Generator Service Training
Generator Service Training
Generator Service Training
Jobayer Ahsan,
Senior Service Engineer
Date : 31/01/2017
© 2017 Energypac Power Generation Ltd.
All rights reserved
Contents:
Generator Rating Definitions
Engine Parts Identification
Air Induction & Ventilation System
Exhaust System
Cooling System
Fuel System
Lubricating system
Crankcase Breather System
Internal Mechanical Feature
Preventive Maintenance and Health Check of Generator.
Safety for Troubleshooting.
Question and Answer.
Fuel Solenoid
Intake Manifold
Damper Pulley
Self Stator
Oil Sump
Oil Filters
• Filtration 98% of all particles greater than 10um (micron) in SAE (Society of
Automotive Engineers) fine test dust
• Outlet/Inlet Sizes
• The outlet opening should have a free flow area approximately 25% larger
than the radiator matrix
• Lube oil and fuel filters, fuel tank and LP/HP fuel systems
– The back pressure for the total system must be kept within the limit of
each engine maximum :-
– P = L x Q2 x 1187 x 109
D5.33
• P = Back pressure (mmHg)
• Q = Gas flow (kg/s)
• L = Total equivalent length * straight pipe (M)
• D = Pipe diameter (mm)
outlet hose
Self venting thermostat housing
inlet hose
Cavitations Erosion
Fuel Filter
• Filtration to 10 microns
Fuel Filter
Water
Separator
Oil Control
Oil consumption is not to exceed 0.1% of the fuel used
An increase in oil consumption to 0.5% of fuel used would require investigation
Lubricating Oil System
• Oil Filtration
• Disposable canister fitted with by-pass, full flow type
Oil Filler
Dipstick
• Filtration to 40 microns
1.Value Malfunctioning
2.Value fixed at a certain level
3.Generator shutdown by showing low oil pressure .
© 2017 Energypac Power Generation Ltd.
All rights reserved
Crankcase Breather Systems
Crankcase Breather System
• Breather
– Check breather exit position, the point of exit of the breather should
be directed away from the engine air intake and cooling group
Fumes would deposit oil on radiator matrix and particles
of dust in the airflow would stick, resulting in radiator
and fan performance fall.
– If possible the pipe work should be less than 5 meters long and should
be of equal or greater diameter than 50.8mm
Oil inlet
Collets
Lower
Spring Seat
Inner Spring Outer Spring
Idler Gear
Compounder Gear Assembly
Fuel Transfer Pump