet side
2. Visually inspect the valve seating and until system pressure is relieved as damage may
ports for cleanliness immediately prior to occur to the valve Remove Valve from the line and
installation. inspect internal parts for wear and tear. Do not
3. All valves should be independently attempt to inspect by removing the inlet side pipe
supported against movement and stress as this will result in damage to the valve.
from the connected piping system.
4. Ensure that the valve pressure rating is
compatible with service conditions
5. Install the valve with the arrow in the
direction of flow
6. Exercise the valve at least once before
installation
7. Check valves must be oriented properly
for flow and gravity and must be installed
sufficiently distant from pumps or other
devices producing turbulence.
Updates the datasheet of 2004-07-19 (Added notes on Installation, Operation, Inspection and Removal Procedures)
Operation
Designed to automatically prevent reverse flow
into the piping system.
2009-06-29