Starting Methods of 3-Phase Induction Motor
Starting Methods of 3-Phase Induction Motor
Starting Methods of 3-Phase Induction Motor
University of Moratuwa
DISCUSSION
The starting current should be kept low to avoid overheating of motor and excessive voltage drop of
the supply network. This could also cause to damage the adjoining equipments. The starting torque
must be about 50 to 100% more than the expected load torque to ensure that the motor runs up In a
reasonably short time. By using a proper starter, we can improve the lifetime of motor.
The motor is switch on directly to the full supply voltage. Hence, the starting current is large, normally
5 to 7 times of rated current. But the starting torque is likely to be 0.75 to 2 times the full load torque.
So the motor will start as quickly as it can. To avoid voltage drop of excessive supply voltage drops
because of large starting currents the method is restricted to small motors only (up to 5 kW).
Star-Delta starter.
This is applicable to motors designed for delta connection in normal running conditions. The two ends
of each phase of the stator winding are brought out to the starter. When the starter moved to the
starting position, these stator windings are connected in star. After the motor is accelerated, the starter
is quickly moved to the running position. Now the stator windings are connected in delta connection.
By using this method we can reduce the starting current by 3 times. But the starting torque will also
reduced by 3 times.